Data Sheet 10/63-6.60-EN Rev
FOUNDATIONJunctions, Co
. C
Fieldbusnnectors, Accessories
F
T
OperateEngineer
Control
Field
FOUNDATION Fieldbus-HSE
Ethernet
LinkingDevice
FO
UN
DAT
ION
Fie
ldbu
s-H
1
FO
UN
DAT
ION
Fie
ldbu
s-H
1
OPCServer
FOUNDATION Fieldbus-H1— Junctions— Connectors— Accessories
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 ENFOUNDATION Fieldbus-H1
Fieldbus cableShielding
8 50 … 706
Shield is connected to the enclosure via the EMC cable glands.Thread the cable gland onto the seal, on the unprepared fieldbus cable Strip fieldbus cable here
Draw back the shielding braid over the sheath of the fieldbus cable
NPJ130-NO, NPJ460-NO, NFJ120-NE, NFJ420-NE – FOUNDATION Fieldbus-H1 Junctions- Non-Ex versionRecommendation of mounting
Technical dataTemperature rangeOperating temperature -40...+80°CType of protection IP 66Material of housing high-quality aluminium alloy (AL-Si 12)Surface stove-enamelled NPJxxx: RAL 7001, NFJxxx: RAL 9005FOUNDATION Fieldbus-H1 connection tension spring 0.5...1.5 mmCable bushing EMC cable gland M16Clamping area 5.5...9.6 mmMeasuring instrument con
TorquesM16 cable gland on housing ~ 5 NmCoupling ring M16 cable gland ~ 3.75 NmHousing lid 1.8...2.0 NmExternal earthing cable 1.8...2.0 Nm
2
Installation advice
nector, 7/8”x1, 4pin contacts brass, surface CuZnAu
The FOUNDATION Fieldbus H1 T-Connectors are available as Standard and Ex(Haz.) version. They are used for coupling1 up to 4 transmitters to the H1 trunk via spurs.
Non-interrupted BUS operation when exchanging or extending a PA transmitterEasy to useLow installation costsExternal grounding cablePressure-compensation elementEMC cable glandTension spring connectionAluminium (standard) housingNon-Ex design (integrated bus termination, switchable)Ex(Haz.) design acc. to ATEX (external bus termination with )
-The spurs can optionally be connected by an M12 connection or directly via
the EMC cable gland.�
�
�
�
�
�
�
�
�
� NPZ100-EX
Use ferrules!
2
3
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 ENFOUNDATION Fieldbus-H1
off on
off on
A A AB B BS S S
off onC1R1
19
58
64
125
onoffR1 C1
AA BB SS AA BB SS A BS A BS19
80
36
,53
6,5
A (-) (1)
S (3)
B (+) (2)n.c. (4)
A
A
A
S
S
S
B
B
B
1uF 50VdcC1
R1
100R
off on
A
A A
AS
S S S
SB
B B B
B
1uF
63V
100R
A (-) (1)
S (3)
B (+) (2)n.c. (4)
off on
A S B A
All drawings not scaled! All units in millimeter!
Bus terminator:
Bus terminator:
The Transmitter (spur, 1-way) are connected using cable bushing.
NPJ130-NO Junction – version,FOUNDATION Fieldbus-H1 Non-Ex with bus termination
NPJ460-NO Junction – version,FOUNDATION Fieldbus-H1 Non-Ex with bus termination
The Transmitter (spurs, 4-way) are connected using cable bushing.
NFJ120-NE Junction – Ex and version,FOUNDATION Fieldbus-H1 Non-Ex without bus termination
The Transmitter (spurs, 1-way) are connected using 7/8” connection.
Technical data: see page 5
- If the NFJ120-NE is used as last participant in an H1 segment an additional external bus termination NPZ100-EX has to
be foreseen!
NFJ420-NE Junction – Ex and version,FOUNDATION Fieldbus-H1 Non-Ex without bus termination
The Transmitter (spurs, 4-way) are connected using 7/8” connection.
Technical data: see page 5
- If the NFJ420-NE is used as last participant in an H1 segment an additional external bus termination NPZ100-EX has to
be foreseen!
Shielding
Bus Terminator
Wire bridge
Enclosure
Shielding
Bus Terminator
Wirebridge
Enclosure
4
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 ENFOUNDATION Fieldbus-H1
Fieldbus cableShielding
8 50 … 706
Shield is connected to the enclosure via the EMC cable glands.Thread the cable gland onto the seal, on the unprepared fieldbus cable Strip fieldbus cable here
Draw back the shielding braid over the sheath of the fieldbus cable
Recommendation of mounting:
Technical dataTemperature rangeOperating temperature -40...+80°CType of protection IP 66Material of housing high-quality aluminium alloy (AL-Si 12)Surface stove-enamelled NPJxxx: RAL 5015, NFJxxx: RAL 9005FOUNDATION Fieldbus-H1 connection tension spring 0.5...1.5 mmCable bushing EMC cable gland M16Clamping area 5.5...9.6 mmMeasuring instrument conn
TorquesM16 cable gland on housing ~ 5 NmCoupling ring M16 cable gland ~ 3.75 NmHousing lid 1.8...2.0 NmAdapter / spur cable hand-tightExternal earthing cable 1.8...2.0 Nm
2
ATEX Certification EEx ia IIC T6
Installation advice
ector, 7/8”x1, 4pin contacts brass, surface CuZnAu
Use ferrules!
NPJ130-EX, NPJ460-EX, NFJ120-NE, NFJ420-NE – FOUNDATION Fieldbus-H1 Junctions– Ex area EEx (ia) ATEX
5
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 ENFOUNDATION Fieldbus-H1
36
,53
6,5
A A AB B BS S S
19
58
64
125
80
AA BB SS AA BB SS A BS A BS19
A S B A S B- + - +
A S B
75
80
19
A
BS A BSA BS A BS A BS A BSA
B
S
On
- +- +
S S S S S
B B B B B
A A A A A
Off
175
80
19
A
A
A-
S
S
S
B
B
B+
PE
58
4
3
2
1
58
A
A A A A
A-
S
S S S S
S
B
B B B B
B+
PE
A
A
A
S
S
S
B
B
B
A (-) (1)
S (3)
B (+) (2)n.c. (4)
A
A A A
A
S
S S S
S
B
B B B
B
A S B
A (-) (1)
S (3)
B (+) (2)n.c. (4)
A (-) (1)
S (3)
B (+) (2)n.c. (4)
A (-) (1)
S (3)
B (+) (2)n.c. (4)
4
3
2
1
All drawings not scaled! All units in millimeter!
Bus terminator:With externalNPZ100-EX only
Bus terminator:With externalNPZ100-EX only
NPJ130-EX FOUNDATION Fieldbus-H1 Junction – Ex area EEx (ia) ATEX, without bus termination
NPJ460-EX FOUNDATION Fieldbus-H1 Junction – Ex area EEx (ia) ATEX, without bus termination
The Transmitter (spur, 1-way) are connected using cable bushing.
The Transmitter (spurs, 4-way) are connected using cable bushing.
NFJ120-NE Junction – ,FOUNDATION Fieldbus-H1 Ex area EEx (ia) ATEX without bus termination
The Transmitter (spurs, 1-way) are connected using 7/8” connection.
NFJ420-NE Junction – ,FOUNDATION Fieldbus-H1 Ex area EEx (ia) ATEX without bus termination
The Transmitter (spurs, 4-way) are connected using 7/8” connection.
Wire-
bridgeBus terminator:With externalNPZ100-EX only
Bus terminator:With externalNPZ100-EX only
Socket 7/8”/ H1 code
Socket 7/8”/ H1 code
Wire-
bridge
Shielding
Wire bridge
Enclosure
Wirebridge
Enclosure
Shielding
Shielding
Shielding
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 EN
30,5
30,5
EEx ia IIC T6Ui 17,5 VIi 380 mA
KEMA 01 ATEX 1058 X
06
EEx m II T610 … 30 V
Ta: -40 … 80 °C
1717 0344
II 2 G D T 80°C IP 67T
45
20
49
EEx ia IIC T6Ui 17,5 VIi 380 mA
KEMA 01 ATEX 1058 X
06
EEx m II T610 … 30 V
Ta: -40 … 80 °C
1717 0344
II 2 G D T 80°C IP 67T
EEx ia IIC T6Ui 17,5 VIi 380 mA
KEMA 01 ATEX 1058 X
06
EEx m II T610 … 30 V
Ta: -40 … 80 °C
1717 0344
II 2 G D T 80°C IP 67T
NPZ100-EX Bus Terminator –FOUNDATION Fieldbus-H1 Ex area EEx (ia) ATEX
Technical data
Installation advice
Temperature range/operating temperature -40...+80 ºCType of protection IP 66Material of housing high-quality aluminium alloy (AL-Si 12)Surface black powder coatedConnecting cable 2 x 0.14 mmCable bushing Bus adapter M16ATEX Certification EEx ia IIC T6, EEx m II T6
TorquesM16 adapter on the housing 6.0 NmExternal earthing cable (if necessary) 1.8...2.0 Nm
2
Cable brown
Cable white
FOUNDATION Fieldbus-H1
7
All drawings not scaled! All units in millimeter!
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 EN
~83~3.3
7/8
”-1
6U
N∅
27
1.0
6
∅2
4,5
.96
.06
1,5
NFE100-NE plug – 7/8”, forFOUNDATION Fieldbus-H1 Ex and Non-Ex area
Technical dataPoles 4Interlock screw 7/8” UNFType of connection screwCross-sectional area of connection max 1.5 mm
Mechanical life > 500 plug cyclesUpper temperature limit + 85 °C
Rated voltage 250 VRated surge voltage 4000 VContamination class 3Overvoltage category IIIsolation group IIITest voltage 4800 VRated current 9 A (40 °)Volume resistivity 5 MInsulation resistance 10
2
10
Cross-sectional area of connection 16 AW
Lower temperature limit - 40 °C
Contact pin Cu Znl (brass)Contact surface Au (gold)Socket PUR/PA (UL 94 HB)Plug PBT (UL 94 V-0)Thread ring alumi
Electrical data
≤ Ω≥ Ω
GØ 6...8 mm
num eloxaded
Cable diameterHousing protection IP 67
Screw terminals 0.4 NmCoupling ring PG cable gland 4.0 NmKnurled screw hand-tight
Materials
Installation advice Torques
Male1234
wire-colourblueorange
not used
bus(-)(+)shieldn.c.
referenzABS
FOUNDATION Fieldbus-H1
8
All drawings not scaled! All units in millimeter!
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 EN
~78,5~3.1
∅2
71
.06
∅2
4,5
.96
7/8
”-1
6U
N
NFE300-NE socket – 7/8”, for Ex and Non-FOUNDATION Fieldbus-H1 Ex area
Technical dataPoles 4Interlock screw 7/8” UNFType of connection screwCross-sectional area of connection max 1.5 mm
Mechanical life > 500 plug cyclesUpper temperature limit + 85 °C
Rated voltage 250 VRated surge voltage 4000 VContamination class 3Overvoltage category IIIsolation group IIITest voltage 4800 VRated current 9 A (40 °)Volume resistivity 5 MInsulation resistance 10
2
10
Cross-sectional area of connection 16 A
Lower temperature limit - 40 °C
Contact pin Cu Znl (brass)Contact surface Au (gold)Socket PUR/PA (UL 94 HB)Plug PBT (UL 94 V-0)Thread ring aluminu
Electrical data
≤ Ω≥ Ω
WGØ 6...8 mm
m eloxaded
Cable diameterHousing protection IP 67
Screw terminals 0.4 NmCoupling ring PG cable gland 4.0 NmKnurled screw hand-tight
Materials
Installation advice Torques
Male1234
wire-colourblueorange
not used
bus(-)(+)shieldn.c.
referenzABS
FOUNDATION Fieldbus-H1
9
All drawings not scaled! All units in millimeter!
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 EN
Ordering information
FOUNDATION Fieldbus-H1 Junctions (IP 66 case) Catalog No.NFJ120-NE (856426) 3KDE636630L0001
FOUNDATION Fieldbus-H1 T (one-way) junction,IP 66 case, 2 x cable bushing and 1 x socket 7/8",for the Ex (Haz.) and Non-Ex area
NFJ420-NE (856428) 3KDE636630L0002FOUNDATION Fieldbus-H1 four-way junction,IP 66 case, 2 x cable bushing and 4 x socket 7/8",for the Ex (Haz.) and Non-Ex area
NPJ130-NO (856409) 63643-9890102PROFIBUS PA / FOUNDATION Fieldbus-H1 T (one-way) junction,IP 66 case, 3 x cable bushing,incl. switchable bus termination
NPJ460-NO (856411) 63643-9890104PROFIBUS PA / FOUNDATION Fieldbus-H1 four-way junction,IP 66 case, 6 x cable bushing,incl. switchable bus termination
NPJ130-EX (856418) 63643-9890106PROFIBUS PA / FOUNDATION Fieldbus-H1 T (one-way) junction,IP 66 case, 3 x cable bushing,for the Ex (Haz.) area
NPJ460-EX (856420) 63643-9890108PROFIBUS PA / FOUNDATION Fieldbus-H1 four-way junction,IP 66 case, 6 x cable bushing,for the Ex (Haz.) area
NPZ100-EX (860619) 63645-9890120PROFIBUS PA / FOUNDATION Fieldbus-H1 bus terminationfor junction modules NPJ_ _0-EX and NFJ_ _0-NE, IP 66 casefor the Ex (Haz.) area
FOUNDATION Fieldbus-H1 Connectors Catalog No.NFE100-NE (180884) 3KDE636640L0101
FOUNDATION Fieldbus-H1 plug for cable, metal / plastic case, 7/8",for the Ex (Haz.) and Non-Ex area
NFE300-NE (181248) 3KDE636640L0102FOUNDATION Fieldbus-H1 socket for cable, metal / plastic case, 7/8",for the Ex (Haz.) and Non-Ex area
FOUNDATION Fieldbus-H1
10
FOUNDATION Fieldbus Junctions, Connectors, Accessories 10/63-6.60 EN
Ordering information
FOUNDATION Fieldbus-H1 Junctions (IP 20 modules) Catalog No.NGJ100-NE
Fieldbus junctions: Line In module (877005) 3KXN623100L0010for PROFIBUS PA / FOUNDATION Fieldbus-H1to connect the trunk to the Current Limiter module,Trunk line is prevented against over voltage (OVP),Input (Trunk line) max. 17.5 V DC / 380 mAIP 20, EEx me II T6, EEx ia IIC T6, for the Ex (Haz.) and Non-Ex area,Dimensions (L x W x H) 88.4 x 8 x 52 mm
Fieldbus junctions: Current Limiter module (877002) 3KXN623100L0020for PROFIBUS PA / FOUNDATION Fieldbus-H1as (one-way) junction to build up spur linesMax. 20 spurs (Modules) per fieldbus segment (Line In module),Field device disconnected by 60 mA or short circuit cases,Output (Spur line) max. 17.5 V DC / 60 mAIP 20, EEx me II T6, EEx ia IIC T6, for the Ex (Haz.) and Non-Ex area,Dimensions (L x W x H) 88.4 x 8 x 52 mm
Fieldbus junctions: Bus Terminator module (877004) 3KXN623100L0040for PROFIBUS PA / FOUNDATION Fieldbus-H1as lock for each trunk line for NGJ100-NEIP 20, EEx me II T6, EEx ia IIC T6, for the Ex (Haz.) and Non-Ex area,Dimensions (L x W x H) 88.4 x 8 x 52 mm
Fieldbus junctions: Shield module (878144) 3KXN623100L0050for PROFIBUS PA / FOUNDATION Fieldbus-H1as stabilization of fieldbus shieldsIP 20, EEx me II T6, EEx ia IIC T6, for the Ex (Haz.) and Non-Ex area,Dimensions (L x W x H) 88.4 x 8 x 52 mm
Fieldbus junctions: FISCO module (879473) 3KXN623100L0060for PROFIBUS PA / FOUNDATION Fieldbus-H1to meet the FISCO recommendationIP 20, EEx me II T6, EEx ia IIC T6, for the Ex (Haz.) and Non-Ex area,Dimensions (L x W x H) 88.4 x 8 x 52 mm
Accessories (IP 20 modules) Catalog No.NGZ100-NE
Accessories (IP 20 modules), (046110) 3KXN622100L00022 pol jumper to wrap the modules easily.Packing unit 50 pcs.Accessories (IP 20 modules), (046130) 3KXN622100L00044 pol jumper to wrap the modules easily.Packing unit 50 pcs.Accessories (IP 20 modules), (190479) 3KXN622100L000615 pol jumper to wrap the modules easily.Packing unit 10 pcs.
11
10/6
3-6.
60-E
N R
ev. C
01.
2011
Contact us
NoteWe reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB.
Copyright© 2011 ABBAll rights reserved