    RT SeriesData Sheet

    Date: April 20, 2015, 6:07 pm

    Project Name Model Qty HP TotalTHYSSEN. PUEBLA RT-822210-A 1 20

    Performance Data Unit dataEWT (F) 104 Quantity of Motors 2LWT (F) 69.8 Motor HP 10.0WBT (F) 62.6 Quantity of Fans 2Total Required Flow Rate (gpm) 521.0 Air Flow (cfm) 107,800Total Nominal Flow Rate (gpm) 536.2 Basin Capacity (gal) 1,431Nominal Flow Rate per Unit (gpm) 536.2 Shipping Weight (lb) 9,506

    Total Required Heat Load (Btu/h) 8,916,227 Operating Weight (lb) 24,415Tower Configuration DOUBLE FANWater Data S.P.L. dB(A) at 5 ft 83

    Evaporation (gpm) 17.179 S.P.L. dB(A) at 50 ft 63Dimensions

    Length (in) 274.00Width (in) 99.50Height (in) 193.50

    Connection diameters Hot Water Inlet (in) 8Cold Water Outlet (in) 10Overflow (in) 2Water make-up (in) 1 1/2Drain (in) 2Purge (in) 3/4

    Notes:

    Location: PUEBLA From: MARIO CONTRERAS Attention: ING. HIGINIO BALBUENA Company:Fábrica Mexicana de Torres

    Company: THYSSENKRUPP Phone:01 56 39 36 13 ext 118

    Date: 20 ABRIL 2015 E-mail:[email protected]