Design Calculation Bus Bar

Embed Size (px)

Citation preview

  • 7/27/2019 Design Calculation Bus Bar

    1/7

    Design calculation for Bus bar

    1) Fault Level for 3sec - 80 KA

    2) Bus bar per phase - 4 Runs of 200 mm X 10 mm

    3) Bus bar material - Copper

    4) Distance between

    Phase to Phase - 175 mm5) Bus bar Support - 14-P-171( R,B & Y Ph.) & 10 P 131( Neutral )

    6) Material - SMC

    DESIGN CALCULATION

    10 -P - 131 Support Used in Neutral ( 2 Run of 200mm X 10 mm )

  • 7/27/2019 Design Calculation Bus Bar

    2/7

    a) SHORT CIRCUIT

    14 -P - 171 Support Used in R,Y & B Phase(4 Run of 200mm X10 mm)

    Minimum cross sectional area of Copper Bus bar required during 80 KA for 3 sec. Short circuit test.

    The formula to calculate this is given in the J & P Switchgear Hand Book .

    ( I/A ) t = 0.122

    or A = ( I/0.122) t

    or A = ( 80 /0.122 ) 3

    or A= 1135mm2

    The cross section of Bus bar being used (4 10 200) mm2 equals to 8000 mm2 ( much higher than

    required section ) .

  • 7/27/2019 Design Calculation Bus Bar

    3/7

    FORCE CALCULATION

    Support 14-P-171 C-C(Ph) 175 mm

    Dynamic Forces developed per meter ( Fm )between bus bar due to 80 KA for 3 sec. Short Circuit

    Test.

    16 I2 10-4 K

    Fm = --------------------------- N/m

    S

    Where, I = The R.M.S. Value of the current in amp =80 103 A

    K= Space factor for Rectangular BarsS = Spacing between the conductors (mm) = 175 mm

  • 7/27/2019 Design Calculation Bus Bar

    4/7

    The value of Space Factor (K) is determined from the graph firstly by determiningthe ratio (s-a)/(a + b) and then from the value on the base scale projecting upwards to the pt. Of

    intersection with the curve appropriate to the ratio a/b.( a=total thickness of Bus bar per phase &

    b= width of Bus bar ) . The value for the K can be calculated from the Graph given in J&P Handbookby taking the ratio of the following

    s-a------- and comparing it with the value of a/b.

    a + b

    Here value of a = 70 mm & b = 200 mm

    Distance between Phase to Phase ( s) = 175 mm

    so ( S -a ) / ( a + b ) = 0.4 and ( a/b) = 0.35

    From Graph Value of K ( approx. ) = 0.86

    16 80 80 106 10-4 0.86

    Dynamic forces developed (Fm) = -------------------------------------------- N/m

    175

    = 50322 N/m ( approx.)

    50322 350

    Forces at a Span of 350 mm(Support to Support Distance ) = ----------------------1000

    = 17612 N

    17612= ------------- Kg f ( as 1 NEWTON = 9.8 Kg f )

    9.8

    = 1797Kg f

  • 7/27/2019 Design Calculation Bus Bar

    5/7

    Breaking Force of the Bus bar support

    Section side - 42 mm 35.4 mm

    Area of Cross Section( which is likely to break during short circuit ) support

    = Surface area of the support

    = ( 4.2 cm 3.54 cm )

    = 14.87 cm2Breaking force of the bus bar support = Area of Cross Section ( which is likely to break,during Short

    Circuit ) of the support Tensile Force of the material ( 700 Kg f )

    = 14.87 cm2 700 Kg f/cm2

    = 10407 Kg f

    Breaking force of the Bus bar Supports > cal. Value (1797 kg f ) which is quite suitable to

    withstand force.

  • 7/27/2019 Design Calculation Bus Bar

    6/7

    Factor of Safety

    Breaking Strength

    Factor of safety = ---------------------------

    Calculated Load

    10407= -------------

    1797

    = 5.8

    Calculated value of the Dynamic Force from the data given is lesser than the Breaking Strength

    of the Support used. So Bus bar Support can easily withstand on the Fault Level of 80 KA for

    3 sec.

  • 7/27/2019 Design Calculation Bus Bar

    7/7

    VALUE OF K ON Y -AXIX

    VALUE OF (s-a ) / ( a+b ) ON X- AXIX .

    Graph Taken from J&P Switchgear Handbook