  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN01_0CYN02_901 0CYN01 CENTRAL CONTROL UNIT AT TG BUILDING 0CYN02 OVERALL MASTER CONTROL STATION AT UNIT CONTROL ROOM MCS Intercom 12P X 0.5 sq mm Shortest route shall be decided at site during Installation 30 B Location description added

    2 0CYN01_0CYN03_901 0CYN01 CENTRAL CONTROL UNIT AT TG BUILDING 0CYN03 UNIT-1 MCS AT UNIT CONTROL ROOM MCS Intercom 12P X 0.5 sq mm Shortest route shall be decided at site during Installation 50 B Location description added

    3 0CYN01_0CYN04_901 0CYN01 CENTRAL CONTROL UNIT AT TG BUILDING 0CYN04 UNIT-2 MCS AT UNIT CONTROL ROOM MCS Intercom 12P X 0.5 sq mm Shortest route shall be decided at site during Installation 50 B Location description added

    4 0CYN01_0CYN05_901 0CYN01 CENTRAL CONTROL UNIT AT TG BUILDING 0CYN05 MCS AT CHP CONTROL ROOM MCS Intercom 12P X 0.5 sq mm Shortest route shall be decided at site during Installation 1200 B Location description added

    5 0CYN01_0CYN06_901 0CYN01 CENTRAL CONTROL UNIT AT TG BUILDING 0CYN06 MCS FOR COMMON SERVICES AT UNIT CONTROL ROOM MCS Intercom 12P X 0.5 sq mm Shortest route shall be decided at site during Installation 50 B Location description added

    6 0CYN01_0CYN07_901 0CYN01 CENTRAL CONTROL UNIT AT TG BUILDING 0CYN07 MCS AT AHP CONTROL ROOM MCS Intercom 12P X 0.5 sq mm Shortest route shall be decided at site during Installation 250 B Location description added

    REV

    TO

    3. Please refer DCPL/DBPL approved data Sheet "DBP-L007-IN-DST-COM-002" for avrious types of cables used for PA system

    2. Please refer below for type of Handsets used:

    a) Type-1- Wall Mounted Outdoor Handset Station

    b) Type-2- Wall Mounted Indoor Handset Station

    c) Type-3- Wall Mounted Pilfer Proof Outdoor Handset Station

    d) Type-4- Desktop Mounted Indoor handset Station

    e) Type-5- Wall mounted Flame Proof Handset Station

    f) MCS- Master Control Station

    CABLE ROUTEACTUAL

    LENGTH(M)REMARKSCABLE TYPES.No. CABLE NUMBER

    FROMSIGNAL

    TYPE

    MCS CABLE

    5. Legends Used:

    a) MCS-Master Control Station

    b) SJB- Station Junction Box

    c) PDB-Power Distribution Board

    4. Please refer DCPL/DBPL approved documents "DBP-L007-IN-DST-COM-001" for avrious types of components like Handset, MCS Loudspeaker used for PA system

    Note:

    1. Please refer below for zone details:

    a) Zone 1 - Power House Building Unit #1, Boiler area unit #1, ESP area Unit #1, Mill &Bunker bay area - Unit#1, ID/FD/PA fan area-Unit #1, DG house & air compressor area.

    b) Zone 2 - Power House Building Unit #2, Boiler area unit #2, ESP area Unit #2, Mill &Bunker bay area - Unit#2, ID/FD/PA fan area-Unit #2

    c) Zone 3 - Common services

    d) Zone 4 - Coal handling Plant area

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 3

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN01GM001_001 0CYN01GM001 MAIN JUNCTION BOX AT TG BUILDING 1CYN01GY001 SJB OF PA HANDSET -1 AT CONTROL ROOM TYPE-4 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 50 B Location description added

    2 1CYN01_8101 1CYN01GY001 SJB OF PA HANDSET -1 AT CONTROL ROOM 1CYN01GY002 SJB OF PA HANDSET -1 AT COMPUTER ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    3 1CYN01_8102 1CYN01GY002 SJB OF PA HANDSET -1 AT COMPUTER ROOM 1CYN01GY003 SJB OF PA HANDSET -1 AT DCS ROOM TYPE-4 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    4 1CYN01_8103 1CYN01GY003 SJB OF PA HANDSET -1 AT DCS ROOM 1CYN01GY004 SJB OF PA HANDSET -1 AT TURBINE HALL AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    5 1CYN01_8104 1CYN01GY004 SJB OF PA HANDSET -1 AT TURBINE HALL AREA 1CYN01GY005 SJB OF PA HANDSET -2 AT TURBINE HALL AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    6 1CYN01_8105 1CYN01GY005 SJB OF PA HANDSET -2 AT TURBINE HALL AREA 1CYN01GY006 SJB OF PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    7 1CYN01_8106 1CYN01GY006 SJB OF PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA 1CYN01GY007 SJB OF PA HANDSET -1 AT UPS ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    8 1CYN01_8107 1CYN01GY007 SJB OF PA HANDSET -1 AT UPS ROOM 1CYN01GY008 SJB OF PA HANDSET -1 AT LT SWGR ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    9 1CYN01_8108 1CYN01GY008 SJB OF PA HANDSET -1 AT LT SWGR ROOM 1CYN01GY009 SJB OF PA HANDSET -1 AT HT SWGR ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    10 1CYN01_8109 1CYN01GY009 SJB OF PA HANDSET -1 AT HT SWGR ROOM 1CYN01GY010 SJB OF PA HANDSET -1 AT TELEPHONE EXCHANGE TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    11 1CYN01_8110 1CYN01GY010 SJB OF PA HANDSET -1 AT TELEPHONE EXCHANGE 1CYN01GY011 SJB OF PA HANDSET -1 AT INSTRUMENT LAB TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    12 1CYN01_8111 1CYN01GY011 SJB OF PA HANDSET -1 AT INSTRUMENT LAB 1CYN01GY012 SJB OF PA HANDSET -1 AT ELECTRICAL LAB TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    13 1CYN01_8112 1CYN01GY012 SJB OF PA HANDSET -1 AT ELECTRICAL LAB 1CYN01GY013 SJB OF PA HANDSET -1 AT ENGINEERS ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    14 1CYN01_8113 1CYN01GY013 SJB OF PA HANDSET -1 AT ENGINEERS ROOM 1CYN01GY014 SJB OF PA HANDSET -1 AT AHU ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    15 1CYN01_8114 1CYN01GY014 SJB OF PA HANDSET -1 AT AHU ROOM 1CYN01GY015 SJB OF PA HANDSET -1 AT MILL AND BUNKER AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 105 B HANDSET TYPE ADDED

    16 1CYN01_8115 1CYN01GY015 SJB OF PA HANDSET -1 AT MILL AND BUNKER AREA 1CYN01GY016 SJB OF PA HANDSET -2 AT MILL AND BUNKER AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    17 1CYN01_8116 1CYN01GY016 SJB OF PA HANDSET -2 AT MILL AND BUNKER AREA 1CYN01GY017 SJB OF PA HANDSET -3 AT MILL AND BUNKER AREA TYPE-3 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    18 1CYN01_8123 1CYN01GY023 SJB OF PA HANDSET -3 AT MILL AND BUNKER AREA 1CYN01GY024 SJB OF PA HANDSET -1 AT BURNER/FIRING FLOOR TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 150 B HANDSET TYPE ADDED

    19 1CYN01_8124 1CYN01GY024 SJB OF PA HANDSET -1 AT BURNER/FIRING FLOOR 1CYN01GY025 SJB OF PA HANDSET -2 AT BURNER/FIRING FLOOR TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    20 1CYN01_8117 1CYN01GY017 SJB OF PA HANDSET -2 AT BURNER/FIRING FLOOR 1CYN01GY018 SJB OF PA HANDSET -3 AT BURNER/FIRING FLOOR TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    21 1CYN01_8118 1CYN01GY018 SJB OF PA HANDSET -3 AT BURNER/FIRING FLOOR 1CYN01GY019 SJB OF PA HANDSET -1 AT FD FAN TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    22 1CYN01_8119 1CYN01GY019 SJB OF PA HANDSET -1 AT FD FAN 1CYN01GY020 SJB OF PA HANDSET -1 AT SJB OF PA FAN TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    23 1CYN01_8120 1CYN01GY020 SJB OF PA HANDSET -1 AT SJB OF PA FAN 1CYN01GY021 SJB OF PA HANDSET -1 AT ID FAN TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    24 1CYN01_8121 1CYN01GY021 SJB OF PA HANDSET -1 AT ID FAN 1CYN01GY022 SJB OF PA HANDSET -1 AT BOILER DRUM PLATFORM TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    25 1CYN01_8122 1CYN01GY022 SJB OF PA HANDSET -1 AT BOILER DRUM PLATFORM 1CYN01GY023 SJB OF PA HANDSET -2 AT BOILER DRUM PLATFORM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    26 1CYN01_8125 1CYN01GY025 SJB OF PA HANDSET -2 AT BOILER DRUM PLATFORM 1CYN01GY026 SJB OF PA HANDSET -1 AT ESP AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    27 1CYN01_8126 1CYN01GY026 SJB OF PA HANDSET -1 AT ESP AREA 1CYN01GY027 SJB OF PA HANDSET -1 AT ESP CONTROL ROOM TYPE-4 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 155 B HANDSET TYPE ADDED

    28 1CYN01_8127 1CYN01GY027 SJB OF PA HANDSET -1 AT ESP CONTROL ROOM 1CYN01GY028 SJB OF PA HANDSET -1 AT DG HOUSE TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    29 1CYN01_8128 1CYN01GY028 SJB OF PA HANDSET -1 AT DG HOUSE 1CYN01GY029 SJB OF PA HANDSET-2 AT DG HOUSE TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKSS.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    ZONE 1 SIGNAL CABLE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 4

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0BRS03_0CYN01GW001_001 0BRS03 PA SYSTEM UPS ACDB AT TG BUILDING 0CYN01GW001 POWER DISTRIBUTION BOARD-1 AT TG BUILDING PDB Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    2 0CYN01GW001_001 0CYN01GW001 POWER DISTRIBUTION BOARD-1 AT TG BUILDING 1CYN01GY001 SJB OF PA HANDSET -1 AT CONTROL ROOM TYPE-4 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    3 1CYN01_8201 1CYN01GY001 SJB OF PA HANDSET -1 AT CONTROL ROOM 1CYN01GY002 SJB OF PA HANDSET -1 AT COMPUTER ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    4 1CYN01_8202 1CYN01GY002 SJB OF PA HANDSET -1 AT COMPUTER ROOM 1CYN01GY003 SJB OF PA HANDSET -1 AT DCS ROOM TYPE-4 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    5 1CYN01_8203 1CYN01GY003 SJB OF PA HANDSET -1 AT DCS ROOM 1CYN01GY004 SJB OF PA HANDSET -1 AT TURBINE HALL AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    6 1CYN01_8204 1CYN01GY004 SJB OF PA HANDSET -1 AT TURBINE HALL AREA 1CYN01GY005 SJB OF PA HANDSET -2 AT TURBINE HALL AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    7 1CYN01_8205 1CYN01GY005 SJB OF PA HANDSET -2 AT TURBINE HALL AREA 1CYN01GY006 SJB OF PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    8 1CYN01_8206 1CYN01GY006 SJB OF PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA 1CYN01GY007 SJB OF PA HANDSET -1 AT UPS ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    9 1CYN01_8207 1CYN01GY007 SJB OF PA HANDSET -1 AT UPS ROOM 1CYN01GY008 SJB OF PA HANDSET -1 AT LT SWGR ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    10 1CYN01_8208 1CYN01GY008 SJB OF PA HANDSET -1 AT LT SWGR ROOM 1CYN01GY009 SJB OF PA HANDSET -1 AT HT SWGR ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    11 1CYN01_8209 1CYN01GY009 SJB OF PA HANDSET -1 AT HT SWGR ROOM 1CYN01GY010 SJB OF PA HANDSET -1 AT TELEPHONE EXCHANGE TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    12 1CYN01_8210 1CYN01GY010 SJB OF PA HANDSET -1 AT TELEPHONE EXCHANGE 1CYN01GY011 SJB OF PA HANDSET -1 AT INSTRUMENT LAB TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    13 1CYN01_8211 1CYN01GY011 SJB OF PA HANDSET -1 AT INSTRUMENT LAB 1CYN01GY012 SJB OF PA HANDSET -1 AT ELECTRICAL LAB TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    14 1CYN01_8212 1CYN01GY012 SJB OF PA HANDSET -1 AT ELECTRICAL LAB 1CYN01GY013 SJB OF PA HANDSET -1 AT ENGINEERS ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    15 1CYN01_8213 1CYN01GY013 SJB OF PA HANDSET -1 AT ENGINEERS ROOM 1CYN01GY014 SJB OF PA HANDSET -1 AT AHU ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    16 1CYN01_8214 1CYN01GY014 SJB OF PA HANDSET -1 AT AHU ROOM 1CYN01GY015 SJB OF PA HANDSET -1 AT MILL AND BUNKER AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 105 B HANDSET TYPE ADDED

    17 1CYN01_8215 1CYN01GY015 SJB OF PA HANDSET -1 AT MILL AND BUNKER AREA 1CYN01GY016 SJB OF PA HANDSET -2 AT MILL AND BUNKER AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    18 1CYN01_8216 1CYN01GY016 SJB OF PA HANDSET -2 AT MILL AND BUNKER AREA 1CYN01GY017 SJB OF PA HANDSET -3 AT MILL AND BUNKER AREA TYPE-3 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    19 1CYN01_8217 1CYN01GY017 SJB OF PA HANDSET -3 AT MILL AND BUNKER AREA 1CYN01GY018 SJB OF PA HANDSET -1 AT BURNER/FIRING FLOOR TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 150 B HANDSET TYPE ADDED

    20 1CYN01_8218 1CYN01GY018 SJB OF PA HANDSET -1 AT BURNER/FIRING FLOOR 1CYN01GY019 SJB OF PA HANDSET -2 AT BURNER/FIRING FLOOR TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    21 1CYN01_8219 1CYN01GY019 SJB OF PA HANDSET -2 AT BURNER/FIRING FLOOR 1CYN01GY020 SJB OF PA HANDSET -3 AT BURNER/FIRING FLOOR TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    22 1CYN01_8220 1CYN01GY020 SJB OF PA HANDSET -3 AT BURNER/FIRING FLOOR 1CYN01GY021 SJB OF PA HANDSET -1 AT FD FAN TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    23 1CYN01_8221 1CYN01GY021 SJB OF PA HANDSET -1 AT FD FAN 1CYN01GY022 SJB OF PA HANDSET -1 AT SJB OF PA FAN TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    24 1CYN01_8222 1CYN01GY022 SJB OF PA HANDSET -1 AT SJB OF PA FAN 1CYN01GY023 SJB OF PA HANDSET -1 AT ID FAN TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    25 1CYN01_8223 1CYN01GY023 SJB OF PA HANDSET -1 AT ID FAN 1CYN01GY024 SJB OF PA HANDSET -1 AT BOILER DRUM PLATFORM TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    26 1CYN01_8224 1CYN01GY024 SJB OF PA HANDSET -1 AT BOILER DRUM PLATFORM 1CYN01GY025 SJB OF PA HANDSET -2 AT BOILER DRUM PLATFORM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    27 1CYN01_8225 1CYN01GY025 SJB OF PA HANDSET -2 AT BOILER DRUM PLATFORM 1CYN01GY026 SJB OF PA HANDSET -1 AT ESP AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    28 1CYN01_8226 1CYN01GY026 SJB OF PA HANDSET -1 AT ESP AREA 1CYN01GY027 SJB OF PA HANDSET -1 AT ESP CONTROL ROOM TYPE-4 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 155 B HANDSET TYPE ADDED

    29 1CYN01_8227 1CYN01GY027 SJB OF PA HANDSET -1 AT ESP CONTROL ROOM 1CYN01GY028 SJB OF PA HANDSET -1 AT DG HOUSE TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    30 1CYN01_8228 1CYN01GY028 SJB OF PA HANDSET -1 AT DG HOUSE 1CYN01GY029 SJB OF PA HANDSET-2 AT DG HOUSE TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 1 POWER CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 5

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 1CYN01AY001_001 1CYN01AY001 PA HANDSET -1 AT CONTROL ROOM 1CYN01GU001 LOUDSPEAKER FOR PA HANDSET -1 AT CONTROL ROOM TYPE-4 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    2 1CYN01AY002_001 1CYN01AY002 PA HANDSET -1 AT COMPUTER ROOM 1CYN01GU002 LOUDSPEAKER FOR PA HANDSET -1 AT COMPUTER ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    3 1CYN01AY003_001 1CYN01AY003 PA HANDSET -1 AT DCS ROOM 1CYN01GU003 LOUDSPEAKER FOR PA HANDSET -1 AT DCS ROOM TYPE-4 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    4 1CYN01AY004_001 1CYN01AY004 PA HANDSET -1 AT TURBINE HALL AREA 1CYN01GU004 LOUDSPEAKER FOR PA HANDSET -1 AT TURBINE HALL AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    5 1CYN01AY005_001 1CYN01AY005 PA HANDSET -2 AT TURBINE HALL AREA 1CYN01GU005 LOUDSPEAKER FOR PA HANDSET -2 AT TURBINE HALL AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    6 1CYN01AY006_001 1CYN01AY006 PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA 1CYN01GU006 LOUDSPEAKER FOR PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    7 1CYN01AY007_001 1CYN01AY007 PA HANDSET -1 AT UPS ROOM 1CYN01GU007 LOUDSPEAKER FOR PA HANDSET -1 AT UPS ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    8 1CYN01AY008_001 1CYN01AY008 PA HANDSET -1 AT LT SWGR ROOM 1CYN01GU008 LOUDSPEAKER FOR PA HANDSET -1 AT LT SWGR ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    9 1CYN01AY009_001 1CYN01AY009 PA HANDSET -1 AT HT SWGR ROOM 1CYN01GU009 LOUDSPEAKER FOR PA HANDSET -1 AT HT SWGR ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    10 1CYN01AY010_001 1CYN01AY010 PA HANDSET -1 AT TELEPHONE EXCHANGE 1CYN01GU010 LOUDSPEAKER FOR PA HANDSET -1 AT TELEPHONE EXCHANGE TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    11 1CYN01AY011_001 1CYN01AY011 PA HANDSET -1 AT INSTRUMENT LAB 1CYN01GU011 LOUDSPEAKER FOR PA HANDSET -1 AT INSTRUMENT LAB TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    12 1CYN01AY012_001 1CYN01AY012 PA HANDSET -1 AT ELECTRICAL LAB 1CYN01GU012 LOUDSPEAKER FOR PA HANDSET -1 AT ELECTRICAL LAB TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    13 1CYN01AY013_001 1CYN01AY013 PA HANDSET -1 AT ENGINEERS ROOM 1CYN01GU013 LOUDSPEAKER FOR PA HANDSET -1 AT ENGINEERS ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    14 1CYN01AY014_001 1CYN01AY014 PA HANDSET -1 AT AHU ROOM 1CYN01GU014 LOUDSPEAKER FOR PA HANDSET -1 AT AHU ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    15 1CYN01AY015_001 1CYN01AY015 PA HANDSET -1 AT MILL AND BUNKER AREA 1CYN01GU015 LOUDSPEAKER FOR PA HANDSET -1 AT MILL AND BUNKER AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    16 1CYN01AY016_001 1CYN01AY016 PA HANDSET -2 AT MILL AND BUNKER AREA 1CYN01GU016 LOUDSPEAKER FOR PA HANDSET -2 AT MILL AND BUNKER AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    17 1CYN01AY017_001 1CYN01AY017 PA HANDSET -3 AT MILL AND BUNKER AREA 1CYN01GU017 LOUDSPEAKER FOR PA HANDSET -3 AT MILL AND BUNKER AREA TYPE-3 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    18 1CYN01AY018_001 1CYN01AY018 PA HANDSET -1 AT BURNER/FIRING FLOOR 1CYN01GU018 LOUDSPEAKER FOR PA HANDSET -1 AT BURNER/FIRING FLOOR TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    19 1CYN01AY019_001 1CYN01AY019 PA HANDSET -2 AT BURNER/FIRING FLOOR 1CYN01GU019 LOUDSPEAKER FOR PA HANDSET -2 AT BURNER/FIRING FLOOR TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    20 1CYN01AY020_001 1CYN01AY020 PA HANDSET -3 AT BURNER/FIRING FLOOR 1CYN01GU020 LOUDSPEAKER FOR PA HANDSET -3 AT BURNER/FIRING FLOOR TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    21 1CYN01AY021_001 1CYN01AY021 PA HANDSET -1 AT FD FAN 1CYN01GU021 LOUDSPEAKER FOR PA HANDSET -1 AT FD FAN TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    22 1CYN01AY022_001 1CYN01AY022 PA HANDSET -1 AT PA FAN 1CYN01GU022 LOUDSPEAKER FOR PA HANDSET -1 AT PA FAN TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    23 1CYN01AY023_001 1CYN01AY023 PA HANDSET -1 AT ID FAN 1CYN01GU023 LOUDSPEAKER FOR PA HANDSET -1 AT ID FAN TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    24 1CYN01AY024_001 1CYN01AY024 PA HANDSET -1 AT BOILER DRUM PLATFORM 1CYN01GU024 LOUDSPEAKER FOR PA HANDSET -1 AT BOILER DRUM PLATFORM TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    25 1CYN01AY025_001 1CYN01AY025 PA HANDSET -2 AT BOILER DRUM PLATFORM 1CYN01GU025 LOUDSPEAKER FOR PA HANDSET -2 AT BOILER DRUM PLATFORM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    26 1CYN01AY026_001 1CYN01AY026 PA HANDSET -1 AT ESP AREA 1CYN01GU026 LOUDSPEAKER FOR PA HANDSET -1 AT ESP AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    27 1CYN01AY027_001 1CYN01AY027 PA HANDSET -1 AT ESP CONTROL ROOM 1CYN01GU027 LOUDSPEAKER FOR PA HANDSET -1 AT ESP CONTROL ROOM TYPE-4 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    28 1CYN01AY028_001 1CYN01AY028 PA HANDSET -1 AT DG HOUSE 1CYN01GU028 LOUDSPEAKER FOR PA HANDSET -1 AT DG HOUSE TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    29 1CYN01AY029_001 1CYN01AY029 PA HANDSET-2 AT DG HOUSE 1CYN01GU029 LOUDSPEAKER FOR PA HANDSET -2 AT DG HOUSE TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 1 LOUDSPEAKER CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 6

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN01GM001_002 0CYN01GM001 MAIN JUNCTION BOX AT TG BUILDING 2CYN02GY001 SJB OF PA HANDSET -1 AT CONTROL ROOM TYPE-4 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 50 B Location description added

    2 2CYN02_8101 2CYN02GY001 SJB OF PA HANDSET -1 AT CONTROL ROOM 2CYN02GY002 SJB OF PA HANDSET -1 AT COMPUTER ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    3 2CYN02_8102 2CYN02GY002 SJB OF PA HANDSET -1 AT COMPUTER ROOM 2CYN02GY003 SJB OF PA HANDSET -1 AT DCS ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    4 2CYN02_8103 2CYN02GY003 SJB OF PA HANDSET -1 AT DCS ROOM 2CYN02GY004 SJB OF PA HANDSET -1 AT TURBINE HALL AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    5 2CYN02_8104 2CYN02GY004 SJB OF PA HANDSET -1 AT TURBINE HALL AREA 2CYN02GY005 SJB OF PA HANDSET -2 AT TURBINE HALL AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    6 2CYN02_8105 2CYN02GY005 SJB OF PA HANDSET -2 AT TURBINE HALL AREA 2CYN02GY006 SJB OF PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    7 2CYN02_8106 2CYN02GY006 SJB OF PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA 2CYN02GY007 SJB OF PA HANDSET -1 AT UPS ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    8 2CYN02_8107 2CYN02GY007 SJB OF PA HANDSET -1 AT UPS ROOM 2CYN02GY008 SJB OF PA HANDSET -1 AT LT SWGR ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    9 2CYN02_8108 2CYN02GY008 SJB OF PA HANDSET -1 AT LT SWGR ROOM 2CYN02GY009 SJB OF PA HANDSET -1 AT HT SWGR ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    10 2CYN02_8109 2CYN02GY009 SJB OF PA HANDSET -1 AT HT SWGR ROOM 2CYN02GY010 SJB OF PA HANDSET -1 AT MILL AND BUNKER AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 110 B HANDSET TYPE ADDED

    11 2CYN02_8110 2CYN02GY010 SJB OF PA HANDSET -1 AT MILL AND BUNKER AREA 2CYN02GY011 SJB OF PA HANDSET -2 AT MILL AND BUNKER AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    12 2CYN02_8111 2CYN02GY011 SJB OF PA HANDSET -2 AT MILL AND BUNKER AREA 2CYN02GY012 SJB OF PA HANDSET -3 AT MILL AND BUNKER AREA TYPE-3 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    13 2CYN02_8112 2CYN02GY012 SJB OF PA HANDSET -3 AT MILL AND BUNKER AREA 2CYN02GY013 SJB OF PA HANDSET -1 AT BURNER/FIRING FLOOR TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    14 2CYN02_8118 2CYN02GY018 SJB OF PA HANDSET -1 AT BURNER/FIRING FLOOR 2CYN02GY014 SJB OF PA HANDSET -2 AT BURNER/FIRING FLOOR TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 150 B HANDSET TYPE ADDED

    15 2CYN02_8119 2CYN02GY019 SJB OF PA HANDSET -2 AT BURNER/FIRING FLOOR 2CYN02GY015 SJB OF PA HANDSET -3 AT BURNER/FIRING FLOOR TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    16 2CYN02_8113 2CYN02GY013 SJB OF PA HANDSET -3 AT BURNER/FIRING FLOOR 2CYN02GY016 SJB OF PA HANDSET -1 AT FD FAN TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    17 2CYN02_8114 2CYN02GY014 SJB OF PA HANDSET -1 AT FD FAN 2CYN02GY017 SJB OF PA HANDSET -1 AT SJB OF PA FAN TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    18 2CYN02_8115 2CYN02GY015 SJB OF PA HANDSET -1 AT SJB OF PA FAN 2CYN02GY018 SJB OF PA HANDSET -1 AT ID FAN TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    19 2CYN02_8116 2CYN02GY016 SJB OF PA HANDSET -1 AT ID FAN 2CYN02GY019 SJB OF PA HANDSET -1 AT BOILER DRUM PLATFORM TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    20 2CYN02_8117 2CYN02GY017 SJB OF PA HANDSET -1 AT BOILER DRUM PLATFORM 2CYN02GY020 SJB OF PA HANDSET -2 AT BOILER DRUM PLATFORM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    21 2CYN02_8120 2CYN02GY020 SJB OF PA HANDSET -2 AT BOILER DRUM PLATFORM 2CYN02GY021 SJB OF PA HANDSET -1 AT ASH WATER PH TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    22 2CYN02_8121 2CYN02GY021 SJB OF PA HANDSET -1 AT ASH WATER PH 2CYN02GY022 SJB OF PA HANDSET -1 AT ASH WATER COMPRESSOR HOUSE TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 125 B HANDSET TYPE ADDED

    23 2CYN02_8122 2CYN02GY022 SJB OF PA HANDSET -1 AT ASH WATER COMPRESSOR HOUSE 2CYN02GY023 SJB OF PA HANDSET -1 AT ESP AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    24 2CYN02_8123 2CYN02GY023 SJB OF PA HANDSET -1 AT ESP AREA 2CYN02GY024 SJB OF PA HANDSET -1 AT ESP CONTROL ROOM TYPE-4 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 230 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 2 SIGNAL CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 7

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN01GW001_002 0CYN01GW001 POWER DISTRIBUTION BOARD-1 AT TG BUILDING 2CYN02GY001 SJB OF PA HANDSET -1 AT CONTROL ROOM TYPE-4 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B Location description added

    2 2CYN02_8201 2CYN02GY001 SJB OF PA HANDSET -1 AT CONTROL ROOM 2CYN02GY002 SJB OF PA HANDSET -1 AT COMPUTER ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    3 2CYN02_8202 2CYN02GY002 SJB OF PA HANDSET -1 AT COMPUTER ROOM 2CYN02GY003 SJB OF PA HANDSET -1 AT DCS ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    4 2CYN02_8203 2CYN02GY003 SJB OF PA HANDSET -1 AT DCS ROOM 2CYN02GY004 SJB OF PA HANDSET -1 AT TURBINE HALL AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    5 2CYN02_8204 2CYN02GY004 SJB OF PA HANDSET -1 AT TURBINE HALL AREA 2CYN02GY005 SJB OF PA HANDSET -2 AT TURBINE HALL AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    6 2CYN02_8205 2CYN02GY005 SJB OF PA HANDSET -2 AT TURBINE HALL AREA 2CYN02GY006 SJB OF PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    7 2CYN02_8206 2CYN02GY006 SJB OF PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA 2CYN02GY007 SJB OF PA HANDSET -1 AT UPS ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    8 2CYN02_8207 2CYN02GY007 SJB OF PA HANDSET -1 AT UPS ROOM 2CYN02GY008 SJB OF PA HANDSET -1 AT LT SWGR ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    9 2CYN02_8208 2CYN02GY008 SJB OF PA HANDSET -1 AT LT SWGR ROOM 2CYN02GY009 SJB OF PA HANDSET -1 AT HT SWGR ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    10 2CYN02_8209 2CYN02GY009 SJB OF PA HANDSET -1 AT HT SWGR ROOM 2CYN02GY010 SJB OF PA HANDSET -1 AT MILL AND BUNKER AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 110 B HANDSET TYPE ADDED

    11 2CYN02_8210 2CYN02GY010 SJB OF PA HANDSET -1 AT MILL AND BUNKER AREA 2CYN02GY011 SJB OF PA HANDSET -2 AT MILL AND BUNKER AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    12 2CYN02_8211 2CYN02GY011 SJB OF PA HANDSET -2 AT MILL AND BUNKER AREA 2CYN02GY012 SJB OF PA HANDSET -3 AT MILL AND BUNKER AREA TYPE-3 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    13 2CYN02_8212 2CYN02GY012 SJB OF PA HANDSET -3 AT MILL AND BUNKER AREA 2CYN02GY013 SJB OF PA HANDSET -1 AT BURNER/FIRING FLOOR TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    14 2CYN02_8213 2CYN02GY013 SJB OF PA HANDSET -1 AT BURNER/FIRING FLOOR 2CYN02GY014 SJB OF PA HANDSET -2 AT BURNER/FIRING FLOOR TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 150 B HANDSET TYPE ADDED

    15 2CYN02_8214 2CYN02GY014 SJB OF PA HANDSET -2 AT BURNER/FIRING FLOOR 2CYN02GY015 SJB OF PA HANDSET -3 AT BURNER/FIRING FLOOR TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    16 2CYN02_8215 2CYN02GY015 SJB OF PA HANDSET -3 AT BURNER/FIRING FLOOR 2CYN02GY016 SJB OF PA HANDSET -1 AT FD FAN TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    17 2CYN02_8216 2CYN02GY016 SJB OF PA HANDSET -1 AT FD FAN 2CYN02GY017 SJB OF PA HANDSET -1 AT PA FAN TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    18 2CYN02_8217 2CYN02GY017 SJB OF PA HANDSET -1 AT PA FAN 2CYN02GY018 SJB OF PA HANDSET -1 AT ID FAN TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    19 2CYN02_8218 2CYN02GY018 SJB OF PA HANDSET -1 AT ID FAN 2CYN02GY019 SJB OF PA HANDSET -1 AT BOILER DRUM PLATFORM TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    20 2CYN02_8219 2CYN02GY019 SJB OF PA HANDSET -1 AT BOILER DRUM PLATFORM 2CYN02GY020 SJB OF PA HANDSET -2 AT BOILER DRUM PLATFORM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    21 2CYN02_8220 2CYN02GY020 SJB OF PA HANDSET -2 AT BOILER DRUM PLATFORM 2CYN02GY021 SJB OF PA HANDSET -1 AT ASH WATER PH TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    22 2CYN02_8221 2CYN02GY021 SJB OF PA HANDSET -1 AT ASH WATER PH 2CYN02GY022 SJB OF PA HANDSET -1 AT ASH WATER COMPRESSOR HOUSE TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 125 B HANDSET TYPE ADDED

    23 2CYN02_8222 2CYN02GY022 SJB OF PA HANDSET -1 AT ASH WATER COMPRESSOR HOUSE 2CYN02GY023 SJB OF PA HANDSET -1 AT ESP AREA TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    24 2CYN02_8223 2CYN02GY023 SJB OF PA HANDSET -1 AT ESP AREA 2CYN02GY024 SJB OF PA HANDSET -1 AT ESP CONTROL ROOM TYPE-4 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 230 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 2 POWER CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 8

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 2CYN02AY001_001 2CYN02AY001 PA HANDSET -1 AT CONTROL ROOM 2CYN02GU001 LOUDSPEAKER FOR PA HANDSET -1 AT CONTROL ROOM TYPE-4 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    2 2CYN02AY002_001 2CYN02AY002 PA HANDSET -1 AT COMPUTER ROOM 2CYN02GU002 LOUDSPEAKER FOR PA HANDSET -1 AT COMPUTER ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    3 2CYN02AY003_001 2CYN02AY003 PA HANDSET -1 AT DCS ROOM 2CYN02GU003 LOUDSPEAKER FOR PA HANDSET -1 AT DCS ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    4 2CYN02AY004_001 2CYN02AY004 PA HANDSET -1 AT TURBINE HALL AREA 2CYN02GU004 LOUDSPEAKER FOR PA HANDSET -1 AT TURBINE HALL AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    5 2CYN02AY005_001 2CYN02AY005 PA HANDSET -2 AT TURBINE HALL AREA 2CYN02GU005 LOUDSPEAKER FOR PA HANDSET -2 AT TURBINE HALL AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    6 2CYN02AY006_001 2CYN02AY006 PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA 2CYN02GU006 LOUDSPEAKER FOR PA HANDSET -1 AT EQUIPMENT LAY DOWN AREA TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    7 2CYN02AY007_001 2CYN02AY007 PA HANDSET -1 AT UPS ROOM 2CYN02GU007 LOUDSPEAKER FOR PA HANDSET -1 AT UPS ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    8 2CYN02AY008_001 2CYN02AY008 PA HANDSET -1 AT LT SWGR ROOM 2CYN02GU008 LOUDSPEAKER FOR PA HANDSET -1 AT LT SWGR ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    9 2CYN02AY009_001 2CYN02AY009 PA HANDSET -1 AT HT SWGR ROOM 2CYN02GU009 LOUDSPEAKER FOR PA HANDSET -1 AT HT SWGR ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    10 2CYN02AY010_001 2CYN02AY010 PA HANDSET -1 AT MILL AND BUNKER AREA 2CYN02GU010 LOUDSPEAKER FOR PA HANDSET -1 AT MILL AND BUNKER AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    11 2CYN02AY011_001 2CYN02AY011 PA HANDSET -2 AT MILL AND BUNKER AREA 2CYN02GU011 LOUDSPEAKER FOR PA HANDSET -2 AT MILL AND BUNKER AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    12 2CYN02AY012_001 2CYN02AY012 PA HANDSET -3 AT MILL AND BUNKER AREA 2CYN02GU012 LOUDSPEAKER FOR PA HANDSET -3 AT MILL AND BUNKER AREA TYPE-3 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    13 2CYN02AY013_001 2CYN02AY013 PA HANDSET -1 AT BURNER/FIRING FLOOR 2CYN02GU013 LOUDSPEAKER FOR PA HANDSET -1 AT BURNER/FIRING FLOOR TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    14 2CYN02AY014_001 2CYN02AY014 PA HANDSET -2 AT BURNER/FIRING FLOOR 2CYN02GU014 LOUDSPEAKER FOR PA HANDSET -2 AT BURNER/FIRING FLOOR TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    15 2CYN02AY015_001 2CYN02AY015 PA HANDSET -3 AT BURNER/FIRING FLOOR 2CYN02GU015 LOUDSPEAKER FOR PA HANDSET -3 AT BURNER/FIRING FLOOR TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    16 2CYN02AY016_001 2CYN02AY016 PA HANDSET -1 AT FD FAN 2CYN02GU016 LOUDSPEAKER FOR PA HANDSET -1 AT FD FAN TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    17 2CYN02AY017_001 2CYN02AY017 PA HANDSET -1 AT PA FAN 2CYN02GU017 LOUDSPEAKER FOR PA HANDSET -1 AT PA FAN TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    18 2CYN02AY018_001 2CYN02AY018 PA HANDSET -1 AT ID FAN 2CYN02GU018 LOUDSPEAKER FOR PA HANDSET -1 AT ID FAN TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    19 2CYN02AY019_001 2CYN02AY019 PA HANDSET -1 AT BOILER DRUM PLATFORM 2CYN02GU019 LOUDSPEAKER FOR PA HANDSET -1 AT BOILER DRUM PLATFORM TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    20 2CYN02AY020_001 2CYN02AY020 PA HANDSET -2 AT BOILER DRUM PLATFORM 2CYN02GU020 LOUDSPEAKER FOR PA HANDSET -2 AT BOILER DRUM PLATFORM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    21 2CYN02AY021_001 2CYN02AY021 PA HANDSET -1 AT ASH WATER PH 2CYN02GU021 LOUDSPEAKER FOR PA HANDSET -1 AT ASH WATER PH TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    22 2CYN02AY022_001 2CYN02AY022 PA HANDSET -1 AT ASH WATER COMPRESSOR HOUSE 2CYN02GU022 LOUDSPEAKER FOR PA HANDSET -1 AT AHP COMPRESSOR HOUSE TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    23 2CYN02AY023_001 2CYN02AY023 PA HANDSET -1 AT ESP AREA 2CYN02GU023 LOUDSPEAKER FOR PA HANDSET -1 AT ESP AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 2 LOUDSPEAKER CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 9

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN01GM001_003 0CYN01GM001 MAIN JUNCTION BOX AT TG BUILDING 0CYN03GY001 SJB OF PA HANDSET -1 AT SERVICE BUILDING TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B Location description added

    2 0CYN03_8101 0CYN03GY001 SJB OF PA HANDSET -1 AT SERVICE BUILDING 0CYN03GY002 SJB OF PA HANDSET -2 AT SERVICE BUILDING TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    3 0CYN03_8102 0CYN03GY002 SJB OF PA HANDSET -2 AT SERVICE BUILDING 0CYN03GY003 SJB OF PA HANDSET -3 AT SERVICE BUILDING TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    4 0CYN03_8103 0CYN03GY003 SJB OF PA HANDSET -3 AT SERVICE BUILDING 0CYN03GY004 SJB OF PA HANDSET -4 AT SERVICE BUILDING TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    5 0CYN03_8104 0CYN03GY004 SJB OF PA HANDSET -4 AT SERVICE BUILDING 0CYN03GY005 SJB OF PA HANDSET -1 AT SWITCHYARD TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 320 B HANDSET TYPE ADDED

    6 0CYN03_8105 0CYN03GY005 SJB OF PA HANDSET -1 AT SWITCHYARD 0CYN03GY006 SJB OF PA HANDSET -2 AT SWITCHYARD TYPE-3 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    7 0CYN03_8106 0CYN03GY006 SJB OF PA HANDSET -2 AT SWITCHYARD 0CYN03GY007 SJB OF PA HANDSET -3 AT SWITCHYARD TYPE-4 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    8 0CYN01GM001_004 0CYN01GM001 MAIN JUNCTION BOX AT TG BUILDING 0CYN03GY008 SJB OF PA HANDSET -1 AT STORE TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 450 B Location description added

    9 0CYN03_8108 0CYN03GY008 SJB OF PA HANDSET -1 AT STORE 0CYN03GY009 SJB OF PA HANDSET -1 AT WORKSHOP TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    10 0CYN03_8109 0CYN03GY009 SJB OF PA HANDSET -1 AT WORKSHOP 0CYN03GY010 SJB OF PA HANDSET -2 AT WORKSHOP TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    11 0CYN03_8110 0CYN03GY010 SJB OF PA HANDSET -2 AT WORKSHOP 0CYN03GY011 SJB OF PA HANDSET -1 AT FIRE STATION TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    12 0CYN03_8111 0CYN03GY011 SJB OF PA HANDSET -1 AT FIRE STATION 0CYN03GY012 SJB OF PA HANDSET -2 AT FIRE STATION TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    13 0CYN01GM001_005 0CYN01GM001 MAIN JUNCTION BOX AT TG BUILDING 0CYN03GY013 SJB OF PA HANDSET -1 AT CW PUMP HOUSE TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 400 B Location description added

    14 0CYN03_8113 0CYN03GY013 SJB OF PA HANDSET -1 AT CW PUMP HOUSE 0CYN03GY014 SJB OF PA HANDSET -1 AT CW SIDE STREAM FILTER PLANT TYPE-3 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 90 B HANDSET TYPE ADDED

    15 0CYN03_8114 0CYN03GY014 SJB OF PA HANDSET -1 AT CW SIDE STREAM FILTER PLANT 0CYN03GY015 SJB OF PA HANDSET -1 AT DM PLANT AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 170 B HANDSET TYPE ADDED

    16 0CYN03_8115 0CYN03GY015 SJB OF PA HANDSET -1 AT DM PLANT AREA 0CYN03GY016 SJB OF PA HANDSET -2 AT DM PLANT AREA TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    17 0CYN03_8116 0CYN03GY016 SJB OF PA HANDSET -2 AT DM PLANT AREA 0CYN03GY017 SJB OF PA HANDSET -3 AT DM PLANT AREA TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    18 0CYN03_8117 0CYN03GY017 SJB OF PA HANDSET -3 AT DM PLANT AREA 0CYN03GY018 SJB OF PA HANDSET -4 AT DM PLANT AREA TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    19 0CYN03_8118 0CYN03GY018 SJB OF PA HANDSET -4 AT DM PLANT AREA 0CYN03GY019 SJB OF PA HANDSET -1 AT CLARIFIED AND FIRE WATER PH TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 75 B HANDSET TYPE ADDED

    20 0CYN03_8119 0CYN03GY019 SJB OF PA HANDSET -1 AT CLARIFIED AND FIRE WATER 0CYN03GY020 SJB OF PA HANDSET -2 AT CLARIFIED AND FIRE WATER PH TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    21 0CYN03_8120 0CYN03GY020 SJB OF PA HANDSET -2 AT CLARIFIED AND FIRE WATER 0CYN03GY021 SJB OF PA HANDSET -1 AT GATE TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 240 B HANDSET TYPE ADDED

    22 0CYN03_8121 0CYN03GY021 SJB OF PA HANDSET -1 AT GATE 0CYN03GY022 SJB OF PA HANDSET -1 AT ADMIN BUILDING TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 90 B HANDSET TYPE ADDED

    23 0CYN03_8122 0CYN03GY022 SJB OF PA HANDSET -1 AT ADMIN BUILDING 0CYN03GY023 SJB OF PA HANDSET -2 AT ADMIN BUILDING TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    24 0CYN03_8123 0CYN03GY023 SJB OF PA HANDSET -2 AT ADMIN BUILDING 0CYN03GY024 SJB OF PA HANDSET -3 AT ADMIN BUILDING TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    25 0CYN03_8124 0CYN03GY024 SJB OF PA HANDSET -3 AT ADMIN BUILDING 0CYN03GY025 SJB OF PA HANDSET -4 AT ADMIN BUILDING TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    26 0CYN03_8125 0CYN03GY025 SJB OF PA HANDSET -4 AT ADMIN BUILDING 0CYN03GY026 SJB OF PA HANDSET -1 AT CANTEEN TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 90 B HANDSET TYPE ADDED

    27 0CYN03_8126 0CYN03GY026 SJB OF PA HANDSET -1 AT CANTEEN 0CYN03GY027 SJB OF PA HANDSET -1 AT SECURITY AND TIME OFFICE TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 110 B HANDSET TYPE ADDED

    28 0CYN01GM001_006 0CYN01GM001 MAIN JUNCTION BOX AT TG BUILDING 0CYN03GY028 SJB OF PA HANDSET -1 AT SEWAGE TREATMENT PLANT TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 610 B Location description added

    29 0CYN03_8128 0CYN03GY028 JB OF PA HANDSET -1 AT SEWAGE TREATMENT PLAN 0CYN03GY029 SJB OF PA HANDSET -1 AT H2 GENERATION MCC ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    30 0CYN03_8129 0CYN03GY029 B OF PA HANDSET -1 AT H2 GENERATION MCC ROO 0CYN03GY030 SJB OF PA HANDSET -1 AT FUEL OIL PH TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    31 0CYN03_8130 0CYN03GY030 SJB OF PA HANDSET -1 AT FUEL OIL PH 0CYN03GY031 SJB OF PA HANDSET -2 AT FUEL OIL PH TYPE-5 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    32 0CYN03_8131 0CYN03GY031 SJB OF PA HANDSET -2 AT FUEL OIL PH 0CYN03GY032 SJB OF PA HANDSET -1 AT UNLOADING MARSHELLING TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    33 0CYN03_8132 0CYN03GY032 JB OF PA HANDSET -1 AT UNLOADING MARSHELLING 0CYN03GY033 SJB OF PA HANDSET -2 AT UNLOADING MARSHELLING TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    34 0CYN03_8133 0CYN03GY033 JB OF PA HANDSET -2 AT UNLOADING MARSHELLING 0CYN03GY034 SJB OF PA HANDSET -1 AT SILO UTILITY BUILDING TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 3 SIGNAL CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 10

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN01GW001_003 0CYN01GW001 POWER DISTRIBUTION BOARD-1 AT TG BUILDING 0CYN03GY001 SJB OF PA HANDSET -1 AT SERVICE BUILDING TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B Location description added

    2 0CYN03_8201 0CYN03GY001 SJB OF PA HANDSET -1 AT SERVICE BUILDING 0CYN03GY002 SJB OF PA HANDSET -2 AT SERVICE BUILDING TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    3 0CYN03_8202 0CYN03GY002 SJB OF PA HANDSET -2 AT SERVICE BUILDING 0CYN03GY003 SJB OF PA HANDSET -3 AT SERVICE BUILDING TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    4 0CYN03_8203 0CYN03GY003 SJB OF PA HANDSET -3 AT SERVICE BUILDING 0CYN03GY004 SJB OF PA HANDSET -4 AT SERVICE BUILDING TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    5 0CYN03_8204 0CYN03GY004 SJB OF PA HANDSET -4 AT SERVICE BUILDING 0CYN03GY005 SJB OF PA HANDSET -1 AT SWITCHYARD TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 320 B HANDSET TYPE ADDED

    6 0CYN03_8205 0CYN03GY005 SJB OF PA HANDSET -1 AT SWITCHYARD 0CYN03GY006 SJB OF PA HANDSET -2 AT SWITCHYARD TYPE-3 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    7 0CYN03_8206 0CYN03GY006 SJB OF PA HANDSET -2 AT SWITCHYARD 0CYN03GY007 SJB OF PA HANDSET -3 AT SWITCHYARD TYPE-4 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    8 0CYN01GW001_004 0CYN01GW001 POWER DISTRIBUTION BOARD-1 AT TG BUILDING 0CYN03GY008 SJB OF PA HANDSET -1 AT STORE TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 450 B Location description added

    9 0CYN03_8208 0CYN03GY008 SJB OF PA HANDSET -1 AT STORE 0CYN03GY009 SJB OF PA HANDSET -1 AT WORKSHOP TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    10 0CYN03_8209 0CYN03GY009 SJB OF PA HANDSET -1 AT WORKSHOP 0CYN03GY010 SJB OF PA HANDSET -2 AT WORKSHOP TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    11 0CYN03_8210 0CYN03GY010 SJB OF PA HANDSET -2 AT WORKSHOP 0CYN03GY011 SJB OF PA HANDSET -1 AT FIRE STATION TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    12 0CYN03_8211 0CYN03GY011 SJB OF PA HANDSET -1 AT FIRE STATION 0CYN03GY012 SJB OF PA HANDSET -2 AT FIRE STATION TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    13 0CYN01GW001_005 0CYN01GW001 POWER DISTRIBUTION BOARD-1 AT TG BUILDING 0CYN03GY013 SJB OF PA HANDSET -1 AT CW PUMP HOUSE TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 400 B Location description added

    14 0CYN03_8213 0CYN03GY013 SJB OF PA HANDSET -1 AT CW PUMP HOUSE 0CYN03GY014 SJB OF PA HANDSET -1 AT CW SIDE STREAM FILTER PLANT TYPE-3 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 90 B HANDSET TYPE ADDED

    15 0CYN03_8214 0CYN03GY014 OF PA HANDSET -1 AT CW SIDE STREAM FILTER PLANT 0CYN03GY015 SJB OF PA HANDSET -1 AT DM PLANT AREA TYPE-1 Power 3C X 2.5 sq mm Shortest route shall be decided at site during Installation 170 B HANDSET TYPE ADDED

    16 0CYN03_8215 0CYN03GY015 SJB OF PA HANDSET -1 AT DM PLANT AREA 0CYN03GY016 SJB OF PA HANDSET -2 AT DM PLANT AREA TYPE-1 Power 3C X 2.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    17 0CYN03_8216 0CYN03GY016 SJB OF PA HANDSET -2 AT DM PLANT AREA 0CYN03GY017 SJB OF PA HANDSET -3 AT DM PLANT AREA TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    18 0CYN03_8217 0CYN03GY017 SJB OF PA HANDSET -3 AT DM PLANT AREA 0CYN03GY018 SJB OF PA HANDSET -4 AT DM PLANT AREA TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    19 0CYN03_8218 0CYN03GY018 SJB OF PA HANDSET -4 AT DM PLANT AREA 0CYN03GY019 SJB OF PA HANDSET -1 AT CLARIFIED AND FIRE WATER PH TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 75 B HANDSET TYPE ADDED

    20 0CYN03_8219 0CYN03GY019 SJB OF PA HANDSET -1 AT CLARIFIED AND FIRE WATER 0CYN03GY020 SJB OF PA HANDSET -2 AT CLARIFIED AND FIRE WATER PH TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    21 0CYN03_8220 0CYN03GY020 SJB OF PA HANDSET -2 AT CLARIFIED AND FIRE WATER 0CYN03GY021 SJB OF PA HANDSET -1 AT GATE TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 240 B HANDSET TYPE ADDED

    22 0CYN03_8221 0CYN03GY021 SJB OF PA HANDSET -1 AT GATE 0CYN03GY022 SJB OF PA HANDSET -1 AT ADMIN BUILDING TYPE-1 Power 3C X 2.5 sq mm Shortest route shall be decided at site during Installation 90 B HANDSET TYPE ADDED

    23 0CYN03_8222 0CYN03GY022 SJB OF PA HANDSET -1 AT ADMIN BUILDING 0CYN03GY023 SJB OF PA HANDSET -2 AT ADMIN BUILDING TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    24 0CYN03_8223 0CYN03GY023 SJB OF PA HANDSET -2 AT ADMIN BUILDING 0CYN03GY024 SJB OF PA HANDSET -3 AT ADMIN BUILDING TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    25 0CYN03_8224 0CYN03GY024 SJB OF PA HANDSET -3 AT ADMIN BUILDING 0CYN03GY025 SJB OF PA HANDSET -4 AT ADMIN BUILDING TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    26 0CYN03_8225 0CYN03GY025 SJB OF PA HANDSET -4 AT ADMIN BUILDING 0CYN03GY026 SJB OF PA HANDSET -1 AT CANTEEN TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 90 B HANDSET TYPE ADDED

    27 0CYN03_8226 0CYN03GY026 SJB OF PA HANDSET -1 AT CANTEEN 0CYN03GY027 SJB OF PA HANDSET -1 AT SECURITY AND TIME OFFICE TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 110 B HANDSET TYPE ADDED

    28 0CYN01GW001_006 0CYN01GW001 POWER DISTRIBUTION BOARD-1 AT TG BUILDING 0CYN03GY028 SJB OF PA HANDSET -1 AT SEWAGE TREATMENT PLANT TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 610 B Location description added

    29 0CYN03_8128 0CYN03GY028 JB OF PA HANDSET -1 AT SEWAGE TREATMENT PLAN 0CYN03GY029 SJB OF PA HANDSET -1 AT H2 GENERATION MCC ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    30 0CYN03_8129 0CYN03GY029 B OF PA HANDSET -1 AT H2 GENERATION MCC ROO 0CYN03GY030 SJB OF PA HANDSET -1 AT FUEL OIL PH TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    31 0CYN03_8130 0CYN03GY030 SJB OF PA HANDSET -1 AT FUEL OIL PH 0CYN03GY031 SJB OF PA HANDSET -2 AT FUEL OIL PH TYPE-5 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 80 B HANDSET TYPE ADDED

    32 0CYN03_8131 0CYN03GY031 SJB OF PA HANDSET -2 AT FUEL OIL PH 0CYN03GY032 SJB OF PA HANDSET -1 AT UNLOADING MARSHELLING TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    33 0CYN03_8132 0CYN03GY032 JB OF PA HANDSET -1 AT UNLOADING MARSHELLING 0CYN03GY033 SJB OF PA HANDSET -2 AT UNLOADING MARSHELLING TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    34 0CYN03_8133 0CYN03GY033 JB OF PA HANDSET -2 AT UNLOADING MARSHELLING 0CYN03GY034 SJB OF PA HANDSET -1 AT SILO UTILITY BUILDING TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 3 POWER CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 11

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN03AY001_001 0CYN03AY001 PA HANDSET -1 AT SERVICE BUILDING 0CYN03GU001 LOUDSPEAKER FOR PA HANDSET -1 AT SERVICE BUILDING TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    2 0CYN03AY002_001 0CYN03AY002 PA HANDSET -2 AT SERVICE BUILDING 0CYN03GU002 LOUDSPEAKER FOR PA HANDSET -2 AT SERVICE BUILDING TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    3 0CYN03AY003_001 0CYN03AY003 PA HANDSET -3 AT SERVICE BUILDING 0CYN03GU003 LOUDSPEAKER FOR PA HANDSET -3 AT SERVICE BUILDING TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    4 0CYN03AY004_001 0CYN03AY004 PA HANDSET -4 AT SERVICE BUILDING 0CYN03GU004 LOUDSPEAKER FOR PA HANDSET -4 AT SERVICE BUILDING TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    5 0CYN03AY005_001 0CYN03AY005 PA HANDSET -1 AT SWITCHYARD 0CYN03GU005 LOUDSPEAKER FOR PA HANDSET -1 AT SWITCHYARD TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    6 0CYN03AY006_001 0CYN03AY006 PA HANDSET -2 AT SWITCHYARD 0CYN03GU006 LOUDSPEAKER FOR PA HANDSET -2 AT SWITCHYARD TYPE-3 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    7 0CYN03AY007_001 0CYN03AY007 PA HANDSET -3 AT SWITCHYARD 0CYN03GU007 LOUDSPEAKER FOR PA HANDSET -3 AT SWITCHYARD TYPE-4 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    8 0CYN03AY008_001 0CYN03AY008 PA HANDSET -1 AT STORE 0CYN03GU008 LOUDSPEAKER FOR PA HANDSET -1 AT STORE TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    9 0CYN03AY009_001 0CYN03AY009 PA HANDSET -1 AT WORKSHOP 0CYN03GU009 LOUDSPEAKER FOR PA HANDSET -1 AT WORKSHOP TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    10 0CYN03AY010_001 0CYN03AY010 PA HANDSET -2 AT WORKSHOP 0CYN03GU010 LOUDSPEAKER FOR PA HANDSET -2 AT WORKSHOP TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    11 0CYN03AY011_001 0CYN03AY011 PA HANDSET -1 AT FIRE STATION 0CYN03GU011 LOUDSPEAKER FOR PA HANDSET -1 AT FIRE STATION TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    12 0CYN03AY012_001 0CYN03AY012 PA HANDSET -2 AT FIRE STATION 0CYN03GU012 LOUDSPEAKER FOR PA HANDSET -2 AT FIRE STATION TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    13 0CYN03AY013_001 0CYN03AY013 PA HANDSET -1 AT CW PUMP HOUSE 0CYN03GU013 LOUDSPEAKER FOR PA HANDSET -1 AT CW PUMP HOUSE TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    14 0CYN03AY014_001 0CYN03AY014 PA HANDSET -1 AT CW SIDE STREAM FILTER PLANT 0CYN03GU014 LOUDSPEAKER FOR PA HANDSET -1 AT CW SIDE STREAM FILTER PLANT TYPE-3 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    15 0CYN03AY015_001 0CYN03AY015 PA HANDSET -1 AT DM PLANT AREA 0CYN03GU015 LOUDSPEAKER FOR PA HANDSET -1 AT DM PLANT AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    16 0CYN03AY016_001 0CYN03AY016 PA HANDSET -2 AT DM PLANT AREA 0CYN03GU016 LOUDSPEAKER FOR PA HANDSET -2 AT DM PLANT AREA TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    17 0CYN03AY017_001 0CYN03AY017 PA HANDSET -3 AT DM PLANT AREA 0CYN03GU017 LOUDSPEAKER FOR PA HANDSET -3 AT DM PLANT AREA TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    18 0CYN03AY018_001 0CYN03AY018 PA HANDSET -4 AT DM PLANT AREA 0CYN03GU018 LOUDSPEAKER FOR PA HANDSET -4 AT DM PLANT AREA TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    19 0CYN03AY019_001 0CYN03AY019 PA HANDSET -1 AT CLARIFIED AND FIRE WATER PH 0CYN03GU019 LOUDSPEAKER FOR PA HANDSET -1 AT CLARIFIED AND FIRE WATER PH TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    20 0CYN03AY020_001 0CYN03AY020 PA HANDSET -2 AT CLARIFIED AND FIRE WATER PH 0CYN03GU020 LOUDSPEAKER FOR PA HANDSET -2 AT CLARIFIED AND FIRE WATER PH TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    21 0CYN03AY021_001 0CYN03AY021 PA HANDSET -1 AT GATE 0CYN03GU021 LOUDSPEAKER FOR PA HANDSET -1 AT GATE TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    22 0CYN03AY022_001 0CYN03AY022 PA HANDSET -1 AT ADMIN BUILDING 0CYN03GU022 LOUDSPEAKER FOR PA HANDSET -1 AT ADMIN BUILDING TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    23 0CYN03AY023_001 0CYN03AY023 PA HANDSET -2 AT ADMIN BUILDING 0CYN03GU023 LOUDSPEAKER FOR PA HANDSET -2 AT ADMIN BUILDING TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    24 0CYN03AY024_001 0CYN03AY024 PA HANDSET -3 AT ADMIN BUILDING 0CYN03GU024 LOUDSPEAKER FOR PA HANDSET -3 AT ADMIN BUILDING TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    25 0CYN03AY025_001 0CYN03AY025 PA HANDSET -4 AT ADMIN BUILDING 0CYN03GU025 LOUDSPEAKER FOR PA HANDSET -4 AT ADMIN BUILDING TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    26 0CYN03AY026_001 0CYN03AY026 PA HANDSET -1 AT CANTEEN 0CYN03GU026 LOUDSPEAKER FOR PA HANDSET -1 AT CANTEEN TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    27 0CYN03AY027_001 0CYN03AY027 PA HANDSET -1 AT SECURITY AND TIME OFFICE 0CYN03GU027 LOUDSPEAKER FOR PA HANDSET -1 AT SECURITY AND TIME OFFICE TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    28 0CYN03AY028_001 0CYN03AY028 PA HANDSET -1 AT SEWAGE TREATMENT PLANT 0CYN03GU028 LOUDSPEAKER FOR PA HANDSET -1 AT SEWAGE TREATMENT PLANT TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    29 0CYN03AY029_001 0CYN03AY029 PA HANDSET -1 AT H2 GENERATION MCC ROOM 0CYN03GU029 LOUDSPEAKER FOR PA HANDSET -1 AT H2 GENERATION MCC ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    30 0CYN03AY030_001 0CYN03AY030 PA HANDSET -1 AT FUEL OIL PH 0CYN03GU030 LOUDSPEAKER FOR PA HANDSET -1 AT FUEL OIL PH TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    31 0CYN03AY031_001 0CYN03AY031 PA HANDSET -2 AT FUEL OIL PH 0CYN03GU031 LOUDSPEAKER FOR PA HANDSET -2 AT FUEL OIL PH TYPE-5 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    32 0CYN03AY032_001 0CYN03AY032 PA HANDSET -1 AT UNLOADING MARSHELLING 0CYN03GU032 LOUDSPEAKER FOR PA HANDSET -1 AT UNLOADING MARSHELLING TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    33 0CYN03AY033_001 0CYN03AY033 PA HANDSET -2 AT UNLOADING MARSHELLING 0CYN03GU033 LOUDSPEAKER FOR PA HANDSET -2 AT UNLOADING MARSHELLING TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    34 0CYN03AY034_001 0CYN03AY034 PA HANDSET -1 AT SILO UTILITY BUILDING 0CYN03GU034 LOUDSPEAKER FOR PA HANDSET -1 AT SILO UTILITY BUILDING TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 3 LOUDSPEAKER CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 12

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN01GM001_007 0CYN01GM001 MAIN JUNCTION BOX AT TG BUILDING 0CYN03GY001 SJB OF PA HANDSET -1 AT TP-8 TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 600 B Location description added

    2 0CYN04_8101 0CYN04GY001 SJB OF PA HANDSET -1 AT TP-8 0CYN04GY002 SJB OF PA HANDSET -1 AT TP-7 TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    3 0CYN04_8102 0CYN04GY002 SJB OF PA HANDSET -1 AT TP-7 0CYN04GY003 SJB OF PA HANDSET -1 AT TP-6 TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    4 0CYN04_8103 0CYN04GY003 SJB OF PA HANDSET -1 AT TP-6 0CYN04GY004 SJB OF PA HANDSET -1 AT TP-5 TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    5 0CYN04_8104 0CYN04GY004 SJB OF PA HANDSET -1 AT TP-5 0CYN04GY005 SJB OF PA HANDSET -1 AT TP-4 TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    6 0CYN04_8105 0CYN04GY005 SJB OF PA HANDSET -1 AT TP-4 0CYN04GY006 SJB OF PA HANDSET -1 AT TP-3 TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 400 B HANDSET TYPE ADDED

    7 0CYN04_8106 0CYN04GY006 SJB OF PA HANDSET -1 AT TP-3 0CYN04GY007 SJB OF PA HANDSET -1 AT RECLAIM HOPPER TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 300 B HANDSET TYPE ADDED

    8 0CYN04_8107 0CYN04GY007 SJB OF PA HANDSET -1 AT RECLAIM HOPPER 0CYN04GY008 SJB OF PA HANDSET -1 AT TP-2 TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 90 B HANDSET TYPE ADDED

    9 0CYN04_8108 0CYN04GY008 SJB OF PA HANDSET -1 AT TP-2 0CYN04GY009 SJB OF PA HANDSET -1 AT TP-1 TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 100 B HANDSET TYPE ADDED

    10 0CYN04_8109 0CYN04GY009 SJB OF PA HANDSET -1 AT TP-1 0CYN04GY010 SJB OF PA HANDSET -1 AT CHP CONTROL ROOM TYPE-4 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    11 0CYN04_8110 0CYN04GY010 SJB OF PA HANDSET -1 AT CHP CONTROL ROOM 0CYN04GY011 SJB OF PA HANDSET -2 AT CHP CONTROL ROOM TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    12 0CYN04_8111 0CYN04GY011 SJB OF PA HANDSET -2 AT CHP CONTROL ROOM 0CYN04GY012 SJB OF PA HANDSET -1 AT CHP CRUSHER HOUSE TYPE-1 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    13 0CYN04_8112 0CYN04GY012 SJB OF PA HANDSET -1 AT CHP CRUSHER HOUSE 0CYN04GY013 SJB OF PA HANDSET -2 AT CHP CRUSHER HOUSE TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 60 B HANDSET TYPE ADDED

    14 0CYN04_8113 0CYN04GY013 SJB OF PA HANDSET -2 AT CHP CRUSHER HOUSE 0CYN04GY014 SJB OF PA HANDSET -1 AT PUMP HOUSE TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 120 B HANDSET TYPE ADDED

    15 0CYN04_8114 0CYN04GY014 SJB OF PA HANDSET -1 AT PUMP HOUSE 0CYN04GY015 SJB OF PA HANDSET -1 AT STACKER RECLAIMER TYPE-2 Intercom 3P X 0.5 sq mm Shortest route shall be decided at site during Installation 300 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 4 SIGNAL CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 13

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0ECA01GW051_001 0ECA01GW051 POWER DISTRIBUTION BOARD-1 AT TP-8 0CYN04GY001 SJB OF PA HANDSET -1 AT TP-8 TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    2 0ECA01GW046_002 0ECA01GW046 POWER DISTRIBUTION BOARD-1 AT TP-7 0CYN04GY002 SJB OF PA HANDSET -1 AT TP-7 TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    3 0ECA01GW041_003 0ECA01GW041 POWER DISTRIBUTION BOARD-1 AT TP-6 0CYN04GY003 SJB OF PA HANDSET -1 AT TP-6 TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    4 0ECA01GW036_004 0ECA01GW036 POWER DISTRIBUTION BOARD-1 AT TP-5 0CYN04GY004 SJB OF PA HANDSET -1 AT TP-5 TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    5 0ECA01GW031_005 0ECA01GW031 POWER DISTRIBUTION BOARD-1 AT TP-4 0CYN04GY005 SJB OF PA HANDSET -1 AT TP-4 TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    6 0ECA01GW026_006 0ECA01GW026 POWER DISTRIBUTION BOARD-1 AT TP-3 0CYN04GY006 SJB OF PA HANDSET -1 AT TP-3 TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    7 0ECA01GW021_007 0ECA01GW021 POWER DISTRIBUTION BOARD-1 AT RH 0CYN04GY007 SJB OF PA HANDSET -1 AT RECLAIM HOPPER TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    8 0ECA01GW016_008 0ECA01GW016 POWER DISTRIBUTION BOARD-1 AT TP-2 0CYN04GY008 SJB OF PA HANDSET -1 AT TP-2 TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    9 0ECA01GW011_009 0ECA01GW011 POWER DISTRIBUTION BOARD-1 AT TP-1 0CYN04GY009 SJB OF PA HANDSET -1 AT TP-1 TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    10 0CYN04_8213 0CYN04GY013 SJB OF PA HANDSET -2 AT CHP CRUSHER HOUSE 0CYN04GY010 SJB OF PA HANDSET -1 AT CHP CONTROL ROOM TYPE-4 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    11 0CYN04_8210 0CYN04GY010 SJB OF PA HANDSET -1 AT CHP CONTROL ROOM 0CYN04GY011 SJB OF PA HANDSET -2 AT CHP CONTROL ROOM TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    12 0ECA01GW005_012 0ECA01GW005 POWER DISTRIBUTION BOARD-1 AT CRUSHER HOUSE 0CYN04GY012 SJB OF PA HANDSET -1 AT CHP CRUSHER HOUSE TYPE-1 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    13 0CYN04_8212 0CYN04GY012 SJB OF PA HANDSET -1 AT CHP CRUSHER HOUSE 0CYN04GY013 SJB OF PA HANDSET -2 AT CHP CRUSHER HOUSE TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    14 0ECA01GW001_014 0ECA01GW001 POWER DISTRIBUTION BOARD-1 AT PUMP HOUSE 0CYN04GY014 SJB OF PA HANDSET -1 AT PUMP HOUSE TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 50 B HANDSET TYPE ADDED

    15 0BTX22_015 0BTX22 POWER DISTRIBUTION BOARD -1 AT STACKER RECLAIMER 0CYN04GY015 SJB OF PA HANDSET -1 AT STACKER RECLAIMER TYPE-2 Power 3C X 1.5 sq mm Shortest route shall be decided at site during Installation 10 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 4 POWER CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 14

  • L&T-SARGENT & LUNDY LTD. D B SUPER THERMAL POWER PROJECT-2 X 600 MW

    at Chhattisgarh

    BALANCE OF PLANT PACKAGE

    CABLE SCHEDULE FOR PA SYSTEM

    PROJECT: O10231-I-PG

    DOC:O10231-I-TP-IN-VD-0061/

    DBP-L007-IN-00-EIC-COM-003

    REV:B

    TAG NO DESCRIPTION TAG NO DESCRIPTION HANDSET TYPE

    1 0CYN04AY001_001 0CYN04AY001 PA HANDSET -1 AT TP-8 0CYN04GU001 PA HANDSET -1 AT TP-8 TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    2 0CYN04AY002_001 0CYN04AY002 PA HANDSET -1 AT TP-7 0CYN04GU002 LOUDSPEAKER OF PA HANDSET -1 AT TP-7 TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    3 0CYN04AY003_001 0CYN04AY003 PA HANDSET -1 AT TP-6 0CYN04GU003 LOUDSPEAKER OF PA HANDSET -1 AT TP-6 TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    4 0CYN04AY004_001 0CYN04AY004 PA HANDSET -1 AT TP-5 0CYN04GU004 LOUDSPEAKER OF PA HANDSET -1 AT TP-5 TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    5 0CYN04AY005_001 0CYN04AY005 PA HANDSET -1 AT TP-4 0CYN04GU005 LOUDSPEAKER OF PA HANDSET -1 AT TP-4 TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    6 0CYN04AY006_001 0CYN04AY006 PA HANDSET -1 AT TP-3 0CYN04GU006 LOUDSPEAKER OF PA HANDSET -1 AT TP-3 TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    7 0CYN04AY007_001 0CYN04AY007 PA HANDSET -1 AT RECLAIM HOPPER 0CYN04GU007 LOUDSPEAKER OF PA HANDSET -1 AT RECLAIM HOPPER TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    8 0CYN04AY008_001 0CYN04AY008 PA HANDSET -1 AT TP-2 0CYN04GU008 LOUDSPEAKER OF PA HANDSET -1 AT TP-2 TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    9 0CYN04AY009_001 0CYN04AY009 PA HANDSET -1 AT TP-1 0CYN04GU009 LOUDSPEAKER OF PA HANDSET -1 AT TP-1 TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    10 0CYN04AY010_001 0CYN04AY010 PA HANDSET -1 AT CHP CONTROL ROOM 0CYN04GU010 LOUDSPEAKER OF PA HANDSET -1 AT CHP CONTROL ROOM TYPE-4 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    11 0CYN04AY011_001 0CYN04AY011 PA HANDSET -2 AT CHP CONTROL ROOM 0CYN04GU011 LOUDSPEAKER OF PA HANDSET -2 AT CHP CONTROL ROOM TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    12 0CYN04AY012_001 0CYN04AY012 PA HANDSET -1 AT CHP CRUSHER HOUSE 0CYN04GU012 LOUDSPEAKER OF PA HANDSET -1 AT CHP CRUSHER HOUSE TYPE-1 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    13 0CYN04AY013_001 0CYN04AY013 PA HANDSET -2 AT CHP CRUSHER HOUSE 0CYN04GU013 LOUDSPEAKER OF PA HANDSET -2 AT CHP CRUSHER HOUSE TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    14 0CYN04AY014_001 0CYN04AY014 PA HANDSET -1 AT PUMP HOUSE 0CYN04GU014 LOUDSPEAKER OF PA HANDSET -1 AT PUMP HOUSE TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    15 0CYN04AY015_001 0CYN04AY015 PA HANDSET -1 AT STACKER RECLAIMER 0CYN04GU015 LOUDSPEAKER OF PA HANDSET -1 AT STACKER RECLAIMER TYPE-2 Intercom 1P X 0.5 sq mm Shortest route shall be decided at site during Installation 4 B HANDSET TYPE ADDED

    CABLE ROUTEACTUAL

    LENGTH(M)REV REMARKS

    ZONE 4 LOUDSPEAKER CABLE

    S.No. CABLE NUMBER

    FROM TOSIGNAL

    TYPECABLE TYPE

    PREPARED BY: PM

    REVIEWED BY: GPJ

    APPROVED BY: GCSR

    PAGE: 15

    PA-1PA-2