Appendix A Definition of geotechnical terms
Report: STM3210B-G01 Page 1 of 2 Appendix A
Definition of geotechnical terms used in this report - foundations Strip foundations. A foundation providing a continuous longitudinal ground bearing. Trench fill concrete foundation. A trench filled with mass concrete providing continuous longitudinal ground bearing. Pad foundation. An isolated foundation to spread a concentrated load. Raft foundation. A foundation continuous in two directions, usually covering an area equal to or greater than the base area of the structure. Substructure. That part of any structure (including building, road, runway or earthwork) which is below natural or artificial ground level. In a bridge this includes piers and abutments (and wing walls), whether below ground level or not, which support the superstructure. Piled foundations and end bearing piles. A pile driven or formed in the ground for transmitting the weight of a structure to the soil by the resistance developed at the pile point or base and the friction along its surface. If the pile supports the load mainly by the resistance developed at its point or base, it is referred to as an end-bearing pile; if mainly by friction along its surface, as a friction pile. Bored cast in place pile. A pile formed with or without a casing by excavating or boring a hole in the ground and subsequently filling it with plain or reinforced concrete. Driven pile. A pile driven into the ground by the blows of a hammer or a vibrator. Precast pile. A reinforced or prestressed concrete pile cast before driving. Driven cast in place pile. A pile installed by driving a permanent or temporary casing, and filling the hole so formed with plan or reinforced concrete. Displacement piles. Piled formed by displacement of the soil or ground through which they are driven. Skin friction. The frictional resistance of the surrounding soil on the surface of cofferdam or caisson walls, and pile shafts. Downdrag or negative skin friction. A downwards frictional force applied to the shaft of a pile caused by the consolidation of compressible strata, e.g. under recently placed fill. Downdrag has the effect of adding load to the pile and reducing the factor of safety.
Appendix A Definition of geotechnical terms
Report: STM3210B-G01 Page 2 of 2 Appendix A
Definition of geotechnical terms used in this report – bearing values Ultimate bearing capacity. The value of the gross loading intensity for a particular foundation at which the resistance of the soil to displacement of the foundation is fully mobilised. Presumed bearing value. The net loading intensity considered appropriate to the particular type of ground for preliminary design purposes. The particular value is based on calculation from shear strength tests or other field tests incorporating a factor of safety against shear failure. Allowable bearing pressure. The maximum allowable net loading intensity at the base of the foundation, taking into account the ultimate bearing capacity, the amount and kind of settlement expected and our estimate of ability of the structure to accommodate this settlement. Factor of safety. The ratio of the ultimate bearing capacity to the intensity of the applied bearing pressure or the ratio of the ultimate load to the applied load.
Definition of geotechnical terms used in this report – road pavements The following definitions are based on Transport and Road Research Laboratory (TRRL) Report LR1132. Equilibrium CBR values. A prediction of the CBR value, which will be attained under the completed pavement. Thin pavement. A thin pavement (which includes both bound and unbound pavement construction materials 1 in 300mm thick and a thick pavement is 1200mm thick (typical of motorway construction).
Appendix B Geo-environmental terms and bibliography
Report: STM3210B-G01 Page 1 of 5 Appendix B
Definition of geo-environmental terms used in this report Conceptual model Textual and/or schematic hypothesis of the nature and sources of contamination, potential migration pathways (including description of the ground and groundwater) and potential receptors, developed on the basis of the information obtained from the investigatory process. Contamination Presence of a substance which is in, on or under land, and which has the potential to cause harm or to cause pollution of controlled water. Controlled water Inland freshwater (any lake, pond or watercourse above the freshwater limit), water contained in underground strata and any coastal water between the limit of highest tide or the freshwater line to the three mile limit of territorial waters. Harm Adverse effect on the health of living organisms, or other interference with ecological systems of which they form part, and, in the case of humans, including property. Pathway Mechanism or route by which a contaminant comes into contact with, or otherwise affects, a receptor. Receptor Persons, living organisms, ecological systems, controlled waters, atmosphere, structures and utilities that could be adversely affected by the contaminant(s). Risk Probability of the occurrence of, and magnitude of the consequences of, an unwanted adverse effect on a receptor. Risk Assessment Process of establishing, to the extent possible, the existence, nature and significance of risk.
Appendix B Geo-environmental terms and bibliography
Report: STM3210B-G01 Page 2 of 5 Appendix B
Definition of environmental risk/hazard terms used in this report.
Based on CIRIA report C552 ‘Contaminated land risk assessment – A guide to good practice’.
Potential hazard severity definition
Category
Definition
Severe Acute risks to human health, catastrophic damage to buildings/property, major pollution of controlled waters
Medium Chronic risk to human health, pollution of sensitive controlled waters, significant effects on sensitive ecosystems or species, significant damage to buildings or structures.
Mild Pollution of non sensitive waters, minor damage to buildings or structures.
Minor Requirement for protective equipment during site works to mitigate health effects, damage to non sensitive ecosystems or species.
Probability of risk definition
Category
Definition
High likelihood Pollutant linkage may be present, and risk is almost certain to occur in long term, or there is evidence of harm to the receptor.
Likely Pollutant linkage may be present, and it is probable that the risk will occur over the long term
Low likelihood Pollutant linkage may be present, and there is a possibility of the risk occurring, although there is no certainty that it will do so.
Unlikely Pollutant linkage may be present, but the circumstances under which harm would occur are improbable.
Level of risk for potential hazard definition
Probability of risk
Potential severity
Severe
Medium Mild Minor
High Likelihood
Very high High Moderate Low/Moderate
Likely
High Moderate Low/Moderate Low
Low Likelihood
Moderate Low/Moderate Low Very low
Unlikely
Low/Moderate Low Very low Very low
Refer sheet 2 for definitions of ‘very high’ to ‘low’
Appendix B Geo-environmental terms and bibliography
Report: STM3210B-G01 Page 3 of 5 Appendix B
Definition of environmental risk/hazard terms used in this report.
Based on CIRIA report C552 ‘Contaminated land risk assessment – A guide to good practice’.
Risk classifications and likely action required:
Very high risk High probability that severe harm could arise to a designated receptor from an identified hazard OR there is evidence that severe harm to a designated receptor is currently happening. This risk, if realised is likely to result in substantial liability. Urgent investigation and remediation are likely to be required. High risk Harm is likely to arise to a designated receptor from an identified hazard. This risk, if realised, is likely to result in substantial liability. Urgent investigation is required and remedial works may be necessary in the short term and are likely over the long term. Moderate risk It is possible that harm could arise to a designated receptor from an identified hazard. However, it is either relatively unlikely that any such harm would be severe, or if any harm were to occur it is likely that the harm would be relatively mild. Investigation is normally required to clarify risks and to determine potential liability. Some remedial works may be required in the long term. Low risk It is possible that harm could arise to a designated receptor from an identified hazard but it is likely that this harm, if realised, would at worst normally be mild. Very low risk It is a low possibility that harm could arise to a designated receptor. On the event of such harm being realised it is not likely to be severe.
Appendix B Geo-environmental terms and bibliography
Report: STM3210B-G01 Page 4 of 5 Appendix B
Gaseous contamination - Extract copy of table 3 of BS8485:2007 Solutions scores
PROTECTION ELEMENT/SYSTEM SCORE COMMENTS
a) Venting/dilution (see Annex A of BS8485)
Passive sub-floor ventilation (venting layer can be a clear void or formed using gravel, geocomposites, polystyrene void formers, etc) A)
Very good performance
2.5 Ventilation performance in accordance with Annex A of BS8485.
Good performance
1
If passive ventilation is poor this is generally unacceptable and some form of active system will be required.
Subfloor ventilation with active abstraction/pressurization (venting layers can be a clear void or formed using gravel, geocomposites, polystyrene void formers, etc)A)
2.5
There have to be robust management systems in place to ensure the continued maintenance of any ventilation system.
Active ventilation can always be designed to meet good performance.
Mechanically assisted systems come in two main forms: extraction and positive pressurization
Ventilated car park (basement or undercroft) 4 Assume car park is vented to deal with car exhaust fumes, designed to Building Regulations Document F and IStructE guidance.
b) Barriers
Floor Slabs It is good practice to install ventilation in all foundation systems to effect pressure relief as a minimum.
Block and beam floor slab 0
Reinforced concrete ground bearing floor slab 0.5
Reinforced concrete ground bearing foundation raft with limited service penetrations that are cast into slab
1.5 Breaches in floor slabs such as joints have to be effectively sealed against gas ingress in order to maintain these performances.
Reinforced concrete cast in situ suspended slab with minimal service penetrations and water bars around all slab penetrations and at joints
1.5
Fully tanked basement 2
c) Membranes
Taped and sealed membrane to reasonable levels of workmanship/in line with current good practice with validation B), C)
0.5 The performance of membranes is heavily dependent on the quality and design of the installation, resistance to damage after installations, and the integrity of joints. Proprietary gas resistant membrane to reasonable levels of workmanship/in line
with current good practice under independent inspection (CQA) B), C) 1
Proprietary gas resistant membrane installed to reasonable levels of workmanship/in line with current good practice under CQA with integrity testing and independent validation.
2
d) Monitoring and detection (not applicable to non-managed property, or in isolation)
Intermittent monitoring using hand held equipment 0.5 Where fitted, permanent monitoring system ought to be installed in the underfloor venting/dilution system in the first instance but can also be provided within the occupied space as a fail safe.
Permanent monitoring and alarm system A) Installed in the underfloor venting/dilution system
2
Installed in the building 1
e) Pathway Intervention
Pathway intervention - This can consist of site protection measures for off-site or on-site sources (see Annex A of BS8485)
NOTE In practice the choice of materials might well rely on factors such as construction method and the risk of damage after installation. It is important to ensure that the chosen combination gives an appropriate level of protection. A) It is possible to test ventilation systems by installing monitoring probes for post installation validation.
B) If a 200g DPM material is to function as a gas barrier it should be installed according to BRE 212)/BRE 414), being taped and sealed to all penetrations.
C) Polymeric Materials > 1 200g can be used to improve confidence in the barrier. Remember that their gas resistance is little more than the standard 1 200g (proportional to thickness) but their physical properties mean that they are more robust and resistant to site damage.
Appendix B Geo-environmental terms and bibliography
Report: STM3210B-G01 Page 5 of 5 Appendix B
List of documents used in assessment of chemical contamination
CIEH Chartered institute of Environmental Health LQM Land Quality Management EA Environment Agency
No. Title Publication reference / publisher 1 Human health toxicological assessment of contaminants in
soil
EA Science Report – SC050021/SR2
2 Updated technical background to the CLEA model
EA Science Report – SC050021/SR3
3 CLEA Software (Version 1.03 beta) Handbook
EA Science Report - SC050021/SR4
4 Guidance on comparing Soil Contamination Data with a Critical Concentration
CIEH
5 Generic Assessment Criteria for Human Health Risk Assessment
LQM/CIEH
6 Assessment of Risks to Human Health from Land Contamination: An overview of the development of soil guideline values and related research
R&D Publication, Contaminated Land Report CLR 7
7 Contaminants of Soil: Collation of Toxicological Data and Intake Values for Humans
R&D Publication, Contaminated Land Report CLR 9
8 The Contaminated Land Exposure Assessment Model (CLEA): Technical Basis and Algorithms
R&D Publication, Contaminated Land Report CLR 10
9 Model Procedures for the Management of Land Contamination
R&D Publication, Contaminated Land Report CLR 11
10 Contaminants in Soil: Collection of Toxicological Data and Intake Values for Human Values
R&D Publications, Tox. 6
11 Soil Guideline Values for Contamination (2002)
R&D Publications, SGV 10
12 Soil Guideline Values (2009) EA Science Reports – SC050021
Key to legends, columns & water observations Trial pit records
Key to legends
Composite materials, soils and lithology
Topsoil Made Ground Boulders
Chalk Clay Coal
Cobbles Cobbles & Boulders Concrete
Gravel Limestone Mudstone
Peat Sand Sand and Gravel
Sandstone Silt Silt / Clay
Note: Composite soil types are signified by combined symbols. Siltstone
Key to ‘test results’ and ’sampling’ columns
Test result Sampling
Depth Records depth that the test was carried out (i.e.: at 2.10m or between 2.10m and 2.55m)
From (m) To (m)
Records depth of sampling
Result
PID - Photo Ionisation Detector result (ppm equivalent Isobutylene) PP – Pocket penetrometer result (kN/m2) HVP – Hand held shear vane result (kN/m2) PP result converted to an equivalent undrained shear strength by applying a factor of 50. Where at least 3 results obtained at same depth then an average value may be reported.
Type
D Disturbed sample
B Bulk disturbed sample
ES Environmental sample comprising plastic and/or glass container
W Water sample
CBR Undisturbed sample in mould (California Bearing Ratio)
Water observations Described at foot of log and shown in the ‘water strike’ column.
= water level observed after specified delay in excavation
= water strike
DESCRIPTION
Grey reinforced CONCRETE. 6mm diameter reinforcement bar located at 0.05m
depth. Blue plas c membrane present at 0.15m depth.
MADE GROUND
Loose dark brown to brown slightly clayey sandy GRAVEL. Gravel consists of
fine to coarse flint and occasional brick and concrete.
MADE GROUND
High and very high strength yellowish brown becoming light grey and orange
brown slightly silty to silty slightly sandy CLAY with occasional black specks and
organic ma0er.
WEALD CLAY FORMATION
Extremely weak to occasionally weak light grey and orange brown MUDSTONE
excavated as angular and tabular gravels and cobbles up to 40mm in thickness.
Thinly interlaminated to very thinly interbedded with brown to orange brown
silty CLAY.
WEALD CLAY FORMATION
…between 2.6m and 2.8m depth, becoming reddish brown.
TRIAL PIT TERMINATED AT 3.30m
LEGENDDEPTH
(m)
0.15
0.45
2.10
3.30
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.20
0.60
1.10
1.60
2.30
TO (m) TYPE
D
D
D
D
D
PP 0.60 150
HVP 0.80 110
PP 0.90 167
HVP 1.20 120
PP 1.50 158
HVP 1.70 100
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on.
Ground level (mAOD) Co-ordinates
526944, 138811
Groundwater observa�ons
Seepage observed at 3.1m insufficient to fill
base of trial pit a5er 5 minutes.
Dimensions (W x L)
0.60m x 2.20m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
Yes
Appendix
C
TP01
Report ref: STM3210B-G01 Revision: 0
DESCRIPTION
Loose to medium dense light brown mo�led white and reddish brown SAND
and GRAVEL with occasional cobbles of concrete. Gravel consists of fine to
coarse sub-angular to rounded flint and occasional brick and concrete.
MADE GROUND
High to very high strength yellowish brown and light grey slightly silty slightly
sandy CLAY.
WEALD CLAY FORMATION
...from 1.5m depth, becoming grey and orange brown.
Extremely weak to occasionally weak light grey and orange brown MUDSTONE
excavated as angular and tabular gravels and cobbles up to 40mm in thickness.
Thinly interlaminated to very thinly interbedded with brown to orange brown
silty CLAY.
WEALD CLAY FORMATION
TRIAL PIT TERMINATED AT 3.20m
LEGENDDEPTH
(m)
0.35
2.40
3.20
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.20
0.60
1.20
1.80
2.50
3.20
TO (m) TYPE
D
D
D
D
D
D
HVP 0.60 140
PP 0.90 208
HVP 1.20 135
PP 1.50 200
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on. Cable encountered at 0.8m depth.
Ground level (mAOD) Co-ordinates
526978, 138801
Groundwater observa�ons
Seepage observed at 2.8m filling trial pit to
2.75m a6er 5 minutes.
Dimensions (W x L)
0.60m x 2.30m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
No
Appendix
C
TP02
Report ref: STM3210B-G01 Revision: 0
DESCRIPTION
Grey reinforced CONCRETE. 6mm diameter reinforcement bar located at 0.05m
depth.
MADE GROUND
Loose light brown slightly clayey to clayey SAND and GRAVEL. Gravel consists of
fine to coarse sub-angular to rounded flint and occasional concrete and brick.
Blue plas.c membrane encountered at 0.35m depth.
MADE GROUND
Very high strength yellowish brown and light grey slightly silty CLAY. Slight
hydrocarbon odour between 0.5m and 1.5m.
WEALD CLAY FORMATION
...from 1.6m depth, becoming orange brown and brown.
Extremely weak to occasionally weak light grey and orange brown MUDSTONE
excavated as angular and tabular gravels and cobbles up to 40mm in thickness.
Thinly interlaminated to very thinly interbedded with brown to orange brown
silty CLAY.
WEALD CLAY FORMATION
TRIAL PIT TERMINATED AT 3.00m
LEGENDDEPTH
(m)
0.20
0.35
2.10
3.00
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.20
0.20
0.50
0.60
1.10
1.20
1.60
2.40
TO (m) TYPE
D
ES
ES
D
ES
D
D
D
PP 0.50 208
HVP 0.70 130
PP 0.80 167
HVP 0.90 105
PP 1.40 142
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on.
Ground level (mAOD) Co-ordinates
526990, 138791
Groundwater observa�ons
Seepages observed from 2.3m to 2.4m depth
insufficient to fill base of trial pit a=er 5
minutes.
Dimensions (W x L)
0.60m x 2.10m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
Yes
Appendix
C
TP03
Report ref: STM3210B-G01 Revision: 0
DESCRIPTION
Loose to medium dense light brown slightly silty SAND and GRAVEL with
frequent cobbles and boulders of concrete up to 0.4mx0.2mx0.1m in size.
Gravel consists of flint, concrete, brick and rare glass and metal fragments.
MADE GROUND
High and very high strength yellowish brown slightly silty slightly sandy CLAY.
WEALD CLAY FORMATION
Extremely weak to occasionally weak light grey and orange brown MUDSTONE
excavated as angular and tabular gravels and cobbles up to 40mm in thickness.
Thinly interlaminated to very thinly interbedded with brown to orange brown
silty CLAY.
WEALD CLAY FORMATION
TRIAL PIT TERMINATED AT 3.00m
LEGENDDEPTH
(m)
0.40
2.20
3.00
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.20
0.50
1.10
2.30
TO (m) TYPE
D
D
D
D
PP 0.50 200
HVP 0.70 115
PP 0.90 208
HVP 1.20 110
PP 1.50 158
PP 1.80 175
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on. Cable and yellow duct encountered at 0.75m depth on north and southern side of trial
pit.
Ground level (mAOD) Co-ordinates
526996, 138768
Groundwater observa�ons
No groundwater encountered.
Dimensions (W x L)
0.60m x 2.00m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
No
Appendix
C
TP04
Report ref: STM3210B-G01 Revision: 0
DESCRIPTION
Grey reinforced CONCRETE. 6mm diameter reinforcement bar located at 0.05m
depth.
MADE GROUND
Loose light brown and grey slightly clayey to clayey SAND and GRAVEL. Gravel
consists of fine to coarse sub-angular to rounded flint and occasional concrete
and brick.
MADE GROUND
High and very high strength light grey and orange brown slightly silty CLAY.
WEALD CLAY FORMATION
...from 1.6m depth, becoming brown and orange brown and friable.
Extremely weak to occasionally weak light grey and orange brown MUDSTONE
excavated as angular and tabular gravels and cobbles up to 40mm in thickness.
Thinly interlaminated to very thinly interbedded with brown to orange brown
silty CLAY.
WEALD CLAY FORMATION
TRIAL PIT TERMINATED AT 2.90m
LEGENDDEPTH
(m)
0.20
0.35
2.50
2.90
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.20
0.30
0.30
0.60
1.10
1.60
2.60
TO (m) TYPE
D
D
ES
D
D
D
D
PP 0.50 150
HVP 0.60 115
PP 0.80 167
HVP 1.00 120
PP 1.20 150
PP 1.50 150
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on.
Ground level (mAOD) Co-ordinates
526987, 138756
Groundwater observa�ons
Seepages observed from 2.4m to 2.5m depth
insufficient to fill base of trial pit a<er 5
minutes.
Dimensions (W x L)
0.60m x 2.00m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
Yes
Appendix
C
TP05
Report ref: STM3210B-G01 Revision: 0
DESCRIPTION
BRICK SET.
MADE GROUND
Loose brown gravelly SAND. Gravel consists of fine to medium igneous-type
rock.
MADE GROUND - SUBBASE
Loose to medium dense reddish brown SAND and GRAVEL. Gravel consists of
fine to coarse angular igneous-type rock.
MADE GROUND - SUBBASE
High and very high strength yellowish brown, orange brown and light grey
slightly silty CLAY.
WEALD CLAY FORMATION
...from 1.8m depth, becoming friable with occasional gravels of mudstone.
Extremely weak to occasionally weak light grey and orange brown MUDSTONE
excavated as angular and tabular gravels and cobbles up to 40mm in thickness.
Thinly interlaminated to very thinly interbedded with brown to orange brown
silty CLAY.
WEALD CLAY FORMATION
TRIAL PIT TERMINATED AT 2.80m
LEGENDDEPTH
(m)
0.08
0.20
0.60
2.40
2.80
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.20
0.50
0.60
1.20
2.00
TO (m) TYPE
D
D
D
D
D
PP 0.70 150
HVP 0.90 115
PP 1.00 183
HVP 1.30 120
PP 1.50 167
PP 1.70 167
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on. 100mm thick concrete slab encountered in eastern side of trial pit.
Ground level (mAOD) Co-ordinates
526946, 138734
Groundwater observa�ons
Seepages observed from 2.5m to 2.6m depth
filling bo=om of trial pit up to 2.75m a>er 5
minutes.
Dimensions (W x L)
0.60m x 2.40m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
Yes
Appendix
C
TP06
Report ref: STM3210B-G01 Revision: 0
DESCRIPTION
BRICK SET.
MADE GROUND
Loose brown gravelly SAND. Gravel consists of fine to medium igneous-type
rock.
MADE GROUND
High strength yellowish brown and light grey slightly silty CLAY.
WEALD CLAY FORMATION
Very high strength reddish brown and dark brown slightly silty CLAY.
WEALD CLAY FORMATION
TRIAL PIT TERMINATED AT 1.45m
LEGENDDEPTH
(m)
0.05
0.30
0.80
1.45
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.20
0.50
0.50
0.80
1.30
TO (m) TYPE
D
D
ES
D
D
PP 0.30 117
PP 0.80 167
PP 1.40 175
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on. Trial pit terminated due to obstruc.on (service present in western side of trial pit).
Ground level (mAOD) Co-ordinates
526942, 138758
Groundwater observa�ons
No groundwater encountered.
Dimensions (W x L)
0.60m x 2.20m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
No
Appendix
C
TP07
Report ref: STM3210B-G01 Revision: 0
DESCRIPTION
BRICK SET.
MADE GROUND
Loose reddish brown and brown gravelly medium to coarse SAND. Gravel
consists of fine to coarse sub-rounded to rounded flint.
MADE GROUND - SUBBASE
Loose dark grey sandy GRAVEL. Gravel consists of fine to coarse angular
limestone.
MADE GROUND - SUBBASE
High and very high strength yellow brown and light grey CLAY.
WEALD CLAY FORMATION
Extremely weak to occasionally weak light grey and orange brown MUDSTONE
excavated as angular and tabular gravels and cobbles up to 40mm in thickness.
Thinly interlaminated to very thinly interbedded with brown to orange brown
silty CLAY.
WEALD CLAY FORMATION
TRIAL PIT TERMINATED AT 3.10m
LEGENDDEPTH
(m)
0.08
0.25
0.50
2.20
3.10
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.10
0.30
0.30
0.60
1.20
2.30
TO (m) TYPE
D
D
ES
D
D
D
PP 0.60 150
HVP 0.80 110
HVP 1.20 105
PP 1.50 183
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on.
Ground level (mAOD) Co-ordinates
526959, 138769
Groundwater observa�ons
No groundwater encountered.
Dimensions (W x L)
0.60m x 2.10m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
Yes
Appendix
C
TP08
Report ref: STM3210B-G01 Revision: 0
DESCRIPTION
BRICK SET.
MADE GROUND
Loose reddish brown gravelly medium to coarse SAND. Gravel consists of flint.
MADE GROUND - SUBBASE
Loose to medium dense dark grey sandy GRAVEL. Gravel consists of fine to
coarse angular limestone.
MADE GROUND - SUBBASE
High and very high strength yellow brown and light grey slightly silty CLAY.
WEALD CLAY FORMATION
Extremely weak to weak light grey and brown MUDSTONE thinly interlaminated
with yellow brown silty clay.
WEALD CLAY FORMATION
TRIAL PIT TERMINATED AT 2.90m
LEGENDDEPTH
(m)
0.08
0.30
0.50
2.30
2.90
WATER
STRIKE
TEST RESULTS
TYPE/
DEPTH (m)RESULT
SAMPLING
FROM
(m)
0.10
0.30
0.30
0.67
1.10
1.80
TO (m) TYPE
D
D
ES
D
D
D
PP 0.60 150
HVP 0.90 115
PP 1.20 175
PP 1.50 167
PP 1.80 150
Proposed commercial development
London Road, Crawley
Notes: Trial pit sides remained upright and stable upon comple.on.
Ground level (mAOD) Co-ordinates
526943, 138781
Groundwater observa�ons
Seepages observed from 2.5m to 2.7m depth
insufficient to fill base of trial pit a<er 5
minutes.
Dimensions (W x L)
0.60m x 2.20m
Method of excava�on
JCB 3CX
Title
Trial pit record
Date of excava�on (range if applicable)
26/06/2015
Loca�on plan on drawing number
02
Surface breaking
Yes
Appendix
C
TP09
Report ref: STM3210B-G01 Revision: 0
Client: Soiltechnics Limited 51015406/15/01
Client Address: Cedar Barn, DAM0054433
White Lodge
Walgrave STM3232A
Postcode: NN6 9PY Client
Contact: Andy Keeler Not Advised
29.06.15
Site: Wickes, London Road, Crawley 03.07.15-06.07.15
Disturbed
Test Results:
TP01 0.60 Cream chalky CLAY 52 29
TP05 1.10 Cream chalky CLAY 43 26
TP09 1.10 Cream chalky CLAY 41 25
Sample Preparation:
*
**
Certified that the laboratory testing was carried out in accordance with BS 1377-2: 1990: Method 3.2, 4.4 and 5
Page: 1 of 1 [�] M. Carr - Section Manager
Date Reported: 08.07.15 Signed [ ] D. Berrill - Laboratory Manager
For and on behalf of Environmental Scientifics Group
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation
This Test Report may not be reproduced other than in full, except with the prior written approval of the issuing laboratory
Environmental Scientifics Group. Registered in England No. 2880501. Registered Office: ESG House, Bretby Business Park, Ashby Road, Burton on Trent DE15 0YZ
abc0001
Client Reference:
Batch Number:
Report No:
Determination of Moisture Content and Atterberg Limits
Moisture
Content
(%)
45248990
Sampled by:
Date Sampled:
Depth (m)
10045248992 N/A 16
% Passing
425µm
(Estimated)
45248991 N/A 17 100
Location Description
N/A 100
Liquid
Limit
Laboratory
Reference
Actual % passing 425µm BS Test Sieve from separate grading analysis
Washed over 425µm BS Test Sieve
As Received
Date Received:
Tested From:
Sample Type:
Plastic
Limit
Plasticity
Index
23
TE
ST
RE
PO
RTESG
2 Newton Close
Drayton Fields Industrial Estate
Daventry
Northants NN11 8RR
Telephone: +44 (0) 1327 703828
Facsimile: +44 (0) 1327 300154
Chemtest Ltd.
Depot Road
Newmarket
CB8 0AL
Tel: 01638 606070
Email: [email protected]
Report Number: 15-15101 Issue-1
Initial Date of Issue: 08-Jul-2015
Client: Soiltechnics Limited
Client Address:
Cedar Barn
White Lodge
Walgrave
Northampton
Northamptonshire
NN6 9PY
Contact(s): Rachel Brown
Project:
Quotation No.: Date Received: 01-Jul-2015
Order No.: 19253 Date Instructed: 01-Jul-2015
No. of Samples: 1
Turnaround: (Wkdays) 5 Results Due Date: 07-Jul-2015
Date Approved: 08-Jul-2015
Approved By:
Details: Darrell Hall, Laboratory Director
Final Report
STM3210B Wickes, London Road, Crawley
Page 1 of 3
Results Summary - 2 Stage WACProject: STM3210B Wickes, London Road, Crawley
Chemtest Job No: 15-15101
Chemtest Sample ID: 159957 Limits
Sample Ref: WAC
Sample ID: 59
Top Depth(m): 0.20
Bottom Depth(m): 0.30
Sampling Date: 26-Jun-2015
Determinand SOP Accred. Units
Total Organic Carbon 2625 U % 1.6 3 5 6
Loss on Ignition 2610 U % 4.2 -- -- 10
Total BTEX 2760 U mg/kg < 0.010 6 -- --
Total PCBs (7 congeners) 2815 U mg/kg < 0.10 1 -- --
TPH Total WAC (Mineral Oil) 2670 U mg/kg 520 500 -- --
Total (of 17) PAHs 2700 N mg/kg 11 100 -- --
pH 2010 U 9.2 -- >6 --
Acid Neutralisation Capacity 2015 N mol/kg 0.31 -- To evaluate To evaluate
Eluate Analysis2:1
mg/l
8:1
mg/l
2:1
mg/kg
Cumulative
10:1
mg/kg
Arsenic 1450 U 0.008 0.005 < 0.050 0.053 0.5 2 25
Barium 1450 U 0.032 0.017 < 0.50 < 0.50 20 100 300
Cadmium 1450 U 0.00013 < 0.00010 < 0.010 < 0.010 0.04 1 5
Chromium 1450 U 0.005 < 0.001 < 0.050 < 0.050 0.5 10 70
Copper 1450 U 0.017 0.007 < 0.050 < 0.050 2 50 100
Mercury 1450 U < 0.0005 < 0.0005 < 0.001 < 0.005 0.01 0.2 2
Molybdenum 1450 U 0.056 0.011 0.11 0.17 0.5 10 30
Nickel 1450 U 0.005 0.002 < 0.050 < 0.050 0.4 10 40
Lead 1450 U 0.002 0.001 < 0.010 0.011 0.5 10 50
Antimony 1450 U 0.013 0.008 0.026 0.088 0.06 0.7 5
Selenium 1450 U 0.005 0.004 0.01 0.039 0.1 0.5 7
Zinc 1450 U 0.011 0.004 < 0.50 < 0.50 4 50 200
Chloride 1220 U 12 7.8 24 83 800 15000 25000
Fluoride 1220 U 1.1 0.17 2.2 2.9 10 150 500
Sulphate 1220 U 120 32 240 430 1000 20000 50000
Total Dissolved Solids 1020 N 200 89 400 1000 4000 60000 100000
Phenol Index 1920 U < 0.030 < 0.030 < 0.30 < 0.50 1 - -
Dissolved Organic Carbon 1610 U 36 16 72 190 500 800 1000
Soild Information
Dry mass of test portion/kg 0.175 0.332
Moisture (%) 9.2 1.4
0.223
Leachant volume 1st extract/l
Leachant volume 2nd extract/l
Eluant recovered from 1st extract/l
Landflll Waste Acceptance Criteria
Inert Waste
Landfill
Stable Non-
reactive
Hazardous
waste in
non-
hazardous
Hazardous
Waste
Landfill
Limit values for compliance leaching
test using BS EN 12457-3 at L/S 10 l/kg
Leachate Test Information
Page 2 of 3
Report Information
Key
U UKAS accredited
M MCERTS and UKAS accredited
N Unaccredited
S This analysis has been subcontracted to a UKAS accredited laboratory that is accredited for this analysis
SN This analysis has been subcontracted to a UKAS accredited laboratory that is not accredited for this analysis
T This analysis has been subcontracted to an unaccredited laboratory
I/S Insufficient Sample
U/S Unsuitable Sample
N/E not evaluated
< "less than"
> "greater than"
Comments or interpretations are beyond the scope of UKAS accreditation
The results relate only to the items tested
Uncertainty of measurement for the determinands tested are available upon request
None of the results in this report have been recovery corrected
All results are expressed on a dry weight basis
The following tests were analysed on samples as received and the results subsequently corrected to a dry
weight basis TPH, BTEX, VOCs, SVCOs, PCBs, Phenols
For all other tests the samples were dried at < 37°C prior to analysis
All Asbestos testing is performed at our Coventry laboratory
Issue numbers are sequential starting with 1 all subsequent reports are incremented by 1
Sample Deviation Codes
A - Date of sampling not supplied
B - Sample age exceeds stability time (sampling to extraction)
C - Sample not received in appropriate containers
D - Broken Container
Sample Retention and Disposal
All soil samples will be retained for a period of 60 days from the date of receipt
All water samples will be retained for 14 days from the date of receipt
Charges may apply to extended sample storage
If you require extended retention of samples, please email your requirements to:
Page 3 of 3
Chemtest Ltd.
Depot Road
Newmarket
CB8 0AL
Tel: 01638 606070
Email: [email protected]
Report Number: 15-15278 Issue-1
Initial Date of Issue: 07-Jul-2015
Client: Soiltechnics Limited
Client Address:
Cedar Barn
White Lodge
Walgrave
Northampton
Northamptonshire
NN6 9PY
Contact(s): Rachel Brown
Project:
Quotation No.: Date Received: 01-Jul-2015
Order No.: 19254 Date Instructed: 01-Jul-2015
No. of Samples: 11 Target Due Date: 03-Jul-2015
Turnaround: (Wkdays) 5 Results Due Date: 07-Jul-2015
Date Approved: 07-Jul-2015
Approved By:
Details: Darrell Hall, Laboratory Director
Final Report
STM3210B - Wickes, London Road, Crawley
Page 1 of 7
Results Summary - Soil
Project: STM3210B - Wickes, London Road, Crawley
Client: Soiltechnics Limited 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278
Quotation No.: 160878 160879 160880 160881 160882 160883 160885 160886 160887 160888
Order No.: 19254 TP01 TP02 TP03 TP03 TP03 TP04 TP06 TP07 TP08 TP09
2 7 17 19 21 24 37 46 51 53
SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL
0.20 0.20 0.50 1.10 1.60 0.20 0.20 1.30 1.20 0.10
26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15
Determinand Accred. SOP Units LOD
ACM Type U 2192 - - - - -
Asbestos Identification U 2192 % 0.001No Asbestos
Detected
No Asbestos
Detected
No Asbestos
Detected
No Asbestos
Detected
No Asbestos
Detected
Asbestos By Fibre Counting U 2192 % 0.001 - - - - -
Total Asbestos N 2192 % 0.001 - - - - -
Moisture N 2030 % 0.02 8.1 7.0 6.8 14 14 8.4 3.4 19 14 4.5
Soil Colour N brown brown brown brown brown brown brown brown
Other Material N stones stones none stones stones none none stones
Soil Texture N clay sand sand sand sand clay clay sand
pH M 2010 9.3 8.8 6.1 9.1 9.2 7.3 7.3 8.7
Boron (Hot Water Soluble) M 2120 mg/kg 0.4 < 0.40 0.85 2.7 0.44 < 0.40
Sulphate (2:1 Water Soluble) as SO4 M 2120 g/l 0.01 0.032 0.091 0.030
Total Sulphur M 2175 % 0.01 0.010 0.020 0.010
Cyanide (Complex) M 2300 mg/kg 0.5 < 0.50 < 0.50 < 0.50 < 0.50 < 0.50
Cyanide (Free) M 2300 mg/kg 0.5 < 0.50 < 0.50 < 0.50 < 0.50 < 0.50
Cyanide (Total) M 2300 mg/kg 0.5 < 0.50 < 0.50 < 0.50 < 0.50 < 0.50
Sulphate (Acid Soluble) M 2430 % 0.01 0.021 0.014 < 0.010
Arsenic M 2450 mg/kg 1 30 17 25 22 8.3
Beryllium U 2450 mg/kg 1 < 1.0 < 1.0 < 1.0 < 1.0 < 1.0
Cadmium M 2450 mg/kg 0.1 0.44 0.24 0.66 0.42 0.15
Chromium M 2450 mg/kg 1 27 22 26 13 16
Copper M 2450 mg/kg 0.5 40 22 20 7.4 12
Mercury M 2450 mg/kg 0.1 0.26 0.10 0.15 < 0.10 < 0.10
Nickel M 2450 mg/kg 0.5 25 25 17 11 20
Lead M 2450 mg/kg 0.5 38 38 44 31 22
Selenium M 2450 mg/kg 0.2 < 0.20 < 0.20 < 0.20 < 0.20 < 0.20
Vanadium U 2450 mg/kg 5 23 18 24 18 16
Zinc M 2450 mg/kg 0.5 72 55 120 55 51
Chromium (Hexavalent) N 2490 mg/kg 0.5 < 0.50 < 0.50 < 0.50 < 0.50 < 0.50
Organic Matter M 2625 % 0.4 2.9 1.2 2.4 0.57 0.90 < 0.40 0.60
Total Organic Carbon M 2625 % 0.2 1.4 0.33
Aliphatic TPH >C5-C6 N 2675 mg/kg 0.01 < 0.010 < 0.010
Aliphatic TPH >C6-C8 N 2675 mg/kg 0.01 < 0.010 < 0.010
Chemtest Job No.:
Top Depth (m):
Bottom Depth(m):
Date Sampled:
Chemtest Sample ID.:
Client Sample Ref.:
Client Sample ID.:
Sample Type:
Page 2 of 7
Results Summary - Soil
Project: STM3210B - Wickes, London Road, Crawley
Client: Soiltechnics Limited 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278
Quotation No.: 160878 160879 160880 160881 160882 160883 160885 160886 160887 160888
Order No.: 19254 TP01 TP02 TP03 TP03 TP03 TP04 TP06 TP07 TP08 TP09
2 7 17 19 21 24 37 46 51 53
SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL
0.20 0.20 0.50 1.10 1.60 0.20 0.20 1.30 1.20 0.10
26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15
Determinand Accred. SOP Units LOD
Chemtest Job No.:
Top Depth (m):
Bottom Depth(m):
Date Sampled:
Chemtest Sample ID.:
Client Sample Ref.:
Client Sample ID.:
Sample Type:
Aliphatic TPH >C8-C10 N 2675 mg/kg 0.1 0.11 20
Aliphatic TPH >C10-C12 N 2675 mg/kg 0.1 6.6 150
Aliphatic TPH >C12-C16 N 2675 mg/kg 0.1 10 360
Aliphatic TPH >C16-C21 N 2675 mg/kg 0.1 2.7 96
Aliphatic TPH >C21-C35 N 2675 mg/kg 0.1 49 4.2
Aliphatic TPH >C35-C44 N 2675 mg/kg 0.1 0.32 < 0.10
Total Aliphatic Hydrocarbons N 2675 mg/kg 1 69 630
Aromatic TPH >C5-C7 N 2675 mg/kg 0.01 < 0.010 < 0.010
Aromatic TPH >C7-C8 N 2675 mg/kg 0.01 < 0.010 < 0.010
Aromatic TPH >C8-C10 N 2675 mg/kg 0.1 < 0.10 11
Aromatic TPH >C10-C12 N 2675 mg/kg 0.1 2.6 40
Aromatic TPH >C12-C16 N 2675 mg/kg 0.1 6.2 39
Aromatic TPH >C16-C21 N 2675 mg/kg 0.1 3.6 12
Aromatic TPH >C21-C35 N 2675 mg/kg 0.1 8.5 2.2
Aromatic TPH >C35-C44 N 2675 mg/kg 0.1 < 0.10 < 0.10
Total Aromatic Hydrocarbons N 2675 mg/kg 1 21 100
Total Petroleum Hydrocarbons N 2675 mg/kg 2 90 740
Benzene M 2760 µg/kg 1 < 1.0 < 1.0
Toluene M 2760 µg/kg 1 < 1.0 < 1.0
Ethylbenzene M 2760 µg/kg 1 < 1.0 < 1.0
m & p-Xylene M 2760 µg/kg 1 < 1.0 < 1.0
o-Xylene M 2760 µg/kg 1 < 1.0 < 1.0
Naphthalene M 2800 mg/kg 0.1 < 0.10 0.40 0.35 < 0.10 0.25
Acenaphthylene N 2800 mg/kg 0.1 < 0.10 0.14 < 0.10 < 0.10 < 0.10
Acenaphthene M 2800 mg/kg 0.1 < 0.10 0.10 0.11 < 0.10 < 0.10
Fluorene M 2800 mg/kg 0.1 < 0.10 0.24 < 0.10 < 0.10 < 0.10
Phenanthrene M 2800 mg/kg 0.1 0.67 0.34 0.49 < 0.10 0.17
Anthracene M 2800 mg/kg 0.1 0.24 0.16 0.11 < 0.10 < 0.10
Fluoranthene M 2800 mg/kg 0.1 1.1 1.2 1.4 < 0.10 0.41
Pyrene M 2800 mg/kg 0.1 0.83 1.1 1.1 < 0.10 0.37
Benzo[a]anthracene M 2800 mg/kg 0.1 0.39 0.42 0.42 < 0.10 < 0.10
Chrysene M 2800 mg/kg 0.1 0.50 0.40 0.40 < 0.10 < 0.10
Benzo[b]fluoranthene M 2800 mg/kg 0.1 0.65 0.53 0.40 < 0.10 < 0.10
Page 3 of 7
Results Summary - Soil
Project: STM3210B - Wickes, London Road, Crawley
Client: Soiltechnics Limited 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278 15-15278
Quotation No.: 160878 160879 160880 160881 160882 160883 160885 160886 160887 160888
Order No.: 19254 TP01 TP02 TP03 TP03 TP03 TP04 TP06 TP07 TP08 TP09
2 7 17 19 21 24 37 46 51 53
SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL SOIL
0.20 0.20 0.50 1.10 1.60 0.20 0.20 1.30 1.20 0.10
26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15 26-Jun-15
Determinand Accred. SOP Units LOD
Chemtest Job No.:
Top Depth (m):
Bottom Depth(m):
Date Sampled:
Chemtest Sample ID.:
Client Sample Ref.:
Client Sample ID.:
Sample Type:
Benzo[k]fluoranthene M 2800 mg/kg 0.1 0.19 0.15 < 0.10 < 0.10 < 0.10
Benzo[a]pyrene M 2800 mg/kg 0.1 0.30 0.35 0.23 < 0.10 < 0.10
Indeno(1,2,3-c,d)Pyrene M 2800 mg/kg 0.1 0.31 0.22 0.11 < 0.10 < 0.10
Dibenz(a,h)Anthracene N 2800 mg/kg 0.1 < 0.10 < 0.10 < 0.10 < 0.10 < 0.10
Benzo[g,h,i]perylene M 2800 mg/kg 0.1 0.31 0.25 0.14 < 0.10 < 0.10
Total Of 16 PAH's N 2800 mg/kg 2 5.5 6.0 5.3 < 2.0 < 2.0
Total Phenols M 2920 mg/kg 0.3 < 0.30 < 0.30 < 0.30 < 0.30 < 0.30
Page 4 of 7
Results Summary - Leachate
Project: STM3210B - Wickes, London Road, Crawley
Client: Soiltechnics Limited 15-15278 15-15278
Quotation No.: 160878 160884
Order No.: 19254 TP01 TP05
2 30
SOIL SOIL
0.20 0.20
26-Jun-15 26-Jun-15
Determinand Accred. SOP Units LOD
pH U 1010 9.7 9.4
Nitrate U 1220 mg/l 0.5 < 0.50 < 0.50
Sulphate U 1220 mg/l 1 35 24
Cyanide (Total) U 1300 mg/l 0.05 < 0.050 < 0.050
Cyanide (Free) U 1300 mg/l 0.05 < 0.050 < 0.050
Cyanide (Complex) U 1300 mg/l 0.05 < 0.050 < 0.050
Sulphide U 1325 mg/l 0.05 < 0.050 < 0.050
Arsenic (Dissolved) U 1450 µg/l 1 5.9 12
Beryllium (Dissolved) U 1450 µg/l 1 < 1.0 < 1.0
Boron (Dissolved) U 1450 µg/l 20 51 110
Cadmium (Dissolved) U 1450 µg/l 0.08 < 0.080 < 0.080
Chromium (Dissolved) U 1450 µg/l 1 6.0 5.1
Copper (Dissolved) U 1450 µg/l 1 10 12
Mercury (Dissolved) U 1450 µg/l 0.5 < 0.50 < 0.50
Nickel (Dissolved) U 1450 µg/l 1 2.0 1.1
Lead (Dissolved) U 1450 µg/l 1 < 1.0 4.1
Selenium (Dissolved) U 1450 µg/l 1 4.5 3.3
Vanadium (Dissolved) U 1450 µg/l 1 7.7 11
Zinc (Dissolved) U 1450 µg/l 1 11 8.8
Naphthalene U 1800 µg/l 0.1 < 0.10 < 0.10
Acenaphthylene U 1800 µg/l 0.1 0.25 < 0.10
Acenaphthene U 1800 µg/l 0.1 < 0.10 < 0.10
Fluorene U 1800 µg/l 0.1 < 0.10 < 0.10
Phenanthrene U 1800 µg/l 0.1 1.0 0.78
Anthracene U 1800 µg/l 0.1 0.66 0.22
Fluoranthene U 1800 µg/l 0.1 1.6 3.7
Pyrene U 1800 µg/l 0.1 1.8 4.1
Benzo[a]anthracene U 1800 µg/l 0.1 0.41 1.1
Chrysene U 1800 µg/l 0.1 0.46 1.1
Benzo[b]fluoranthene U 1800 µg/l 0.1 0.54 1.3
Benzo[k]fluoranthene U 1800 µg/l 0.1 0.18 0.51
Benzo[a]pyrene U 1800 µg/l 0.1 0.40 0.93
Indeno(1,2,3-c,d)Pyrene U 1800 µg/l 0.1 0.31 0.44
Chemtest Job No.:
Top Depth (m):
Bottom Depth(m):
Date Sampled:
Chemtest Sample ID.:
Client Sample Ref.:
Client Sample ID.:
Sample Type:
Page 5 of 7
Results Summary - Leachate
Project: STM3210B - Wickes, London Road, Crawley
Client: Soiltechnics Limited 15-15278 15-15278
Quotation No.: 160878 160884
Order No.: 19254 TP01 TP05
2 30
SOIL SOIL
0.20 0.20
26-Jun-15 26-Jun-15
Determinand Accred. SOP Units LOD
Chemtest Job No.:
Top Depth (m):
Bottom Depth(m):
Date Sampled:
Chemtest Sample ID.:
Client Sample Ref.:
Client Sample ID.:
Sample Type:
Dibenz(a,h)Anthracene U 1800 µg/l 0.1 < 0.10 < 0.10
Benzo[g,h,i]perylene U 1800 µg/l 0.1 0.29 0.87
Total Of 16 PAH's U 1800 µg/l 2 7.9 15
Total Phenols U 1920 mg/l 0.03 < 0.030 < 0.030
Page 6 of 7
Report Information
Key
U UKAS accredited
M MCERTS and UKAS accredited
N Unaccredited
S This analysis has been subcontracted to a UKAS accredited laboratory that is accredited for this analysis
SN This analysis has been subcontracted to a UKAS accredited laboratory that is not accredited for this analysis
T This analysis has been subcontracted to an unaccredited laboratory
I/S Insufficient Sample
U/S Unsuitable Sample
N/E not evaluated
< "less than"
> "greater than"
Comments or interpretations are beyond the scope of UKAS accreditation
The results relate only to the items tested
Uncertainty of measurement for the determinands tested are available upon request
None of the results in this report have been recovery corrected
All results are expressed on a dry weight basis
The following tests were analysed on samples as received and the results subsequently corrected to a dry
weight basis TPH, BTEX, VOCs, SVCOs, PCBs, Phenols
For all other tests the samples were dried at < 37°C prior to analysis
All Asbestos testing is performed at our Coventry laboratory
Issue numbers are sequential starting with 1 all subsequent reports are incremented by 1
Sample Deviation Codes
A - Date of sampling not supplied
B - Sample age exceeds stability time (sampling to extraction)
C - Sample not received in appropriate containers
D - Broken Container
Sample Retention and Disposal
All soil samples will be retained for a period of 60 days from the date of receipt
All water samples will be retained for 14 days from the date of receipt
Charges may apply to extended sample storage
If you require extended retention of samples, please email your requirements to:
Page 7 of 7
Proposed commercial developmentLondon Road, Crawley
Adopted Model:
Contaminant Guideline value
No. of tests
Min. Max. Mean Initial screening Concentration Shapiro-Wilk Normality test
Probability plot test
Data normally distributed?
95% UCL of mean
Contaminant
mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg
Arsenic SGV 640 5 8.3 30.0 20.5 0 Mean value below guideline y 0 0 normal normal n 36.6 Arsenic
Beryllium GAC 420 5 1.0 1.0 1.0 0 Mean value below guideline y 0 0 not normal not normal n 1.0 Beryllium
Boron GAC 192000 5 0.4 2.7 1.0 0 Mean value below guideline n 0 0 not normal not normal n 2.9 Boron
Cadmium SGV 230 5 0.2 0.7 0.4 0 Mean value below guideline y 0 0 normal normal n 0.8 Cadmium
Chromium GAC 30400 5 13.0 27.0 20.8 0 Mean value below guideline y 0 0 normal normal n 32.8 Chromium
Copper GAC 71700 5 7.4 40.0 20.3 0 Mean value below guideline y 0 0 normal normal n 44.7 Copper
Cyanide (total) ATK 34 5 0.5 0.5 0.5 0 Mean value below guideline y 0 0 not normal not normal n 0.5 Cyanide (total)
Lead ATK 6490 5 22.0 44.0 34.6 0 Mean value below guideline y 0 0 normal normal n 51.0 Lead
Mercury# SGV 26 5 0.1 0.3 0.1 0 Mean value below guideline n 0 0 not normal not normal n 0.3 Mercury#
Nickel SGV 1800 5 11.0 25.0 19.6 0 Mean value below guideline y 0 0 normal normal n 31.1 Nickel
Selenium SGV 13000 5 0.2 0.2 0.2 0 Mean value below guideline y 0 0 not normal not normal n 0.2 Selenium
Vanadium GAC 3160 5 16.0 24.0 19.8 0 Mean value below guideline y 0 0 normal normal n 26.6 Vanadium
Zinc GAC 665000 5 51.0 120.0 70.6 0 Mean value below guideline n 0 0 not normal not normal n 126.7 Zinc
SGV Soil Guideline Value as published by the Environment Agency 2009GAC Generic Assessment Criterion as published by LQM and CIEHSSV Soil Screening Value as derived by SoiltechnicsATK Soil Screening Value derived by AtkinsNGV No Guideline ValueBPG5 Guideline from BPG Note 5 as published by Forest Research
# Assumed to be elemental mercury as initial screening value
Analysis of test data in relation to concentrations of inorganic chemical contaminantsIndustrial/Commercial
Receptor: Proposed site users and construction operatives
No.
of t
ests
ab
ove
guid
elin
e va
lue
Test procedure Summary of test data Initial comparison Outlier test Normality test UCL
Gui
delin
e so
urce
Pass
out
lier
test
?
Num
ber o
f ou
tlier
s
Loca
tion
of
outli
er
Dept
hTable number 1
Title Analysis of test data in relation to concentrations of inorganic chemical contaminants
Report ref: STM3210B-G01 August 2015 Appendix F
Proposed commercial developmentLondon Road, Crawley
Adopted model:Receptor:
Contaminant Guideline value
No. of tests
Min. Max. Mean Initial screening Concentration Shapiro-Wilk Normality test
Probability plot test
Data normally distributed?
95% UCL of mean
Contaminant
mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg
Acenaphthene GAC 85000 5 0.1 0.1 0.1 0 Mean value below guideline n 0 0 not normal not normal n 0.1 Acenaphthene
Acenaphthylene GAC 84000 5 0.1 0.1 0.1 0 Mean value below guideline n 0 0 not normal not normal n 0.1 Acenaphthylene
Anthracene GAC 530000 5 0.1 0.2 0.1 0 Mean value below guideline y 0 0 normal normal n 0.3 Anthracene
Benzo(a)anthracene GAC 90 5 0.1 0.4 0.3 0 Mean value below guideline y 0 0 not normal not normal n 0.6 Benzo(a)anthracene
Benzo(a)pyrene GAC 14 5 0.1 0.4 0.2 0 Mean value below guideline y 0 0 normal normal n 0.4 Benzo(a)pyrene
Benzo(b)fluoranthene GAC 100 5 0.1 0.7 0.4 0 Mean value below guideline y 0 0 normal normal n 0.8 Benzo(b)fluoranthene
Benzo(g,h,i)perylene GAC 650 5 0.1 0.3 0.2 0 Mean value below guideline y 0 0 normal normal n 0.4 Benzo(g,h,i)perylene
Benzo(k)fluoranthene GAC 140 5 0.1 0.2 0.1 0 Mean value below guideline y 0 0 normal normal n 0.2 Benzo(k)fluoranthene
Chrysene GAC 140 5 0.1 0.5 0.3 0 Mean value below guideline y 0 0 normal normal n 0.7 Chrysene
Dibenzo(a,h)anthracene GAC 13 5 0.1 0.3 0.2 0 Mean value below guideline y 0 0 normal normal n 0.4 Dibenzo(a,h)anthracene
Fluoranthene GAC 23000 5 0.1 1.4 0.8 0 Mean value below guideline y 0 0 normal normal n 1.9 Fluoranthene
Fluorene GAC 64000 5 0.1 0.2 0.1 0 Mean value below guideline n 0 0 not normal not normal n 0.3 Fluorene
Indeno(1,2,3-cd)pyrene GAC 60 5 0.1 0.1 0.1 0 Mean value below guideline y 0 0 not normal not normal n 0.1 Indeno(1,2,3-cd)pyrene
Naphthalene GAC 200 5 0.1 0.4 0.2 0 Mean value below guideline y 0 0 normal normal n 0.5 Naphthalene
Phenanthrene GAC 22000 5 0.1 0.7 0.4 0 Mean value below guideline y 0 0 normal normal n 0.8 Phenanthrene
Phenols SGV 3200 5 0.3 0.3 0.3 0 Mean value below guideline y 0 0 not normal not normal n 0.3 Phenols
Pyrene GAC 54000 5 0.1 1.1 0.7 0 Mean value below guideline y 0 0 not normal not normal n 1.6 Pyrene
Notes
SGV Soil Guideline Value as published by the Environment AgencyGAC Generic Assessment Criterion as published by LQM and CIEHSSV Soil Screening Value as derived by SoiltechnicsNGV No Guideline Value
Industrial/Commercial
Analysis of test data in relation to concentrations of organic chemical contaminants
Pass
out
lier
test
?
Num
ber o
f ou
tlier
s
No.
of t
ests
ab
ove
guid
elin
e va
lue
Gui
delin
e so
urce
Loca
tion
of
outli
er
Dept
h
Proposed site users, construction operatives and vegetation
Normality test UCLTest procedure Summary of test data Initial Screening Oulier test
Table number 2
Title Analysis of test data in relation to concentrations of organic chemical contaminants.
Report ref: STM3210BG01 Revision 0
August 2015 Appendix F
Proposed commercial developmentLondon Road, Crawley
Adopted Model:
Contaminant Guideline value
No. of tests
Min. Max. Mean Initial screening Concentration Shapiro-Wilk Normality test
Probability plot test
Data normally distributed?
95% UCL of mean
Contaminant
mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg
Arsenic SGV 640 5 8.3 30.0 20.5 0 Mean value below guideline y 0 0 normal normal n 36.6 Arsenic
Beryllium GAC 420 5 1.0 1.0 1.0 0 Mean value below guideline y 0 0 not normal not normal n 1.0 Beryllium
Boron GAC 192000 5 0.4 2.7 1.0 0 Mean value below guideline n 0 0 not normal not normal n 2.9 Boron
Cadmium SGV 230 5 0.2 0.7 0.4 0 Mean value below guideline y 0 0 normal normal n 0.8 Cadmium
Chromium GAC 30400 5 13.0 27.0 20.8 0 Mean value below guideline y 0 0 normal normal n 32.8 Chromium
Copper BPG5 130 5 7.4 40.0 20.3 0 Mean value below guideline y 0 0 normal normal n 44.7 Copper
Cyanide (total) ATK 34 5 0.5 0.5 0.5 0 Mean value below guideline y 0 0 not normal not normal n 0.5 Cyanide (total)
Lead ATK 6490 5 22.0 44.0 34.6 0 Mean value below guideline y 0 0 normal normal n 51.0 Lead
Mercury# SGV 26 5 0.1 0.3 0.1 0 Mean value below guideline n 0 0 not normal not normal n 0.3 Mercury#
Nickel SGV 1800 5 11.0 25.0 19.6 0 Mean value below guideline y 0 0 normal normal n 31.1 Nickel
Selenium SGV 13000 5 0.2 0.2 0.2 0 Mean value below guideline y 0 0 not normal not normal n 0.2 Selenium
Vanadium GAC 3160 5 16.0 24.0 19.8 0 Mean value below guideline y 0 0 normal normal n 26.6 Vanadium
Zinc BPG5 300 5 51.0 120.0 70.6 0 Mean value below guideline n 0 0 not normal not normal n 126.7 Zinc
SGV Soil Guideline Value as published by the Environment Agency 2009GAC Generic Assessment Criterion as published by LQM and CIEHSSV Soil Screening Value as derived by SoiltechnicsATK Soil Screening Value derived by AtkinsNGV No Guideline ValueBPG5 Guideline from BPG Note 5 as published by Forest Research
# Assumed to be elemental mercury as initial screening value
Pass
out
lier
test
?
Num
ber o
f ou
tlier
s
Loca
tion
of
outli
er
Dept
h
Analysis of test data in relation to concentrations of inorganic chemical contaminantsIndustrial/Commercial and BPG5
Receptor: Vegetation
No.
of t
ests
ab
ove
guid
elin
e va
lue
Test procedure Summary of test data Initial comparison Outlier test Normality test UCL
Gui
delin
e so
urce
Table number 3
Title Analysis of test data in relation to concentrations of inorganic chemical contaminants.
Report ref: STM3210B-G01 August 2015 Appendix F
Proposed commercial developmentLondon Road, Crawley
Summary of petroleum hydrocarbon test results
BTEX (Red highlights indicate exceedance of guideline value)
Indicator unit Guideline value ConcentrationTP03 TP03 0 0 00.50 1.10 0 0 0
Benzene mg/kg 95 0.001 0.001 0 0 0Toluene mg/kg 4400 0.001 0.001 0 0 0Ethylbenzene mg/kg 2800 0.001 0.001 0 0 0o-Xylene mg/kg 2600 0.001 0.001 0 0 0m,p-Xylene mg/kg 3200 0.001 0.001 0 0 0
Hydrocarbon banding (Red highlights indicate exceedance of GAC value)
Fraction unit GAC ConcentrationTP03 TP03 0 0 00.50 1.10 0 0 0
AliphaticEC 5 - 6 mg/kg 3400 < 0.010 < 0.010 0 0 0EC >6 - 8 mg/kg 8300 < 0.010 < 0.010 0 0 0EC >8 - 10 mg/kg 2100 0.11 20 0 0 0EC >10 - 12 mg/kg 10000 6.6 150 0 0 0EC >12 - 16 mg/kg 61000 10 360 0 0 0EC >16 - 35 mg/kg 1600000 51.7 100.2 0 0 0EC >35 - 44 mg/kg 1600000 0.32 < 0.10 0 0 0AromaticEC 5 - 7 (benzene) mg/kg 28000 < 0.010 < 0.010 0 0 0EC >7 - 8 (toluene) mg/kg 59000 < 0.010 < 0.010 0 0 0EC >8 - 10 mg/kg 3700 < 0.10 11 0 0 0EC >10 - 12 mg/kg 17000 2.6 40 0 0 0EC >12 - 16 mg/kg 36000 6.2 39 0 0 0EC >16 - 21 mg/kg 28000 3.6 12 0 0 0EC >21 - 35 mg/kg 28000 8.5 2.2 0 0 0EC >35 - 44 mg/kg 28000 < 0.10 < 0.10 0 0 0
Notes 1. Generic Assessment Criteria (GAC) as presented in "Generic Assessment Criteria for Human Health Risk Assessment" published by Land Quality Management (LQM) and the Chartered Institute of Environmental Health (CIEH).
Table number 4
Title Comparison of measured concentrations of petroleum hydrocarbons with guideline values.
Report ref: STM3210BG01
August 2015 Appendix F
Proposed commercial developmentLondon Road, Crawley
Summary of leachate test resultsReceptor GroundwaterWater type FreshwaterFish type SalmonidWater hardness >250 mg/l
Location TP01 TP05Depth (m) 0.20 0.20
Inorganics (μg/l)Arsenic 50 EQS (f) 6 12Boron 2000 EQS (f) 51 110Cadmium 5 EQS (f) < 0.080 < 0.080Chromium 50 EQS (f) 6 5Copper 28 EQS (f) 10 12Lead 20 EQS (f) < 1.0 4Mercury 1 EQS (f) < 0.50 < 0.50Nickel 200 EQS (f) 2 1Selenium1 10 UKDWS 5 3
Vanadium2 60 EQS (f) 8 11Zinc 125 EQS (f) 11 9Free Cyanide1 50 UKDWS <50 <50 0Nitrate as N 50000 UKDWS <500 <500 <500Sulphate as SO4 400000 EQS(f) 35000 24000 0
PAH (μg/l)
Benzo(a)pyrene1,4 0.01 UKDWS 0.40 0.93
Naphthalene2 10 EQS (f) < 0.10 < 0.10
Sum of 4 PAH1 0.1 UKDWS 1.1 2.8 #VALUE!
TPH (μg/l)
Hydrocarbons1 10 UKDWSBenzene 30 EQS (f)Toluene2 50 EQS (f)Ethyl benzene3 300 WHOXylene2 30 EQS (f)
Contaminant Guideline value (μg/l)
Guideline source
(measured at a concentration of ?? located at ??)$
Notes 1 EQS values not available 2 UKDWS not available 3 Lower detectable limit above UKDWS. Concentrations below detectable limits are not considered further. * Taken as lower detection limit # Taken as lower detection limit of a single compound $ Hardness data presented by the Environment Agency UKDWS UK Drinking Water Standard Guideline taken from "The Water Supply (Water Quality) Regulations 2000" EQS (f) Environmental Quality Standard for freshwater published by the Environment Agency EQS (s) Environmental Quality Standard for saltwater published by the Environment Agency
Table number 5
Title Comparison of measured concentrations with guideline values for water receptors
Report ref: STM3210B-G01 Revision 0
August 2014 Appendix F
Proposed commercial developmentLondon Road, Crawley
Source Pathway ReceptorHumans Vegetation Water RiskIngestion of air-borne dusts
Ingestion of soil Ingestion of vegetables and soil attached to vegetables
Inhalation of air-borne dusts
Inhalation of vapours
Dermal contact with soil and dust
Root uptake, deposition to shoots and foliage contact
Percolation of water through contaminated soils
Near-surface water run-off through contaminated
Saturation of contaminated soils by flood waters
SoilsLikely Low likelihood Unlikely Likely Likely Likely - - - - Proposed site users Adult Medium ModerateLikely Likely Unlikely Likely Likely Likely - - - - Construction operatives Adult Medium Moderate- - - - - - Likely - - - Vegetation (current) - Medium Moderate- - - - - - Likely - - - Vegetation (proposed) - Medium Moderate- - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Medium ModerateLikely Low likelihood Unlikely Likely Likely Likely - - - - Proposed site users Adult Medium ModerateLikely Likely Unlikely Likely Likely Likely - - - - Construction operatives Adult Medium Moderate- - - - - - Likely - - - Vegetation (current) - Medium Moderate- - - - - - Likely - - - Vegetation (proposed) - Medium Moderate- - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Medium ModerateLikely Low likelihood Unlikely Likely Likely Likely - - - - Proposed site users Adult Medium ModerateLikely Likely Unlikely Likely Likely Likely - - - - Construction operatives Adult Medium Moderate- - - - - - Likely - - - Vegetation (current) - Medium Moderate- - - - - - Likely - - - Vegetation (proposed) - Medium Moderate- - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Medium ModerateLikely Low likelihood Unlikely Likely Likely Likely - - - - Proposed site users Adult Medium ModerateLikely Likely Unlikely Likely Likely Likely - - - - Construction operatives Adult Medium Moderate- - - - - - Likely - - - Vegetation (current) - Medium Moderate- - - - - - Likely - - - Vegetation (proposed) - Medium Moderate- - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Medium Moderate
Risk assessment to CIRIA C552
Initial Conceptual Model (following source-pathway-receptor assessment)Proposed site use commercial/industrial
Made Ground
Hydrocarbons at TP03
Adjacent bus depot
Adjacent petrol filling station
Consequence of risk occurring via most likely pathway
Title Conceptual Site Model
Report ref: STM3210B-G01 Revision 0
August 2015 Appendix G
Table number 1
Proposed commercial developmentLondon Road, Crawley
Source Pathway ReceptorHumans Vegetation Water RiskIngestion of air-borne dusts
Ingestion of soil Ingestion of vegetables and soil attached to vegetables
Inhalation of air-borne dusts
Inhalation of vapours
Dermal contact with soil and dust
Root uptake, deposition to shoots and foliage contact
Percolation of water through contaminated soils
Near-surface water run-off through contaminated soils
Saturation of contaminated soils by flood waters
SoilsLikely Low likelihood Unlikely Likely Likely Likely - - - - Proposed site users Adult Minor LowLikely Likely Unlikely Likely Likely Likely - - - - Construction operatives Adult Minor Low- - - - - - Likely - - - Vegetation (current) - Minor Low- - - - - - Likely - - - Vegetation (proposed) - Minor Low- - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Minor LowLikely Low likelihood Unlikely Likely Likely Likely - - - - Proposed site users Adult Minor LowLikely Likely Unlikely Likely Likely Likely - - - - Construction operatives Adult Minor Low- - - - - - Likely - - - Vegetation (current) - Minor Low- - - - - - Likely - - - Vegetation (proposed) - Minor Low- - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Minor LowLikely Low likelihood Unlikely Likely Likely Likely - - - - Proposed site users Adult Minor LowLikely Likely Unlikely Likely Likely Likely - - - - Construction operatives Adult Minor Low- - - - - - Likely - - - Vegetation (current) - Minor Low- - - - - - Likely - - - Vegetation (proposed) - Minor Low- - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Minor LowLikely Low likelihood Unlikely Likely Likely Likely - - - - Proposed site users Adult Minor LowLikely Likely Unlikely Likely Likely Likely - - - - Construction operatives Adult Minor Low- - - - - - Likely - - - Vegetation (current) - Minor Low- - - - - - Likely - - - Vegetation (proposed) - Minor Low- - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Minor Low
LeachateLeachable PAH - - - - - - - Unlikely Likely Unlikely Water (current and proposed) - Minor Low
Adjacent petrol filling station
Updated Conceptual Model (following laboratory testing)
Risk assessment to CIRIA C552Consequence of risk occurring via most likely pathway
Made Ground
Hydrocarbons at TP03
Adjacent bus depot
Title Conceptual Site Model
Report ref: STM3210B-G01 Revision 0
August 2015 Appendix G
Table number 2
Proposed commercial developmentLondon Road, Crawley
Table comparing cumulative compound concentrations with hazardous waste threshold values
Irritant Harmful∑N : R50-53/0.25 ∑N : 50-53 ∑N : 50-53+∑N : R51-53/2.5 +∑N : R50 +∑N : 51-53+∑N : R52-53/25 +∑N : 52-53
C R34 C R35 +∑N : R53Contaminant Highest H4 H5 H6 H6 H7 H7 H8 H8 H10 H10 H11 H11 H14 H14 H14
concentration (%) (%) (%) (%) (%) (%) (%) (%) (%) (%) (%) (%)MetalsArsenic 30.00 0.0040 0.0046 0.0046 0.4556 0.0046 0.0046Beryllium 0.00 0.0000 0.0000 0.0000 0.0000 0.0000Copper 40.00 0.0100 0.0100 0.0100 0.0100Cadmium 0.66 0.0001 0.0001 0.0001Chromium 27.00 0.0044 0.0044 0.0044Lead 44.00 0.0047 0.0047 0.0047 0.0047 0.0047Mercury 0.26 0.0000 0.0000 0.0000Nickel 25.00 0.0032 0.0032 0.0032 0.0032 0.0032Selenium 0.00 0.0000 0.0000 0.0000Zinc 120.00 0.0870 0.0870 0.0332 0.0250 0.0564 0.0870 0.0870Vanadium 24.00 0.0035 0.0035 0.0035 0.0035 0.0035
PAHNaphthalene 0.40 0.0000 0.0000 0.0000Benzo(a)anthracene 0.42 0.0000 0.0000 0.0000 0.0000Chrysene 0.50 0.0001 0.0001 0.0001 0.0001 0.0001Benzo(b)fluoranthene 0.65 0.0001 0.0001 0.0001 0.0001Benzo(k)fluoranthene 0.19 0.0000 0.0000 0.0000 0.0000Benzo(a)pyrene 0.35 0.0000 0.0000 0.0000 0.0000 0.0000Dibenzo(a,h)anthracene 0.31 0.0000 0.0000 0.0000 0.0000
TPHBenzene 0.00 0.0000 0.00001,2,4-trimethylbenzene 0.00 0.0000 0.0000 0.0000PRO (C6 - C10) 31.00 0.0031 0.0031 0.0031DRO (C10 - C35) 703.40 0.0703 0.0703 0.0703
Total (or greatest) 0.1005 0.1785 0.0040 0.0084 (0.0000) (0.0703) 0.0250 0.0000 (0.0000) (0.0000) (0.0000) (0.0564) 0.4556 0.1142 0.1912Threshold 20% 25% 0.10% 3% 0.10% 1% 5% 1% 0.50% 5% 0.10% 1% 1 25% 25%Exceeded Y/N N N N N N N N N N N N N N N N
Category of danger
Risk Phrase Xi Xn Muta Cat 2
Toxic
T+ T
EcotoxicCarcinogenic Toxic for reproduction
Carc Cat 1 or 2 Carc Cat 3
Repr Cat 1 or 2 Repr Cat 3 Muta Cat 3
MutagenicCorrosive
Table number
1 of 1
Title
Hazard assessment spreadsheet
Report ref: STM3210B-G01 Revision: 0
August 2015
Appendix H
Proposed commercial developmentLondon Road, Crawley
Landfill Waste
ParameterInert waste
landfill
Stable non-reactive hazardous waste in
non-hazardous landfill
Hazardous waste landfill
Parameters determined on the wasteTotal organic carbon (w/w %) 3% 5% 6%*Loss on ignition 10%*BTEX (mg kg-1) 6PCBs (7 congeners) (mg kg-1) 1Mineral oil C10 - C40 (mg kg-1) 500PAH (17 congeners) 100pH >6Acid neutralisation capacity pH 6 (mol kg-1)
To be evaluated To be evaluated
Acid neutralisation capacity pH 4 (mol kg-1)
To be evaluated To be evaluated
Limit values (mg kg-1) for compliance test using BN 12457-3 at L/S 10 l kg-1
As (arsenic) 0.5 2 25Ba (barium) 20 100 300Cd (cadmium) 0.04 1 5Cr (chromium (total)) 0.5 10 70Cu (Copper) 2 50 100Hg (mercury) 0.01 0.2 2Mo (molybdenum) 0.5 10 30Ni (nickel) 0.4 10 40Pb (lead) 0.5 10 50Sb (antimony) 0.06 0.7 5Se (selenium) 0.1 0.5 7Zn (zinc) 4 50 200Cl (chloride) 800 15,000 25,000F (fluoride) 10 150 500SO4 (sulphate) 1000# 20,000 50,000Total Dissolved Solids (TDS)+ 4,000 60,000 100,000Phenol index 1Dissolved organic carbon at own pH or pH 7.5-8.0@ 500 800 1000
PRIMARY CLASSIFICATION SECONDARY CLASSIFICATION
832.9
NON-HAZARDOUS
NON-HAZARDOUS
4301000
< 0.50
190
0.053
< 0.50
< 0.50< 0.010< 0.050< 0.050
0.17< 0.0500.0110.0880.039
Laboratory test data
Composite Sample 1
1.64.2
< 0.010< 0.10
< 0.005
520119.2
0.31
Notes * Either TOC or LOI must be used for hazardous waste # If an inert waste does not meet the SO4 L/S10 limit, alternative limit values of 1500 mg l-1 SO4 at Co (initial eluate from the percolation test (prCEN/TS 14405:2003)) AND 6000 mg kg-1 SO4 at L/S10 (either from the percolation test or batch test BS EN 12457-3), can be used to demonstrate compliance with the acceptable criteria for inert wastes. + The value for TDS can be used instead of the values for Cl and SO4 @ DOC at pH 7.5-8.0 abd L/S10 can be determined or eluate derived from a modified version of the pH dependence Test, prEN 14429, if the limit value at own pH (BS EN 12457 eluate) is not met
Title Comparison of test data with landfill waste acceptance criteria (table 5.1)(Secondary Assessment)
Appendix I
August 2015 Appendix I
Report ref: STM3210B-G01 Revision 0
Proposed commercial development London Road, Crawley
Report: STM3210B-G01 Page 1 of 1 August 2015 Revision 0 Appendix J
Basic categorisation schedule for Made Ground soils Produced following the requirements of The Landfill (England and Wales) (Amendment)
Regulations 2004 Part 2 (5) (a) Source and origin of waste
Proposed development at London Road, Crawley RH10 9UY
(b) Process producing the waste
Foundation and service trench excavations / general site clearance
(c) Statement on waste treatment
Refer to pre-treatment confirmation form
(d) Composition of the waste
Light brown, brown and dark brown slightly clayey sand and gravel consisting of flint, limestone, concrete and
brick
(e) Appearance of the waste
As above
(f) European waste catalogue code
17-05-04 (for non-hazardous waste)
(g) Hazardous waste properties
None
(h) Is the waste prohibited under regulation 9?
No
(i) Landfill class
Non-hazardous (elevated antimony)
(j) Additional precautions required at landfill
None
(k) Can waste be recycled or recovered?
Yes
(l) Name and address of waste producer
TBC
(m) Name and address of consultant
Soiltechnics Limited, Cedar Barn, White Lodge, Walgrave, Northampton. NN6 9PY.
Tel: (01604) 781877 E-mail: [email protected]
Fax: (01604) 781007 Website: www.soiltechnics.net
Schedule Date:
17th
August 2015
signed
Seb Crolla B.Sc.(Hons), MIEnvSc., F.G.S.
Senior geo-environmental Engineer, Soiltechnics Limited
Soiltechnics reference
STM3210B
Proposed commercial development London Road, Crawley
Report: STM3210B-G01 Page 1 of 1 August 2015
Basic categorisation schedule for Weald Clay Formation soils Produced following the requirements of The Landfill (England and Wales) (Amendment)
Regulations 2004 Part 2 (5) (a) Source and origin of waste
Proposed development at London Road, Crawley RH10 9UY
(b) Process producing the waste
Foundation excavations / general site clearance
(c) Statement on waste treatment
Refer to pre-treatment confirmation form
(d) Composition of the waste
Grey brown clay
(e) Appearance of the waste
As above
(f) European waste catalogue code
17-05-04 (for non-hazardous waste)
(g) Hazardous waste properties
None
(h) Is the waste prohibited under regulation 9?
No
(i) Landfill class
Inert based on soils being of natural origin and unlikely to be affected by artificial contamination
(j) Additional precautions required at landfill
None
(k) Can waste be recycled or recovered?
Yes
(l) Name and address of waste producer
TBC
(m) Name and address of consultant
Soiltechnics Limited, Cedar Barn, White Lodge, Walgrave, Northampton. NN6 9PY.
Tel: (01604) 781877 E-mail: [email protected]
Fax: (01604) 781007 Website: www.soiltechnics.net
Schedule Date:
17th
August 2015
Signed
Seb Crolla B.Sc.(Hons), MIEnvSc., F.G.S.
Senior geo-environmental Engineer, Soiltechnics Limited
Soiltechnics reference
STM3210B
CIV/005/02 1
SPECIAL REQUIREMENTS IN RELATION TO LEVEL 3 PLANT
1. In this special requirement, the following terms shall have the meanings assigned to it :-
a. “Company” means Level 3. b. “Company Representative” means the staff of Level 3 or its Authorized Representatives and
Agents. c. “Apparatus” means all surface or sub-surface equipment and plant including any associated
cabling and/or ducting owned leased or rented by Level 3. 2. Before commencing any work or moving heavy plant or equipment over any portion of the site, the
contractor shall confirm details of the Apparatus, owned, leased or rented by the Company, within the site with the Company Representative, who can be contacted at the following point: -
Instalcom Limited
Borehamwood Industrial Park
Rowley Lane
Borehamwood
Hertfordshire
WD6 5PZ
Tel: 0208 731 4600
Fax: 0208 731 4601
E-mail: [email protected]
3. Where such details show that the works or the movement of plant or equipment may endanger the
Apparatus of the Company the Contractor must give the Company Representative at least 7 days written notice of the date on which it is intended to commence such works of the movement of plant and equipment in order that the presence of any sub-surface apparatus can be indicated by markers to be supplied by the Company and placed by the Contractor under the supervision of a Company Representative. The Contractor shall ensure that all Company Apparatus, particularly surface running cabling is adequately protected from damage and such protective measures shall be approved by the Company Representative.
4. In the event of a Company marker being disturbed for any reason, it shall not be replaced other than in the
exact position of its former depth unless the repositioning is carried out at the direction and under the supervision of a Company Representative.
5. The Contractor shall take particular care in relation to the protection of Company Apparatus, where such
Apparatus includes the presence within the site of optical fibre cabling. The contractor should particularly note that the damage to such Apparatus is extremely disruptive to the Company network and costly to reinstate. The Contractor shall make every effort to avoid the disturbance of Company Apparatus more than is absolutely necessary for the completion of the works in accordance with the contract.
CIV/005/02 2
6. When excavating around, moving or backfilling around Company Apparatus, the Company Representative
shall be given adequate notice, which shall not be less than 3 days, of the contractor’s intentions in order that he may supervise the works. The Contractor should note that the normal depth of cover for Company Apparatus and ducts are as follows: -
a. Carriageways 600mm
b. Footways 350mm
c. Verges 450mm
These minimum depths of cover should be maintained wherever possible. Where the minimum depths of cover cannot be maintained, the Contractor shall carry out the instructions of the Company Representative for the protection of Company Apparatus. Where cables are not in duct and the required depth of cover cannot be maintained, such cables as are affected shall be enclosed and protected in UPVC duct or equivalent materials as supplied by the Company and by the method directed by the Company Representative. With regard to excavation in the vicinity of Company Apparatus the Contractor should have particular regard to the possibility of reduced cover and the encountering of such Company Apparatus at depths of cover less than that given at a, b and c above.
7. All excavation adjacent to Company Apparatus is to be carried out by hand until the exact extent and/or
location of Company Apparatus is known. Mechanical borers and/or excavators shall not be used within 1.0m of Company Apparatus without the supervisory presence of a Company Representative, To prevent any movement of Company Apparatus during excavations, complete shuttering shall be used as directed by the Company Representative if:-
a. Excavation is deeper than the depth of cover of adjacent Company Apparatus.
b. Excavation is within 1.0m of Company Apparatus in stable ground.
c. Excavation is within 5.0m of Company Apparatus in unstable ground.
If for the completion of the works, the Contractor intends using any of the following: -
a. Pile driving equipment within 10.0m of Company Apparatus.
b. Explosives within 20.0m of Company Apparatus.
c. Laser equipment within 10.0m of Company Apparatus.
The Contractor shall advise the Company Representative, giving at least 7 working days written notice in order that any special protective measure for the Company Apparatus affected may be arranged.
8. All Company manhole, joint box and /or other access points and chambers within the site shall be kept clear and unobstructed. Access for vehicles, winches, cable drums and/or further equipment required by the Company for the maintenance of it’s Apparatus, must be maintained at all reasonable times. The Contractor should particularly note that footway type jointing chambers are not specified for carriageway loadings and will need to be adequately protected and/or demolished and rebuilt under the supervision of a Company Representative where such chambers are likely to be placed at risk, either temporarily or permanently, from the movement of plant and/or equipment on the site.
CIV/005/02 3
9. The covers to Company chambers and/or Apparatus shall only be lifted by means of appropriate keys
obtained from the Company Representative and under the direct supervision of the Company Representative. No employee of the Contractor or of any sub-contractor employed by the Contractor shall enter any chamber and/or Apparatus of the Company unless under the supervision of the Company Representative and in any case not before the mandatory gas check has been carried out in the presence of the Company Representative and such checks have shown it to be safe to enter the chamber and/or Apparatus of the Company. The Company Representatives shall be given reasonable access to all Company Apparatus and chambers when required.
10. In the event of any damage whatsoever to Company Apparatus, the Contractor shall immediately inform
the Company Representative and report the occurrence immediately by contacting the Company as follows:-
Telephone:-
0208 731 4600 Mon-Fri Office Hours (Instalcom Head Office)
0208 510 3111/3101 Out of Office Hours (24Hr Level 3 Network Operations Centre)
11. The above requirements do not relieve the Contractor of any of his obligations under the Contract. The accuracy of information on the plans cannot be guaranteed and no liability can be accepted for errors or omissions.
Damage to Communications Plant is Expensive – Please Take Care.
Plant Location95 Kilbirnie StreetGlasgowG5 8JD
Phone: 0141 418 4093Phone: 0845 070 3497Fax: 0141 429 6432
Email: [email protected]
Margaret Ward, .
Dempster Binning LLP
5 West LinksTollgateChandlers FordHampshire, SO53 3TG.
Our Ref:
Your Ref:
Dear Customer,
SO/0063284
SF22422093000
Date: 23/06/2015
Re: Enquiry at: Land at London Road, Crawley, West Sussex RH10.
Thank you for your enquiry regarding the above location. If your client plans to carry out any on site works they contact ourselves directly so that a full safety and engineering risk assessment can be carried out to any work starting.
Listed below is the information we would require from your client and our contact details:
Searches - Important Information
Full contact details (name, company name, address, telephone number and e-mail address).
Full site address, post code and easting/northing grid reference.
Plan showing the site boundary.
Details of the work to be carried out.
The proposed start date (please specify if work is at the planning stage).
It must be stressed that both direct and consequential damage to gas plant can be dangerous both for your client's employees and the general public, repairs to any such damage will incur a charge. Your client's works should be carried out in such a manner that we are able to gain access to our apparatus throughout the duration of your client's operations.
Our contact information is:
Address - Scotia Gas Networks, Plant Location Dept, 95 Kilbirnie Street, Glasgow, G5 8JD.
E Mail - [email protected]
Fax - 0141 429 6432
mustprior
minimum
24 hour gas escape number 0800 111 999*
*Calls will be recorded and may be monitored
Southern Gas Networks plc is part of the Scotia Gas Networks GroupRegistered Office: St Lawrence House Station Approach Horley Surrey RH6 9HJRegistered in England & Wales No. 05167021http://www.sgn.co.uk
Yours faithfully,
June Sheridan
0141 418 4145
If you require any further information please contact the number below.
Please note that the information supplied by Scotia Gas Networks is given without
warranty. Whilst we understand the information supplied to be correct, no reliance
should be given in respect of the location of our apparatus. We can locate apparatus on
site at your client’s request prior to any development works to be carried out in the
vicinity of our pipelines.
24 hour gas escape number 0800 111 999*
*Calls will be recorded and may be monitored
Southern Gas Networks plc is part of the Scotia Gas Networks GroupRegistered Office: St Lawrence House Station Approach Horley Surrey RH6 9HJRegistered in England & Wales No. 05167021http://www.sgn.co.uk
E
L
L
E
L
LL
L
E
E
E
E
E
E E E E
R R
R
Drai
n
HouseOak
1
2
El Su b St a
3
4
Astral TowersGar age
5
COUNTY OAK LANE
Club
Drai
n Cou nty OakWHITWO RTH ROAD
El Su
b St a
Industrial Estate
FLEMING WAY
Premie r Inn
65.9 m
El Su b St a
Cra wle y Busines s Q ua rt er
El Su b St a
64.7 m
Tui Hous e
M ast
The Fleming Centre
Stas
Sub
El
TCB
A1
B1
LBCycle Tr ack
B2
5 to
6
Business Vi llage
D
The Satel li te
C
A2
Farad ayCou rt
63.5 m
64.2m
63.9
m
ED &
War
d B
dy
LOND
ON R
OAD
CR
Ea st ma n House
El Su b St a
Sub S ta
El
El Su b St a
66.7 m
Flight TrainingCentre
Linac H ouse
67.1 m
El Su b St a
1
El Su b
Busin ess Villag e
Sta
Space H ouse
The Sa tellite
1 to 36
Dr ain
Path ( um)
Dr ain
Sub S ta
El
1
Cha rlw ood Court
16
15
Merlin C
e n tre
4
6
5
10
Ente rp rise Court
13
14
Sew age P umpin g St ation 2
15
1
El Su b St a
El Su b St aEl Su
b St a
OAK LANE
COUNTY
METCALF WAY
3
2
Path
( um)
COUNTY OAK WAY
Drain
Drain
Dr ain
1
Oak Court
4
7
Industria l EstateBETTS WAY
El Su b St aOak Cot ta geHouse
Av iareps
Beec h House
Pl ayi ng F ield
Playing Field
Cycl e Tra ck
Dr ain
61.4 m
CentreBase po in t Busi ne ss
151 MARTYRS AVENUE 63.4 m
181169 DEPO T ROAD
173 177179167 171 175
185
183
El Su b St a
Lang ley Gree n H os pit al
Waste Tr ansfer Stat ion
and
Recyclin g C entre
Retail Park
Cou nty Oak38 - 68
WB
75 10
69
Dr ain
80
117
74
El Su b St a
O2
19
6
266 STEPHEN CLOSE
68
23
9825
12
100
8
120
118
104
CLO SE29
106 110129
112
116 5
122
108
LATIMER133
114131
130
153
101
115
Ashmore House
1 to 32
15 1
14
13
12
12
8
9
136
1327OLD M
A R TYR S 2116
1
2
201
65.3 m
1
191
68.3 m
M osque
151
157
ED &
War
d B
dy
CRDe
f
El Su b St a
El Su b St a
Alte on Hous e
Br ooke H ouse
88 BEC KETT LANE
Unconfirmed Route
AS SU M E D R OU TE
.
.
.
-
-
-
DOC 0 .8
DOC 0 .5 -
DOC 0 .6
12 5 PE p ip e fo un dbe twe en th ese lo ca t io ns.Fur the r e xte ntun co nf i rme d .Da te d : 08 /04 /2 00 9DR4 : 10 4 17 2
90 PE p ip e n o t fo u ndat th is p oi nt .Da te d : 08 /07 /2 00 9DR4 : 10 4 17 0
-
-
-
-
-
-
Valve Card
0.8
0.6
22.2
1.2
1.5
75.0
24.0
1.0
5.0
19.7
29.0
8.1
1.7
6.5
5.8
4.5
22.7
1.2
1.7
6.7
7.0
20.0
5.0
1.5
8.5
3.40.5 8.9
2.2
12.9
3.0
2.0
42.7
2.01.7
11.0
81.5
7.0
8.1
16.5
6.3
17.4
2.0
1.0
1.0
0.7
4.5
4.0
0.7
0.8
0.8
0.61.03.0
3.0
4.04.04.0
0.7
1.0
1.0
4.0
1.0
1.0
1.8
0.8
2.5
1.00.9
0.7
1.0
4.8
2.0
0.5
17.0
3.0
0.8 0.8
3.0
11.0
12.3
9.5
1.7
3.3
11.0
4.6
7.87.82.5
1.0
23.0
6.7
2.5
3.8
1.04.3
1.0
1.0
3.0
0.9
25.0
0.3
11.0
0.8
23.118.1 5.2
8.5
15.0
6.7
1.5
3.6
55
5
5
55
5
5
5
55
5
5 5
5
5
5
5
55
5
5
5
5
5
55
5
5
5
55
5
5
5
5
5
5
5
5
5
5
555
5 5
5
55
5
5
5
5
5
555
5
5
5
55
5
5
5
$
$
44 $
3
$
3
M
B
Q
MM
M
B
N
N
N25
0 PE
M/P
25 0 PE M /P
250 P
E M/
P
25 0 PE M /P
250 PE M/P
250 PE M/P
25 0 PE M /P
25 0 PE M /P
25 0 PE M /P
250 PE M /P (IN 0 )
250 PE M /P
32 PE
M/P
32 P E M / P
250 PE M/P! $!
$ !
$
"
$ $
!"
$ $
!"
$
$ !$!$
$
$
$
$$
$
$
$
$
! $
!
$
$ $
$
!
B
I
Q
I
B
Q
B
B
Q
B
B
B
B
B
Q
I
B
B
B
Q
Q
I
Q
B
N
N
N
N
N
N
N
N
N
N
125
PE
250 PE
90 P E
125 PE ( IN 0 )
90 P
E ( I
N 4 " S
I )
125 PE ( IN 0 )
6" D I
63 PE
180 P
E
63 PE
180 PE
180 P
E
90 P E
8" SI
63 PE
6" D I
180 PE
180 PE (IN 8" CI)
180 PE
63 P E
63 P E
125 PE 63
PE
6" DI ( IN 25 PE)
90 PE
125 PE ( IN 0 )
63 PE
63 PE
90 P
E ( I
N 4 "
CI )
180 PE
90 PE
8" CI
125 PE
4" S
I
63 PE
180 P
E
75 P E ( IN 4 " S
I )
250 PE
90 P E ( IN 4 " S
I )
6" DI ( IN 25 PE)
63 PE
90 PE ( IN 0 )
90 PE ( IN 0 )
12 5 PE
63 P
E
180 P
E
90 PE
12 5 PE
90 PE
125 PE ( IN 0 )
63 P E ( IN 4 " S I )
125 PE
4" S I
125 PE ( IN 0 )
18 0 PE 250 DI
63 PE
180 PE
125 PE
90 PE (IN 4" CI)
90 PE
125 PE
90 PE ( IN 4 " S I )
75 P E ( IN 4 " S I )
8" SI
12 5 PE
125 PE
63 P
E
180 P
E
250 PE
12 5 PE180 PE 8" SI
8" SI
8" SI
90 P E
63 PE
90 P E
2" PE
90 P
E
90 PE ( IN 0 )
125 PE
63 PE
63 PE
90 PE
63 P E ( IN 4 " S I )
90 PE
90 PE ( IN 4" C I)
90 P E
8" S
I
63 PE
250 PE
63 PE
180 PE
63 PE
0.7
0. 6 0.8
0. 80. 9
0.6
1. 2
0. 8
1. 0
0. 9
0. 8
0. 3 0. 8
0. 7 0. 7
0. 5
0.7
1.0 CVR
1.0 CVR
0. 90. 7
0.70. 7
0.8 1. 5
0.8
0.7
0. 8
65 1 5 8 07 8 6
6508
5743
065 0 6 2 50 7 5
TQ2638NE TQ2738NW
TQ2638SE TQ2738SW
TQ2638NW
TQ2638SW
TQ2738NE
TQ2738SE
0 40 Meters
This plan shows the location of those pipes owned by Scotia Gas Networks (SGN) by virtue of being a licensed Gas Transporter (GT). Gaspipes owned by other GTs or third parties may also be present in this area but are not shown on this plan. Information with regard to suchpipes should be obtained from the relevant owners. No warranties are given with regard to the accuracy of the information shown on this plan.Service pipes, valves, siphons, sub-connections etc are not shown but their presence should be anticipated. You should be aware that a smallpercentage of our pipes/assets may be undergoing review and will temporarily be highlighted in yellow. If your proposed works are close toone of these pipes, you should contact the SGN Plant Protection Team on 08450703497 for advice. No liability of any kind whatsoever isaccepted by SGN or its agents, servants or sub-contractors for any error or omission contained herein. Safe digging practices, in accordancewith HS (G)47, must be used to verify and establish the actual position of mains, pipes, services and other apparatus on site before anymechanical plant is used. It is your responsibility to ensure that plant location information is provided to all persons (whether direct labour orsub-contractors) working for you on or near gas apparatus. Information included on this plan should not be referred to beyond a period of 28days from the date of issue.
This plan is reproduced from or based on the OS map by Scotia Gas Networks plc, with the sanction of the controller of HM Stationery Office.Crown Copyright Reserved.
West Sussex County AreaINTRANET MAP VERSION 2.1LP MAINS
GRID REFERNCE:INTERNAL USE ONLY
USER ID:MP MAINSIP MAINSLHP MAINSHISTORY DATALAsGTs SSSIs
Some examples of Plant items:Valve Depth of
CoverSyphon Diameter
ChangeMaterialChange
DATE: 23/06/2015
SCALE 1:
E526972,N138675,TQ 26 38
JS548861387
Asset Location
Search
Thames Water Utilities Ltd, Property Searches, PO Box 3189, Slough SL1 4W, DX 151280 Slough 13
T0845 070 [email protected] I www.thameswater-propertysearches.co.uk
Page 1 of 10
Soiltechnics Limited Cedar Barn Walgrave,Cedar Barn NORTHAMPTON NN6 9PY
Search address supplied Premier House
London Road
Crawley
Your reference STM3210B
Our reference ALS/ALS Standard/2015_3071948
Search date 17 June 2015
You are now able to order your Asset Location Search requests online by visiting
www.thameswater-propertysearches.co.uk
You are now able to order your Asset Location Search requests online by visiting
www.thameswater-propertysearches.co.uk
Asset Location
Search
Thames Water Utilities Ltd, Property Searches, PO Box 3189, Slough SL1 4W, DX 151280 Slough 13
T0845 070 [email protected] I www.thameswater-propertysearches.co.uk
Page 2 of 10
Search address supplied: Premier House, London Road, Crawley,
Dear Sir / Madam
An Asset Location Search is recommended when undertaking a site development.It is
essential to obtain information on the size and location of clean water and sewerage assets
to safeguard against expensive damage and allow cost-effective service design.
The following records were searched in compiling this report: - the map of public sewers &
the map of waterworks. Thames Water Utilities Ltd (TWUL) holds all of these.
This searchprovides maps showing the position, size of Thames Water assets close to the
proposed development and also manhole cover and invert levels, where available.
Please note that none of the charges made for this report relate to the provision of Ordnance
Survey mapping information. The replies contained in this letter are given following
inspection of the public service records available to this company. No responsibility can be
accepted for any error or omission in the replies.
You should be aware that the information contained on these plans is current only on the day
that the plans are issued. The plans should only be used for the duration of the work that is
being carried out at the present time. Under no circumstances should this data be copied or
transmitted to parties other than those for whom the current work is being carried out.
Thames Water do update these service plans on a regular basis and failure to observe the
above conditions could lead to damage arising to new or diverted services at a later date.
Contact Us
If you have any further queries regarding this enquiry please feel free to contact a member of
the team on 0845 070 9148, or use the address below:
Thames Water Utilities Ltd
Property Searches
PO Box 3189
Slough
SL1 4WW
Email: [email protected]
Web: www.thameswater-propertysearches.co.uk
Asset Location
Search
Thames Water Utilities Ltd, Property Searches, PO Box 3189, Slough SL1 4W, DX 151280 Slough 13
T0845 070 [email protected] I www.thameswater-propertysearches.co.uk
Page 3 of 10
Waste Water Services
Please provide a copy extract from the public sewer map.
Enclosed is a map showing the approximate lines of our sewers. Our plans do not show sewer connections from individual properties or any sewers not owned by Thames Water unless specifically annotated otherwise. Records such as "private" pipework are in some cases available from the Building Control Department of the relevant Local Authority. Where the Local Authority does not hold such plans it might be advisable to consult the property deeds for the site or contact neighbouring landowners. This report relates only to sewerage apparatus of Thames Water Utilities Ltd, it does not disclose details of cables and or communications equipment that may be running through or around such apparatus. The sewer level information contained in this response represents all of the level data available in our existing records. Should you require any further Information, please refer to the relevant section within the 'Further Contacts' page found later in this document. For your guidance:
• The Company is not generally responsible for rivers, watercourses, ponds, culverts
or highway drains. If any of these are shown on the copy extract they are shown for
information only.
• Any private sewers or lateral drains which are indicated on the extract of the public
sewer map as being subject to an agreement under Section 104 of the Water
Industry Act 1991 are not an ‘as constructed’ record. It is recommended these
details be checked with the developer.
Clean Water Services
Please provide a copy extract from the public water main map. With regard to the fresh water supply, this site falls within the boundary of another water company. For more information, please redirect your enquiry to the following address: Southern Water Southern House Yeoman Road
Asset Location
Search
Thames Water Utilities Ltd, Property Searches, PO Box 3189, Slough SL1 4W, DX 151280 Slough 13
T0845 070 [email protected] I www.thameswater-propertysearches.co.uk
Page 4 of 10
Worthing West Sussex BN13 3NX Tel: 01903 264 444 Fax: 01903 691 435 For your guidance:
• Assets other than vested water mains may be shown on the plan, for information
only.
• If an extract of the public water main record is enclosed, this will show known public
water mains in the vicinity of the property. It should be possible to estimate the
likely length and route of any private water supply pipe connecting the property to
the public water network.
Payment for this Search
A charge will be added to your suppliers account.