Upload
vanminh
View
222
Download
0
Embed Size (px)
Citation preview
College of Technological Studies
Department of Power & Refrigeration Technology
Course Contents
Course Designation: Air Conditioning Control systems
Course No. : 0463 272
Credit Hrs.: 3 Lecture Hrs.: 2 Lab Hrs.: 2
Lecturer: Eng. Raad Alsaleh
Course Topics
i. Background
ii. Compressor Control System
Reciprocating Compressors Control
Capacity, safety and operation controls.
Centrifugal Compressor Control
Capacity, Surge, and safety control.
iii. Air handling systems control
Outside Air Control Minimum Outside Air, Economy Cycle Outside Air, Enthalpy Control, Static
pressure Control, Air Stratification
Heating Coil Control
Preheat of outside or mixed air, Normal heating, Reheat
cooling Coil Control Direct Expansion (DX) coils, Chilled water coils
Humidity Control humidifying, Dehumidifying
iv. Applications
Single Zone, Multi zone and dual-duct, 3 deck Multi zone, Variable Air Volume
Textbooks
1- Control Systems for Heating, Ventilating and Air Conditioning
by Roger W. Haines
2- Handbook of Air Conditioning System Design,
by Carrier
Grading Policy
1. Attendance - 10
2. Homework - 10
3. Exam 1 - 15
4. Exam 2 - 15
5. Lab. - 20
6. Final - 30
I. Background
A. The purpose of the control system:
1. Provide automatic operation.
2. Maintain the controlled conditions closer than could be achieved by manual
operation.
3. Provide maximum efficiency and economy of operation.
4. Ensure safe operation.
B. Control Fundamentals:
1. The desired temperature is ________________________________.
2. _____________________________ the actual quantity which is being controlled.
Examples: _________________, ______________________, __________________________.
3. The _________________________ measures the controlled variable and convey
the value to the controller.
Examples: Electric _______________________
Pneumatic ______________________
Mechanical _____________________
4. The _________________________ compares the actual quantity (Controlled
variable) with the desired quantity (set point).
Examples: _______________________
______________________
_____________________
5. The _________________________ reacts to signals received from the controller
to vary a flow
Examples: _______________________
______________________
______________________
6. The ________________________ is the medium manipulated by the controlled
device.
Examples: _______________________
______________________
______________________
7. The mathematical relationships of control systems are usually represented
by
________________________________. A ______________________ is the symbol which
is used to indicate a summing operation, and a _______________________ is the
symbol for multiplication.
C. Components of Control Systems:
Control systems are consisting of a loop that contain:
1. _______________________
2. _______________________
3. ________________________
4. ________________________
The communication signals between control system components are:
1. _______________________
2. _______________________
3. ________________________
D. Control Action:
1. Two-Position action:
It is the simplest of automatic regulation. There is no intermediate position
between the two extremes of full ON and full OFF.
2. Timed Two-Position action:
A heater element is added to offset operation time lag.
3. Floating action:
The control device will be turned off at any position if it reaches upper limit
or lower limit.
4. Proportional action:
Continuous action either toward OFF position or ON position, and it is of three
types:
a. Proportional.
b. Proportional Plus Integral.
c. Proportional plus derivate
Figure 3.1 Reciprocating compressor, (a) Suction stroke, (b) Discharge stroke
II. Compressor Control System:
A. General:
The purpose of the compressor in the vapor compression
cycle is to accept the low-pressure dry gas from the
evaporator and raise its pressure to that of the condenser.
Compressors may be of two types:
1. _______________________________ the general form is the piston type,
or Reciprocating compressors, being adaptable in size, number of
cylinders, speed and method of drive.
2. _____________________________ they impart energy to the gas by
velocity or centrifugal force and then convert this force to pressure
energy. The most common type is the Centrifugal compressors.
B. Reciprocating Compressors Controls:
1. Capacity Control:
A refrigeration system will be designed to have a maximum duty to
balance a calculated maximum load, and for much of its life may work
at some lower load. Such variations require capacity reduction devices.
Capacity reduction means mainly reducing the __________________________________
compressed by the compressor according to a set heat load.
Methods of capacity control are:
a) ON - OFF Control:
This is generally used with residential air conditioners, where starting
and stopping the compressor may be done directly by room
thermostat. On a rise in room temperature the thermostat opens a
Solenoid valve. The low-pressure switch closes and starts the
compressor. When the Solenoid valve closes, the refrigerant is pumped
out of the evaporator, opens the low-pressure switch, stopping the
compressor.
This type of capacity control is recommended only when the load on
the system is moderately constant.
b) Multispeed Compressor
Since the capacity of a compressor is proportional with its speed, multispeed
motor may be used to regulate its capacity (Two-speed motor). This motor
may be controlled by two stage thermostat and two speed magnetic starter.
The added cost is the disadvantage of this control method.
c) Multiple Compressors:
There are some applications where failure of refrigerant in equipment could
result in financial loss beyond the equipment repair expense. In such cases it
advisable to break the refrigeration load into multiple stages, each has its own
compressor.
d) Loading and Unloading Cylinders:
Except in very small sizes, reciprocating compressors have multistage capacity
control. This is generally achieved by loading and unloading cylinders under
control of a suction pressure controller, by raising the suction valve off its
seat.
When the load increase: (Unloading stage)
Suction pressure is high
Bellow shrink and Bleed port arm go up closing bleed port
Pressure in the piston room increase
Piston pin moves down
Suction valve operates No load
When load decrease or in starting: (Loading stage)
Suction pressure decrease
Bellow expands moving bleed port arm down opening bleed port
Pressure in piston room decrease
Piston pin moves up
Suction valve (on load)
e) Hot Gas Bypass Control:
Hot gas bypass may also be used for capacity control, for system that operates at
or below minimum temperature of compressor unloading.
A constant pressure expansion valve is used to maintain the evaporator pressure
and temperature at constant level, regardless of load.
2. Safety Controls
Any gas control system must include such safety controls as high or low
temperature limits and high or low pressure limits
a) Oil safety switch
All compressors except the smallest have mechanical lubrication and will
fail if the oil pressure falls because of a pump fault or oil shortage A
safety cut-out is required which will stop the compressor. This takes the
form of a differential pressure switch with starting time delay.
A pressure gauge on the pump discharge will indicate the total pressure
at that point Any detection element for true oil pump pressure must
sense both suction and pump outlet pressures and transduce the
difference Oil safety cut-out have pipe connections to both sides of the
oil pump and two internal bellows to measure the difference.
Since there will be no oil pressure at the moment of starting, a time delay
must be fitted to allow the oil pressure to build up This timer may be
thermal or mechanical or electric.
Oil safety cut-out control indicates an unsafe condition and such controls are
made with hand reset switch, and normally operate an alarm to warn of the
malfunction.
b) Refrigerant Pressure Controls
Pressure controls are used for safety protection with compressor and
condenser type systems.
High-pressure control actuates the system if high-side pressure
exceeds the preset level When the switch in the pressure control
opens, the compressor is stopped.
This type of safety control is required to:
Prevent the compressor motor from overloading.
Prevent the system from rupture.
Low-pressure control is used to stop the compressor motor
whenever the low-side pressure falls below a preset level Too low
suction pressure mast often occurs when there is a refrigerant leak in
the system. Damage to the system might result if the unit to operate
under this condition, drawing moisture and air.
High and low pressure switches are similar in appearance. The pressure range at
which the switch bellows mechanism operates determines whether it is a high or
a low pressure control. All pressure switches regardless of type have a common
element which is the ______________________________.
PRESSURE OPERATED SWITCH
3. Operation Control
a) Water Tower Controls
A reverse-acting fan pressure control in a water-cooled air conditioning
system. A water tower is often used to supply cooled water to the
condenser. For the system to operate efficiently, the head(high-side)
pressure of the compressor must maintained within certain limits. If the
head pressure becomes too low, the evaporator does not function properly.
Low head pressure could be the result of too cool water being supplied to
the condenser. To solve this problem, a reverse-acting fan pressure control
connected to the high side pressure line of the compressor is used. When
pressure is below a set limit, the fan motor will stop.
b) Pump-Down circuit control:
A low-pressure switch is used in conjunction with a thermostat and a
solenoid valve to form the pump-down circuit. In this method of control,
the thermostat does not stop the compressor but de-energizes the liquid
line solenoid valve to stop the supply of refrigerant to the evaporator. The
compressor continues to run and pumps down the evaporator until stopped
by the low-pressure switch. When the thermostat again calls for cooling, it
opens the solenoid valve to let the liquid refrigerant enters the evaporator
and the compressor restart again by the low-pressure switch. This method is
used to ensure that the evaporator is kept clear of liquid refrigerant when
the plant, is off.
C. Centrifugal compressors Control:
Centrifugal compressors are built for heavy duty continuous operation.
Centrifugal compressors are of two types:
a. Open - have a shaft which projects outside the compressors housing
OPEN CENTRIFUGAL MACHINE
b. Hermetic - have the driver built into the unit, completely
isolating the refrigerant space from the atmosphere
Hermetic Centrifugal Machine
1. Capacity Control
a. Hermetic Centrifugal
Temperature control is obtained by means of variable inlet guide
vanes at the suction inlet of the compressor.
This control reduces capacity by varying the angle at which the suction gas
is directed into the eye of the impeller. At low flow the change of inlet
gas direction has little effect on capacity and the control operates
primarily as a suction damper. The minimum partial load capacity of the
machine is based upon the amount of gas leakage thru the fully closed
capacity regulating vanes.
When the temperature changes, the thermostat signals the control to
reposition the capacity regulating vanes which changes the capacity of the
system, to maintain the desired temperature. When the vanes reach the closed
position and the leaving temperature continues to decrease to a predetermined
minimum, the low temperature cutout switch stops the compressor.
b. Open Centrifugal
Capacity control on an open centrifugal compressor may be obtained with
a suction damper, variable inlet guide vanes or variable speed drive.
Suction damper is controlled by a thermostat to reduce the capacity
of the compressor by throttling the gas suction inlet.
Variable inlet guide vanes control is identical to that discussed
under Hermetic centrifugal.
Variable speed drives may be controlled manually when the change
in loading is gradual or when a suction damper is used for automatic
control. Automatic speed control is used with steam, gas turbine or
gas engine drives. Automatic speed control provides very
economical operation, and require less input than other methods of
control.
COMPARATIVE PERFORMANCE, CENTRIFUGAL COMPRESSOR CAPACITY CONTROL
1. Safety Control
a. Surge Control
Surge is a characteristic of centrifugal compressors which occurs at
reduced capacities. This condition is a result of the breakdown in flow
which occurs in the impeller. When this happen, the impeller can no longer
maintain the condenser pressure, and there occurs a momentary reversal of
flow and the compressor is unable to force the gas into the condenser.
The following are some conditions which may cause compressor "surge":
Air in System - increases condenser pressure.
Low Refrigerant Charge - lowers cooler pressure.
Dirty Condenser Tubes - increases condenser pressure.
Low Condenser Water Flow - may increase condenser pressure.
High Entering Condensing Water Temperature – increase condenser
pressure
Faulty Float Valve Operation - decreases cooler pressure or increases
condenser pressure.
Division Plate By-pass - increases condenser pressure & decreases
cooler pressure.
Notice all tend to increase lift by either raising condenser pressure or
lowering cooler pressure.
Surge is solved by lowering the condenser pressure This allow the impeller
to function normally again, and gas flow returns to its normal direction. The
operation is stable until the condenser pressure builds up and surge occurs
again. Surging can be detected primarily by the change in sound level of
the machine.
Surge in a centrifugal machine does not occur at partial loads if the
head or lift decreases sufficiently with the load.
“Lift is defined as the difference between chiller
suction and discharge pressures.”
The figure below shows a typical lift versus load diagram at different positions
of the inlet guide vanes:
Line (B) when the loading is such that the total lift of the compressor
reduces sufficiently as the loading also reduces.
Line (A) when the lift remains almost constant or decreases slightly, it
can be seen that line (B) does not enter surge until load is under
minimum. Line (A) enters the surge region above minimum load.
IIFT-IOAD DIAGRAM, HERMETIC CENTRIFUGAL
To control surge occurring at partial load, a hot bypass valve between the
condenser and the evaporator is used to load the compressor artificially The
valve may be either manual or automatic, and controlled in sequence with the
automatic suction damper
or speed of the compressor
or position of the inlet guide vanes
So that the valve starts to open just before there is an indication of surge
HOT GAS BYPASS VALVE
b. Condenser high pressure cutout switch
It stops the compressor when the condenser pressure becomes
too high due to a condenser water stoppage, excessive
condenser scaling or air in the system.
c. Evaporator low pressure cutout switch
It stops the compressor when the evaporator pressure
becomes too low due to a chilled water stoppage, excessive
cooler scaling, or insufficient refrigerant charge.
d. Low oil pressure cutout switch
stops the compressor when the oil pressure drops below the
required minimum.
e. Low chilled water temperature cutout switch
stops the compressor when leaving chilled water temperature
drops below the minimum allowable temperature
f. Chilled water flow switch
stops the compressor when chilled water ceases to flow, and
prevents a start-up of the compressor motor until chilled
water flow is established.
TYPICAL SAFETY CONTROL SYSTEM. HERMETIC MACHINE
TYPICAL SAFETY CONTROL SYSTEM, OPEN MOTOR DRIVEN MACHINE
III. Air Handling System Control:
A. Outside Air Control:
Before deciding on how to control the amount of outside air it is
necessary to determine how much is required by the HVAC system
and why.
For example,
Laboratories require 100% exhaust and makeup; so chemical
labs require a negative pressure to prevent exfiltration.
Clean rooms require that a positive internal pressure be
maintained to prevent infiltration from surrounding areas.
When there are no special requirements, the minimum amount of
outside air required is that needed to meet the code requirements for
ventilation rates.
Once the criteria have been determined, one of the following methods of
control can be used
1. Minimum Outside Air
The simplest method of outdoor air control is to open a minimum
outside air damper whenever the supply fan is running.
2. Economy Cycle Outside Air
There many times when it is necessary to operate the cooling coil even
when outdoor air temperatures are near or below the freezing mark, with
outside and return dampers controlled by air temperature.
a. When the outside air at design winter temperature
Outside air dampers are in minimum open position
Return air dampers are in maximum open position
b. When outside air temperature increases
The mixed air thermostat (T1) gradually opens the outside air
damper to maintain constant mixed air temperature.
Return dampers modulate correspondingly
c. When outside air temperature become moderate
100* outside air will be provided and used for
cooling.
d. As outside air temperature continues to increase
Outdoor air high-limit thermostat(T2) cut the system back to
minimum outside air, decreasing cooling load
An interlock from the supply fan to close the outside air damper
when the fan is off to keep out dirt and unwanted things from
entering the system.
3. Enthalpy Control
The outside air economy cycle control based on dry bulb temperatures is
not always the most economical. That is, in very humid climates the
total heat (Enthalpy) of the outside air may be greater than of the return
air even though the dry bulb temperature is lower
Since the cooling coil must remove the total heat from the air to
maintain the desired condition, it is more economical in this case to hold
outside air to a minimum.
4. Static pressure Control
For those spaces requiring a constant positive or negative pressure with
respect to their surroundings, the outside and return air dampers will be
controlled by static pressure controllers.
The static pressure controller senses the difference in pressure between the
controlled space and a reference location outdoors, and adjusts the dampers
to maintain that pressure differential.
5. Air Stratification
Stratification of return air and outside air streams in mixing plenums can be a
serious problem. In a worst condition case, two air streams will not mix and
remain separate for a long distance through filters and coils. If the outside air
temperature is below freezing, the separate air stream can cause localized
freezing in heating and cooling coils. Or if a good low temperature safety
control is provided, the HVAC system will cycle OFF and ON.
The mixing plenum and its dampers should therefore be designed to promote
good mixing of the air streams.
Some of these methods are:
a. Parallel Blade Dampers - to have the air streams meet head on
b. Opposed Blade Dampers - the air streams enter opposite sides of
the mixing plenum.
c. Dynamic mixing - propeller fan is added, set at right angles of the
air streams, to provide mechanical mixing
B. Heating Coil Control:
Heating may be done as:
Preheat of outside or mixed air
Normal heating
Reheat for humidity control
1. Preheat
Preheating is used with large percentages of outside air to prevent freezing
of downstream heating and cooling coils and to provide a usable mixed air
temperature.
a. The simplest control Is a two-position valve in the steam or hot water
supply, with an outdoor thermostat which opens the valve whenever
the outdoor temperature is below 35-40o F.
b. Face and bypass dampers are added at the coil and controlled by
means of a downstream thermostat (T2) to provide a usable mixture
temperature. The difficulty here is stratification of the two air streams.
c. In many cases a sufficient distance for mixing is not available. The best
solution in this case is to use hot water with recirculating pump. Now
there can be full flow through the coil at all times with the temperature
of the water varied to suit the requirements. No air is bypassed, so
there are no mixing problems. Very accurate control of air
temperature is possible. Notice the opposed flow arrangement, with
the hot water supply entering the air leaving side of the coil. When
dealing with freezing air certain precautions are necessary. For hot
water, it has been shown experimentally that water velocities of 2.5- 3
ft./sec (0.9 m/s) in the coil tubes are sufficient to prevent freezing at
outdoor temperatures down to -30oF.
2. Normal Heating
Normal heating refers to the coil in a single-zone, multi zone or dual-duct air
system which handles all or a major portion of the system air at entering
temperature of (45o to 50o F) or higher.
3. Reheat
is used mainly with humidity control or individual zone control. In either
case, control of steam or hot water supply valves is usually done by room
thermostat.
C. cooling Coil Control:
There are two types of cooling coils:
Direct Expansion (DX) coils.
Chilled water coils.
1. Direct Expansion coils:
DX coils must by their nature use two-position control with its wide operating
differential. This system is often used in small units.
a. The room thermostat opens the solenoid valve, allowing refrigerant
liquid to flow through the expansion valve to the coil. The expansion
valve modulates to maintain a minimum refrigerant suction
temperature. A low limit discharge thermostat (T2) keeps the supply air
temperature from becoming too cold.
b. Controllability can be improved by providing face and bypass
dampers, but this may lead to lack of humidity control and coil icing
at high bypass rates.
c. A different approach adds a variable back pressure valve in the
refrigerant suction line, controlled by room thermostat. As the room
thermostat decreases, the valve is throttled, increasing the suction
temperature at the coil and decreasing the coil capacity.
d. Hot gas bypass may also be used for capacity control. There are
limitations on the percentage of total refrigeration flow which may be
bypassed, and on pressure drops in the piping system.
e. Two-Stage direct expansion will often provide adequate capacity
control. The stages should be made by rows of the coil rather than by
sectioning the coil.
In sectioning the active section may ice up forcing most of the
air flow through the inactive section and reducing the coil
capacity.
In multi-row coil the first stage should be first row in the
direction of air flow, and second stage the rest of the rows A
two stage thermostat is used
2. Chilled Water Coils:
Chilled water coils are controlled by
Three-way valve (Two-position or Modulating).
Recirculating pump.
Recirculating pump is used in two cases:
For extremely accurate temperature control.
To avoid coil freezing.
Parallel and Counter flow:
Consider the cooling coil with air flowing through it, decreasing in
temperature from 80oto 55oF, and with water flowing parallel or
counter to the air, and increasing in temperature from 42oto 50oF.
The heat transfer from air to water in the coil is a function of
Tube wall
Air and water films inside the tube wall.
Total internal tube surface area.
MED (Mean Equivalent Temperature Difference).
where:
CTD = greatest temperature difference between water and air.
LTD = least temperature difference between water and air.
MED = mean equivalent temperature difference.
ln = natural log (log to base).
If we calculate the MED for each of the two flow
arrangements, we get:
1. Parallel flow:
GTD = 80 - 42 = 38
LTD = 55 - 52 = 3
𝑴𝑬𝑫 = 𝟑𝟖−𝟑
𝐥𝐧𝟑𝟖
𝟑
= 13.3
2. Counter flow:
GTD = 80 - 52 = 28
LTD = 55 - 42 = 13
𝑴𝑬𝑫 = 𝟐𝟖−𝟏𝟑
𝐥𝐧𝟐𝟖
𝟏𝟑
= 18.7
This is an increase of nearly 1/3 in the heat transfer capacity. This
should allow water temperature of 47oF in and 57oF out, and still get
the design condition (55oF leaving air), which is impossible with
parallel flow.
The higher water temperature, increases chiller efficiency and
capacity.
D. Humidity Control:
Sometimes it may be necessary to raise or lower the humidity of
the supply air in order to maintain selected humidity conditions
in the air conditioned space.
1. Air Washer Humidifier:
Often used for its sensible cooling capability, it is then known as
an evaporative loader. The cooling is accomplished by using the
sensible heat of the air to evaporate water. Thus the air passing
through the washer changes conditions along a constant wet
bulb line, with the final state being dependent on the initial
state and the saturation efficiency of the washer. The is no
control of humidity.
2. Steam Humidifier:
Steam humidifiers are often used because of their simplicity. A
piping manifold with small orifices is provided in the air duct or
plenum. The steam supply valve is controlled by space or duct
humidistat. A duct high-limit humidistat must be provided to
avoid condensation in the duct.
3. Chemical Dehumidifier:
Chemical dehumidifiers use a chemical adsorbent. One form of
dehumidifiers uses a wheel containing silica gel, which revolves
first through the conditioned air stream, absorbing moisture,
and then through a regenerative air stream of heated outside
air, which dries the gel. In the process, a great deal of heat is
transferred to the conditioned air, and a cooling is necessary.
Space humidistat control the heating coil in the regenerative
(drying) air stream, and room thermostat control the space
temperature.
4. Dehumidifying by Refrigeration:
Low temperature cooling coil is used to reduce humidity to low
values. Special DX coils with wide fin spacing must be used.
A provision must be made for defrosting by:
a. Hot gas
b. Electric heater
c. Warm air
This approach has some limitations:
a. Inefficient at low humidifies.
b. Intermittent shutdown for defrosting.
c. Reheat is necessary.
Since space humidity is largely a function of coil temperature, fairly
good control can be achieved through a humidistat.
A room thermostat controls the cooling coil when the humidistat is
satisfied.
V. Applications:
A. Single Zone:
A space thermostat controls heating and cooling directly.
If used, a humidifier is controlled by the humidistat.
B. multi Zone and dual duct:
The mixing dampers controlled by the zone space
thermostat for each zone. If used, humidifiers are usually
controlled by a return air humidistat.
C. Three-deck multi Zone system:
The zone dampers operate with sequenced damper motor
either with:
1. Mix hot supply air with bypass air when the cold deck
damper is closed.
2. Mix cold supply air with bypass air when the hot deck
damper is closed.
D. Variable air volume system:
Motorized dampers in each zone supply duct. A related
zone space thermostat controls each damper by a (flow
sensor controller), that is reset by the thermostat. If used,
humidifiers are controlled by a return air humidistat.