Upload
trung
View
58
Download
1
Embed Size (px)
DESCRIPTION
book
Citation preview
1
Design Guide (abstract from AB-6536, AB-6656) DC221-03E
(For Remote unit input/output table)
1. Point type
ID
Analog input
Analog output Digital input Digital input/output Totalizer Para
meter Momentary Maintained Transfer0 1 2 3 4 5 6 7
1 AI Analog input
SOP Status
COPmS/S
(Momentary)
COPlS/S
(Maintained)
TTD Pulse TOT
PRDDigital
parameter2 AOP
Alarm CCPm
S/S+Status (Momentary)
CCPlS/S+Status (Maintained)
TTA Analog
TOT
PRAAnalog
parameter3 AO3
Analog output
M/M
SAP Status
+Alarm
CAPmS/S+Status
+Alarm (Momentary)
CAPlS/S+Status
+Alarm (Maintained)
4 AO4 Analog output
4 to 20mA
(SCP) Running
monitoring (Local command)
(OOAm)ON-OFF
-AUT (Momentary)
OOAtON-OFF
-AUT (Transfer)
5 AO5 Analog output (Voltage)
HOLmHI-OFF
-LO (Momentary)
HOLtHI-OFF
-LO (Transfer)
6 CCPfS/S+Status
(Momentary remote)
7 CAPfS/S+Status
+Alarm (Momentary remote)
8 HOLfHI-OFF
-LO (Momentary remote)
Note: 1. The point type ID number is a 2-digit number. Ex. AI: 01, CCPl: 42 2. The following point types are not available for Infilex GC/GD. Point type: SCP, OOAm
3. If the point has no input/output, such as analog parameter, set pseudo (1).
2
2. Digital Input/Output Point
COP: Command Only Point
SOP: Status Only Point 52X
AOP: Alarm Only Point 51X (ex. Trip alarm)
SAP: SOP + AOP
CCP: COP + SOP + command fail +COS alarm
CCPf (momentary remote): COP + SOP + command fail
CAP: COP + SOP + AOP +command fail + COS alarm
CAPf (momentary remote): COP + SOP + AOP +command fail
Note:
Refer to the document, DC221-01E page 36
COS alarm: Only status changes, although ON/OFF point where receives no command.
Command fail: Status does not change, after ON/OFF point where receives the start and stop
command.
Period monitoring time inhibit command fail (default 2 seconds)
XXXf (momentary remote): detect command fail, not detect COS alarm
Which is better CCP or CAP?
Merit of CAP: CAP can monitor the reason of stop (trouble or remote)
Other digital input/output
OOA: 3 position control (ON/OFF/AUTO) + SOP + command fail + COS alarm
HOL: 3 position control (Hi/Lo/OFF) + status (Hi) + status (Lo) +command fail + COS alarm
Example:
Light: full, half, off
Fan speed: high, low, off
3
3. Relationship with input/output list
Input/output list table Point type
Name O
utpu
t
Stat
us
Ala
rm
Ana
log
Tota
lizer
Para
met
er
M O CCPl C O CCPm or CCPf M O CAPl O C O CAPm or CAPf O A O OOAm or HOLm or HOLf O O SOP
O
O
SAP
O AOP O AI O TTD O AO6 M COPl (Usage: point interphone) (DIF-II only)
Symbol Description
M: Maintained/Latched output, 1a C: Momentary output, 1a+1a A: Maintained 3-position output, 1a+1a
4
4. Point parameter item list
Name displayed Item name SOP SAP SCP AOP COP m l t
CCP m l
CAP m l f
OOA m l t
HOL m l t CCPt
TYPE Point type
A/D A/D
IPD IPD
SEG Segregation
ABL Rated power ×
DLAYs On delay time × × × ×
TIMEs Timeout monitoring time ×
NRCV Batch restoration disabled × × × ×
DI1 I/O DI1 ×
DI2 I/O DI2 × × × × × ×
DO1 I/O DO1 × × × ×
REC OI Command/COS log (Not in use.) ×
LOG1 Boolean calculation 1 × × × ×
LOG2 Boolean calculation 2 × × × ×
VLV Switch valve × × × × × × × × ×
BCNT NC contact changeover × × × × × × × × ×
TIMs Alarm decision time × × × × × × × × ×
Name displayed Item name AI AO3 AO4/5 TTD TTA PRD PRA
TYPE Point type
A/D A/D
IPD IPD
SEG Segregation
DPOS Decimal position
COEF Coefficient × × × × × ×
SCL Prescale range × × × × × ×
RTIO Sampling ratio × × × × × ×
MAXS High limit × × ×
MINS Low limit × × ×
MAX Output high limit × × × × × ×
MIN Output low limit × × × × × ×
FLG Output × × × × × ×
AIS Linearization table No. × × × × × ×
ZERO Zero adjustment × × × × × ×
FBC Fully-close raw data × × × × × ×
5
Name displayed Item name AI AO3 AO4/5 TTD TTA PRD PRA FBO Fully-open raw data × × × × × ×
GAP Gap × × × × × ×
HYS Hysteresis × × × × × ×
CLMP Clamp delete/assign × × × × ×
AOCYs Minimum output interval × × × × ×
COV COV × ×
RNG Input type signal × × × × × ×
HYC Measuring cycle Normal/increased interval × × × × × ×
AI1 I/O × × × × × ×
AO1 I/O × × × × ×
TO1 I/O × × × × × ×
AIP Related AI point No. × × × × × ×
Note:
When the point is a central monitoring point, not write anything in the column of Central. And set SEG=
10000000.
When the point is not a central monitoring point, write [X] in the column of Central. And set SEG=
00000000.
5. Operation type (Digital Output point)
Point type Operation type Description COPm, CCPm, CAPm A Non-voltage normally open (ON) + normally open (OFF)
R Remote control relay output COPl, CCPl, CAPl A Non-voltage normally open (ON/OFF) (OOAm) HOLm, HOLf B Non-voltage normally open (ON) + normally open (OFF) OOAt, HOLt C Non-voltage SPDT CCPf, CAPf A Non-voltage normally open (ON) + normally open (OFF)
R Remote control relay output
6
6. Analog linearization table (AIS No.)
Linearization Table No.
1~6, 8~14, 18 7 15 16 17
Linearization Table
X Y X Y X Y X Y X Y
00 0.000 0 0.000 0 37.002 0 7.824 -500 25.431 -200 01 0.000 0 10.002 100 39.878 50 16.651 -350 31.226 -100 02 0.000 0 20.000 200 42.754 100 25.413 -200 37.002 0 03 0.000 0 30.002 300 45.627 150 34.106 -50 42.754 100 04 0.000 0 40.000 400 48.480 200 42.754 100 48.480 200 05 0.000 0 50.002 500 51.333 250 51.333 250 54.183 300 06 0.000 0 60.000 600 54.183 300 59.863 400 59.863 400 07 0.000 0 70.002 700 57.032 350 68.327 550 65.520 500 08 0.000 0 80.000 800 59.863 400 76.746 700 71.139 600 09 0.000 0 90.002 900 62.693 450 85.085 850 76.746 700 10 0.000 0 100.00 1000 65.520 500 93.389 1000 82.319 800
Application Reserve Linear Pt 100 Pt 100 Pt 100
Range - 0.0 ~ 100.0 0.0 ~ 50.0 -50.0 ~ 100.0 -20.0 ~ 80.0 Unit - % ºC ºC ºC
Linearization Table No.
19 20 21 22 23 24
Linearization Table
X Y X Y X Y X Y X Y X Y
00 0.000 0 37.002 0 20.561 -30 20.561 150 25.413 -200 0.000 0 01 10.002 10 42.754 100 79.439 30 79.439 300 23.312 -150 15.258 500 02 20.000 20 48.480 200 0.000 0 0.000 0 31.226 -100 0.000 0 03 30.002 30 54.183 300 0.000 0 0.000 0 34.106 -50 0.000 0 04 40.000 40 59.863 400 0.000 0 0.000 0 37.002 0 0.000 0 05 50.002 50 65.520 500 0.000 0 0.000 0 39.878 50 0.000 0 06 60.000 60 71.139 600 0.000 0 0.000 0 42.754 100 0.000 0 07 70.002 70 76.746 700 0.000 0 0.000 0 45.627 150 0.000 0 08 80.000 80 82.319 800 0.000 0 0.000 0 48.480 200 0.000 0 09 90.002 90 87.866 900 0.000 0 0.000 0 51.333 250 0.000 0 10 100.00 100 93.389 1000 0.000 0 0.000 0 54.183 300 0.000 0
Application Humidity (Linear) Pt 100 Relative Value
Neoplate Absolute Value
Neoplate Pt 100
Inside Neopanel, inside wireless Neopanel, Wireless sensors (Temperature)
Ranges 0 ~ 100 0.0 ~ 100.0 -3.0 ~ 3.0 15.0 ~ 30.0 -20.0 ~ 30.0 0.0 ~ 50.0 Unit % ºC ºC ºC ºC ºC
Note: Set the number of Linearization Table in the column of AIS No for each AI point.
7
Linearization Table No.
25 26 27~99
Linearization Table
X Y X Y X Y
00 0.000 0 0.000 0 0.000 0 01 3.052 100 7.782 255 0.000 0 02 0.000 0 0.000 0 0.000 0
03 0.000 0 0.000 0 0.000 0
04 0.000 0 0.000 0 0.000 0
05 0.000 0 0.000 0 0.000 0
06 0.000 0 0.000 0 0.000 0
07 0.000 0 0.000 0 0.000 0
08 0.000 0 0.000 0 0.000 0
09 0.000 0 0.000 0 0.000 0
10 0.000 0 0.000 0 0.000 0
Application Humidity (Linear) Buttery Shortage
Notice For JOB
Ranges 0 ~ 100 0.0 ~ 255.0 - Unit % - -
7. Signal type Point type Input symbol Description I/O Module model number
AI PT PT100ohms 0-50 ºC RY5004P0000 RY5004J0000 (AIx2, PTx2) PT100ohms 0-100 ºC
PT100ohms -20-80 ºC PT100ohms -20-30 ºC PT100ohms -50-100 ºC
AIA Current input 4-20 mA DC RY5004A0000 RY5004J0000 (AIx2, PTx2) AIV1 Voltage input 1-5 V DC
AIV2 Voltage input 0-5 V DC AIV4 Voltage input 0-10 V DC AIV5 Voltage input 2-10 V DC
AO3 MM Modutrol motor drive RY5001F0000 (For 1 pt) RY5003F0000 (For 3 pts)
AO4 AOA Current output 4-20 mA DC RY5002M0000 (For 2 pts) RY5004M0000 (For 4 pts) AO5 AOV1 Voltage output 1-5 V DC
AOV2 Voltage output 2-10 V DC AOV3 Voltage output 0-5 V DC AOV4 Voltage output 0-10 V DC
Note: Set the input symbol in the column of Signal Type for each AI/AO point.
8
8. RNG (Analog input signal type)
Parameter Analog input signal type 1 4~20 mA
2 0~5 V 3 1~5 V 4 0~10 V 5 2~10 V 11 0~50 (ºC) 12 0~100 (ºC) 13 -20~30 (ºC) 14 -20~80 (ºC) 16 -50~100 (ºC) 0 None
Note: Set the value of parameter in the column of RNG for each AI point.
9
9. I/O module list table
Model Selection Table Model number Description Object points and I/O points to be used Abbr. of
modules Connection to Infilex AC
RY50 Base model number ⎯
08 S 0000 I/O module for 8 digital input points
For SOP, AOP: DI 1 point For SAP, SCP: DI 2 points For CCP, OOA inputs: DI 1 point For CAP, HOL inputs: DI 2 points
DI No 16 S 0000 I/O module for 16 digital input
points
08 D 0000 I/O module for 8 relay output points (N.O. (normally open) contacts)
For COP maintained, CCP maintained, CAP maintained: DO 1 point*1 For COP momentary/local, CCP momentary/local, CAP momentary/local: DO 2 points
DO No
16 D 0000 I/O module for 16 relay output points (N.O. contacts)
16 R 0000 I/O module for 8 relay output points (N.O. contacts) + 8 digital input points
∗ Combination of modules (For relay output, see DO. For digital input, see DI.)
DO+DI Yes*5,*7
08 C 0000 I/O module for 8 relay output points (N.O./N.C. (normally open/normally close) contacts)
For OOA transfer/HOL transfer: NO/NC contact DO 2 points*2 When using HOL momentary/local => <See Note ∗4 >
DOC No
04 Y 0000 I/O module for 4 remote control relay output points
For limited to CCP local: RRD 1 point (DI is not necessary.) RRD No
04 T 0000 I/O module for 4 totalizer pulse input points
For limited to TTD: Pulse input 1 point TOT No 16 T 0000 I/O module for 16 totalizer pulse
input points
02 M 0000 I/O module for 2 voltage/current output points For limited to AO4 or AO5: AO 1 point
AO4 (4-20 mA) or AO5 (2-10 V/0-10 V/1-5 V/0-5 V) AO Yes*6,*7
04 M 0000 I/O module for 4 voltage/current output points No
04 A 0000 I/O module for 4 voltage/current input points
For limited to AI: AI 1 point (4-20 mA/2-10 V/0-10 V/1-5 V/0-5 V) AI No
04 P 0000 I/O module for 4 temperature input points
For limited to AI: Pt 1 point (0 to 100 °C/0 to 50 °C /-20 to 80 °C /-20 to 30 °C /-50 to 100 °C)
Pt No
04 J 0000 I/O module for 2 voltage /current input points + 2 temperature input points
∗ Combination of modules (For voltage/current input, see AI. For temperature input, see Pt.)
AI+Pt Yes*7
01 F 0000 I/O module for 1 Modutrol Motor output point
Output is limited to AO3. Input (measurement of actual opening) MM 1 point*3 is limited to AI.
MM No 03 F 0000 I/O module for 3 Modutrol Motor
output points
01 U 0000 User terminal (UT) module For Neopanel™, Neoplate, Operator Panel (panel mount type) UT Yes
01 Q 0000 Operator Panel (integral type) For Neopanel™ , Neoplate OP Yes
SOP: Status Only Point AOP: Alarm Only Point SAP: Status Alarm Point SCP: Status and COS (Change of Status) Point CCP: Command with COS Point OOA: ON/OFF/Auto Point
CAP: Command witn SAP HOL: HI (high)/OFF/LO (low) Command with COS Point TTD: Totalizer Digital Point
10
Notes: ∗1 Since the DO module does not have any N.C. (normally close) contact, the DOC module is used for the OOA or
HOL. ∗2 In the OOA transfer, ON/OFF is assigned to the first N.O./N.C. contact, and AUTO is assigned to the second
N.O./N.C. contact. In the HOL transfer, HI/OFF is assigned to the first N.O./N.C. contact, and LO is assigned to N.O. of the second N.O./N.C. contact.
∗3 Two points, AO3 and AI, are assigned to one MM point in the point file. The following shows the points correnponsing to IO numbers.
IO number Point type MM1: (1, 2) (AO3, AI) MM2: (3, 4) (AO3, AI) MM3: (5, 6) (AO3, AI)
∗4 For the HOL momentary/local, 3 points of N.O./N.C. contact DO of the DOC module are required. HI: N.O. contact of DO, OFF: NC contact of DO2, and LO: NO contact of DO3
∗5 For DO+DI module connected to Infilex AC (Model WY5117C1400), I/O points are limited to DI 4 points and DO 4 points.
∗6 For AO module connected to Infilex AC (Model WY5117C1400), voltage output (0-5 V, 0-10 V, 1-5 V, 2-10 V) is only available.
∗7 For DO+DI module, AO module, and AI+Pt module, connectabe Infilex AC is Model WY5117C1400 only.
11
Model No. RY5008S Model No. RY5016S Model No. RY5008D Model No. RY5016D Model No. RY5016R
Module ID = 1
DI 8
Module ID = 2
DI 16
Module ID = 3
DO 8
Module ID = 4
DO 16
Module ID = 5
DIO
I/O N
o.
Termial N
o.
I/O N
o.
Termial N
o.
I/O N
o.
Termial N
o.
I/O N
o.
Termial N
o.
I/O N
o.
Termial N
o.
1 DI 1 1 1 DI 1 1 1 DO 1 1 1 DO 1 1 1 DO 1 1
2 DI 2 2 2 DI 2 2 2 DO 2 2 2 DO 2 2 2 DO 2 2
3 DI 3 3 3 DI 3 3 3 DO 3 3 3 DO 3 3 3 DO 3 3
4 DI 4 4 4 DI 4 4 4 DO 4 4 4 DO 4 4 4 DO 4 4
5 DI 5 5 5 DI 5 5 5 DO 5 5 5 DO 5 5 5 DO 5 5
6 DI 6 6 6 DI 6 6 6 DO 6 6 6 DO 6 6 6 DO 6 6
7 DI 7 7 7 DI 7 7 7 DO 7 7 7 DO 7 7 7 DO 7 7
8 DI 8 8 8 DI 8 8 8 DO 8 8 8 DO 8 8 8 DO 8 8
COM 9 COM 9 COM 9 COM 9 DO COM 9
COM 10 COM 10 COM 10 COM 10 DO COM 10
9 DI 9 11 9 DO 9 11 9 DI 1 11
10 DI 10 12 10 DO 10 12 10 DI 2 12
11 DI 11 13 11 DO 11 13 11 DI 3 13
12 DI 12 14 12 DO 12 14 12 DI 4 14
13 DI 13 15 13 DO 13 15 13 DI 5 15
14 DI 14 16 14 DO 14 16 14 DI 6 16
15 DI 15 17 15 DO 15 17 15 DI 7 17
16 DI 16 18 16 DO 16 18 16 DI 8 18
COM 19 COM 19 DI COM 19
COM 20 COM 20 DI COM 20
12
Model No. RY5008C Model No. RY5004Y Model No. RY5004T Model No. RY5016T
Module ID = 6
DOC 8
Module ID = 7
RRD 4
Module ID = 8
TOT 4
Module ID = 9
TOT 16
I/O N
o.
Termial No.
I/O N
o.
Termial No.
I/O N
o.
Termial No.
I/O N
o.
Termial No.
1
DO 1a 1 1 RRD 1 (Red) 1 1 TOT 1 1 1 TOT 1 1
COM 1 2 2 RRD 1 (White) 2 2 TOT 2 2 2 TOT 2 2
DO 1b 3 3 (Virtual DI 1) 3 TOT 3 3 3 TOT 3 3
2
DO 2a 4 4 RRD 2 (Red) 3 4 TOT 4 4 4 TOT 4 4
COM 2 5 5 RRD 2 (White) 4 NC 5 5 TOT 5 5
DO 2b 6 6 (Virtual DI 2) NC 6 6 TOT 6 6
3
DO 3a 7 7 RRD 3 (Red) 5 NC 7 7 TOT 7 7
COM 3 8 8 RRD 3 (White) 6 NC 8 8 TOT 8 8
DO 3b 9 9 (Virtual DI 3) COM 9 COM 9
4
DO 4a 10 10 RRD 4 (Red) 7 COM 10 COM 10
COM 4 11 11 RRD (White) 8
DO 4b 12 12 (Virtual DI 4)
5
DO 5a 13 9 TOT 9 11
COM 5 14 10 TOT 10 12
DO 5b 15 11 TOT 11 13
6
DO 6a 16 12 TOT 12 14
COM 6 17 13 TOT 13 15
DO 6b 18 14 TOT 14 16
7
DO 7a 19 15 TOT 15 17
COM 7 20 16 TOT 16 18
DO 7b 21 COM 19
8
DO 8a 22 COM 20
COM 8 23
DO 8b 24
13
Model No. RY5002M Model No. RY5004M Model No. RY5004A Model No. RY5004P Model No. RY5004J
Module ID = 10
AO 2
Module ID = 11
AO 4
Module ID = 12
AI 4
Module ID = 13
Pt 4
Module ID = 14
AI/Pt
I/O N
o.
Termial No.
I/O N
o.
Termial No.
I/O N
o.
Termial No.
I/O N
o.
Termial No.
I/O N
o.
Termial No.
1
AOV 1 + 1
1
AOV 1 + 1
1
AIV 1 1
1
Pt 1A 1
1
AIV 1 1
AOV 1 - 2 AOV 1 - 2 AII 1 2 Pt 1B 2 AII 1 2
AOI 1 + 3 AOI 1 + 3 COM 1 3 Pt 1B 3 COM 1 3
AOI 1 - 4 AOI 1 - 4
2
AOV 2 + 5
2
AOV 2 + 5
2
AIV 2 4
2
Pt 2A 4
2
AIV 2 4
AOV 2 - 6 AOV 2 - 6 AII 2 5 Pt 2B 5 AII 2 5
AOI 2 + 7 AOI 2 + 7 COM 2 6 Pt 2B 6 COM 2 6
AOI 2 - 8 AOI 2 - 8
3
AOV3 + 9
3
AIV 3 7
3
Pt 3A 7
3
Pt 1A 7
AOV3 - 10 AII 3 8 Pt 3B 8 Pt 1B 8
AOI3 + 11 COM 3 9 Pt 3B 9 Pt 1B 9
AOI3 - 12
4
AOV4 + 13
4
AIV 4 10
4
Pt 4A 10
4
Pt 2A 10
AOV4 - 14 AII 4 11 Pt 4B 11 Pt 2B 11
AOI4 + 15 COM 4 12 Pt 4B 12 Pt 2B 12
AOI4 - 16
14
Model No. RY5001F Model No. RY5003F
Module ID = 15
MM1
Module ID = 16
MM3
I/O N
o.
Termial No.
I/O N
o.
Termial No.
1
MM1 Close 1
1
MM1 Close 1
MM1 Open 2 MM1 Open 2
MM1 COM 3 MM1 COM 3
MM1 COM 4 MM1 COM 4
MM1 POT G 5 MM1 POT G 5
MM1 POT Y 6 MM1 POT Y 6
MM1 POT T 7 MM1 POT T 7
2 (Virtual AI 1) 2 (Virtual AI 1) 8
3
MM2 Close 9
MM2 Open 10
MM2 COM 11
MM2 COM 12
MM2 POT G 13
MM2 POT Y 14
MM2 POT T 15
4 (Virtual AI 2) 16
5
MM3 Close 17
MM3 Open 18
MM3 COM 19
MM3 COM 20
MM3 POT G 21
MM3 POT Y 22
MM3 POT T 23
6 (Virtual AI 3) 24
15
Model No. RY5001U
Module ID=17 UT
I/O No. Terminal No.
Linearization table No. used
1 (Pseudo AI1)
Neopanel built-in sensor 24
2 (Pseudo AI2)
Input value of Neoplate POT 21/22
3 (Pseudo AI3)
Battery shortage notice 26
4 (Pseudo AI4)
Neosensor wireless transmitter address 1 temperature *1 24
5 (Pseudo AI5)
Neosensor wireless transmitter address 1 humidity 25
6 (Pseudo AI6)
Neosensor wireless transmitter address 2 temperature *2 24
7 (Pseudo AI7)
Neosensor wireless transmitter address 2 humidity 25
8 (Pseudo AI8)
Reserved
9 (Pseudo AI9)
Reserved
10 (Pseudo AI10)
Reserved
11 (Pseudo AI11)
Reserved
12 (Pseudo AI12)
Reserved
Linearization table No. used No.21: Neoplate fine-adjustment type (-3.0 to 3.0°C) No.22: Neoplate absolute value type (15.0 to 3.0°C) No.24: Neopanel built-in sensor/Neopanel wireless built-in sensor/ Neosensor wireless temperature (0.0 to 50.0°C) No.25: Neosensor wireless humidity (for 0 to 100%) No.26: For Neosensor wireless/Neopanel wireless battery shortage notice Point data for battery shortage notice information is as follows: 0: Both transmitters normal 1: Battery shortage notice included for
transmitter address 1 2: Battery shortage notice included for
transmitter address 2 3: Battery shortage notice included for both
transmitters *1 Neopanel wireless (transmitter address 1) built-in sensor is pseudo AI4. *2 Neopanel wireless (transmitter address 2) built-in sensor is pseudo AI6.
16
CAPl (maintained/latched)
CAPm (momentary)