Delta Confidential
E n er gy S ystem s
Why Uninterruptible Power Supply (UPS)?
Power Failure Backup Power
Over VoltageUnder Voltage Buck Voltage
Boost Voltage
ProtectionSurge
Power SagNoise
Transient
VariationHarmonic
Adjust
Delta Confidential
E n er gy S ystem sDifferent UPS architectures
Off-Line(Passive Standby)
Line-Interactive
UPS Type
On-Line(Double Conversion)
Delta Confidential
E n er gy S ystem s
Charger
Utility
SwitchLoad
Off-Line UPS
BatteryInverter
Block Diagram
Filter
Utility is normal: UPS output is equal to utility but through noise filterOver or under voltage: Inverter transfers battery’s energy to provide load Inverter Output: Stepped sinewaveCapacity: 350VA ~ 1500VA
Normal
Power event
Delta Confidential
E n er gy S ystem s Off-Line UPS
PC, Terminal
peripherals
Fax Machine
Cashier
Desk Lamp
Application
Delta Confidential
E n er gy S ystem s
Block Diagram
Line-Interactive UPS
Battery
Load
Utility
AVR
Inverter
Filter
Utility is normal: UPS output is equal to utility but through noise filterOver or Under Voltage: AVR activates to adjust the utilityUtility too high or two low: Inverter transfers battery’s energy to provide load Output: Pure Sinewave or Stepped SinewaveCapacity: 350VA ~ 3000VA
Switch
Normal
Power event
Normal charger
Delta Confidential
E n er gy S ystem s Line-Interactive UPS
High Level PC
Workstation
LAN
Hub
Application
Delta Confidential
E n er gy S ystem s
Block Diagram
Load
On-Line UPS
Utility
Battery
InverterAC to DC
Filter
Utility within operation range: UPS supplies clean, undisturbed power via inverterUtility too low or too high: Inverter transfers battery’s energy to provide load Output: Pure SinewaveCapacity: 1000VA ~ 200KVA
Bypass
Switch
Normal
Power event
Delta Confidential
E n er gy S ystem s On-Line UPS
IDC, Server
RAID, MIS Facility
Industrial Equipment
Enterprise
Application
Delta Confidential
E n er gy S ystem s
OFF-LINE LINE
INTERACTIVE ON-LINE
I/P Normal Utility Utility Input Inverter
I/P Over or Under
Battery Inverter
AVR Input Inverter
I/P Out of range
Battery Inverter
Battery Inverter
Battery Inverter
Output tolerance
Big Small Under 2%
Transfer Time <10 ms <10 ms Zero
Cost Lowest Low Higher
Architecture Simpler Simple More complex
Comparison between different architectures
Delta Energy Systems UPS product line
Delta Confidential
E n er gy S ystem sExtended runtime
LoadUtility
Battery
InverterAC to DC
Filter
Bypass
Switch
Battery
External battery can be connected to extend backup time Available for whole DES product range
features onl
ine UPS
Delta Confidential
E n er gy S ystem s Bypass types
Automatic bypass: In case of low battery or UPS fault the load will be transferred to bypass Available for whole DES product range
Manual bypass: Manual switch to power output during maintenance of the UPS Built in for J 7-11kVA, H and NT series
InverterAC to DC
Bypass
Automatic Bypass Load
Manual Bypass
features onl
ine UPS
Delta Confidential
E n er gy S ystem s Dual input
The UPS can be connected to two separate AC sources to increase system reliability.
Built in for J 7-11kVA and NT series (H series optional)
Utility B
Utility A
Battery
InverterAC to DC
Filter
Bypass
Switch
features onl
ine UPS
Delta Confidential
E n er gy S ystem s Hot standby
InverterAC to DC
Bypass
Switch
InverterAC to DC
Bypass
Switch
One UPS output connects to another UPS’s bypass input source Two paths that provide loads backup protection -> increased reliability Possible with dual input UPS (J 7-11kVA and NT series, H series optional)
Load
features onl
ine UPS
Delta Confidential
E n er gy S ystem s Parallel UPS
Switch
Parallel UPS to: extend capacity or provide N+1 redundancy Available for NT series
UPS 1
UPS 2
UPS N+1
To loads
features onl
ine UPS
Delta Confidential
E n er gy S ystem s Economic Mode
Load
Battery
InverterAC to DC
Filter
Bypass normal
Switch
In ECO mode the load is powered by the bypass path Energy saving Some transfer time in case of mains failure (< 10ms) Available for J7-11kVA and H series single phase models
features onl
ine UPS
Utility
© 2023年4月19日 Delta Energy Systems
E n er gy S ystem s
Delta Confidential
Clarification about EMC standards
Generic UPS standard Telecom standard
Old:EN50091
New:IEC62040
EN300386
B = C1 = B J 1-2kVA
A = C2 = A N series, J3-7-9-11kVA
A (A+) = C3 = --- H and NT series
A+ / C3 : For UPS models > 16Amps ~10-20 dBs more are allowed in the generic UPS product standard. Does not exist in Telecom norm and did lead to confusion in the past
Note: The term A+ is not an official term, officially it is class A also, but for currents > 16Amps the limits are higher.
Clarify requirements
in the beginning of a
project
© 2023年4月19日 Delta Energy Systems
E n er gy S ystem s
Delta Confidential
Key design parameters for UPS project
Load requirements - kVA / kW (kW = kVA x Power factor)
- number of phases
- voltage rating
EMC requirements (UPS standards / Telecom standards)
Required backup time
Verify external transient protection (same as with other products, see ‘Generic installation manual for power systems’)
Delta Confidential
E n er gy S ystem s
Comparison UPS – Inverter system
Advantages UPS: Large range of load power ratings available (1 – 800kVA) The UPS you can integrate into a network of IT equipment and:
- use extensive monitoring features- perform sequential equipment shutdown in backup mode, etc.
Advantages Inverter system: Redundancy can be built Can be powered from DC power system (mixed AC and DC
system) Fulfils all telecom standards