    1.0 SYSTEM CONDITIONS

    1.1 Nominal Voltage

    1.2 Maximum Voltage

    1.3 Number of Phases

    1.4 Frequency

    1.5 Max. symmetrical Fault level

    1.6 Type of Neutral Earthing

    1.7 Limited Earth Fault Current thro ET

    2.0

    2.1 Altitude above sea Level

    2.2 Max / Min Air Temperatures

    2.3Mean Max Air Temperature

    2.4 Mean Max Exposed Sun-light Temp

    2.5 Solar Radiation - Peak

    2.6 Max. Relative Humidity at >300 C

    2.7 Wind speeds

    2.8 Regional open Air Climate

    2.9 Excessive dust

    2.10 Excessive Salt mist

    2.11 Condensation

    2.12 Vibration Due to heavy Vehicles

    2.13 Service condition class

    2.14 Local Control of Humidity & Temp

    2.15 Environmental Conditions - Category

    3.0 APPLICABLE STANDARDS

    3.1 AC metal enclosed Switchgear

    3.2 HV Switchgear Common specs.

    3.3 HV Circuit Breakers

    3.4 HV AC Disconnector & Earth Switches

    3.5 HV AC Switches

    3.6 For Other applicable standards

    4.0 SWITCHGEAR CHARACTERISTICS

    4.1 Manufacturer Name (vendor to specify)

    4.2 Place of Manufacturing (vendor to specify)

    A. 11kV SWITCHGEAR PANELS Common Parameters for All Types of Panels

    NORMAL & SPECIAL SERVICE CONDITIONS

  • 7/27/2019 Data Schedule1

    2/39

    4.3 Product Model/Type (vendor to specify)

    4.4Switchgear shall be metal enclosed, air-insulated, with vacuum circuit-breaker,

    and withdrawal type

    4.5 Main Device (CB truck) shall be withdraw-able, roll-on floor operated

    4.6 CB truck shall be Horizontal Isolation, Horizontal withdrawal type

    4.7Application of the switchgear shall be suitable for Electricity Secondary

    Distribution Network under specified service conditions

    4.8 Usage Area/Class

    4.9 Type of Bus-bar system

    4.10 Compartments Partition class

    4.11 Loss of Service continuity - Category

    4.12 Rated Voltage (Ur )

    4.13 Number of Phases4.14 Rated frequency (fr )

    4.15 Rated Insulation Level:

    - Rated LI withstand voltage

    - Phase to Earth

    - Across Isolating Distance

    - Rated power frequency withstand voltage

    - Phase to Earth

    - Across the isolating distance

    4.16

    - Incomer

    - Main Bus-bar

    - Feeder

    4.17 Rated short-time with-stand current (Ik)

    - For Group-A Switchgear panels

    - Main Circuit

    - Earth Circuit

    - For Group-B Switchgear panels

    - Main Circuit

    - Earth Circuit

    4.18 Rated duration of short circuit (tk)4.19 Rated peak withstand current (Ip)

    - For Group-A Switchgear panels

    - Main Circuit

    - Earth Circuit

    - For Group-B Switchgear panels

    - Main Circuit

    - Earth Circuit

    Rated Normal Current (Ir ) at +500 C and specified service conditions (Submit cal

  • 7/27/2019 Data Schedule1

    3/39

    4.20Rated supply voltage of closing/opening devices And of auxiliary and control

    circuits (Ua)

    4.21 Rated Voltage & Frequency of spring charge motor

    4.22 Degrees of Protection

    - Enclosure

    - Bus-bar & cable compartments, Internal partitions

    - Circuit-Breaker Compartment

    - Door Closed- Door Opened

    - LV Compartment

    - Shutters & Spouts

    - Pressure relief Flaps

    - VT compartment (where applicable)

    4.23 Partial Discharge test voltage shall be as per

    - Typical partial discharge values observed

    4.24 Busbar & Line Earthing

    - Main Bus-bar Earthing shall be by an separate integral Earth Switch or with

    suitable interlocks using Cable Earth Switch

    - cable/ Line (Circuit) Earthing shall be by integral Earth switch

    5.0

    CIRCUIT BREAKER & ISOLATOR/DISCONNECTOR CHARACTERISTICS ,for F class

    switchgear additional & individual data schedule to be added for

    ISOLATOR/DISCONNECTOR

    Name of manufacturer (vendor to provide)

    Model/Type Designation (Vendor to provide)

    Generic Type

    Isolation type

    Fully solid Insulated/encapsulated

    Applicable standards

    Rated Voltage (Ur)

    No of poles (phases)

    Class

    Rated frequency

    Rated Normal Current at 500 C ambient

    Temperature rise at full-load *

    Rated Lightning withstand voltage

    - Phase to earth

    - Across the isolating distance

    Rated power frequency withstand voltage

    - Phase to earth

    - Across the isolating distance

    Rated short-time withstand current (Ik)- For Group-A panels at 3 sec (tk) duration

    - For Group-B panels at 3 sec (tk) duration

    Rated peak withstand current (Ip)

    - For Group-A Panels

    - For Group-B Panels

    Rated Operating Sequence

    Rated short-circuit breaking current (Isc)

    - For Group-A panels (ac r.m.s Component)

  • 7/27/2019 Data Schedule1

    4/39

    - For Group-B panels (ac r.m.s component)

    Rated short-circuit making current

    - For Group-A panels

    - For Group-B panels

    Rated Cable charging breaking current (Ic)

    Rated Mechanical Endurance class

    Rated Electrical Endurance Class

    Rated supply voltage of closing/opening devices And of auxiliary and controlcircuits (Ua)

    Rated Voltage & Frequency of spring charge motor

    Rated time quantities (offered values to be mentioned by vendor)

    - Opening time

    - Arcing time

    - Break-time

    - Make time

    - Pre-arcing time

    - Closing time

    6.0 ENCLOSURE & COMPARTMENTS OTHER TECHNICAL REQUIREMENTS

    Layout and access- CB Compartment at Floor level & Having Front Access

    - Cable & CT compartment at Floor Level, with rear access

    - Bus-bar compartment is above Cable comp, with side & top access

    - LV Compartment is above CB compartment. with front access

    - VT Compartment, if located on rear-top shall have rear access

    Material of Construction

    - Main Bus-bar - Hard drawn, high conducting Electrolytic Copper

    - Main Bus-bars cross-section size (width x Thickness), in mm

    - Main Bus-bars in all compartments, connecting strips to VT , E/S and CVDs

    shall be fully insulated with heat-shrink sleeves

    - Earth-Bars cross section ( width x Thickness), in mm

    - Enclosure body/Partitions/Shutters shall be metallic

    - Thickness of the Enclosure sheet, in mm

    - All nuts, bolts, washers, hinges shall be made of non-corrosive alloy steel or

    stainless steel

    Other requirements for Switchgear Panels

    - Enclosure/partitions/Shutters to be Individually earthed

    - Inter-panel jointing (assembly work) shall be made easy by using fewer

    number of bolts & nuts of robust design, instead of using too many of smaller

    size bolts & nuts

    - Use of proper spring washers shall be mandatory for any inter-panel

    assembly work, foundation bolts, jointing, fixing of mechanical and electrical

    connections- All bolts & nuts shall be tightened to their respective torques and marked

    with distinct colour (torque marks).

    -The frame of each panel assembly work shall be so rigid that, during

    installation, the aligning of internal components including CB truck movement

    shall not be affected due to uneven floor surface conditions. Assembly work

    shall not be sensitive

    - Removable type circuit labels as described in this specification shall be fixed

    both on front & back of each panel

  • 7/27/2019 Data Schedule1

    5/39

    - Danger symbols shall be permanently marked on both front & back of each

    panel (stickers are not acceptable)

    - Painting work on panels shall not have any scratches/peel-offs/ chippings,

    and quality requirements shall comply with the spec

    - Two name plates, with all details as specified, shall be fixed one on front side

    and other at rear side of each panel.

    - CT name plates details shall be permanently fixed at panel rear wall, in LV

    Cabinet, and on CT itself in every panel

    -All metal work & Live components shall not have any sharp edges

    All un-used holes/openings/orifices/cable entry holes/inter-compartmental

    wiring apertures shall be closed with caps/plugs. (temporary arrangements

    like silicone sealing/foam filling are not acceptable)

    - All entry holes for earth bus-bars shall be fully closed without gaps with

    proper sealing grommets, plates etc. (temporary arrangements like silicone

    sealing/foam filling are not acceptable)

    -Pressure relief flaps for internal arc protection shall be located on top of panel

    For CB compartment

    - Main Door Hinges shall be Robust design & Construction

    - Pad-locking facility for main door, as specified, shall be provided

    - Proper alignment of main contacts of CB shall be ensured

    - Shutters shall be clearly paint marked with BUSBARS and FEEDERS

    respectively with large white letters.

    -Bus-bar shutter shall be RED coloured, and that of Feeder shall be LEMEN

    YELLOW

    -Caution symbols are also to be paint marked on the shutters along with

    legend markings.

    -Shall have integral manual shutter opening device. The device mechanismshall have facility for opening & latching individual shutter in open condition.

    -Insertion of CB truck into the compartment shall override the manual shutter

    operating device and normal shutter operation is restored

    -Individual Shutters shall have pad locking facility when shutters are in closed

    condition

    -For BUS-SECTION panels, provide arrow markings on the shutters as specified

    (indicating direction of bus-section connected)

    -Viewing window, as specified, shall be fixed on front door

    -Permanent phase colour markings shall be made (no stickers)

    -For Bus-bar Compartment-Main Bus-bars shall be fully insulated with heat-shrink sleeves

    -Loose taping on bus-bar joints & connections are not acceptable

    -All bus-bar joints & connections shall be shrouded with insulating boots, as

    specified.

    -There shall not be any scope to enter water droplets (due to condensation)

    into these joints & connections

  • 7/27/2019 Data Schedule1

    6/39

    -

    -Bus-bar end covers design shall be such that there shall be easy access

    without any hindrance for installing or dismantling. But, the screws or bolts

    used for this purpose shall not be accessible from outside.

    -For Cable Compartment

    - -All 11kV cable entry shall be from rear bottom of panels

    -Capable of terminating 3Core XLPE and PILC cables up to 300mm2

    --Cable terminal connections shall be suitable for making heat-shrinkterminations with right-angled or straight insulating boots.

    -

    -Clearance between 11kV connection terminals and bottom plate shall not be

    less than 650mm.

    -Viewing window, as specified, shall be fixed on rear door

    -

    -Proper alignment between cable entry holes at bottom and the cable

    connecting terminals shall be maintained

    -All panels shall be supplied with required number of un-insulated brass

    wiping glands conforming to BS 2562 & Size Y

    -Matching mounting holes (free holes without any welded nuts) at cable entry

    points on bottom plate shall be made to fix the glands

    -Cable entry & gland mounting holes shall be closed with temporarycaps/plugs/blanking plates when panels are supplied

    -Permanent phase identification colour markings (preferably by screen

    printing) shall be provided both inside the cable compartment and outside on

    the rear cover

    7.0 OPERATIONAL REQUIREMENTS

    All normal operations shall be possible only when main door is in closed

    condition

    Ensure correct alignment of all front orifices with respective

    mechanisms/handles

    All orifices meant for operations, shall remain in closed in normal condition,

    with the help of spring-loaded self-closing shutters/covers, and automaticallyget closed when the operating handles are removed from the orifices.

    Rack-in rack-out operations shall be easy to be operated with single hand

    Rack-in/rack-out operation shall be smooth without any bumpy/jerky

    movements

    Mechanical spring charging of CB shall be possible with main door both in open

    & closed conditions

    Mechanical spring charging shall be possible in both CB truck in TEST or

    SERVICE positions

    Mechanical tripping/opening of CB shall be made through the operation of

    mechanical push-buttonMechanical tripping/opening of CB shall be possible in both main door closed

    and open conditions

    Mechanical tripping/opening of CB shall be possible in both CB truck in TEST or

    SERVICE positions

    Mechanical closing of CB shall be possible with CB truck in both TEST and

    SERVICE positions.

  • 7/27/2019 Data Schedule1

    7/39

    Under emergency requirements, mechanical closing of CB shall be possible in

    main door open condition, by disabling the main door interlock

    There shall be pad-locking arrangement for disabling mechanism of main door

    interlock.

    Related instructions for disabling the main door interlock shall be permanently

    printed on front of main door.

    Remote/Local selection for Electrical operation of CB shall be made through

    cam operated selector switch fitted for the purpose on LV compartment door

    Electrical closing & opening operations of CB shall be accomplished through

    cam operated switch fitted for the purpose on the LV compartment door

    Electrical closing operation of CB shall be incorporated with anti-pumping

    feature

    Electrical closing operation of CB shall be incorporated with trip-free feature

    Earth switches shall be operated mechanically from front side of the panel with

    the help of operating handles8.0 MECHANICAL & ELECTRICAL INDICATIONS

    All mechanical status or position indications shall be through positively driven

    mechanisms in both directions of their operations.

    Precise mechanical position indicators shall be available at front of the panel to

    indicate exact positions of CB truck in TEST or SERVICE positions.

    Mechanical status indicators of spring charge mechanism shall be provided on

    the CB truck. CLOSE status shall be indicated with suitable symbol along with

    inscriptions engaged. OPEN status shall be indicated with a blank disengaged

    using standard colour backgrounds

    Mechanical status indicators of CB ON/OFF positions shall be available at front

    of the panels by using standard colours for background and letters. If these are

    provided on the CB truck, shall be clearly visible from front viewing window

    both in TEST & SERVICE positions.

    Mechanical status indicators of Earth Switches ON/OFF positions shall be

    available at front of the panels by using standard colours for background and

    ON/OFF inscription letters.

    Operations counter shall be provided on CB truck and visible from viewing

    window

    Clear and permanent demarcation lines shall be marked inside CB

    compartment to precisely indicate the positions of CB truck in TEST and

    SERVICE positions

    Electrical status indication of CB ON/OFF positions shall be made through

    indicator lamps using standards colours of light

    9.0 PAD-LOCKING PROVISIONS

    CB compartment main door shall have padlocking facility

    LV compartment door shall have padlocking facility

    CB trip/close electrical cam switch shall have padlocking facility

    Remote/Local electrical selector switch shall have padlocking facility

  • 7/27/2019 Data Schedule1

    8/39

    Earth switches operation shall have padlocking facility in both ON/OFF

    positions

    CB trip/open mechanical push-button shall have padlocking facility

    CB mechanical close push-button shall have padlocking facility

    Shutter of CB compartment shall have padlocking facility

    VT shutters/operating handle shall have padlocking facility

    Main door interlock defeating mechanism shall have padlocking facility

    Locking the isolator cum earthing switch in the isolated and earthed position

    10.0

    INTERLOCKS (MECHANICAL & ELECTRICAL) : Manufacturers need to provide all

    required mechanical & electrical interlocks for safe and logical operation of

    the switchgear panels. They may consider including additional interlocks,

    wherever required, over and above the mandatory interlocks mentioned

    below.

    Additional & Individual DATA SHEET to be added for ISOLATOR

    /DISCONNECTOR interlocking with reference to clause 8.3

    WHEN

    CB truck in SERVICE positionCB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in SERVICE position

    CB truck in INTERMEDIATE position

    CB truck in INTERMEDIATE position

    CB truck in INTERMEDIATE position

    CB truck in INTERMEDIATE position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

  • 7/27/2019 Data Schedule1

    9/39

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    CB truck in TEST position

    Manual spring charging is initiated

    Bus-bar Earth Switch is closed

    B ENERGY METERS REQUIREMENTS

    General- Conforming to latest IEC standards unless other-wise specified

    - Generic type: Static/Digital with 5-Yrs warranty

    - Shall be fitted only in Type-5/Type-6/Type-7 switchgear panels

    - Suitable for Indoor application under specified special service conditions

    - Maters shall be matched and rated to operate to required degree of accuracy

    in conjunction with the related VT and CTs

    - Flush mounted in LV compartment in concerned switchgear panels

    - Meter cases (enclosures) shall be fully insulated

    - Suitable for 3-ph un-balanced loads

    - Meters shall have roller-counter type numbers/digits for display of reading

    - The numbers/digits shall be 6mm high

    - Meters shall have direct reading facility without need for multiplying factor

    - Meters shall have facility to accept wire-seals on removable covers

    - Each meter shall be supplied fitted with panels (loose supply not acceptable)

    - Each Meter supplied along with its own calibration certificate

    E E) PROTECTION RELATED DATA SCHEDULE FOR

    TYPE-1 PANELS

    TRANSFORMER CBS WITH OVER-CURRENT AND EARTH FAULT PROTECTION

    SPECIFICATION (FOR 11/0.433KV TRANSFORMERS UP TO 1600KVA)

    Current Transformers for O/C & E/F protection

    -CT Ratio

    -Number of CTs

    -Class

    -Burden

    -Short Circuit current for 3 sec (based on Group-A/B/C of Panel)

  • 7/27/2019 Data Schedule1

    10/39

    -Name of Manufacturer

    -Manufacturer type/model designation

    -Reference of Type test reports submitted (as per IEC standards)

    Current Transformers for Instruments

    -CT ratio

    -Number of CTs

    -Class

    -Burden-Short Circuit current for 3 sec (based on Group-A/B of panel)

    -Name of Manufacturer

    -Manufacturer type/model designation

    -Reference of Type test reports submitted (as per IEC standards)

    Protection Relays (EDMIT) for O/C & E/F protection (51/51N & 50/50N)

    Type: Over-current and Earth-Fault protection instantaneous and time

    delayed Relay Characteristics

    4-pole extremely inverse definite minimum time (EIDMT) over- current &

    earth fault protection relay with high set instantaneous over current and

    earth fault elements (51/51N & 50/50N). Including other IEC inverse

    curves.Relay Generic type/design/settings

    -Numeric with 5-Yrs warranty

    -Name of Manufacturer & Country of Origin

    -Manufacturer type/model designation

    -Range of Over-current EIDMT setting

    -High-set instantaneous over-current setting range

    -Range of earth-fault EIDMT setting

    -Range of high set instantaneous Earth-Fault setting

    -Type of Indication shall be LED indication

    -Rated tripping & relay supply voltage

    -Suitable test block fitted for routine check

    SOTF (Switch on to fault) Facility

    Shall be wired through CB closing and Local/Remote switches

    High set element of O/C & E/F shall enable tripping of the CB with minimum

    time duration, if any fault occurs/prevails during closing operation of CB

    SOFT relay setting will be done locally by KM staff

    Trip circuit supervision shall be wired and enabled through the protection

    relay for trip circuit supervision, CB open/close condition

    Ammeters

    Generic Type Moving Iron type, Flush mounted

    Bezel sizeAccuracy class

    No of Ammeters to be fitted (one for each phase)

    Scale/Range: 0-100A, suitable for CT mentioned above

    Suitable CT ratio

    Name of Manufacturer & Country of Origin

    Inter trip Facility

  • 7/27/2019 Data Schedule1

    11/39

  • 7/27/2019 Data Schedule1

    12/39

    Relay type : Electromagnetic/static/numeric with 5 yrs warranty

    Name of Manufacturer

    Manufacturer type/model designation

    Current rating

    Rated insulation

    Relay shall work with 2 pilot cores

    Rated DC voltage

    Current check-guard relay to be provided (for numeric relays)-Name of Manufacturer

    -Manufacturer type/model Designation

    -Generic type of relay (numeric etc)

    - Over-current (O/C) setting range

    - Earth-Fault (E/F) setting range

    Pilot wire Supervision Relay to be provided

    Name of Manufacturer

    Manufacturer type/model Designation

    Generic type of relay (numeric/static etc)

    - Suitable pilot wire supervision scheme to be provided

    - Panels with No. of sending & receiving end supervision relays

    IDMT over-current & Earth-Fault Protection (51/51N)

    Relay type : 4pole numeric with 5 yrs warranty with all the IEC inverse cu

    Name of Manufacturer

    Manufacturer type/model designation

    Current rating

    Voltage rating

    3 x Over-current elements with settings range

    1 x Earth-fault element with setting range

    Suitable Test terminal facility for relay testing shall be provided

    Type of trip Indication (LED)

    OC & E/F fault protection trip shall have independent indications

    SOTF (Switch on to fault) Facility

    Shall be wired through CB closing and Local/Remote switches

    High set element of O/C & E/F shall enable tripping of the CB with

    minimum time duration, if any fault occurs/prevails during closing

    operation of CB

    SOFT relay setting will be done locally by KM staff

    Trip circuit supervision shall be wired and enabled through the

    protection relay for trip circuit supervision

    Ammeter

    Generic Type Moving Iron type, Flush mounted

    No of Ammeters to be fitted (one for each phase)Scale/Range: 0-400A and suitable for CT mentioned above

    Bezel size

    Accuracy class

    Suitable for CT ratio

    Name of Manufacturer & Country of Origin

    Tripping Supply

    Tripping supply wires shall be wired from adjacent panels either from left or

    right side

  • 7/27/2019 Data Schedule1

    13/39

    Size of 30VDC supply wires for tripping shall be 4C X 4mm2 Stranded

    CU/PVC/SWA/PVC as per BS 6346

    Size of inter-trip wires shall be 4C x 2.5mm2 CU/PVC/SWA/PVC as per BS 6346

    Pilot Cable termination

    Connecting terminals in the pilot wire marshalling (control) box shall be

    suitable for connecting 4C x 4mm2 CU/XLPE/SWA/PVC cable

    5 numbers of M25 cable glands(brass) are to be provided at bottom of Pilot

    Cable marshalling box for terminating

    G) PROTECTION RELATED DATA SCHEDULE FOR

    TYPE-3 PANELS

    BUS-SECTION (BUS COUPLER + BUS-RISER) CB PANELS WITH OVER-CURRENT &

    Current Transformers for O/C & E/F protection

    CT Ratio

    Number of CTs

    Class

    burden

    Short circuit current for 3 sec (based on Group-A/B of Panel)

    Name of Manufacturer & Country of OriginManufacturer type/model designation

    Reference of Type test reports submitted (as per IEC standards)

    Current Transformers for Instruments

    CT ratio

    Number of CTs

    Class

    Burden

    Short circuit current for 3 sec (base on Group-A/B/C of Panel)

    Name of Manufacturer & Country of Origin

    Manufacturer type/model designation

    Reference of Type test reports submitted (as per IEC standards)

    IDMT over-current & Earth-Fault Protection (51/51N)

    Relay type : 4 pole numeric with 5 yrs warranty

    Name of Manufacturer & Country of Origin

    Manufacturer type/model designation

    Current rating

    Voltage rating

    3 x Over-current & 1 Earth-Fault IDMT and Definite characteristic

    Relay characteristics: All IEC inverse curves

    This relay shall be suitable for tripping directly and shall be wired fully

    If relay is numeric type, it shall be wired for 3 Pole O/C + E/F relay

    Suitable Test Terminal Block for relay testing shall be provided

    Type of trip Indication ( LED)OC & E/F fault protection trip shall have independent indications

    SOTF (Switch on to fault) Facility

    Shall be wired through CB closing and Local/Remote switches

    High set element of O/C & E/F shall enable tripping of the CB with minimum

    time duration, if any fault occurs/prevails during closing operation of CB

    SOFT relay setting will be done locally by KM staff

  • 7/27/2019 Data Schedule1

    14/39

    Trip circuit supervision shall be wired and enabled through the protection relay

    for trip circuit supervision

    Ammeter

    Generic Type Moving Iron type, Flush mounted

    No of Ammeters to be fitted (one for each phase)

    Scale/Range: (suitable for CT mentioned above)

    Bezel Size

    Accuracy ClassSuitable for CT ratio

    Name of Manufacturer & Country of Origin

    Tripping Supply

    Supply voltage

    Tripping supply wires wired from adjacent panels either from left or right side

    Size of 30VDC supply wires for tripping shall be 4C X 4mm2 Stranded

    CU/PVC/SWA/PVC as per BS 6346

    H) PROTECTION RELATED DATA SCHEDULE FOR

    TYPE-4 PANELS

    FEEDER CB PANELS WITH PILOT WIRE PROTECTION AND DIRECTIONAL OVER

    CURRENT (DOC) & DIRECTIONAL EARTH FAULT (DEF) PROTECTION

    Current Transformers for Pilot wire protection

    CT Ratio

    Number of CTs

    Class

    burden

    Short Circuit current for 3 sec (based on Group-A/B of panel)

    Name of Manufacturer & Country of Origin (supplier to specify)

    Manufacturer type/model designation (supplier to specify)

    Knee Point Voltage (supplier to provide data & specify the formula)

    [Supplier to Note: The Knee point voltage should be established by

    calculation for 25/31.5 kA faults current using the formula provided by

    the pilot wire protection relay manufacturer and with data of loop

    resistance]

    CT resistance for 300/5 ratio (in ohms)

    CT resistance for 400/5 ratio (in ohms)

    Excitation current at Knee Point Voltage

    Reference of Type test reports submitted

    Current Transformers for DO/C & DE/F protection

    CT Ratio

    Number of CTs

    Classburden

    Short Circuit current for 3 sec (based on Group-A/B of panel)

    Name of Manufacturer & Country of Origin

    Manufacturer type/model designation

    Reference of Type test reports submitted

    Current Transformers for Instruments

    CT ratio

    Number of CTs

  • 7/27/2019 Data Schedule1

    15/39

    Class

    Burden

    Short Circuit current for 3 sec (based on Group-A/B of panel)

    Name of Manufacturer & Country of Origin

    Manufacturer type/model designation

    Reference of Type test reports submitted

    Pilot Wire Protection (PWP) - (87P)

    Details same as those mentioned underType-2 panelDirectional O/C & Directional E/F Protection (67/67N)

    Relay type : 4 pole numeric with 5 yrs warranty

    Name of Manufacturer

    Manufacturer type/model designation

    Current rating

    Voltage rating

    If relay is numeric type it shall be wired for 3 pole O/C + E/F

    3 Single pole Directional O/C IDMTL relays, 450 current leading, 5A,

    voltage polarizing 110Vac 50Hz in phases R & B / 3 phase

    Over current setting range

    One single pole Directional E/F IDMTL relay, range 10-40%, 12.50

    or150 current lagging (multiple angle selection relay)

    Earth-Fault Setting Range

    Suitable Test terminal facility for relay testing shall be provided

    Type of trip Indication (Mechanical flag/LED)

    OC & E/F fault protection trip shall have independent indications

    SOTF (Switch on to fault) Facility

    Shall be wired through CB closing and Local/Remote switches

    High set element of O/C & E/F shall enable tripping of the CB with minimum

    time duration, if any fault occurs/prevails during closing operation of CB

  • 7/27/2019 Data Schedule1

    16/39

  • 7/27/2019 Data Schedule1

    17/39

  • 7/27/2019 Data Schedule1

    18/39

  • 7/27/2019 Data Schedule1

    19/39

  • 7/27/2019 Data Schedule1

    20/39

    kV 1

    kV 12

    No 3

    Hz 50

    kA 25/31.5

    By Earthing Transformer (ET) at Primary Sub-

    station

    kA 4.5

    Less than 100

    50 / 5

    45

    75

    1030

    100

    More than 15

    Hot sub-tropical

    Present

    Present

    Frequent Occurance

    Possible

    Indoor

    None

    3K6/3Z11/3Z4/3B2/3C2/3S3/3M2

    IEC 62271-200

    IEC 62271-1

    IEC 62271-100

    IEC 62271-102

    IEC 62271-103

    Refer main document

    OfferedUNIT

    DATA VALUES

    Required

  • 7/27/2019 Data Schedule1

    21/39

    Yes

    Yes

    Yes

    Yes

    Indoor

    Single

    PM

    LSC2B

    kV 12

    No 3Hz 50

    kV 75

    kV 85

    kV 28

    kV 32

    A 400

    A 800

    A 400

    kA 25

    kA 25

    kA 31.5

    kA 31.5

    sec 3

    kA 62.5

    kA 62.5

    kA 80

    kA 80

    lculation sheet if offered ratings are based on 400 C)

  • 7/27/2019 Data Schedule1

    22/39

    V, DC 30

    V, AC 240V ac, 50Hz

    IP 41

    IP 3X

    IP 41IP XX

    IP 41

    IP 3X

    IP 41

    IP 41

    IEC 60270

    pC

    Yes

    Yes

    Vacuum, (FMW C F )

    Horizontal withdrawal &roll- on-floor type

    Yes

    IEC 62271-100, 62271-1

    kV 12

    No 3

    Indoor

    Hz 50

    A 400

    K

    kV 75

    kV 85

    kV 28

    kV 32

    kV 25

    kV 31.5

    kA 62.5

    kA 80

    O 0.3sec CO - 3min - CO

    kA

    kA 25

  • 7/27/2019 Data Schedule1

    23/39

    kA 31.5

    kA 62.5

    kA 80

    A 25

    Class M2 (10,000)

    Class E2

    V, DC 30

    V, AC 240Vac, 50Hz

    ms

    ms

    ms

    ms

    ms

    ms

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Sheet Steel

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

  • 7/27/2019 Data Schedule1

    24/39

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    YesYes

    Yes

    Yes

    Yes

  • 7/27/2019 Data Schedule1

    25/39

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

  • 7/27/2019 Data Schedule1

    26/39

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

  • 7/27/2019 Data Schedule1

    27/39

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    AND Interlock to be satisfied

    CB is closed Cable E/S cannot be closedCB is closed Bus-bar E/S cannot be closed

    CB is closed CB truck cannot be racked-out

    CB is closed Cannot open the main door

    CB is closed Cannot remove LV control Plug

    CB is opened CB truck can be racked-out

    CB is opened Cannot open the main door normally

    CB is opened Cannot remove LV control plug

    CB is opened Cable E/S cannot be closed

    CB is opened Bus-bar E/S cannot be closed

    Main contacts fully not

    closedCB cannot be closed

    CB is closedPrevent un-desirable operation of any

    mechanical selectors/interlocks

    - Cannot remove LV control plug

    - Cannot open the main door

    - CB cannot be closed

    -Cannot charge the Spring mechanically or

    Electrically

    CB is closed CB truck cannot be racked-in

    CB is closed Main door can be opened

    CB is opened Main door can be opened

    CB is opened and LV

    plug connected CB truck can be racked-in

    CB is opened, but LV

    plug disconnectedCB truck cannot be racked-in

    CB is opened LV plug can be removed

    CB is closed LV plug can be removed

    CB is opened, and

    Feeder Cable is dead

    Cable E/S can be closed

  • 7/27/2019 Data Schedule1

    28/39

    CB is closed, and

    Feeder cable is dead

    Cable E/S can be closed

    CB is opened, and

    Feeder Cable is liveCable E/S cannot be closed

    CB is opened, but LV

    plug connectedCB truck cannot be racked-out

    CB is opened, but LV

    plug disconnected

    CB truck can be racked-out

    LV plug is connected CB can be closed

    LV plug disconnected CB can be closed mechanically

    Cable E/S is Closed CB truck cannot be racked-in

    - Spring charge motor cannot be operated

    -

    CB trucks cannot be racked into SERVICE

    position (in the section)

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    100/5A

    3

    5P10

    15 VA

    25/31.5 kA

  • 7/27/2019 Data Schedule1

    29/39

    100/5A

    3 No

    1.0

    15VA25/31.5kA

    Yes

    Yes

    30VDC

    Yes

    Yes

    Yes

    Yes

    Yes

    72 x 721

    3 Nos

    100/5A

  • 7/27/2019 Data Schedule1

    30/39

  • 7/27/2019 Data Schedule1

    31/39

    5A

    5kV

    Yes

    30VDC

    Yes

    Yes

    Yes

    (50% +50%)

    rves

    5A

    30VDC

    50-200%

    20-80%

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    3 NosYes

    72x72mm

    1

    400/5A

  • 7/27/2019 Data Schedule1

    32/39

    Yes

    Yes

    ARTH FAULT IDMT PROTECTION

    400/5A

    3

    5P10

    15 VA

    25/31.5 kA

    400/5A

    3 No

    1

    15 VA

    25/31.5 kA

    5A

    30VDC

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

  • 7/27/2019 Data Schedule1

    33/39

    Yes

    Yes

    3 Nos

    0-400A

    72x72mm

    1400/5A

    30VDC

    400/300/5A

    3

    X

    15 VA

    25/31.5 kA

    -

    -

    Yes

    -

    -

    400/5A

    3

    5P1015 VA

    25/31.5 kA

    400/5A

    3

  • 7/27/2019 Data Schedule1

    34/39

    5P10

    15 VA

    25/31.5 kA

    5A

    30VDC

    Yes

    Yes

    50-200%

    Yes10-80%

    Yes

    Yes

    Yes

    Yes

    Yes