DATA CENTER Challenge

Data Centers have evolved as a secure storage place for the rapidly expanding volume of information a company

needs to function.

The dramatic growth of “IT Dependency” in all businesses has increased significantly demand for Data Centers all

over the world.

Guidelines to design, build and operate a Data Center are provided by different standarts' for different products and

services. Some commonly Data Center standarts are formed by organisations such as ASHREA, CENELEC, ISO/IEC, TIA,

BICSI, UPTIME, IEEE, NEB.

6

Today’s real challanges in a Data Center can be summarised as :

• Energy Efficiency for Power&Cooling (PUE-DCIE)

• High Density Servers ; Storage Servers

• Co-location

• Refurbishment

www.hescs.com

Page 3: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

POWER

As the main continous need to run all systems, power is the major element for all Data Centers. Data center designers should

consider carefully in order to build efficient and effective Data Center power infrastructure.

Definitions of PUE (Power Usage Effectiveness) and DCIE (Data Center Infrastructure Efficiency):

PUE = Total Facility Power / IT Equipment Power

DCiE = IT Equipment Power / Total Facility Power

PUE DCiE Efficiency Level

3.0 %33 Un-efficient

2.5 %40 Low efficient

2.0 %50 Average

1.5 %67 Efficient

1.2 %83 Well Efficient

Electrical Power IN

IT Equipment Power

CRACs

Chillers

UPS

Generator

PDU & Switch gear

Lighting

PU

E

7www.hescs.com

Page 4: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

8

ENVIROMENTAL MONITORING & MANAGEMENT

Proper Data Center cooling is the key factor for operational life of hardware, shortening downtime of Data Center, saving on

operational costs and accessing to green IT.

Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters

which ensures your uptime and efficiency.

www.hescs.com

COOLING

Page 5: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

RACKS & CABLING

The physical infrastructure of Data Centers are generated from racks and cabling.

High-density, future-proof structured cabling systems are first choice for Data Center cabling projects.

Racks provide efficient housing solutions for valuable active and also passive equipments. The correct rack deployment

strategy leads to efficient cooling and capacity management; helping significant savings on operation costs.

9www.hescs.com

Page 6: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS DATA CENTER SOLUTIONS - RACKS & CONTAINMENTS

Data Centers are very dynamic environments demanding high density, scaleable and flexible solutions to cope up with the

rising IT applications: cabinets take an important part on answering those needs. Although cabinets are not the most expen-

sive portion of the Data Center investment, their housing function for the valuable active and passive equipment and contribu-

tion to efficient cooling, make cabinets one of the key section for each Data Center.

Based on this awareness, HCS presents future-proof and feature-rich Data Center cabinet solutions, HCS Data Center Cabinet

product portfolio is covering large variety of server cabinets and accessories, hot&cold corridor cabinet containment, overhead

cabling management and open frames.

10 www.hescs.com

Page 7: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Cold Corridor Containment serves for energy savings in Data Center cooling. The sliding doors are self-closing with mechani-

cal lock. If required, doors can be electrically closed and integrated to the building management system.

Ergonomically designed and aesthetic looking HCS

DataLine 16 Data Center cabinets are designed in order to

meet varios needs of secure housing for existing and new

generation servers and other active equipments. Thanks to

its solid and stable construction, many heavy equipments

can easily be deployed. Adjustable mounting vertical

flanges allow installing additional data and power cables

and equipment, even by pre-installed hardware.

Cabinet top cable management accessories and

top&bottom cable entries provide neat & clean cable

management.

11www.hescs.com

Page 8: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

• ANSI/TIA-568-C (all parts) • CENELEC EN 50173 & EN 50228 (all sections) • ISO/IEC 11801 & IEC 61156 (all sections)

HCS CAT 6 angled patch panels

HCS DATA CENTER SOLUTIONS - STRUCTURED CABLING

Cabling as the physical layer is the transmission media of the data

which shall be choosen according to the network application

requirements to be implemented today and shall be future-proof

for the Data Centers.

Cabling design and installation should answer high MAC (Moves,

adds and changes) needs of the Data Center. Monitoring and

managing the physical layer and the network status shall ensure

better uptime.

HCS cabling solution is applicable on Data Centers including a mix

of copper and fibre components having high density, high reliabil-

ity and high performance, enabling flexible design guide-lines,

speed of installation, future readiness and ease of use.

HCS Data-Center Solutions include the following:

12

HCS solution includes all the components needed (i.e cables,

patch-panels, CP and CC patching, outlets and patch cords) tested

and verified at the component-level based on the most recognised

standarts and drafts such as ;

www.hescs.com

HCS CAT 6A CablesHCS DataLink 100e Category 5e components specified up to 100MHz• 24-Port & 48-Port Telco (RJ-21) and iPass Panels.• 24-Pair RJ-45 to RJ-21, RJ-45 to RJ-21 Cords.

HCS DataLink 250 Category 6 components specified up to 250MHz• UTP and shielded horizontal cables.• Shielded and unshielded modular cords, CC and CP pre-terminated cords.• Shielded and unshielded connectors. • Unshielded module patch panels of 24 Port-1U & 48 Port-2U.• Blank KSJ Panels up to 48 ports in 1U.• Wall Mount & Rack Mount 110 Wiring Blocks.

HCS DataLink 500A Augmented Category 6 components specified up to 500MHz• UTP and shielded horizontal cables.• Shielded and unshielded modular cords, CC and CP pre-terminated cords.• Shielded and unshielded connectors.• Blank & staggered KSJ Panels up to 48 ports in 1U.

Page 9: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS DataLink 600Category 7/Class F components specified up to 600 MHz

• Shielded horizontal cable

• Special HCS Cat7 Connector for Class F links/channels

• Shielded modular cords, CC and CP pre-terminated cords.

• Blank shielded Panels up to 24 ports in 1U

• True Class F performance on component base

HCS DataLink 1200 Category 7A / Class Fa components specified up to 1000 MHz

• Shielded 22AWG horizontal cable

• Special HCS Cat7 Connector for Class Fa links/channels

• Shielded & unshielded modular cords, CC and CP preterminated cords.

• Blank shielded Panels up to 24 ports in 1U.

• Expected to supports 40 GBASE-T on 100 meter distance

• True CAT7A / Class Fa performance

BreakoutCables

MTDCables

Ribbon Ruggedized (Trunk)

Cables

HCS DataLight Data-Center FO Cables

MPO Connectors, Adapters & AssembliesHCS DataLight patch panels & Rack Mount Cabinets

13

HCS Datalink Fiber-Optic components• Single mode standart fibers (most ITU standards), including bend-insensitive types.• Multi mode fibers including OM1, OM2, OM3 and OM4; bend-insensitive for OM2,OM3 and OM4.• MTD, Ribbon & Ruggedized Ribbon Trunk cables.• Modular pre-terminated cables.• MPO Panels, Connectors & Adapters.• MPO Hybrid Fan-out modular cords (4 to 24 Fibers).• Modular optical cords and pigtails.• Fiberoptic 19" panels.• Fiberoptic wall-mount patch panels and distribution boxes.• Fiberoptic high-Capacity Fiber-Optic Rack-Mount Cabinets up to 288 ports.

HCS CAT 7 Connector

HCS CAT 7 S/FTP 23AWG cable

HCS CAT 7 patch cord

HCS CAT 7 patch panel

www.hescs.com

Page 10: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Phy-Fixx Real Time Physical Layer Monitoring and Management System

HCS physical layer monitoring and management ensures your Data Center cabling infrastructure reliability and gives you high flexibility in your MACs with a compatibility to other network management tools.

Rack Cabling Management

• Cable and Outlet Management• Remote Site Management including network attached devices and reporting• MACs and Work Order Management• Compatibility with other network management tools

HCS DATA CENTER SOLUTIONS - STRUCTURED CABLING

14 www.hescs.com

Page 11: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Cable tray and mesh cable tray systems run power and data cables

either in ceilings or in raised floors. The variety of our solutions

guarantee the right solution for any conceivable application.

Cable routing for power and copper cables

The modular system ensures a flexible,secure connection of

sensitive fibre optic cables to the computer infrastructure. With

various routing duct variants, fittings, end pieces, reductions and

exits, you can match the system exactly to local requirements. The

cable routing duct requires non metallic components and is

completely halogen-free (PPO, ROHS-compliant, UL2024A standard

certified).

Cable routing for fibre optic cables

Cable routing duct for fibre optic cables, mesh cable trays or cable trays have common requirement: Universally applicable

mounting systems. They ensure secure fixing beneath the ceiling, on the wall or in the floor, and are available in many differ-

ent varieties.

Mounting systems

In case of fire, extinguishing process is the most important issue

which also prevents spread of the fire. Cables, which are running

alongside the building can cause fire spreading out the whole

facility. HCS fire protection systems work as a barrier to the fire via

cable penetrations preventing the spread of fire and smoke into

the next rooms.

Fire protection

15www.hescs.com

Page 12: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Data Center Environmental Monitoring and Management is the key to ensure maximum uptime. All the critical parameters

either rack-based or room based such as temperature, humidity, water flooding, pressure control, smoke, door access,

movement, light intensity, IP camera recording, electrical parameters and also 3rd party hardware parameters such as cooling

systems, ups systems and other required parameters shall be real time and centrally monitored, recorded and archieved.

In case the measured values exceed pre-defined levels, alarming procedures shall take place and required actions shall be taken

on time either by the system itself or by the responsible managers to avoid any downtime in the operation of the datacenter.

All these operations are applicable for any number of Data Centers even spread globally, on a centralised software solution.

HCS DATA CENTER SOLUTIONS - ENVIRONMENTAL MONITORING & MANAGEMENT

16 www.hescs.com

Page 13: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Power consumption cost is extremely important for Data Center operation - this is pushing Data Center designers and manag-

ers to focus this area specifically.

The main reason of the poor power efficiency in the most of the existing Data Centers arise from the old power components

such as UPS, PDU and server power supplies rather than the incoming power distribution (transformer-switchgears etc.).

HCS offers metered-monitored and managed&switched Power Distribution Units to monitor and manage your real-time power

consumption and to review and plan your power budgets.

HCS DATA CENTER SOLUTIONS - POWER DISTRIBUTION UNITS

17www.hescs.com

Page 14: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS 17' LCD KVM Console drawer provides easy access to your servers in your Data Centers with a superior video quality

enabling an optional remote console over-IP and multi-platform support, based on a robust metal case.

Equipped with C13 and/or C19 outlets and 32A IEC 60309 plug, and circuit breakers, the professional HCS PDUs enable you

to measure and display current,voltage, power and power consumption, temperature and humidity in real time. Web Access,

SNMP Telnet/SSH, e-mail alarming are other important features that HCS PDUs provide in order to monitor and manage your

Data Center power.

HCS DATA CENTER SOLUTIONS - LCD CONSOLES

IEC 60309IEC 60320 C19IEC 60320 C13

18 www.hescs.com

Page 15: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

SECTION A: Free Standing Data Center Cabinets

Data Center Server Cabinets 20-23

Data Center Network Cabinets 24-27

Data Center Cabling Open Frames 28-29

“State of the art Data Center Solutions”

Page 16: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

DATALINE 16 DATA CENTER SERVER CABINETS

Qualifications and Approvals

HCS DataLine 16 Server Cabinets are supported by HCS DoubleSafe™ QA Program and they comply to the following standards:

Applications

The special design of HCS DataLine 16 Data Center Server Cabinets allow the use of a large variety and types of accessories, including 19" panels, hubs and active equipment, fixed and/or sliding shelves, fan units, power strips, pulleys, grounding and potential equalization bus bars, lighting units, stacking kits, floor fixing kits, cable management panels, and many other 19” devices and accessories.

Description

HCS DataLine 16 Data Center Server Cabinets are specially designed for new generation Data Centers, in order to provide best possible housing for your valuable equipments.

HCS DataLine 16 Server Cabinets are having an attractive design combined with a long-lasting, solid & stable construction, guaranteed by the HCS DataLine Logo & Trademark.

DIN EN 10130-91DIN EN 10327EREGLI 6112

TS EN 60297-3-100/101/102DIN 41494TS EN 60529-1IP20 (Optional IP 42)

General Steel Sheets Powder Coating

DIN 67530ASTM D 2796ASTM D 3451

TS EN 61587-1

Mechanical Assembly

TS EN 60917-2-1/-2

IT equipment safety

TS EN 60950-1IEC 60364-7-707

Fan Unit & Power Strips

TS EN 60439-1TS EN 62208

20 www.hescs.com

Page 17: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Benefits & Features

π Solid and stable construction - providing support for large loads upto 1500 kg

π Light cabinet weight - allowing more equipment housing

π Adjustable profile positioning inside the cabinets (while there are servers and other active equipments)-

enabling efficient installation of different size devices and maximise uptime

π Aesthetic & attractive design - can be used in open office environments.

π Flat packed design option- providing minimal storage space and saving transportation costs.

π 1100 & 1200 mm depth - enabling easy and comfortable installation of new generation deep servers (blade servers).

π Sophisticated cable channeling - enabling concealed cords routing.

π Clear u-marking inside the cabinets (both front and rear 19” profile) - enabling easy & simple equipment installation planning.

π Removable side panels via handles - enabling fast & easy cabinet stacking.

π Removable side, front and rear doors- allows using cabinet event as relay rack, if needed.

π Various cable entry holes - providing comfortable multiple cable entry.

π Toolless adjustable top cable organizers - enabling neat cabling for power & data.

π Stackable construction - allows to proper installation many cabinets side to side

π PVC stoppers - avoid metal surface noise while side panels are mounted

π Top & bottom fixing points - Providing fixing to floor and/or overhead cable tray

21www.hescs.com

Page 18: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

DATALINE 16 DATA CENTER SERVER CABINETS

General Properties

Material of Construction Sheet & Galvanized steel. 1.0/1.2/1.5/2.0 mm thickness. Paint and Color Special steel finish with electrostatic powder coat, RAL 9005 black. Other colors available upon request.Front Door Solid metal, Oval shaped, nominal 85% perforated, one part. Opening left & right. 180 degree opening (135 degree when used in a row). Interchangable door hinges.Side Panels 2 parts, Removable with handles & lockable with slim latch.Rear Door Solid metal, flat, nominal 85% perforated, two parts. Opening left & right. 180 degree opening (135 degree when used in a row). Interchangable door hinges.Top Chasis & Cover Monoblock, welded, CDFx form construction. Fan tray mountable. 2x(150x85 mm) + 2x (150x150 mm) cable entry spaces, all brush mountable. Fixing possiblity to ceiling (with fixing accessory).Bottom Chasis Monoblock, welded, CDFx form construction. Fixing points either fixing to floor or raised floor. 150x300 mm cable entry hole (brush mountable) + 400x 680 mm ventilation hole (filter mountable). 19" profiles Adjustable, 4 units (2 front, 2 rear). U-marked.Vertical Cable Organizer Mountable on sides & rear vertically (optional).Front Door Lock High quality, three-point lockable cylindrical mechanism with handle.Levelling feet & Pulleys Available (optional).Loading Capacity 1500 kg max. (42U, TS EN 61587-1).

22 www.hescs.com

Page 19: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

23

HCS P/N Internal Heightmm

NotesDimensions

Widthmm

Depthmm

Heightmm

Net WeightKg

Description

Ordering Information

www.hescs.com

C16-04261 42U19" (600x1100) mm DataLine™16 1880 600 1100 2028 117 Data Center Server CabinetC16-04761 47U19" (600x1100) mm DataLine™16 2102 600 1100 2250 132 Data Center Server CabinetC16-04262 42U19" (600x1200) mm DataLine™16 1880 600 1200 2028 134 Data Center Server CabinetC16-04762 47U19" (600x1200) mm DataLine™16 2102 600 1200 2250 155 Data Center Server Cabinet

Page 20: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

DATALINE 16 DATA CENTER NETWORK CABINETS

24

Qualifications and Approvals

HCS DataLine 16 Network Cabinets are supported by HCS DoubleSafe™ QA Program and they comply to the following standards:

Applications

The special design of HCS DataLine 16 Data Center Network Cabinets allow the use of a large variety and types of accessories, including 19" panels, hubs and active equipment, fixed and/or sliding shelves, fan units, power strips, pulleys, grounding and potential equalization bus bars, lighting units, stacking kits, floor fixing kits, cable management panels, and many other 19” devices and accessories.

Description

HCS DataLine 16 Data Center Network Cabinets are specially designed for new generation Data Centers, in order to provide high density backbone cabling and networking for your valuable equipments.

HCS DataLine 16 Server Cabinets are having an attractive design combined with a long-lasting, solid & stable construction, guaranteed by the HCS DataLine Logo & Trademark.

DIN EN 10130-91 DIN EN 10327 EREGLI 6112

TS EN 60297-3-100/101/102 DIN 41494 TS EN 60529-1 IP20 (Optional IP 42)

DIN 67530 ASTM D 2796 ASTM D 3451

TS EN 61587-1 TS EN 60917-2-1/-2 TS EN 60950-1 IEC 60364-7-707

TS EN 60439-1 TS EN 62208

www.hescs.com

General Steel Sheets Powder Coating Mechanical Assembly IT equipment safety

Fan Unit & Power Strips

Page 21: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

π Solid and stable construction - providing support for large loads upto 1500 kg

π Light cabinet weight - allowing more equipment housing

π Adjustable profile positioning inside the cabinets (while there are servers and other active equipments)

enabling efficient installation of different size devices and maximise uptime.

π Aesthetic & attractive design - can be used in open office environments.

π Flat packed design option- providing minimal storage space and saving transportation costs.

π 1100 & 1200 mm depth - enabling easy and comfortable installation of new generation deep servers (blade servers).

π Sophisticated cable channeling - enabling concealed cords routing.

π Clear u-marking inside the cabinets (both front and rear 19” profile) - enabling easy & simple equipment installation planning.

π Removable side panels via handles - enabling fast & easy cabinet stacking.

π Removable side, front and rear doors- allows using cabinet event as relay rack, if needed.

π Various cable entry holes - providing comfortable multiple cable entry.

π Toolless adjustable top cable organizers - enabling neat cabling for power & data.

π Stackable construction - allows to proper installation many cabinets side to side

π PVC stoppers - avoid metal surface noice while side panels are mounted

π Top & bottom fixing points - Providing fixing to floor and/or overhead cable tray.

Benefits & Features

25www.hescs.com

Page 22: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

DATALINE 16 DATA CENTER NETWORK CABINETS

General Properties

Material of Construction Sheet & Galvanized steel. 1.0/1.2/1.5/2.0 mm thickness. Paint and Color Special steel finish with electrostatic powder coat, RAL 9005 black. Other colors available upon request.Front Door Solid metal, Oval shaped, nominal 85% perforated, one part. Opening left & right. 180 degree opening (135 degree when used in a row). Interchangable door hinges.Side Panels 2 parts, Removable with handles & lockable with slim latch.Rear Door Solid metal, flat, nominal 85% perforated, two part. Opening left & right. 180 degree opening (135 degree when used in a row). Interchangable door hinges.Top Chasis & Cover Monoblock, welded, CDFx form construction. Fan tray mountable. 2x(150x85 mm) + 2x (150x150 mm) + 2x(300x65 mm) + 2x(65x65 mm) cable entry spaces, all brush mountable. Fixing possiblity to ceiling (with fixing accessory).Bottom Chasis Monoblock, welded, CDFx form construction. Fixing points either fixing to floor or raised floor. 2x(150x85 mm) + 2x (150x150 mm) cable entry hole (brush mountable) + 400x 680 mm ventilation hole (filter mountable). 19" profiles Adjustable, 4 units (2 front, 2 rear). U-marked.Vertical Cable Organizer Mountable on sides & rear vertically (optional).Front Door Lock High quality, three-point lockable cylindrical mechanizm with handle.Levelling fit & Pulleys Available (optional).Loading Capacity 1500 kg max. (42U, TS EN 61587-1).

26 www.hescs.com

Page 23: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

27

HCS P/N Internal Heightmm

NotesDimensions

Widthmm

Depthmm

Heightmm

Net WeightKg

Description

Ordering Information

www.hescs.com

C16-04281 42U19" (800x1100) mm DataLine™16 1880 800 1100 2028 130 Data Center Network CabinetC16-04781 47U19" (800x1100) mm DataLine™16 2102 800 1100 2250 146 Data Center Network CabinetC16-04282 42U19" (800x1200) mm DataLine™16 1880 800 1200 2028 148 Data Center Network CabinetC16-04782 47U19" (800x1200) mm DataLine™16 2102 800 1200 2250 167 Data Center Network Cabinet

Page 24: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

DATALINE 13 OPEN FRAMES

Qualifications and Approvals

HCS DataLine 13 Open Frames are supported by HCS DoubleSafe™ QA Program and they comply to the following standards:

Applications

The special design of HCS DataLine 13 Open Frames allow the use of a large variety and types of accessories, including 19" high-density patch panels, pulleys, floor fixing kits, cable management panels, and many other 19” devices and accessories.

Description

HCS DataLine 13 Open Frames are specially designed for new generation Data Centers, in order to provide best possible housing for high-density cabling. HCS DataLine 13 Open Frames are having an attractive design combined with a long-lasting, solid & stable construction, guaranteed by the HCS DataLine Logo & Trademark.

Benefits & Features

π Solid and stable construction - providing support for large loads upto 500 kg

π Aesthetic & attractive design - can be used in open office environments.

π Flat packed design option- providing minimal storage space and saving transportation costs.

π Sophisticated cable channeling - enabling concealed cords routing.

π Top & bottom fixing points - providing fixing to floor and/or overhead cable tray.

π User-friendly design - easy to install and operate.

28

DIN EN 10130-91DIN EN 10327EREGLI 6112

TS EN 60297-3-100/101/102DIN 41494TS EN 60529-1IP20 (Opsiyonel IP 42)

DIN 67530ASTM D 2796ASTM D 3451

TS EN 61587-1 TS EN 60917-2-1/-2

www.hescs.com

General Steel Sheets Powder Coating Mechanical Assembly IT equipment safety

Fan Unit & Power Strips

Page 25: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS P/N NotesDimensions

Widthmm

Depthmm

Heightmm

Net WeightKg

Description

Ordering Information

C13-04214 42U 19" (1671x465)mm DataLine™13 Open Frame 1671 465 2073

C13-04514 45U 19" (1671x465)mm DataLine™13 Open Frame 1671 465 2206

C13-04714 47U 19" (1671x465)mm DataLine™13 Open Frame 1671 465 2296

29

General Properties

www.hescs.com

Material of Construction Sheet & Galvanized steel. 1.0/1.2/1.5/2.0 mm thickness.Paint and Color Special steel finish with electrostatic powder coat, RAL 9005 black. other colors available upon request.Side&Top Cover Cold rolled steel thickness : 1,2 mm ; (2 pcs) - powder coatedFinger ducts Plastic and cold rolled steel cable management slots thickness 1,5 mm ; (4 pcs) - powder coated, 150 mm width.Top Cover Cold rolled steel thickness : 1,2 mm ; (2 pcs) - powder coated

Page 26: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and
Page 27: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

“State of the art Data Center Solutions”

SECTION B: Free Standing Data Center Cabinet Accessories

Cabinet Accessories 32

Corridor Containment 33

Overhead Cabling Management 34

Snapfix Cable Containment Brackets, Snapfix Pdu Brackets, Grounding Kits 35

Brush Kits, Levelling Feet, Castor Group, Baying Kit 36

Shelves, 19” Blank Panels 37

Horizontal Cable Organiser 38

Page 28: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

DATALINE DATA CENTER CABINETS’ ACCESSORIES

Applications

The large variety of HCS DataLine Cabinet Accessories for endless applications, including cabling, network and Data Center applications.

Description

HCS DataLine series includes a wide range of high quality racks, cabinets and enclosures, specially designed for structured premise cabling in local area networks (LANs), Data Center environments, including distribution and equipment, cross connect cabinets and racks, splice boxes, climate control and many more components for both copper and fiber optic cabling systems.HCS DataLine Accessories are compatible with all HCS DataLine Cabinets, providing an extensive range of accessories making HCS DataLine Cabinets extremely versatile, user-friendly and efficient.All HCS DataLine Accessories have an attractive design combined with a long-lasting, solid&stable construction, guaranteed by HCS DataLine Logo & Trademark.

32 www.hescs.com

Page 29: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS P/NDimensions

Widthmm

Heightmm

Description

Ordering Information

C00-012E01 Containment Door System, double doors with secure glass, manual operated 1200 2000

C00-012E02 Containment Roof System, transparent roof reinforced with metal frame (600 mm) 1200 600

C00-012E03 Containment Roof System, transparent roof reinforced with metal frame (800 mm) 1200 800

Cold Corridor Doors

Cold Corridor Roof

CORRIDOR CONTAINMENT

33www.hescs.com

Page 30: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

OVERHEAD CABLING MANAGEMENT

Ordering Information

C00-10E01 U-shaped cable path,h:85. for w600 DC Cabinets 600 85

C00-10E02 U-shaped cable path,h:130. for w600 DC Cabinets 600 130

C00-10E03 W-shaped cable path,h:200. for w600 DC Cabinets 600 200

C00-10E04 U-shaped cabinet front label panel,h:200. for w600 DC Cabinets 600 200

C00-10E05 U-shaped cable path,h:85. for w800 DC Cabinets 800 85

C00-10E06 U-shaped cable path,h:130. for w800 DC Cabinets 800 130

C00-10E07 W-shaped cable path,h:200. for w800 DC Cabinets 800 200

C00-10E08 U-shaped cabinet front label panel,h:200. for w800 DC Cabinets 800 200

C00-10G01 Top chasis cable routing organiser, for DC cabinets w600, 6 pcs/set

C00-10G02 Top chasis cable routing organiser, for DC cabinets w800, 10 pcs/set

34 www.hescs.com

Heightmm

HCS P/NDimensions

Widthmm

Description Notes

Page 31: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

PDU BRACKETS

C00-03G02 fixing ring for Vertical power strips, for DC cabinets (1 set: 2 pcs)

HCS P/N Description

Ordering Information

GROUNDING KITS

HCS P/NDimensions

Widthmm

Heightmm

Description

Ordering Information

C00-06A04 6 mm2 Door grounding kit for DataLine 16 cabinets

C00-06A05 16/25 mm2 Cabinet Body Grounding Kit fpr DataLine 16 cabinets

35

CABLE ORGANIZER RINGS

Depthmm

HCS P/NDimensions

Widthmm

Description

Ordering Information

Notes

Notes

C00-09D01 Cable organizer ring, modular, 35x60 mm. 35 60

C00-09D02 Cable organizer ring, modular, 60x88 mm. 60 88 DataLine 16, W=800 cabinets only

C00-09D02 Cable organizer ring, modular, 60x100 mm. 60 100 DataLine 16, W=800 cabinets only

C00-09D03 Cable organizer ring, modular, 35x120 mm. 35 120

www.hescs.com

Page 32: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

BRUSH KITS & LEVELLING FEET & CASTOR GROUP & FIXING KITS

HCS P/NDimensions

Widthmm

Heightmm

Description

Ordering Information

C00-10F01 Brush kit for DataLine 16 cabinets (600x1100)

C00-10F02 Brush kit for DataLine 16 cabinets, (800x1100)

C00-04G01 Set of 4, adjustable levelling feet for DataLine 16 cabinets, h: 150 mm

C00-04G02 Set of 4 castor group for DataLine 16 cabinets - without breaking system

C00-12C05 DataLine 16 cabinets w600 floor L-form fixing kit (1 set=2 pcs).

C00-12C06 DataLine 16 cabinets w600 raised floor 3D fixing kit (1 set=4 pcs).

C00-12C07 DataLine 16 cabinets w600 raised floor 2D fixing kit (1 set=2 pcs).

C00-012F01 DataLine 16 cabinets w600/800 bottom chasis 3D-vibration absorption set (1 set: 4 pcs).

C00-012F02 DataLine 16 cabinets w600/800 bottom chasis 2D-vibration absorption set (1 set: 4 pcs).

C00-012F03 DataLine 16 cabinets w600/800 top chasis 2D-vibration absorption set (1 set: 4 pcs).

HCS P/NDimensions

Widthmm

Heightmm

Description

Ordering Information

C00-012D01 DataLine 16 cabinets baying kit, 4 pcs/set

BAYING KIT

36 www.hescs.com

Page 33: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Drawers

SHELVES

HCS P/N Depthmm Notes

Additional Items

IncludedDescription Load

Capacity

Ordering Information

C00-01B04 Fixed Shelf, Vented Steel Sheet, 1/2U,19", 4 Fixing Points 1000 mm 30 Kg max. Mounting Kit C00-01B08 Fixed Shelf, Vented Steel Sheet, 1/2U,19", 4 Fixing Points, with Support Profile 1000 mm 60 Kg max. Mounting Kit C00-01B11 Fixed Shelf, Vented Steel Sheet, Heavy Duty, 1U,19", 4 Fixing Points, with Support Profile 1000 mm 100 Kg max. Mounting Kit C00-01C04 Sliding Shelf, Vented Steel Sheet, 1/2U,19", 4 Fixing Points, Rail Locked 1000 mm 35 Kg max. Mounting Kit C00-01C07 Sliding Shelf, Vented Steel Sheet, Heavy Duty, 1U,19", 8 Fixing Points 1000 mm 100 Kg max. Mounting Kit Depth AdjustableC00-01C08 Sliding Shelf, Vented Steel Sheet, 1U,19", Teleskobic Cable Carry Mechanizm - - Mounting Kit 750mm opening Depth Adjustable

C00-01D01 1U, 19", lockable drawer 350 mm - Mounting Kit C00-01D02 2U, 19", lockable drawer 550 mm - Mounting Kit Depth AdjustableC00-01D03 3U, 19", lockable drawer 550 mm - Mounting Kit Depth Adjustable

Ordering Information

Additional Items IncludedHCS P/N NotesDescription Color

C00-10A01 1U 19" Blank Panel Steel Sheet Black RAL 9005 - -

C00-10A02 2U 19" Blank Panel Steel Sheet Black RAL 9005 - -

C00-10A04 4U 19" Blank Panel Steel Sheet Black RAL 9005 - -

C00-10A08 8U 19" Blank Panel Steel Sheet Black RAL 9005 - -

C00-10A16 16U 19" Blank Panel Steel Sheet Black RAL 9005 - -

C00-10A24 24U 19" Blank Panel Steel Sheet Black RAL 9005 - -

C00-10H01 Fan Tray Blank Panel for DataLine 16 cabinets Steel Sheet Black RAL 9005 - -

C00-10H02 Ventilation hole blank panel for DataLine 16 cabinets Steel Sheet Black RAL 9005 - -

Material

BLANK PANELS

37www.hescs.com

Page 34: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HORIZONTAL CABLE ORGANIZER

Hook & Ring SizeHCS P/N NotesDescription ColorHook & Ring

Ordering Information

38 www.hescs.com

C00-09C01 1U 19" cable organizer ring, metal hook 1 pcs Black RAL 9005 44x44 mm -

C00-09C02 1U 19" cable organizer ring, metal hook 1 pcs Black RAL 9005 44x88 mm -

C00-09C03 2U 19" cable organizer ring, metal hook 10 pcs Black RAL 9005 88x88 mm -

C00-09C04 1U 19" cable organizer ring, plastic hook 1 pcs Black RAL 9005 44x88 mm -

C00-09A08 1U 19" cable organizer, plastic rings 5 pcs Black RAL 9005 44x44 mm -

C00-09A01 1U 19" cable organizer, plastic rings 5 pcs Black RAL 9005 44x88 mm -

C00-09A09 1U 19" cable organizer, metal rings 5 pcs Black RAL 9005 44x44 mm -

C00-09A02 1U 19" cable organizer, metal rings 5 pcs Black RAL 9005 44x88 mm -

C00-09A03 2U 19" cable organizer, plastic rings 10 pcs Black RAL 9005 88x88 mm -

C00-09A10 2U 19" cable organizer, plastic rings 5 pcs Black RAL 9005 44x88 mm -

C00-09A11 1U 19" cable organizer, metal rings and closing cover 5 pcs Black RAL 9005 44x44 mm -

C00-09A04 1U 19" cable organizer, metal rings and closing cover 5 pcs Black RAL 9005 44x88 mm -

C00-09A05 2U 19" cable organizer, metal rings and closing cover 10 pcs Black RAL 9005 88x88 mm -

C00-09A13 1U 19" cable organizer, metal rings and brush 5 pcs Black RAL 9005 44x88 mm -

C00-09A14 2U 19" cable organizer, metal rings and brush 10 pcs Black RAL 9005 88x88 mm -

C00-09A07 1U 19" cable organizer, metal, with brush - Black RAL 9005 - -

C00-09A06 1/2U 19" cable organizer, metal, with brush and clamping - Black RAL 9005 - -

C00-09A12 1U 19" cable organizer, metal, with brush and clamping - Black RAL 9005 - -

C00-09B01 1U d=400 mm Depth cable organizer, metal - Black RAL 9005 - -

C00-09B02 1U d=600 mm Depth cable organizer, metal - Black RAL 9005 - -

C00-09B03 1U d=800 mm Depth cable organizer, metal - Black RAL 9005 - -

C00-09B04 1U d=1000 mm Depth cable organizer, metal - Black RAL 9005 - -

Page 35: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

“State of the art Data Center Solutions”

SECTION C: Data Center Accessories

Data Center Environmental Monitoring & Management Solution 40-41

Power Distribution Units - Basic 42-43

Power Distribution Units - Metered 44-45

Power Distribution Units - Ip Monitored 46-47

Power Distribution Units - Managed & Ip Switched 48-49

LCD Consoles With Kvm Switch (Ip) 50-51

Page 36: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

ENVIRONMENTAL MONITORING & MANAGEMENT SOLUTION

Applications

The special design of HCS DataLine Environmental Monitoring & Management Tool allows centralised monitoring, management, storing and archiving of vital parameters in a Data Center such as temperature-humidity-water flooding-pressure control -smoke-door access-movement-light intensity-IP camera recording-electrical parameters.

Description

HCS DataLine Environmental Monitoring & Management tool is specially designed for new generation Data Centers, in order to provide best possible uptime.

Qualifications and Approvals

CE

Benefits & Features

π Large variety of monitoring parameters - providing management from single source.

π Professional and Centralised Management including IP cams recording - support best possible uptime for Data Center

π Ultimate report & archive tool - provide excellent back-up utility

π Third party hardware integration - providing simple and efficient management tool

π Power and Network Access Redundancy - ensures management tool is online all the time.

40 www.hescs.com

Page 37: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

General Properties

Mounting Size 1U, 19” adaptable main unit Feeding Voltage 12V DCStorage Temperature -40…..+ 85 C ; 0……%85 Rh&Humidity Range Operational Temperature -10…..+ 70 C ; 0……%70 Rh&Humidity Range Dimensions (WxDxH) 260x105x25 mmWeigth 500 g.Colour BlackExternal Device Input 8 (supports up to 128 sensors)Access Ports 1x10/100 Ethernet, 2xUSB, 1xRS323Monitoring Temperature-humidity-water flooding-air flow-pressure control-smoke-fire-air quality-door access-movement light intensity-IP camera recording-eletrcial parameters, voltage frequencyAlarming WEB, E-Mail, SMS, Voice Calling, Buzzer, LCD Module, SNMP TrapsManagement All the sensors as well as all 3rd party hardware such as air-conditioning systems-UPS- IPcams- eLectrical infrastructure over professional centralised software (optional) via RS232, RS485, TCP/IP, SNMP,XML, MODBUS)

HCS P/N Description

Ordering Information

C00-13A02 Main Unit + Web packC00-13A03 Combo SensorC00-13A04 Humidity & Temperature High SensitivityC00-13A05 Humidity & Temperature Standart C00-13A06 Temperature Sensor StandartC00-13A07 Flood SensorC00-13A08 Water Detect Cable 1 meterC00-13A09 Water Detect Cable 5 meterC00-13A10 3-phase VF ModuleC00-13A11 3-phase Energy MıoduleC00-13A12 UPS RS-232 ModuleC00-13A13 LCD ModuleC00-13A14 Expansion ModuleC00-13A15 Dry Contact Module 1 portC00-13A16 Dry Contact Module 8 portC00-13A17 Dry Contact Module 24 portC00-13A18 Relay Output Module 4 port - 0.5AC00-13A19 Relay Output Module 12 port - 0.5AC00-13A20 Alarm Signal Input ModuleC00-13A21 Integration Module (SNMP/RS232/RS485)C00-13A22 Server Integration Module (SNMP)C00-13A23 Analog Module 1 Port - 4-20mA or 0-10VC00-13A24 Analog Module 24 PortC00-13A25 Proximity Module

HCS P/N Description

Ordering Information

C00-13A26 Resetter ModuleC00-13A27 Voice Calling ModuleC00-13A28 Air Flow ModuleC00-13A29 Air Quality ModuleC00-13A30 Light SensorC00-13A31 Battery Pack (12V - 55W)C00-13A32 GSM ModuleC00-13A33 3G Router Module (Reduntant DSL 3G)C00-13A34 Smoke DetectorC00-13A35 Door DetectorC00-13A36 Movement DetectorC00-13A37 Vibration DetectorC00-13A38 Proximity ReaderC00-13A39 Proximity CardC00-13A40 Cabinet Door LockC00-13A41 Room Entrance LockC00-13A42 Power AdapterC00-13A43 Signal Tower with BuzzerC00-13A44 BuzzerC00-13A45 Centralised Software for 1-5 NodsC00-13A46 Centralised Software for 1-15 NodsC00-13A47 Centralised Software for 15+ NodsC00-13A48 IP Cam - Indoor

41www.hescs.com

Page 38: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

IEC 60309 32A (2P+E)Plug

DIN 49440 16AOutlet Socket

VERTICAL POWER DISTRIBUTION UNITS - BASIC

Applications

The special design of HCS DataLine Vertical PDUs helps for high-quality & clean power to the servers in Data Center cabinets.

Description

HCS DataLine Vertical PDUs are specially designed for new generation Data Centers, in order to supply high-quality & clean power to your valuable active equipment and servers.

Qualifications and Approvals

ROHS, CE

Benefits & Features

π ZeroU, Single Phase 32A

π Schuko DIN 49440 16A outlets

π IEC 60309 plug

π 2x16A Circuit Breaker with Cover

π 8/24 way outlet alternatives

42 www.hescs.com

Page 39: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS P/N Description

Ordering Information

General Properties

43www.hescs.com

C00-03D04 Vertical mounting, 24 way power strip, european (schuko) type, 18xschuko (din 49440 16a) sockets, iec60309 32a (2P+E) plug, aluminium housing, with 2 ways circuit breaker (250vac, 1x20a, 3x6.0mm_x3.0m)

Output socket type&quantity 18 or24 way DIN 49440 16A Schuko typePlug Type IEC60309 plug (32A 2P+E)Rating Voltage 250VAC 50/60 HzMax.Power 8000 WattsSafety Authentication CERating Current 32AProtection 2x16A circuit breaker with coverProduct Size L x W x H = 1612 x 44.4 x 66 mmMounting Length Zero U, 1584 mmCase Colour BlackCable dimension 3x6.0mm2

Cable Length 3 metres

C00-03D03 Vertical mounting, 18 way power strip, european (schuko) type, 18xschuko (din 49440 16a) sockets, iec60309 32a (2P+E) plug, aluminium housing, with 2 ways circuit breaker (250vac, 1x20a, 3x6.0mm_x3.0m)

Page 40: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

VERTICAL POWER DISTRIBUTION UNITS - METERED

Applications

The special design of HCS DataLine Vertical Metered PDUs helps for high-quality & clean power to the servers in Data Center cabinets.

Description

HCS DataLine Vertical Metered PDUs are specially designed for new generation Data Centers, in order to supply high-quality & clean power to your valuable active equipment and servers.

Qualifications and Approvals

ROHS, CE

Benefits & Features

π ZeroU, Single Phase 32A

π IEC C13&C19 outlets

π IEC 60309 plug

π 2x16A Circuit Breaker with Cover

π Digital AC Ampermeter - Total PDU Current Load Monitoring

π Voice alarm

IEC 60309 32A (2P+E)Plug

IEC 60320 C13 10A

Outlet Socket (with anti-fall

device)

IEC 60320 C19 16A

Outlet Socket

44 www.hescs.com

Page 41: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS P/N Description

Ordering Information

C00-03D05 20 way C13 & 4 way C19 IEC 320 power strip with ampermeter display, 0U, 32 Amp EN60309 Input Plug - 3M lead, 2 x 16A MCB

45

General Properties

www.hescs.com

Output socket type&quantity 24 way IEC320 C13 10A and 4 way IEC320 C19 16APlug Type IEC60309 plug (32A 2P+E)Rating Voltage 250VAC 50/60 HzMax.Power 8000 WattsSafety Authentication CERating Current 32AProtection 2x16A circuit breaker with coverProduct Size L x W x H = 1645x 44.4 x 66 mmMounting Length Zero U, 1618,5 mmCase Colour BlackCable dimension 3x6.0mm2

Cable Length 3 metres Monitoring Functions Total PDU load currentAlarm Functions Max value of PDU total load currentAlarming Method Total PDU load current on the LCD display with voice alarm.

Page 42: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

VERTICAL IP MONITORED POWER DISTRIBUTION UNITS

Applications

The special design of HCS DataLine Vertical Managed & IP Monitored PDUs helps for high-quality & clean power to the servers in Data Center cabinets.

Description

HCS DataLine Vertical Managed & IP Monitored PDUs are specially designed for new generation Data Centers, in order to supply high-quality & clean power to your valuable active equipment and servers.

Qualifications and Approvals

ROHS, CE

Benefits & Features

π ZeroU, Single Phase 32A PDU with IEC C13&C19 outlets and IEC 60309 plug

π Total load current, voltage, power(kW), energy consumption(kWh) and power factor monitoring

π Total energy consumption (kWh) recording

π Temperature/Humidity Sensors

π Max/Min alarming values setup via snmp and e-mail

π Web, SNMP and Telnet Access with SSH as option

π User Authorisation

46

IEC 60309 32A (2P+E)Plug

IEC 60320C13 10A

Outlet Socket (with anti-fall

device)

IEC 60320C19 16A

Outlet Socket

www.hescs.com

Page 43: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS P/N Description

Ordering Information

C00-03D06 20 way C13 & 4 way C19 IEC 320 power strip, IP MONITORED, 0U, 32 Amp EN60309 Input Plug - 3M lead, 1x32A MCB

General Properties

47www.hescs.com

Output socket type&quantity 20 way IEC320 C13 10A and 4 way IEC320 C19 16APlug Type IEC60309 plug (32A 2P+E)Rating Voltage 250VAC 50/60 HzMax.Power 8000 WattsSafety Authentication CERating Current 32AProtection 32A circuit breaker with coverProduct Size L x D x W = 1528 x 44.4 x 68 mmMounting Length Zero U, 1495 mmCase Colour BlackCable dimension 3x6.0mm2

Cable Length 3 metres Sensor Ports 3 x Temperature&HumidityMonitoring Functions Total load current, voltage, power(kW), energy consumption(kWh) and power factor, Operation state of the PDU, Temperature/Humidity stateAlarm Functions Max./Min. value of total load current, Max./Min. value of Temperaturea/Humidity, When total load current exceeds preset limited value (system default)Alarming Method State indicator on NPDU control interface flashes, and NPDU buzzer rings, State indicator on Web interface flashes, and PC buzzer rings, E-mail automatically sent to system administrator, SNMP trap and Level signal sent by LOGIC portEnergy Consumption Functions Recording total energy consumption (kWh) in per unit timeLinking Functions Supporting to cascade and radial connected of up to 10pcs NPDUsEvent Log Record Recording and saving alarm and operation informationUser Management User authority definitionAccess Method Accessing through Web browser, such as IE Accessing through Standard Network Management Protocal, SNMP(V1/V2) Telnet SSH (optional)System Supporting Supporting multi-user operation, and software updating

Page 44: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

48

VERTICAL MANAGED & IP SWITCHED POWER DISTRIBUTION UNITS

Applications

The special design of HCS DataLine Vertical Managed & IP Switched PDUs helps for high-quality & clean power to the servers in Data Center cabinets.

Description

HCS DataLine Vertical Managed & IP Switched PDUs are specially designed for new generation Data Centers, in order to supply high-quality & clean power to your valuable active equipment and servers.

Qualifications and Approvals

ROHS, CE

Benefits & Features

π ZeroU, Single Phase 32A PDU with IEC C13&C19 outlets and IEC 60309 plug

π Total load current, voltage, power(kW), energy consumption(kWh) and power factor monitoring

π Outlet based load current, power(kW) and energy consumption(kWh) monitoring

π Outlet based on/off switching

π Total energy consumption (kWh) recording

π Temperature/Humidity Sensors

π Max/Min alarming values setup via snmp and e-mail

π Web, SNMP and Telnet Access with SSH as option

π User Authorisation

IEC 60309 32A (2P+E)Plug

IEC 60320C13 10A

Outlet Socket (with anti-fall

device)

IEC 60320C19 16A

Outlet Socket

www.hescs.com

Page 45: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

General Properties

HCS P/N Description

Ordering Information

C00-03D07 16 way C13 & 4 way C19 IEC 320 power strip, IP SWITCHED, 0U, 32 Amp EN60309 Input Plug - 3M lead, 1x32A MCB

49www.hescs.com

Output socket type&quantity 16 way IEC320 C13 10A and 4 way IEC320 C19 16APlug Type IEC60309 plug (32A 2P+E)Rating Voltage 250VAC 50/60 HzMax.Power 8000 WattsSafety Authentication CERating Current 32AProtection 32A circuit breaker with coverProduct Size L x D x W = 1848 x 66.6 x 44.4 mmMounting Length Zero U, 1798 mmCase Colour BlackCable dimension 3x6.0mm2

Cable Length 3 metres Sensor Ports 3 x Temperature&HumidityMonitoring Functions Total load current, voltage, power(kW), energy consumption(kWh) and power factor, Outlet load current, power(kW) and energy consumption(kWh) Outlet on/off state System running state, Logical port output, Temperature/Humidity stateControlling Functions Outlet switch on/off (also on LCD), Set the delay of outlet sequential switching, Set the automatic switching time of outlet, Set whether to immediately cut off power or not when it exceeds limited value, Keep the former state of individual outlet after reset Alarm Functions Max./Min. value of total load current, Max./Min. value of Temperaturea/Humidity, When total load current exceeds preset limited value (system default), When outlet load current exceeds preset limited valueAlarming Method State indicator on NPDU control interface flashes, and NPDU buzzer rings, State indicator on Web interface flashes, and PC buzzer rings, E-mail automatically sent to system administrator, SNMP trap and Level signal sent by LOGIC portEnergy Consumption Functions Recording total energy consumption (kWh) in per unit timeLinking Functions Supporting to cascade and radial connected of up to 10pcs NPDUsEvent Log Record Recording and saving alarm and operation informationUser Management User authority definitionAccess Method Accessing through Web browser, such as IE Accessing through Standard Network Management Protocal, SNMP(V1/V2) Telnet SSH (optional)System Supporting Supporting multi-user operation, and software updating

Page 46: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

LCD CONSOLES

Applications

HCS DataLine LCD Console acts as a single LCD drawer or LCD KVM drawer. HCS DataLine LCD Consoles can be equipped with 8 or 16 KVM ports and/or with optional IP port to access your servers with a superior video quality by offering multiplatform and combo connection features.

Description

HCS DataLine LCD Consoles are specially designed for new generation Data Centers, in order to provide easy access to the servers.

Qualifications and Approvals

ROHS, CE

π 17' LCD display

π Turkish or English keyboard

π Optional Integrated 8 or16 Port KVM Switch

π Supports an optional remote console (CAT5 based or Over-IP)

π CAT5 Console upto 300 metres away from KVM switch

π Supports multiplatform - PS/2 or USB computers (SUN and MAC)

π Supports DOS, Windows, Netware, Unix, Linux, MacOS

π Hot pluggable - Add or remove connected PCs without having to power down the KVM switch or PCs

π Superior video quality - Up to 1280x1024, DDC2B

π No software required - easy PC selection via push buttons hot keys or OSD (on screendisplay)

π Supports daisy-chaining up to 7 units

π Auto scan mode

π Metal case, rack mountable

Benefits & Features

50 www.hescs.com

Page 47: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS P/N Description

Ordering Information

General Properties

51www.hescs.com

C00-13B01 17” Rack Mountable LCD Drawer

C00-13B02 17” Rack Mountable LCD Drawer with 8 port KVM

Switch

C00-13B03 17” Rack Mountable LCD Drawer with 16 port KVM

LCD Size 17”Computer Connections (Maximum) Single / 8 (64) / 16 (128)Computer Connectors DB 15 FemaleConsole Ports 1 (One Local), plus 1 Optional Modules : Selectable CAT5-Based or IP-Based Remote ConsoleCAT5-Based Remote Console RJ-45 Connector Console up to 300 metres away from KVM switch with superior auto-adjust RGB gain/delay control capabilityIP-Based Remote Module RJ-45 8P8C for 10/100M Ethernet DB-9 pin mal efor Modem, Null modem and serial power Control Mini USB 2.0 receptacle Daisy Chaining Daisy Chainable upto 8 levels ; Connector : DB15 (Female Type)Computer Selection On Screen Display (OD), Hot Key, Push ButtonHotkey Provides various Hotkeys (Scroll-Lock/ Caps-Lock/ Num-Lock/ Ctrl/ Alt/ Win)Auto-Scan Intervals 5 - 99 s.Keyboard / mouse Emulation PS/2Video Resolution (Local Console) 1280x1024 Video Resolution (Remote Console) 1600x1200 for CAT5-Based 150 metres remote console, 1024x768 for CAT5-Based 300 metres remote console, 1600x1200 for IP-Based remote console Power Adapter DC 12VPower Adaptor for CAT5 DC 9V, 500mA Remote Console Dongle Housing Heavy-Duty MetalSize 19” Rack mount, 1UWeight 20,9/21,1kg / 21,5kgDimensions (LxWxH) 600x450x44 mm.

Page 48: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and
Page 49: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

SECTION D: Data Center Copper & Fiber Optic Cabling Solutions

“State of the art Data Center Solutions”

Note: For all cable alternatives, please refer to the “HCS Product Catalog”

DATALINK 250 Category 6 Horizontal Cables; U/UTP Cables, U/FTP Cables 54-57

DATALINK 250E Category 6E Horizontal Cables; U/UTP Cables 58-59

DATALINK 500A Augmented Category 6 Horizontal Cables; U/MRTP Cables, U/FTP Cables, S/FTP Cables 60-65

DATALINK 600 Category 7 Horizontal Cables; S/FTP Cat7+ Cables Tested @ 1000mhz 66-67

DATALINK 600 Category 7 Horizontal Cables; S/FTP Cat7+ Cables Tested @ 1200mhz 68-69

DATALINK 100e Category 5e Unshielded Rj-45 To Telco Copper Patch Panels 70-71

DATALINK 100e Category 5e Unshielded Rj-45 To Ipass Pre-Terminated Copper Patch Panels 72-73

DATALINK 250E Category 6E Patch Panels Unshielded Rj-45 Copper Angled Patch Panels (Jacks) 74-75

DATALINK Blank Keystone-jack Copper Patch Panels 76-77

DATALINK 500A Augmented Category 6A Cable Assemblies 78-79

DATALIGHT MTD Indoor/Outdoor Multi-Tight Distribution Fiber Optic Cables 80-81

DATALIGHT SLT Indoor/Outdoor Single-Loose Tube Fiber Optic Cables 82-83

DATALIGHT MLT Indoor/Outdoor Dielectric Dry-Core Multi-Loose Tube Fiberoptic Cables 84-85

DATALIGHT Fiber Optic Patch Cords And Pigtails 86-87

DATALIGHT Fiber Optic Pre-terminated 19" Patch Panels 88-89

DATALIGHT MPO Cable Assemblies 90-91

DATALIGHT Fiber Options & Test Methods 92-93

Page 50: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Basic Conductor Solid, 23AWG, 0.57 mm, bare annealed copper

Insulation Polyolefin

Number of insulated conductors 8, twisted in 4 pairs. (8 pairs in FIG-8 cables)

Color Code of Pairs Blue x White/Blue, Orange x White/Orange, Green x White/Green, Brown x White/Brown.

Overall Tape Wrap None.

Overall shield None.

Drain wire None.

Outer Jacket LS0H Halogen free flame retardant or PVC compound.

Standard Jacket Color Light Gray RAL 7035. Other colors available upon request.

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number.

Pulling force 50 N/mm2 max.

Short Term Bend Radius 8xOD mm

Long Term Bend Radius 4xOD mm

Storage Temperature -20 to +80C

Temperature operating range -20 to +60C

Installation temperature range 0 to +50C

Flame Test IEC 60332-1

Halogen content in LS0H cables Null.

Benefits & Features

Category 6 U/UTP 100 Ohm Horizontal LAN Cables

Description

Applications

HCS DataLink 250 cable series consists of 100 Ohm impedance, 4-pair and 8-pair U/UTP cables for horizontal installations in local area networks (LANs). All cables fully conform to and provide a substantial margin above all Category 6 requirements of ANSI/TIA/568-C.2 and IEC 61156-5.

HCS DataLink 250 Horizontal cables support all relevant LAN applications, including the following protocols:

1000BASE-T Gigabit Ethernet ATM 25 ATM 155 10BASE-T Ethernet TP-PMD Token Ring 4 Mbps and 16 Mbps 100BASE-T Fast Ethernet Broadband and Baseband Video 100BASE-T2 ISDN Basic and Primary Access 100BASE-T4 1BASE-5 Starlan 100BASE-TX ISALAN Token Ring 100 Mbps ITU V.21 ve X.11 ATM 52

Qualifications and Approvals    

HCS DataLink 250 Cables are tested and verified for full compliance with the following standards: ANSI/TIA/568-C.2 IEC 61156-5 (ISO/IEC-11801 2nd Edition). CENELEC EN 50288-5

Testing every box or reel of cable prior to shipment - providing the highest degree of quality assurance. Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. High ACR values - providing low BER (Bit-Error-Rate) in all applications.  Extremely high pair-balance - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Revolutionary pair lay scheme - providing an extremely low delay skew.  Co-extruded crisp and clear spiral color coding of wires - providing positive wire identification and ease of installation. Descending sequential meter mark - providing easy stock and left-over handling. Smooth and rigid jacket - proving fast and easy cable pulling and installation. Batch number printed every meter - providing fast retrieval of test results from data-base. A comprehensive product range - providing all state-of-the-art cable constructions. Large variety of packaging options - providing minimum scrap and left-over cable sections. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

Physical and Mechanical Properties  

4 color-coded, unshielded twisted pairs cabled together around a star-shaped filler and overall jacketed. Siamese (Figure-8) cables are made of two identical 4-pair cables connected in a zip-cord formation, one cable identified with two raised ribs on the jacket surface.

54 www.hescs.com

Page 51: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Transmission Properties and Electrical Specifications

FREQ.

MHz

Insertion Loss

Max Nom Std

TCL

Min

EL-TCL

Min

1.00 2.0 1.65 2.0 77.3 84.3 74.3 75.3 82.3 72.3 70.8 80 67.8 68.8 77 64.8 20.0 25 20.0 40 35

10.00 5.9 5.6 6.0 61.3 69.3 59.3 60.3 67.3 57.3 50.8 65 47.8 48.8 62 44.8 26.0 30 25.0 40 15

25.00 9.4 9.0 9.5 56.3 63.3 53.3 54.3 61.3 51.3 42.8 57 39.8 40.8 54 36.8 25.3 30 24.3 36 7.0

31.25 10.6 10.2 10.7 54.9 61.9 51.9 52.9 59.9 49.9 40.9 53 37.9 38.9 50 34.9 24.6 28 23.6 35.1 5.5

62.50 15.2 14.9 15.4 50.4 57.4 47.4 48.4 55.4 45.4 34.9 45 31.9 32.9 43 28.9 22.5 27 21.5 32 NS

100.00 19.6 19.2 19.8 47.3 54.3 44.3 45.3 52.3 42.3 30.8 43 27.8 28.8 40 24.8 21.1 26 20.1 30 NS

200.00 28.7 27.5 29.0 42.8 49.8 39.8 40.8 47.8 37.8 24.8 40 21.8 22.8 37 18.8 19.0 25 18.0 27 NS

250.00 32.6 31.0 32.8 41.3 48.3 38.3 39.3 46.3 36.3 22.8 37 19.8 20.8 34 16.8 18.3 25 17.3 26 NS

300.00 36.1 34.6 NS 40.1 43.0 NS 38.1 40.0 NS 21.3 32 NS 19.3 29 NS 17.8 25 NS NS NS

NEXT

Min Nom Std

PS NEXT

Min Nom Std

EL FEXT

Min Nom Std

PS EL FEXT

Min Nom Std

RL

Min Nom Std

Typical NEXT Loss

Category 6 U/UTP 100 Ohm Horizontal LAN Cables

Typical Return Loss

Ordering Information

HCS P/N Description ODmm

WeightKg/Km

Cal. ValueKj/m Packaging Notes

H06-00401-BK 4x2x23# U/UTP CAT 6 PVC Grey 5.6 36 580 1000ft Reelex II™ -

H06-00401-DP 4x2x23# U/UTP CAT 6 PVC Grey 5.6 36 580 500m Drum -

H06-00401-DM 4x2x23# U/UTP CAT 6 PVC Grey 5.6 36 580 1000m Drum -

H06-00402-FK 4x2x23# U/UTP CAT 6 LS0H Grey 5.6 36 585 1000ft Reelex II™ -

H06-00402-DP 4x2x23# U/UTP CAT 6 LS0H Grey 5.6 36 585 500m Drum -

H06-00402-DM 4x2x23# U/UTP CAT 6 LS0H Grey 5.6 36 585 1000m Drum -

H06-00803-DP 2x(4x2x23#) CAT 6 U/UTP PVC Grey 5.6x11.3 72 1180 500m Drum FIG-8

H06-00803-DM 2x(4x2x23#) CAT 6 U/UTP PVC Grey 5.6x11.3 72 1180 1000m Drum FIG-8

H06-00804-DP 2x(4x2x23#) CAT 6 U/UTP LS0H Grey 5.6x11.3 72 1190 500m Drum FIG-8

H06-00804-DM 2x(4x2x23#) CAT 6 U/UTP LS0H Grey 5.6x11.3 72 1190 1000m Drum FIG-8

Characteristic Impedance 100±6 Ohm @ 1-300 MHz

DC Resistance 72 Ohm/Km max.

Resistance unbalance 2% max.

Capacitance 45 pF/m nom. @ 1 KHz

Cap. Unbalance (wire to ground)  1500 pF/Km max. @ 1 KHz.

Voltage rating 72 Vdc max.

Dielectric strength 1500 Volts/1 minute min rms

Velocity of Propagation (NVP) 67-69%

Propagation Delay 514 + 36/f1/2  nS/100m max @ 1-300 MHz

Propagation Delay Skew 35 nS/100m max @ 1-300 MHz

Insulation Resistance 5000 MegaOhm•Km min. @ 500 Vdc

Coupling attenuation 40 dB min @ 30-100 MHz  40-20Log(f/100) @100-300 MHz

Transfer Impedance N/A

Note: Standard jacket color: Light Gray RAL 7035. Other colors available upon request.

55www.hescs.com

dB/100m dB dB dB/100m dB/100m dB dB dB

Page 52: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Category 6 U/FTP 100 Ohm Horizontal LAN Cables

Benefits & Features

Description

Applications

HCS DataLink 250 cable series consists of 100 Ohm impedance, 4-pair and 8-pair U/FTP cables for horizontal installations in local area networks (LANs). All cables fully conform to and provide a substantial margin above all Category 6 requirements of ANSI/TIA/568-C.2 and IEC 61156-5.

HCS DataLink 250 Horizontal cables support all relevant LAN applications, including the following protocols:

1000BASE-T Gigabit Ethernet ATM 25 ATM 155 10BASE-T Ethernet TP-PMD Token Ring 4 Mbps and 16 Mbps 100BASE-T Fast Ethernet Broadband and Baseband Video 100BASE-T2 ISDN Basic and Primary Access 100BASE-T4 1BASE-5 Starlan 100BASE-TX ISALAN Token Ring 100 Mbps ITU V.21 ve X.11 ATM 52

Qualifications and Approvals

HCS DataLink 250 Cables are tested and verified for full compliance with the following standards:

ANSI/TIA/568-C.2 IEC 61156-5 (ISO/IEC-11801 2nd Edition) CENELEC EN 50288-5

Physical and Mechanical Properties

Basic Conductor Solid, 23AWG, 0.57 mm, bare annealed copper

Insulation Polyolefin

Number of insulated conductors 8, twisted in 4 pairs. (8 pairs in FIG-8 cables)

Color Code of Pairs Blue x White, Orange x White, Green x White, Brown x White.

Individual pair shield Laminated aluminum foil (foil face outward) providing 100% coverage.

Drain wire Solid, 24AWG, 0.51 mm, tin-coated annealed copper

Overall Tape Wrap Polyester tape, providing 100% coverage.

Outer Jacket LS0H Halogen free flame retardant or PVC compound.

Standard Jacket Color Light Gray RAL 7035. Other colors available upon request.

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number.

Pulling force 50 N/mm2 max.

Short Term Bend Radius 8xOD mm

Long Term Bend Radius 4xOD mm

Storage Temperature -20 to +80C

Temperature operating range -20 to +60C

Flame Test IEC 60332-1

Halogen content in LS0H cables Null.

Testing every reel of cable prior to shipment - providing the highest degree of quality assurance. Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. High ACR values - providing low BER (Bit-Error-Rate) in all applications.  Extremely high pair-balance and individual pair shield - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Revolutionary pair lay scheme - providing an extremely low delay skew.  Descending sequential meter mark - providing easy stock and left-over handling. Smooth and rigid jacket - proving fast and easy cable pulling and installation. Batch number printed every meter - providing fast retrieval of test results from data-base. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

4 color-coded, individually foil-shielded twisted pairs cabled together with a tin-coated drain-wire, overall wrapped with a polyester tape and overall jacketed. Siamese (Figure-8) cables are made of two identical 4-pair cables connected in a zip-cord formation, one cable identified with two raised ribs on the jacket surface.

56 www.hescs.com

Page 53: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Typical NEXT Loss

Category 6 U/FTP 100 Ohm Horizontal LAN Cables

Typical Return Loss

Ordering Information

HCS P/N DescriptionODmm

WeightKg/Km

Cal. ValueKj/m Packaging Notes

Characteristic Impedance 100±6 Ohm @ 1-250 MHz

DC Resistance 72 Ohm/Km max.

Resistance unbalance 2% max.

Capacitance 45 pF/m nom. @ 1 KHz

Cap. Unbalance (wire to ground)  1500 pF/Km max. @ 1 KHz.

Voltage rating 72 Vdc max.

Dielectric strength 1500 Volts/1 minute min rms

Velocity of Propagation (NVP) 78-80%

Propagation Delay 514 + 36/f1/2  nS/100m max @ 1-250 MHz

Propagation Delay Skew 25 nS/100m max @ 1-250 MHz

Insulation Resistance 5000 MegaOhm•Km min. @ 500 Vdc

Coupling attenuation 85 dB min @ 30-100 MHz  55-20Log(f/100) @100-250 MHz

Transfer Impedance 10 mOhm/m max @ 1-10 MHz 30 mOhm/m max @ 30 MHz

H06-00431-DP 4x2x23# U/FTP CAT 6 PVC Grey 6.8 47 600 500m Drum -

H06-00431-DM 4x2x23# U/FTP CAT 6 PVC Grey 6.8 47 600 1000m Drum -

H06-00432-DP 4x2x23# U/FTP CAT 6 LS0H Grey 6.8 47 605 500m Drum -

H06-00432-DM 4x2x23# U/FTP CAT 6 LS0H Grey 6.8 47 605 1000m Drum -

H06-00833-DP 2x(4x2x23#) U/FTP CAT 6 PVC Grey 6.8x13.7 94 1200 500m Drum FIG-8

H06-00833-DM 2x(4x2x23#) U/FTP CAT 6 PVC Grey 6.8x13.7 94 1200 1000m Drum FIG-8

H06-00834-DP 2x(4x2x23#) U/FTP CAT 6 LS0H Grey 6.8x13.7 94 1210 500m Drum FIG-8

H06-00834-DM 2x(4x2x23#) U/FTP CAT 6 LS0H Grey 6.8x13.7 94 1210 1000m Drum FIG-8

Note: Standard jacket color: Light Gray RAL 7035. Other colors available upon request.

57

Transmission Properties and Electrical Specifications

1.00 2.0 1.65 2.0 77.3 84.3 74.3 75.3 82.3 72.3 70.8 80 67.8 68.8 77 64.8 20.0 25 20.0 40 35

10.00 5.9 5.6 6.0 61.3 69.3 59.3 60.3 67.3 57.3 50.8 65 47.8 48.8 62 44.8 26.0 30 25.0 40 15

25.00 9.4 9.0 9.5 56.3 63.3 53.3 54.3 61.3 51.3 42.8 57 39.8 40.8 54 36.8 25.3 30 24.3 36 7.0

31.25 10.6 10.2 10.7 54.9 61.9 51.9 52.9 59.9 49.9 40.9 53 37.9 38.9 50 34.9 24.6 28 23.6 35.1 5.5

62.50 15.2 14.9 15.4 50.4 57.4 47.4 48.4 55.4 45.4 34.9 45 31.9 32.9 43 28.9 22.5 27 21.5 32 NS

100.00 19.6 19.2 19.8 47.3 54.3 44.3 45.3 52.3 42.3 30.8 43 27.8 28.8 40 24.8 21.1 26 20.1 30 NS

200.00 28.7 27.5 29.0 42.8 49.8 39.8 40.8 47.8 37.8 24.8 40 21.8 22.8 37 18.8 19.0 25 18.0 27 NS

250.00 32.6 31.0 32.8 41.3 48.3 38.3 39.3 46.3 36.3 22.8 37 19.8 20.8 34 16.8 18.3 25 17.3 26 NS

FREQ.

MHz

Insertion Loss

dB/100m

Max Nom Std

TCL

dB

Min

EL-TCL

dB

Min

NEXT

dB

Min Nom Std

PS NEXT

dB

Min Nom Std

EL FEXT

dB/100m

Min Nom Std

PS EL FEXT

dB/100m

Min Nom Std

RL

dB

Min Nom Std

www.hescs.com

Page 54: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Basic Conductor Solid, 23AWG, 0.57 mm, bare annealed copper

Insulation Polyolefin

Number of insulated conductors 8, twisted in 4 pairs. (8 pairs in FIG-8 cables)

Color Code of Pairs Blue x White/Blue, Orange x White/Orange, Green x White/Green, Brown x White/Brown.

Overall Tape Wrap None.

Overall shield None.

Drain wire None.

Outer Jacket LS0H Halogen free flame retardant or PVC compound.

Standard Jacket Color Light Gray RAL 7035. Other colors available upon request.

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number.

Pulling force 50 N/mm2 max.

Short Term Bend Radius 8xOD mm

Long Term Bend Radius 4xOD mm

Storage Temperature -20 to +80C

Temperature operating range -20 to +60C

Installation temperature range 0 to +50C

Flame Test IEC 60332-1

Halogen content in LS0H cables Null.

Category 6E U/UTP 100 Ohm Horizontal LAN Cables

Description

HCS DataLink 250E cable series consists of 100 Ohm impedance, 4-pair and 8-pair U/UTP cables for horizontal installations in local area networks (LANs). All cables fully conform to and provide a substantial margin above all Category 6 requirements of ANSI/TIA/568-C.2 and IEC 61156-5.

Applications

HCS DataLink 250E UTP yatay kablolar, ilgili tüm LAN uygulamalarını aşa¤ıdaki protokoller de dahil olmak üzere desteklemektedir:

1000BASE-T Gigabit Ethernet ATM 25 ATM 155 10BASE-T Ethernet TP-PMD Token Ring 4 Mbps ve 16 Mbps 100BASE-T Fast Ethernet Broadband ve Baseband Video 100BASE-T2 ISDN Basic ve Primary Access 100BASE-T4 1BASE-5 Starlan 100BASE-TX ISALAN Token Ring 100 Mbps ITU V.21 ve X.11 ATM 52

Qualifications and Approvals    

HCS DataLink 250E Cables are tested and verified for full compliance with the following standards:

ANSI/TIA/568-C.2 IEC 61156-5 (ISO/IEC-11801 2nd Edition). CENELEC EN 50288-5

Benefits & Features

Testing every box or reel of cable prior to shipment - providing the highest degree of quality assurance. Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. High ACR values - providing low BER (Bit-Error-Rate) in all applications.  Extremely high pair-balance - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Revolutionary pair lay scheme - providing an extremely low delay skew.  Co-extruded crisp and clear spiral color coding of wires - providing positive wire identification and ease of installation. Descending sequential meter mark - providing easy stock and left-over handling. Smooth and rigid jacket - proving fast and easy cable pulling and installation. Batch number printed every meter - providing fast retrieval of test results from data-base. A comprehensive product range - providing all state-of-the-art cable constructions. Large variety of packaging options - providing minimum scrap and left-over cable sections. Unique DoubleSafe™ Quality Assurance Program  providing lowest rejection rate available.

Physical and Mechanical Properties  

4 color-coded, unshielded twisted pairs cabled together around a star-shaped filler and overall jacketed.Siamese (Figure-8) cables are made of two identical 4-pair cables connected in a zip-cord formation, one cable identified with two raised ribs on the jacket surface.

58 www.hescs.com

Page 55: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Category 6E U/UTP 100 Ohm Horizontal LAN Cables

Characteristic Impedance 100±6 Ohm @ 1-600 MHz

DC Resistance 72 Ohm/Km max.

Resistance unbalance 2% max.

Capacitance 45 pF/m nom. @ 1 KHz

Cap. Unbalance (wire to ground)  1500 pF/Km max. @ 1 KHz.

Voltage rating 72 Vdc max.

Dielectric strength 1500 Volts/1 minute min rms

Velocity of Propagation (NVP) 67-69%

Propagation Delay 514 + 36/f1/2 nS/100m max @ 1-600 MHz

Propagation Delay Skew 35 nS/100m max @ 1-600 MHz

Insulation Resistance 5000 MegaOhm•Km min. @ 500 Vdc

Coupling attenuation 40 dB min @ 30-100 MHz  40-20Log(f/100) @100-600 MHz

Transfer Impedance N/A

Typical NEXT Loss Typical Return Loss

Ordering Information

HCS P/N Description ODmm

WeightKg/Km

Cal. ValueKj/m

Packaging Notes

H6E-00401-DP 4x2x23# U/UTP CAT 6E PVC Grey 5.6 36 580 500m Drum -

H6E-00401-DM 4x2x23# U/UTP CAT 6E PVC Grey 5.6 36 580 1000m Drum -

H6E-00402-DP 4x2x23# U/UTP CAT 6E LS0H Grey 5.6 36 585 500m Drum -

H6E-00402-DM 4x2x23# U/UTP CAT 6E LS0H Grey 5.6 36 585 1000m Drum -

Transmission Properties and Electrical Specifications

FREQ.

MHz

Insertion Loss

dB/100m

Max Nom

RL

dB

Min Nom

SKEW

nS/100m

Max

EL-TCTL

dB

Min

PS NEXT

dB

Min Nom 1.00 2.0 1.7 74.3 82 72.3 79 67.8 75 64.8 72 20.0 28 30 570 40.0 35.0

10.00 5.9 5.4 59.3 79 57.3 76 47.8 70 44.8 67 25.0 32 30 545 40.0 15.0

20.00 8.3 7.5 54.8 75 52.8 72 41.8 60 38.8 57 25.0 33 30 542 37.0 9.0

25.00 9.3 8.4 53.3 73 51.3 70 39.8 58 36.8 55 24.3 33 30 541 36.0 7.0

30.00 10.2 9.5 52.1 72 50.1 69 38.3 55 35.3 52 23.8 33 30 541 35.2 5.5

62.50 14.9 13.5 47.4 70 45.4 67 31.9 48 28.9 45 21.5 35 30 539 32.0 NS

100.00 19.0 17.5 44.3 65 42.3 62 27.8 46 24.8 43 20.1 34 30 538 30.0 NS

200.00 27.5 25.1 39.8 58 37.8 55 21.8 40 18.8 37 18.0 30 30 537 27.0 NS

250.00 31.0 28.3 38.3 55 36.3 52 19.8 38 16.8 35 17.3 25 30 536 26.0 NS

300.00 34.2 31.0 37.1 52 35.1 49 18.3 32 15.3 29 16.8 23 30 536 25.2 NS

400.00 40.0 36.0 35.3 48 33.3 45 15.8 28 12.8 25 15.9 22 30 536 24.0 NS

500.00 45.3 41.1 33.8 47 31.8 44 13.8 25 10.8 22 15.2 21 30 536 23.0 NS

600.00 50.1 45.0 32.6 46 30.6 43 12.2 22 9.2 19 14.7 20 30 535 22.2 NS

NEXT

dB

Min Nom

EL FEXT

dB/100m

Min Nom

PS EL FEXT

dB/100m

Min Nom

Delay

nS/100m

Max

TCL

dB

Min

Note: Standard jacket color: Light Gray RAL 7035. Other colors available upon request.

59www.hescs.com

Page 56: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Basic Conductor Solid, 23AWG, 0.57 mm, bare annealed copper

Insulation Polyolefin

Number of insulated conductors 8, twisted in 4 pairs. (8 pairs in FIG-8 cables)

Color Code of Pairs Blue x White, Orange x White, Green x White, Brown x White.

Overall Tape Wrap Plastic tape, providing 100% coverage.

Drain wire None.

Metal Reflector Laminated aluminum foil (foil face in) providing 100% coverage.

Outer Jacket LS0H Halogen free flame retardant or PVC compound.

Standard Jacket Color Light Gray RAL 7035. Other colors available upon request.

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number.

Pulling force 50 N/mm2 max.

Short Term Bend Radius 8xOD mm

Long Term Bend Radius 4xOD mm

Storage Temperature -20 to +80C

Temperature operating range -20 to +60C

Flame Test IEC 60332-1

Halogen content in LS0H cables Null.

Benefits & Features

Augmented Category 6 U/MRTP 100 Ohm Horizontal LAN Cables

Description

Applications

HCS DataLink 500A cable series consists of 100 Ohm impedance, 4-pair and 8-pair U/MRTP cables for horizontal installations in local areanetworks (LANs). All cables fully conform to and provide a substantial margin above all Augmented Category 6 UTP requirements of TIA/EIA568-C.2 and Category 6A of IEC 61156-5.

HCS DataLink 500A Horizontal cables support all presently available and future LAN applications, including the following protocols:

10GBASE-T 10 Gigabit Ethernet ATM 52 1000BASE-T Gigabit Ethernet ATM 25 ATM 155 10BASE-T Ethernet TP-PMD Token Ring 4 Mbps and 16 Mbps 100BASE-T Fast Ethernet Broadband and Baseband Video 100BASE-T2 ISDN Basic and Primary Access 100BASE-T4 1BASE-5 Starlan 100BASE-TX ISALAN Token Ring 100 Mbps ITU V.21 ve X.11

Qualifications and Approvals    

HCS DataLink 500A Cables are tested and verified for full compliance with the following standards::

Augmented Category 6 UTP according to ANSI/TIA/EIA-568-C.2 Category 6A according to IEC 61156-5.

Exceptional transmission properties - suitable for 10GBE applications on 100m channels. Testing every reel of cable prior to shipment - providing the highest degree of quality assurance. Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. High ACR values - providing low BER (Bit-Error-Rate) in all applications.  Extremely high pair-balance - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Revolutionary pair lay scheme - providing an extremely low delay skew. Descending sequential meter mark - providing easy stock and left-over handling. Smooth and rigid jacket - proving fast and easy cable pulling and installation. Batch number printed every meter - providing fast retrieval of test results from data-base. Unique DoubleSafe™ Quality Assurance Program  providing lowest rejection rate available.

Physical and Mechanical Properties  

4 color-coded twisted pairs, each covered by a metal-reflector, cabled together, overall wrapped with a polyester tape and overall jacketed.Siamese (Figure-8) cables are made of two identical 4-pair cables connected in a zip-cord formation, one cable identified with two raised ribs on the jacket surface.

60 www.hescs.com

Page 57: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Augmented Category 6 U/MRTP 100 Ohm Horizontal LAN Cables

Ordering Information

HCS P/N DescriptionODmm

WeightKg/Km

Cal. ValueKj/m

Packaging Notes

H6A-00405-DK 4x2x23# U/MRTP CAT 6A PVC Grey 6.8 46 600 305m Drum -

H6A-00405-DP 4x2x23# U/MRTP CAT 6A  PVC Grey 6.8 46 600 500m Drum -

H6A-00405-DM 4x2x23# U/MRTP CAT 6A PVC Grey 6.8 46 600 1000m Drum -

H6A-00406-DK 4x2x23# U/MRTP CAT 6A LS0H Grey 6.8 46 605 305m Drum -

H6A-00406-DP 4x2x23# U/MRTP CAT 6A LS0H Grey 6.8 46 605 500m Drum -

H6A-00406-DM 4x2x23# U/MRTP CAT 6A LS0H Grey 6.8 46 605 1000m Drum -

H6A-00805-DP 2x(4x2x23#) U/MRTP CAT 6A PVC Grey 6.8x13.7 92 1200 500m Drum FIG-8

H6A-00805-DM 2x(4x2x23#) U/MRTP CAT 6A PVC Grey 6.8x13.7 92 1200 1000m Drum FIG-8

H6A-00806-DP 2x(4x2x23#) U/MRTP CAT 6A LS0H Grey 6.8x13.7 92 1210 500m Drum FIG-8

H6A-00806-DM 2x(4x2x23#) U/MRTP CAT 6A LS0H Grey 6.8x13.7 92 1210 1000m Drum FIG-8

Characteristic Impedance 100±6 Ohm @ 1-500 MHz

DC Resistance 72 Ohm/Km max.

Resistance unbalance 2% max.

Capacitance 45 pF/m nom. @ 1 KHz

Cap. Unbalance (wire to ground)  1500 pF/Km max. @ 1 KHz.

Voltage rating 72 Vdc max.

Dielectric strength 1500 Volts/1 minute min rms

Velocity of Propagation (NVP) 67-69%

Propagation Delay Skew 45 nS/100m max @ 1-500 MHz

Insulation Resistance 5000 MegaOhm•Km min. @ 500 Vdc

Coupling attenuation 40 dB min @ 30-100 MHz  40-20Log(f/100) @100-500 MHz

Transfer Impedance NA

Note: Standard jacket color: Light Gray RAL 7035. Other colors available upon request.

Typical NEXT Loss Typical Return Loss

61

Transmission Properties and Electrical Specifications

FREQ. Insertion Loss PS NEXTLoss

PSANEXT

PSAACR-F

1 2.0 74.3 72.3 67.8 64.8 20.0 570 40.0 35.0 67.0 67.0 10 5.9 59.3 57.3 47.8 44.8 25.0 545 40.0 15.0 67.0 58.2 20 8.3 54.8 52.8 41.8 38.8 25.0 542 37.0 9.0 67.0 52.2 25 9.3 53.3 51.3 49.8 36.8 24.3 541 36.0 7.0 67.0 50.2 30 10.2 52.1 50.1 38.3 35.3 23.8 541 35.2 5.5 67.0 48.7 62.5 14.9 47.4 45.4 31.9 28.9 21.5 539 32.0 NS 65.6 42.3 100 19.0 44.3 42.3 27.8 24.8 20.1 538 30.0 NS 62.5 38.2 200 27.5 39.8 37.8 21.8 18.8 18.0 537 27.0 NS 58.0 32.2 250 31.0 38.3 36.3 19.8 16.8 17.3 536 26.0 NS 56.5 30.2 300 34.2 37.1 35.1 18.3 15.3 16.8 536 25.2 NS 55.3 28.7 400 40.0 35.3 33.3 15.8 12.8 15.9 536 24.0 NS 53.5 26.2 500 45.3 33.8 31.8 13.8 10.8 15.2 536 23.0 NS 52.0 24.2

NEXTLoss

MHz dB/100m

Max Max

dB dB

Min Min

dB

Min

dB

Min

dB

Min

dB

Min

dB

MinMin

dB/100m

Min

dB/100m

ELFEXT PS ELFEXT RL Delay

nS/100m

TCL EL-TCL

www.hescs.com

Page 58: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Augmented Category 6 U/FTP 100 Ohm Horizontal LAN Cables

Description

HCS DataLink 500A cable series consists of 100 Ohm impedance, 4-pair and 8-pair U/FTP cables for horizontal installations in local area networks (LANs). All cables fully conform to and provide a substantial margin above all Augmented Category 6 ScTP requirements of ANSI/TIA/568-C.2 and Category 6A of IEC 61156-5.

Applications

HCS DataLink 500A Horizontal cables support all presently available and future LAN applications, including the following protocols:

10GBASE-T 10 Gigabit Ethernet ATM 52 1000BASE-T Gigabit Ethernet ATM 25 ATM 155 10BASE-T Ethernet TP-PMD Token Ring 4 Mbps and 16 Mbps 100BASE-T Fast Ethernet Broadband and Baseband Video 100BASE-T2 ISDN Basic and Primary Access 100BASE-T4 1BASE-5 Starlan 100BASE-TX ISALAN Token Ring 100 Mbps ITU V.21 ve X.11

Qualifications and Approvals

HCS DataLink 500A Cables are tested and verified for full compliance with the following standards:

Augmented Category 6 ScTP according to ANSI/TIA/568-C.2 Category 6A according to IEC 61156-5.

Basic Conductor Solid, 23AWG, 0.57 mm, bare annealed copper

Insulation Polyolefin

Number of insulated conductors 8, twisted in 4 pairs. (8 pairs in FIG-8 cables)

Color Code of Pairs Blue x White, Orange x White, Green x White, Brown x White.

Individual pair shield Laminated aluminum foil (foil face outward) providing 100% coverage.

Drain wire Solid, 24AWG, 0.51 mm, tin-coated annealed copper

Overall tape Polyester tape providing 100% coverage.

Outer Jacket LS0H Halogen free flame retardant or PVC compound.

Standard Jacket Color Light Gray RAL 7035. Other colors available upon request.

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number.

Pulling force 50 N/mm2 max.

Short Term Bend Radius 8xOD mm

Long Term Bend Radius 4xOD mm

Storage Temperature -20 to +80C

Temperature operating range -20 to +60C

Flame Test IEC 60332-1

Halogen content in LS0H cables Null.

Benefits & Features

Exceptional transmission properties - suitable for 10GBE applications on 100m channels. Testing every reel of cable prior to shipment - providing the highest degree of quality assurance. Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. High ACR values - providing low BER (Bit-Error-Rate) in all applications.  Extremely high pair-balance and individual foil shields - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Revolutionary pair lay scheme - providing an extremely low delay skew.  Descending sequential meter mark - providing easy stock and left-over handling. Smooth and rigid jacket - proving fast and easy cable pulling and installation. Batch number printed every meter - providing fast retrieval of test results from data-base. Unique DoubleSafe™ Quality Assurance Program  providing lowest rejection rate available.

Physical and Mechanical Properties

4 color-coded, individually foil-shielded twisted pairs cabled together with a tin-coated drain-wire, overall wrapped with a polyester tape and overall jacketed. Siamese (Figure-8) cables are made of two identical 4-pair cables connected in a zip-cord formation, one cable identified with two raised ribs on the jacket surface.

62 www.hescs.com

Page 59: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Augmented Category 6 U/FTP 100 Ohm Horizontal LAN Cables

Ordering Information

HCS P/N DescriptionODmm

WeightKg/Km

Cal. ValueKj/m Packaging Notes

Characteristic Impedance 100±6 Ohm @ 1-500 MHz

DC Resistance 72 Ohm/Km max.

Resistance unbalance 2% max.

Capacitance 45 pF/m nom. @ 1 KHz

Cap. Unbalance (wire to ground)  1500 pF/Km max. @ 1 KHz.

Voltage rating 72 Vdc max.

Dielectric strength 1500 Volts/1 minute min rms

Velocity of Propagation (NVP) 78-80%

Propagation Delay Skew 45 nS/100m max @ 1-500 MHz

Insulation Resistance 5000 MegaOhm•Km min. @ 500 Vdc

Coupling attenuation 55 dB min @ 30-100 MHz  55-20Log(f/100) @100-500 MHz

Transfer Impedance 10 mOhm/m max @ 1-10 MHz 30 mOhm/m max @ 30 MHz

H6A-00431-DK 4x2x23# U/FTP CAT 6A PVC Grey 6.8 47 600 305m Drum -

H6A-00431-DP 4x2x23# U/FTP CAT 6A PVC Grey 6.8 47 600 500m Drum -

H6A-00431-DM 4x2x23# U/FTP CAT 6A PVC Grey 6.8 47 600 1000m Drum -

H6A-00432-DK 4x2x23# U/FTP CAT 6A LS0H Grey 6.8 47 605 305m Drum -

H6A-00432-DP 4x2x23# U/FTP CAT 6A LS0H Grey 6.8 47 605 500m Drum -

H6A-00432-DM 4x2x23# U/FTP CAT 6A LS0H Grey 6.8 47 605 1000m Drum -

H6A-00833-DP 2x(4x2x23#) U/FTP CAT 6A PVC Grey 6.8x13.7 94 1200 500m Drum FIG-8

H6A-00833-DM 2x(4x2x23#) U/FTP CAT 6A PVC Grey 6.8x13.7 94 1200 1000m Drum FIG-8

H6A-00834-DP 2x(4x2x23#) U/FTP CAT 6A LS0H Grey 6.8x13.7 94 1210 500m Drum FIG-8

H6A-00834-DM 2x(4x2x23#) U/FTP CAT 6A LS0H Grey 6.8x13.7 94 1210 1000m Drum FIG-8

Note: Standard jacket color: Light Gray RAL 7035. Other colors available upon request.

Typical NEXT Loss Typical Return Loss

63

Transmission Properties and Electrical Specifications

1 2.08 75.30 73.30 68.00 65.00 20.00 570.00 40.00 35.00 67.00 67.00 10 5.93 60.30 58.30 48.00 45.00 25.00 545.38 40.00 15.00 67.00 58.20 20 8.38 55.78 53.78 41.98 38.98 25.00 542.05 36.99 8.98 67.00 52.18 25 9.38 54.33 52.33 40.04 37.04 24.32 541.20 36.02 7.04 67.00 50.24 30 10.29 53.14 51.14 38.46 35.46 23.77 540.57 35.23 5.46 67.00 48.66 62.5 14.99 48.36 46.36 32.08 29.08 21.54 538.55 32.04 NS 65.56 42.28 100 19.14 45.30 43.30 28.00 25.00 20.11 537.60 30.00 NS 62.50 38.20 200 27.58 40.78 38.78 21.98 18.98 18.00 536.55 26.99 NS 57.98 32.18 250 31.07 39.33 37.33 20.04 17.04 17.32 536.28 26.02 NS 56.53 30.24 300 34.27 38.14 36.14 18.46 15.46 17.30 536.08 25.23 NS 55.34 28.66 400 40.05 36.27 34.27 15.96 12.96 17.30 535.80 23.98 NS 53.47 26.16 500 45.26 34.82 32.82 14.02 11.02 17.30 535.61 23.01 NS 52.02 24.22

FREQ.

MHz

Insertion Loss

dB/100m

Max

PS NEXTLoss

NEXTLoss

dB dB

Min Min Min

dB/100m

Min

dB/100m

PSANEXT

PSAACR-F

Max

dB

Min

dB

Min

dB

Min

dB

Min

dB

Min

RL Delay

nS/100m

TCL EL-TCLACR- F PS ACR-F

www.hescs.com

Page 60: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Basic Conductor Solid, 23AWG, 0.57 mm, bare annealed copper

Insulation Polyolefin

Number of insulated conductors 8, twisted in 4 pairs. (8 pairs in FIG-8 cables)

Color Code of Pairs Blue x White, Orange x White, Green x White, Brown x White.

Individual pair shield Laminated aluminum foil (foil face outward) providing 100% coverage.

Drain wire None.

Overall shield Tin coated copper braid laid in close contact over the inner foils.

Outer Jacket LS0H Halogen free flame retardant or PVC compound.

Standard Jacket Color Light Gray RAL 7035. Other colors available upon request.

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number.

Pulling force 50 N/mm2 max.

Short Term Bend Radius 8xOD mm

Long Term Bend Radius 4xOD mm

Storage Temperature -20 to +80C

Temperature operating range -20 to +60C

Flame Test IEC 60332-1

Halogen content in LS0H cables Null.

Augmented Category 6 S/FTP 100 Ohm Horizontal LAN Cables

Description

HCS DataLink 500A cable series consists of 100 Ohm impedance, 4-pair and 8-pair S/FTP cables for horizontal installations in local areanetworks (LANs). All cables fully conform to and provide a substantial margins above all Augmented Category 6 ScTP requirements of ANSI/TIA/568-C.2 and Category 6A of IEC 61156-5.

Applications

HCS DataLink 500A Horizontal cables support all presently available and future LAN applications, including the following protocols:

10GBASE-T 10 Gigabit Ethernet ATM 52 1000BASE-T Gigabit Ethernet ATM 25 ATM 155 10BASE-T Ethernet TP-PMD Token Ring 4 Mbps and 16 Mbps 100BASE-T "Fast Ethernet" Broadband and Baseband Video 100BASE-T2 ISDN Basic and Primary Access 100BASE-T4 1BASE-5 Starlan 100BASE-TX ISALAN Token Ring 100 Mbps ITU V.21 ve X.11

Qualifications and Approvals

HCS DataLink 500A Cables are tested and verified for full compliance with the following standards:

Augmented Category 6 ScTP according to ANSI/TIA/568-C.2 Category 6A according to IEC 61156-5.

Benefits & Features

Exceptional transmission properties - suitable for 10GBE applications on 100m channels. Testing every reel of cable prior to shipment - providing the highest degree of quality assurance. Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. High ACR values - providing low BER (Bit-Error-Rate) in all applications. Extremely high pair-balance, individual and overall foil shields - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Revolutionary pair lay scheme - providing an extremely low delay skew. Batch number printed every meter - providing fast retrieval of test results from data-base. Unique DoubleSafe™ Quality Assurance Program providing lowest rejection rate available.

Physical and Mechanical Properties

4 color-coded, individually foil-shielded twisted pairs cabled together, overall shielded with tin-coated copper braid and overall jacketed.Siamese (Figure-8) cables are made of two identical 4-pair cables connected in a zip-cord formation, one cable identified with two raised ribs on the jacket surface.

64 www.hescs.com

Page 61: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Augmented Category 6 S/FTP 100 Ohm Horizontal LAN Cables

65

Characteristic Impedance 100±6 Ohm @ 1-500 MHz

DC Resistance 72 Ohm/Km max.

Resistance unbalance 2% max.

Capacitance 45 pF/m nom. @ 1 KHz

Cap. Unbalance (wire to ground) 1500 pF/Km max. @ 1 KHz.

Voltage rating 72 Vdc max.

Dielectric strength 1500 Volts/1 minute min rms

Velocity of Propagation (NVP) 78-80%

Propagation Delay Skew 45 nS/100m max @ 1-500 MHz

Insulation Resistance 5000 MegaOhm•Km min. @ 500 Vdc

Coupling attenuation 85 dB min @ 30-100 MHz 85-20Log(f/100) @100-500 MHz

Transfer Impedance 50 mOhm/m max @ 1 MHz.

100 mOhm/m max @ 10 MHz.

200 mOhm/m max @ 30 MHz.

1000 mOhm/m max @ 100 MHz.

Ordering Information

HCS P/N Description ODmm

WeightKg/Km

Cal. ValeueKj/m Packaging Notes

H6A-00451-DK 4x2x23# S/FTP CAT 6A PVC Grey 7.0 50 650 305m Drum -H6A-00451-DP 4x2x23# S/FTP CAT 6A PVC Grey 7.0 50 650 500m Drum -H6A-00451-DM 4x2x23# S/FTP CAT 6A PVC Grey 7.0 50 650 1000m Drum -H6A-00452-DK 4x2x23# S/FTP CAT 6A LS0H Grey 7.0 50 655 305m Drum -H6A-00452-DP 4x2x23# S/FTP CAT 6A LS0H Grey 7.0 50 655 500m Drum -H6A-00452-DM 4x2x23# S/FTP CAT 6A LS0H Grey 7.0 50 655 1000m Drum -H6A-00853-DP 2x(4x2x23#) S/FTP CAT 6A PVC Grey 7.0x14.1 100 1300 500m Drum FIG-8H6A-00853-DM 2x(4x2x23#) S/FTP CAT 6A PVC Grey 7.0x14.1 100 1300 1000m Drum FIG-8H6A-00854-DP 2x(4x2x23#) S/FTP CAT 6A LS0H Grey 7.0x14.1 100 1310 500m Drum FIG-8H6A-00854-DM 2x(4x2x23#) S/FTP CAT 6A LS0H Grey 7.0x14.1 100 1310 1000m Drum FIG-8

Note: Standard jacket color: Light Gray RAL 7035. Other colors available upon request.

Typical NEXT Loss Typical Return Loss

Transmission and Electrical Specifications

1 2.08 75.30 73.30 68.00 65.00 20.00 570.00 40.00 35.00 67.00 67.00 10 5.93 60.30 58.30 48.00 45.00 25.00 545.38 40.00 15.00 67.00 58.20 20 8.38 55.78 53.78 41.98 38.98 25.00 542.05 36.99 8.98 67.00 52.18 25 9.38 54.33 52.33 40.04 37.04 24.32 541.20 36.02 7.04 67.00 50.24 30 10.29 53.14 51.14 38.46 35.46 23.77 540.57 35.23 5.46 67.00 48.66 62.5 14.99 48.36 46.36 32.08 29.08 21.54 538.55 32.04 NS 65.56 42.28 100 19.14 45.30 43.30 28.00 25.00 20.11 537.60 30.00 NS 62.50 38.20 200 27.58 40.78 38.78 21.98 18.98 18.00 536.55 26.99 NS 57.98 32.18 250 31.07 39.33 37.33 20.04 17.04 17.32 536.28 26.02 NS 56.53 30.24 300 34.27 38.14 36.14 18.46 15.46 17.30 536.08 25.23 NS 55.34 28.66 400 40.05 36.27 34.27 15.96 12.96 17.30 535.80 23.98 NS 53.47 26.16 500 45.26 34.82 32.82 14.02 11.02 17.30 535.61 23.01 NS 52.02 24.22

FREQ.

MHz

Insertion Loss

dB/100m

Max

PS NEXTLoss

NEXTLoss

dB dB

Min Min Min

dB/100m

Min

dB/100m

PSANEXT

PSAACR-F

Max

dB

Min

dB

Min

dB

Min

dB

Min

dB

Min

RLProp.Delay

nS/100m

TCL EL-TCLACR- F PS ACR-F

www.hescs.com

Page 62: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Category 7+ S/FTP 100 Ohm Horizontal LAN CablesTested to 1000 MHz

Description

HCS DataLink 600 CAT 7+ cable series consists of 100 Ohm impedance, 4-pair and 8-pair S/FTP cables for horizontal installations in local area networks (LANs). All cables fully conform to and provide a substantial margin above all Category 7 requirements of IEC 61156-5 (Specified in ISO/IEC 11801) and are tested up to 1000MHz.

Applications

HCS DataLink 600 CAT 7+ Horizontal cables support all presently available and future LAN applications, including the following protocols:

Broadband Digital and Analog CATV signals up to 1000 MHz Token Ring 100 Mbps SOHO and multiple simultaneous applications on all 4 pairs ATM 52 10GBASE-T 10 Gigabit Ethernet ATM 25 1000BASE-T 1 Gigabit Ethernet 10BASE-T Ethernet ATM 155 Token Ring 4 Mbps and 16 Mbps TP-PMD Broadband and Baseband Video 100BASE-T Fast Ethernet ISDN Basic and Primary Access 100BASE-T2 1BASE-5 Starlan 100BASE-T4 ISALAN 100BASE-TX ITU V.21 ve X.11

Qualifications and Approvals

HCS DataLink 600 CAT 7+ Cables are tested and verified for full compliance with the following standards:

IEC 61156-5 (ISO/IEC-11801) CENELEC EN 50288-4

Qualifications and Approvals

Exceptional transmission properties - suitable for 10GBE applications on 100m channels. Testing every reel of cable prior to shipment - providing the highest degree of quality assurance. Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. High ACR values - providing low BER (Bit-Error-Rate) in all applications.  Extremely high pair-balance and double shield - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation, maximizing noise immunity and preventing any alien-crosstalk (AXT). Revolutionary pair lay scheme - providing an extremely low delay skew.  Descending sequential meter mark - providing easy stock and left-over handling. Smooth and rigid jacket - proving fast and easy cable pulling and installation. Batch number printed every meter - providing fast retrieval of test results from data-base. A comprehensive product range - providing all state-of-the-art cable constructions. Large variety of packaging options - providing minimum scrap and left-over cable sections. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available. Full compliance with EU Directive 2002/95/CE (RoHS).

Physical and Mechanical Properties

4 color-coded, individually foil shielded twisted pairs cabled together, overall shielded with a tin-coated copper braid and overall jacketed. Siamese (Figure-8) cables are made of two identical 4-pair cables connected in a zip-cord formation, one cable identified with two raised ribs on the jacket surface.

Basic Conductor Solid, 23AWG, bare annealed copper

Insulation Polyolefin

Number of insulated conductors 8, twisted in 4 pairs. (8 pairs in FIG-8 cables)

Color Code of Pairs Blue x White, Orange x White, Green x White, Brown x White.

Individual pair shield Polyester-aluminum foil (foil face out), providing 100% coverage.

Overall shield Tin coated copper braid laid in close contact over the inner foils.

Outer Jacket LS0H Halogen free flame retardant or PVC compound.

Standard Jacket Color Light Gray RAL 7035. Other colors available upon request.

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number.

Pulling force 50 N/mm2 max.

Short Term Bend Radius 8xOD mm

Long Term Bend Radius 4xOD mm

Storage Temperature -20 to +60C

Temperature operating range -20 to +60C

Installation temperature range 0 to +50C

Flame Test IEC 60332-1, IEC 60332-3-24 or IEC 60332-3-25.

Halogen content in LS0H cables IEC 60754 (gas) & IEC 61034 (smoke)

66 www.hescs.com

Page 63: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Category 7+ S/FTP 100 Ohm Horizontal LAN Cables Tested to 1000 MHz

Characteristic Impedance 100±5 Ohm @ 1-1000 MHz

DC Resistance 72 Ohm/Km max.

Resistance unbalance 2% max.

Capacitance 45 pF/m nom. @ 1 KHz

Cap. Unbalance (wire to ground)  1500 pF/Km max. @ 1 KHz.

Voltage rating 72 Vdc max.

Dielectric strength 700 Volts/1 minute min rms

Velocity of Propagation (NVP) 77-80%

Propagation delay 500 + 36/f1/2 @ 1-1000 MHz.

Delay Skew 25 nS/100m max @ 1-1000 MHz.

Insulation Resistance 5000 MegaOhm•Km min. @ 500 Vdc

Coupling attenuation 85 dB min @ 30-100 MHz  85-20Log(f/100) @100-600 MHz

Screening Attenuation 60 dB min @ 30-600 MHz

Transfer Impedance 10 mOhm/m max @ 1-30 MHz 30 MOhm/m max @ 30-100 MHz

Ordering Information

HCS P/N Description ODmm

WeightKg/Km

Cal. ValueKj/m Packaging Notes

H07-F0411-DP 4x2x23# S/FTP CAT 7+ PVC Grey, Tested to 1000 MHz 7.0 48 660 500m Drum

H07-F0411-DM 4x2x23# S/FTP CAT 7+ PVC Grey, Tested to 1000 MHz 7.0 48 660 1000m Drum

H07-F0412-DP 4x2x23# S/FTP CAT 7+ LS0H Grey, Tested to 1000 MHz 7.0 48 660 500m Drum

H07-F0412-DM 4x2x23# S/FTP CAT 7+ LS0H Grey, Tested to 1000 MHz 7.0 48 660 1000m Drum

H07-F0813-DP 2x(4x2x23#) CAT 7+ S/FTP PVC Grey,Tested to 1000 MHz 7.0x14.2 100 1320 500m Drum FIG-8

H07-F0813-DM 2x(4x2x23#) CAT 7+ S/FTP PVC Grey,Tested to 1000 MHz 7.0x14.2 100 1320 1000m Drum FIG-8

H07-F0814-DP 2x(4x2x23#) CAT 7+ S/FTP LS0H Grey, Tested to 1000 MHz 7.0x14.2 100 1320 500m Drum FIG-8

H07-F0814-DM 2x(4x2x23#) CAT 7+ S/FTP LS0H Grey, Tested to 1000 MHz 7.0x14.2 100 1320 1000m Drum FIG-8

Flame Test conformance F=0: IEC 60332-1 F=C: IEC 60332-3-24 F=D: IEC 60332-3-25

Note: Standard jacket color: Light Gray RAL 7035. Other colors available upon request.

67

Transmission Properties and Electrical Specifications

1 NS 78.0 75.0 78.0 75.0 20.0 40.0 35.0 67.0 67.0

4 3.74 78.0 75.0 83.3 80.3 23.0 40.0 23.0 67.0 67.0

8 5.24 78.0 75.0 77.2 74.2 24.5 40.0 16.9 67.0 67.0

10 5.86 78.0 75.0 75.3 72.3 25.0 40.0 15.0 67.0 67.0

16 7.41 78.0 75.0 71.2 68.2 26.0 38.0 10.9 67.0 67.0

20 8.29 78.0 75.0 69.3 66.3 25.0 37.0 9.0 67.0 67.0

25 9.29 78.0 75.0 67.3 64.3 24.3 36.0 7.0 67.0 65.2

31.25 10.41 78.0 75.0 65.4 62.4 23.6 35.1 5.1 67.0 63.3

62.5 14.88 75.5 72.5 59.4 56.4 21.5 32.0 NS 67.0 57.3

100 19.02 72.4 69.4 55.3 52.3 20.1 30.0 NS 67.0 53.2

150 23.56 69.8 66.8 51.8 48.8 18.9 28.2 NS 67.0 49.7

200 27.47 67.9 64.9 49.3 46.3 18.0 27.0 NS 67.0 47.2

250 30.97 66.4 63.4 47.3 44.3 17.3 26.0 NS 67.0 45.2

300 34.19 65.2 62.2 45.8 42.8 17.3 NS NS 67.0 43.7

400 40.01 63.4 60.4 43.3 40.3 17.3 NS NS 67.0 41.2

500 45.26 61.9 58.9 41.3 38.3 17.3 NS NS 67.0 39.2

600 50.10 60.7 57.7 39.7 36.7 17.3 NS NS 65.8 37.6

700 54.63 59.7 56.7 38.4 35.4 16.6 NS NS 64.8 36.3

800 58.92 58.9 55.9 37.2 34.2 16.1 NS NS 64.0 35.1

1000 66.93 57.4 54.4 35.3 32.3 15.1 NS NS 62.5 33.2

Note: Values above 600Mhz are nominal,for reference only

FREQ.

MHz

Insertion Loss

dB/100m

Max

NEXTLoss

dB

Min

PS NEXTLoss

dB

Min

PSANEXT

dB

Min

PSAFEXT

dB

MinMin

dB/100m

ELFEXT

Min

dB/100m

PS ELFEXT

dB

Min

RL

dB

Min

TCL

dB

Min

EL-TCTL

www.hescs.com

Page 64: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Category 7+ S/FTP 100 Ohm Horizontal LAN Cables Tested to 1200 MHz

Description

HCS DataLink 600 CAT 7+ kablo serisi; 100 Ohm empedansda, yatay yapısal kablolama sistemleri için kulanılmakta olan 4 ve 8 perli S/FTP kabloları kapsamaktadır. Tüm DataLink 600 serisi kablolar, IEC 61156-5 (ISO/IEC 11801) standardının gereksinimlerinin çok üzerinde bir performans sergilemekte ve 1200 MHz’e kadar test edilmektedirler.

Qualifications and Approvals

HCS DataLink 600 CAT 7+ yatay kablolar aşa¤ıdaki standartlara göre tamamen test edilip onaylanmıştır:

IEC 61156-5 (ISO/IEC-11801) CENELEC EN 50288-4

Benefits & Features

Ola¤anüstü iletim de¤erleri - 100 metre uç tan uca kanal (Channel) uygulamalarında 10GBE'yi destekler. Sevkiyat öncesi her makara veya kutu kablonun tek tek test edilmesi - En üst düzey kalite güvencesini sa¤lar. Ola¤anüstü malzeme özellikleri ve kablo dizaynı - Benzersiz Century™ Ömür Boyu Garanti sa¤lar. Yüksek ACR de¤erleri - Tüm uygulamalarda en düşük veri kayıp oranını sa¤lar.  Oldukça yüksek per dengesi ve çift folyolu yapı - kablodan dışarı sızan ışımayı minimize, gürültü ba¤ışıklı¤ını maksimize ederek mükemmel Elektro Manyetik Uyumluluk (EMC) sa¤lar. Aynı zamanda Alien Crosstalk (AXT)'un da oluşmasına engel olur. Benzersiz per yayma dizaynı - perler arasındaki sinyal gecikmesini minimize eder. Kolay anlaşılabilen ve ayırdedilebilen renk kodlaması - perlerin kolayca ayrıştırılabilmesini sa¤lar ve kablonun sonlandırılmasını kolaylaştırır. Aşa¤ı do¤ru azalan ardışık metraj bilgisi- Kolay stok ve kablo kalan miktarı takibi sa¤lar. Pürüzsüz ve rijit dış kılıf- Kablonun kutusundan kolay ve hızlı çekilmesi ve kurulmasına yardımcı olur. Metraj bilgisinde yer alan parti numarası- Kabloya ait test sonucuna veri tabanımızdan ulaşılmasını sa¤lar. Oldukça geniş ürün yelpazesi - En son teknoloji ürünü tüm kablo konstrüksiyonlarını mevcut kılar. Alternatifli paketleme imkanı - kablonun en verimli kullanılması ve atık kablo oranının en az olmasını sa¤lar. Benzersiz DoubleSafe™ Kalite Güvence Programı - ürün iade oranının minimize edilmesini sa¤lar. 2002/95/CE (RoHS) AB Direktiflerine tam uyumludur.

Physical and Mechanical Properties

4 adet renk kodlu, ayr› ayr› folyolanm›ş bükümlü perler birlikte kablolaşt›r›lm›ş, kalay kapl› bak›r saç örgü ile kaplanm›ş ve k›l›flanm›şt›r. Siamese (Fig-8) kablolar iki özdeş kablonun "fermuar" şeklinde birleştirilmesiyle imal edilmektedirler.Kabloların bir tanesinde dış kılıf üzerinde yer alan çıkıntı ile kablonun sonlandırma yapılırken do¤ru tarafta sonlandırılması sa¤lanmış olur.

Applications

HCS DataLink 600 CAT 7+ yatay kablolar, günümüzde mevcut ve gelecekteki muhtemel LAN uygulamalarını aşa¤ıdaki protokoller de dahil olmak üzere desteklemektedir:

1200 MHz’e kadar Broadband Dijital ve Analog CATV sinyalleri Token Ring 100 Mbps SOHO ve tüm 4 perde çift simultane uygulama ATM 52 10GBASE-T 10 Gigabit Ethernet ATM 25 1000BASE-T 1 Gigabit Ethernet 10BASE-T Ethernet ATM 155 Token Ring 4 Mbps ve 16 Mbps TP-PMD Broadband ve Baseband Video 100BASE-T Fast Ethernet ISDN Basic ve Primary Access 100BASE-T2 1BASE-5 Starlan 100BASE-T4 ISALAN 100BASE-TX ITU V.21 ve X.11

Temel ‹letken Kat›, 23AWG, tavl› ç›plak bak›r.

‹zolasyon Polyolefin

‹zole ‹letken Say›s› 8, bükülmüş 4 per halinde (Fig-8 kablolarda 16 izole iletken, 8 per halinde).

Perlerin Renk Kodlar› Mavi x Beyaz, Turuncu x Beyaz, Yeşil x Beyaz, Kahverengi x Beyaz.

Per folyosu Polyester-alüminyum folyo (folyo yüzü d›ş tarafa), %100 koruma sa¤lar.

D›ş Folyo (Blendaj) Per folyolar›yla yak›n temasta kalay kapl› bak›r saç örgü.

D›ş K›l›f LS0H (Halogen free) alev geciktirmeli veya PVC bileşen.

Standart D›ş K›l›f Rengi Aç›k Gri RAL 7035. ‹stenirse di¤er renkler mevcuttur.

Standart kablo yaz› bilgisi HCS Ürün kodu, kablo tan›mlamas›, metraj bilgisi ve parti numaras›.

Çekme kuvveti 50 N/mm2 maks.

Bükülme yar›çap› (kurulum (k›sa dönem)) 8xKablo d›ş çap› (mm).

Bükülme yar›çap› (kullan›m (uzun dönem)) 4xKablo d›ş çap› (mm).

Depolama S›cakl›¤› -20 / +80C

Çal›şma S›cakl›¤› -20 / +60C

Kurulum (Enstelasyon) S›cakl›¤› 0 / +50C

Alev Testi IEC 60332-1, IEC 60332-3-24 veya IEC 60332-3-25

LS0H kablolarda halojen miktar› IEC 60754 (gaz) & IEC 61034 (duman)

68 www.hescs.com

Page 65: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Category 7+ S/FTP 100 Ohm Horizontal LAN Cables Tested to 1200 MHz

Empedans Karakteristi¤i 100±5 Ohm @ 1-1200 MHz

DC Direnci 72 Ohm/Km maks.

Direnç Dengesizli¤i 2% maks.

Kapasitans 45 pF/m nom. @ 1 KHz

Kapasitans Dengesizli¤i (topra¤a göre) 1500 pF/Km maks. @ 1 KHz.

Voltaj 72 Vdc maks.

Dielektrik Kuvvet 700 Volt/1 dakika min rms

Sinyal Hızı (NVP) 77-80%

Sinyal ‹letim Süresi (Prop. Delay) 500+36/f1/2 @ 1-1200 MHz.

Perler Arası Sinyal Gecikmesi (Skew) 25 nS/100m maks @ 1-1200 MHz.

‹zolasyon Direnci 5000 MegaOhm•Km min. @ 500 Vdc

Birleşim Zayıflaması 85 dB min @ 30-100 MHz  85-20Log(f/100) @100-600 MHz

Ekranlama Zayıflaması 60 dB min @ 30-600 MHz

Transfer Empedansı 10 mOhm/m maks @ 1-30 MHz 30 MOhm/m maks @ 30-100 MHz.

Ordering Information

Description ODmm

WeightKg/Km

Cal. ValueKj/m Packaging

H07-F0421-DP 4x2x23# S/FTP CAT 7+ PVC Gri, 1200 MHz 7.0 48 660 500m Makara  

H07-F0421DM 4x2x23# S/FTP CAT 7+ PVC Gri, 1200 MHz 7.0 48 660 1000m Makara  

H07-F0422-DP 4x2x23# S/FTP CAT 7+ LS0H Gri, 1200 MHz 7.0 48 660 500m Makara  

H07-F0422-DM 4x2x23# S/FTP CAT 7+ LS0H Gri,1200 MHz 7.0 48 660 1000m Makara  

H07-F0823-DP 2x(4x2x23#) S/FTP CAT 7+ PVC Gri, 1200 MHz 7.0x14.2 100 1320 500m Makara FIG-8

H07-F0823-DM 2x(4x2x23#) S/FTP CAT 7+ PVC Gri,1200 MHz 7.0x14.2 100 1320 1000m Makara FIG-8

H07-F0824-DP 2x(4x2x23#) S/FTP CAT 7+ LS0H Gri, 1200 MHz 7.0x14.2 100 1320 500m Makara FIG-8

H07-F0824-DM 2x(4x2x23#) S/FTP CAT 7+ LS0H Gri,1200 MHz 7.0x14.2 100 1320 1000m Makara FIG-8

Flame Test Conformance F=0: IEC 60332-1 F=C: IEC 60332-3-24 F=D: IEC 60332-3-25

Not: Standart dış kılıf rengi: Açık Gri RAL 7035. Di¤er renkler iste¤e ba¤lı olarak sa¤lanabilir.

69

Transmission Properties and Electrical Specifications

1 NS 78.0 75.0 78.0 75.0 20.0 40.0 35.0 67.0 67.0

4 3.75 78.0 75.0 83.1 80.1 23.0 40.0 23.0 67.0 67.0

10 5.82 78.0 75.0 75.1 72.1 25.0 40.0 15.0 67.0 67.0

20 8.21 78.0 75.0 69.1 66.1 25.0 37.0 9.0 67.0 67.0

25 9.18 78.0 75.0 67.1 64.1 24.3 36.0 7.0 67.0 65.2

31.25 10.26 78.0 75.0 65.2 62.2 23.6 35.1 5.1 67.0 63.3

62.5 14.57 78.0 75.0 59.2 56.2 21.5 32.0 NS 67.0 57.3

100 18.53 75.4 72.4 55.1 52.1 20.1 30.0 NS 67.0 53.2

200 26.47 70.9 67.9 49.1 46.1 18.0 27.0 NS 67.0 47.2

250 29.73 69.4 66.4 47.1 44.1 17.3 26.0 NS 67.0 45.2

300 32.69 68.2 65.2 45.6 42.6 17.3 NS NS 67.0 43.7

400 38.01 66.4 63.4 43.1 40.1 17.3 NS NS 67.0 41.2

500 42.76 64.9 61.9 41.1 38.1 17.3 NS NS 67.0 39.2

600 47.10 63.7 60.7 39.5 36.5 17.3 NS NS 65.8 37.6

700 51.13 62.7 59.7 38.2 35.2 16.6 NS NS 64.8 36.3

800 54.92 61.9 58.9 37.0 34.0 16.1 NS NS 64.0 35.1

1000 61.93 60.4 57.4 35.1 32.1 15.1 NS NS 62.5 33.2

1200 68.36 59.2 56.2 33.5 30.5 14.3 NS NS 61.3 31.6

Not: 600 MHz üzerindeki de¤erler referans için verilmiştir.

FREQ.

MHz

Insertion Loss

dB/100m

Max

NEXTLoss

dB

Min

PS NEXTLoss

dB

Min

PSANEXT

dB

Min

PSAFEXT

dB

MinMin

dB/100m

ELFEXT

Min

dB/100m

PS ELFEXT

dB

Min

RL

dB

Min

TCL

dB

Min

EL-TCTL

HCS P/N Notes

www.hescs.com

Page 66: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

4-Pair and 2-Pair Category 5e Unshielded RJ-45 to TELCO Copper Patch Panels

Description

HCS DataLink unshielded copper RJ-45 to TELCO patch panel series includes high performance 24-Port and 48-Port Category 5e panels specially designed for data-centers for structured premise cabling in local area networks (LANs).HCS RJ-45 to TELCO patch panels are available in two optional configurations:- 4-Pair CAT 5e RJ-45 to TELCO panels provide one TELCO back interconnection 25 Pair block for each module of 6 RJ-45 ports, ready for 25 Pair TELCO patch-cords (RJ-21). This configuration supports all CAT 5e applications, including 1GBASE-T.- 2-Pair CAT 5e RJ-45 to TELCO panels provide one TELCO back interconnection 25 Pair block for each two modules of 6 RJ-45 ports, ready for 25 Pair TELCO patch-cords (RJ-21). In this configuration, only two pairs in each RJ-45 port are terminated: Pins 1-2 and 3-6, providing 10BASE-T and 100BASE-TX support only.All panels fully conform to and provide a substantial margin above all ANSI/TIA/568-C.2 Category 5e, CENELEC EN 50173 and ISO/IEC-11801 (2nd Edition) requirements.The HCS Logo and the DataLink 100e Trademark ensure long lasting high-performance and full support of all relevant applications, including 1000BASE-T (Gigabit-Ethernet).

Qualifications and Approvals

HCS DataLink 100e panels are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling system.HCS DataLink 100e panels comply to the following standards:

General Properties

Transmission EMC Safety

ANSI/TIA/568-C.2 ISO/IEC-11801 (2nd Edition)

EN-55022, Class B (Europe) FCC Part 15, Subpart J, Class A (USA)

UL94 V-0 rated plastic materials Zero-halogen in LS0H constructions.

Applications

HCS DataLink 100e unshielded copper RJ-45 to TELCO patch panels are used mainly in data-centers and telecommunications rooms and they fully support all relevant LAN applications, including the following protocols:

1000BASE-T Gigabit Ethernet 100BASE-TX Broadband and Baseband Video ATM 155 Token Ring 100 Mbps ISDN Basic and Primary Access TP-PMD ATM 52 1BASE-5 Starlan 100BASE-T Fast Ethernet ATM 25 ISALAN 100BASE-T2 10BASE-T Ethernet ITU V.21 and X.11 100BASE-T4 Token Ring 4 Mbps and 16 Mbps

Benefits & Features

Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Detailed installation manual in English and Turkish - providing clear and comprehensive instructions. Exceeding Category 5e performance - providing full support to Gigabit Ethernet. High quality metal casing - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Robust and installer-friendly design and Printed labels for port identification - providing reduced installation and operating costs. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

Material of construction Galvanized Steel.

Paint and standard color Black, Powder paint finish or plastic front.

Connector module holder High impact, Flame-retardant plastic compound, UL 94 V-0.

Housing material - Jack & IDC High impact FR plastic rated UL 94 V-0. 

Jack spring contact coating 1.27µm (50µ-Inch) hard Gold over 2.54µm (100µ-Inch) Nickel plating.

Plug Retention Force 14 Kgf (140N) min.

Plug to jack contact force 100 grams min. (using HCS approved plug).

Plug insertion durability 750 mating cycles

Storage temperature range -40 to +70C

Operation conditions -20 to +60C at 0-90% RH (Non condensing)

Packaging One unit per box.

70 www.hescs.com

Page 67: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

4-Pair and 2-Pair Category 5e Unshielded RJ-45 to TELCO Copper Patch Panels

Propagation Delay 2.5 nS max @ 1-100 MHzPropagation Delay Skew  1.25 nS max @ 1-100 MHzAkım 1.5 A max.Contact resistance  20 mOhm max (per contact)Input/Output resistance  200 mOhm maxInput/Output resistance Unbalance 50 mOhm maxVoltage rating 72 Vdc maxDielectric strength 1000 Volts rms for 1 minuteInsulation Resistance 500 MegaOhm min @ 500 VdcDC Resistance 0.1 Ohm max @ 20CTCL 28-20·Log(f/100) dB min @ 1-100 MHzTransfer Impedance N/A

Typical NEXT Loss Typical Return Los

Typical Test Results at the Component Level

Ordering Information

HCS P/N Panels Description TELCOBlocks Units

mm

SizeNotes

P5E-T2401-1U 24 port RJ-45 to TELCO Unshielded CAT5e 19" Panel 4 1u 43.7x482.6 1.75x19 - 

P5E-T4801-2U 48 port RJ-45 to TELCO Unshielded CAT5e 19" Panel 8 2u 87.4x482.6 3.44x19 - 

P5E-T2402-2U 24 port RJ-45 to TELCO Unshielded 2P 19" Panel 2 2u 43.7x482.6 3.44x19 - 

P5E-T4802-2U 48 port RJ-45 to TELCO Unshielded 2P 19" Panel 4 2u 87.4x482.6 3.44x19 - 

inch

HCS P/N Modular Cords Description Plugs Length Notes

T5E-T02510-XX 25x2x24# UTP CAT 5e PVC RJ21 modular Cord Grey TELCO XXm - 180° to 180°T5E-T02520-XX 25x2x24# UTP CAT 5e LS0H RJ21 modular Cord Grey TELCO XXm - 180° to 180°T5E-T02530-XX 25x2x24# UTP CAT 5e PVC RJ21 modular Cord Grey TELCO XXm - 110° to 180°T5E-T02540-XX 25x2x24# UTP CAT 5e LS0H RJ21 modular Cord Grey TELCO XXm - 110° to 180°T5E-T02550-XX 25x2x24# UTP CAT 5e PVC RJ21 modular Cord Grey TELCO XXm - 110° to 110°T5E-T02560-XX 25x2x24# UTP CAT 5e LS0H RJ21 modular Cord Grey TELCO XXm - 110° to 110°

71

Transmission and Electrical Specifications Typical Return Loss (Forward, Component Level)

1.00 0.02 0.10 85.0 65.0 77.0 65.0 55.0 30.0

4.00 0.03 0.10 75.0 65.0 65.0 63.1 50.0 30.0

8.00 0.04 0.11 70.0 64.9 60.0 57.0 48.0 30.0

10.00 0.04 0.13 68.0 63.0 58.0 55.1 42.0 30.0

16.00 0.05 0.16 64.0 58.9 54.0 51.0 40.0 30.0

25.00 0.06 0.20 60.0 55.0 50.0 47.1 35.0 30.0

31.25 0.07 0.22 58.0 53.1 48.0 45.2 33.0 30.0

62.50 0.11 0.32 52.0 47.1 42.0 39.1 28.1 24.1

100.00 0.15 0.40 45.0 43.0 38.0 35.1 24.0 20.0

Nom Nom Nom NomMin Min MinMaxdB dB dB dB

Insertion Loss NEXT FEXT RL

MHz

Frequency

www.hescs.com

Page 68: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Benefits & Features

Category 5e Unshielded RJ-45 to iPass Pre-Terminated Copper Patch Panels

Açıklama

Uygulamalar

HCS DataLink unshielded copper RJ-45 to iPass patch panel series includes high performance 24-Port and 48-Port Category 5e panels specially designed for data-centers and structured premise cabling in local area networks (LANs). HCS iPass to RJ-45 patch panels consist of 12-port (4 x 6) or 12-port preterminated cassettes loaded into a 1U Rack Mount Enclosure. The cassettes slide easily in and out of the panels, allowing fast installation. The Simple cassette design allows for fast upgrades or expansion of systems with minimum installation time. All cassettes are 100% factory tested, enabling flexible configuration and cost effective installation, while minimizing the need for on-site testing. 6-port cassettes have one iPass port, 12-port cassettes have two iPass Ports. Pre-terminated iPass to iPass 25 pair Category 5e cables (1-90 meter length) can be connected to iPass ports at the back side of cassettes. All panels fully conform to and provide a substantial margin above all ANSI/TIA-568-C.2 Category 5e, CENELEC EN 50173 and ISO/IEC-11801 (2nd Edition) requirements. The HCS Logo and the DataLink 100e Trademark ensure long lasting high-performance and full support of all relevant applications up to 1000BASE-T (Gigabit-Ethernet).

Nitelikler ve Onaylar

HCS DataLink 100e panels are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling system.HCS DataLink 100e panels comply to the following standards:

Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Detailed installation manual in English and Turkish - providing clear and comprehensive instructions. Exceeding Category 5e performance - providing full support to Gigabit Ethernet. High quality metal casing - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Robust and installer-friendly design - providing reduced installation and operating costs Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

General Properties : Panel & Cassettes

Transmission EMC Safety

ANSI/TIA-568-C.2 ISO/IEC-11801 (2nd Edition)

EN-55022, Class B (Europe) FCC Part 15, Class A (USA)

UL94 V-0 plastic materials Zero-halogen in LS0H constructions.

HCS DataLink 100e unshielded copper RJ-45 to iPass patch panels are used mainly in data-centers and telecommunications rooms and they fully support the following protocols

1000BASE-T (Gigabit-Ethernet) 100BASE-TX Broadband and Baseband Video ATM 155 Token Ring 100 Mbps ISDN Basic and Primary Access TP-PMD ATM 52 1BASE-5 Starlan 100BASE-T Fast Ethernet ATM 25 ISALAN 100BASE-T2 10BASE-T Ethernet ITU V.21 and X.11 100BASE-T4 Token Ring 4 Mbps and 16 Mbps

Material of construction Cold rolled steel, 1.5 mm thickness

Paint and standard color Black, Powder paint finish or plastic front.

Storage temperature range -40 to +70C

Operation conditions -20 to +60C at 0-90% RH (Non condensing)

Packaging One unit per box.General Properties: Cassettes RJ-45 receptables

Housing material Thermoplastic Rated UL94 V-0.

Jack spring contact coating 1.27µm (50µ-Inch) hard Gold over 2.54µm (100µ-Inch) Nickel plating

Plug Retention Force 49N minimum.

Plug to jack contact force 100 grams min. (using HCS approved plug).

Plug insertion durability 750 mating cycles

General Properties: Cassettes iPass receptablesHousing material Zinc AlloyContact Material Copper AlloyContact Plating 1.27µm (50µ-Inch) hard Gold over 2.54µm (100µ-Inch) Nickel platingInsertion Force 60 N

General Properties – Distribution Cable AssemblyConductor size 24AWG solid bare copperMAX OD 12.7mmJacket PVC or LS0HTemperature range -20 to +60C at 0-90% RH (Non condensing)Flame Performance Conforming to IEC 60332-1General Properties – iPass Plug Connector

Housing Zinc AlloyContact Material FR4 PCBContact Pad Plating PVC or LS0HInsertion Force 1.27µm (50µ-Inch) hard Gold over 2.54µm (100µ-Inch) Nickel platingFlame Performance 60 N

72 www.hescs.com

Page 69: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

73

Typical NEXT Loss Typical Return Loss

Propagation Delay 2.5 nS max @ 1-100 MHz

Propagation Delay Skew  1.25 nS max @ 1-100 MHz

Current rating 1.5 A max.

Contact resistance  20 mOhm max (per contact)

Input/Output resistance  200 mOhm max

Input/Output resistance Unbalance 50 mOhm max

Voltage rating 72 Vdc max

Dielectric strength 1000 Volts rms for 1 minute

Insulation Resistance 500 MegaOhm min @ 500 Vdc

DC Resistance 0.1 Ohm max @ 20C

TCL 28-20.Log(f/100) dB min @ 1-100 MHz

Transfer Impedance N/A

Typical Test Results at the Component Level

Ordering Information

HCS P/N

HCS P/N

Panels DescriptionTELCOBlocks Units Notes

Modular Cords Description Plugs Length Notes

T5E-P02510-XX 25x2x24# UTP CAT 5e PVC iPass modular Cord Grey iPass XX m

T5E-P02520-XX 25x2x24# UTP CAT 5e LS0H iPass modular Cord Grey iPass XX m

P00-P0401-1U Unshielded empty patch panel, 19”, 1U, for 4xiPass cassettes insert - 1u - P5E-P0602-1U 6 port RJ-45 to iPass Unshielded 1000BASE-T 19” cassette 1 1u - P5E-P1202-1U 12 port RJ-45 to iPass Unshielded 1000BASE-T 19” cassette 2 1u -

Category 5e Unshielded RJ-45 to iPass Pre-Terminated Copper Patch Panels

Transmission and Electrical Specifications

1.00 0.02 0.10 85.0 65.0 77.0 65.0 55.0 30.0

4.00 0.03 0.10 75.0 65.0 65.0 63.1 50.0 30.0

8.00 0.04 0.11 70.0 64.9 60.0 57.0 48.0 30.0

10.00 0.04 0.13 68.0 63.0 58.0 55.1 42.0 30.0

16.00 0.05 0.16 64.0 58.9 54.0 51.0 40.0 30.0

25.00 0.06 0.20 60.0 55.0 50.0 47.1 35.0 30.0

31.25 0.07 0.22 58.0 53.1 48.0 45.2 33.0 30.0

62.50 0.11 0.32 52.0 47.1 42.0 39.1 28.1 24.1

100.00 0.15 0.40 45.0 43.0 38.0 35.1 24.0 20.0

Typical Return Loss (Forward, Component Level)

Nom Nom Nom NomMin Min MinMaXdB dB dB dB

Insertion Loss NEXT FEXT RL

MHz

Frequency

www.hescs.com

Page 70: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Benefits & Features

Category 6E Unshielded RJ-45 Copper Angled Patch Panels (Jacks)

Description

Applications

HCS DataLink 250E unshielded copper RJ-45 patch panel series includes high performance Enhanced Category 6 panels specially designed for structured premise cabling in local area networks (LANs).HCS DataLink 250E Angled Patch Panels are ideal for data-centers and installations of high density or which utilize extensive side and end-of-the-rack cable management.The angled feature provides enhanced port access and minimizes patch cord bend radius to the rack. The IDC section consists of V-shaped contacts that flex (not fatigue) when terminated. Each RJ45 port features a patented spring-loaded shutter and can be color coded to match jack outlets with the use of optional port icons. Offering both front and rear labeling options, the patch panel is constructed of cold-rolled steel for additional strength and durability.All panels fully conform to and provide a substantial margin above all ANSI/TIA/568-C.2 and ISO/IEC-11801 (2nd Edition) Category 6 component requirements, tested at the component level.The HCS Logo and the DataLink 250E Trademark ensure long lasting high-performance and full support of all relevant applications.

Qualifications and Approvals     HCS DataLink 250E panels are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling system.HCS DataLink 250 panels are tested at the component level and they comply to the following standards:

Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Detailed installation manual in English and Turkish - providing clear and comprehensive instructions. Exceeding Category 6 performance - providing full support to Gigabit Ethernet over Category 5e and Category 6 cabling systems. Robust and installer-friendly design - providing reduced installation and operating costs Compatible with 22-24 AWG solid conductors - providing support to a wider range of cabling types. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available. Each port features the patented spring-loaded shutter prevents incomplete mating & protects from dust and contaminants. Patented IDC V-shaped contacts that flex (not fatigue) when terminated. Features pointed IDC towers to speed termination and enhance cable retention. Dual color-coding allows for 568 A/B wiring configuration. Front and rear port labeling (port sequence 1–48) as well as panel identification label. 4 x 6 ganged jack configuration. Individually removable patch panel ports. Removable cable management shelves ensure bend radius compliance. Can be terminated using industry standard punch-down tools. RJ45 port which is RJ-11 compatible. Molded category identification on each port face as well as optional port identification icons.

General Properties    

Transmission EMC Safety

ANSI/TIA/568-C.2 ISO/IEC-11801

EN-55022, Class B (Europa) FCC Part 15, Subpart J, Class A (US)

UL94 V-0 rated plastic materials Zero-halogen in LS0H constructions.

HCS DataLink 250E unshielded copper RJ-45 Angled patch panels are mainly used for horizontal distribution or equipment terminations in data-centers, dense telecommunications rooms and for interconnection terminations in consolidation points, and they fully support all relevant LAN applications, including the following protocols:

1000BASE-T Gigabit Ethernet Token Ring 100 Mbps Token Ring 4 Mbps ve 16 Mbps ATM 155 ATM 52 Broadband & Baseband Video TP-PMD ATM 25 ISALAN 100BASE-T "Fast Ethernet" 10BASE-T Ethernet ITU V.21 ve X.11 100BASE-T2 ISDN Basic ve Primary Access 100BASE-TX 100BASE-T4 1BASE-5 Starlan

Wire size range 22 to 24 AWG, Solid conductors.

Material of construction CRS (Cold rolled steel), 1.5mm thickness.

Paint and standard color Black or Grey.

Plastic parts High impact, Flame-retardant plastic compound, UL 94 V-0.

Housing material - Jack & IDC High impact FR plastic rated UL 94 V-0.

Jack spring contact Phosphor Bronze with 50G" hard Gold over 100G" Nickel plating

Plug Retention Force 50N min.

Plug to jack contact force 100 grams min. (using HCS approved plug).

IDC terminations cycles 200 min.

IDC type Gas tight

Plug insertion durability 750 mating cycles

Storage temperature range -40 to +70C

Operation conditions -20 to +60C at 0-90% RH (Non condensing)

Packaging One unit per box.

74 www.hescs.com

Page 71: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Ordering Information

HCS P/N Description T568

P6E-02404-1U 24 port RJ-45 Unshielded Angled CAT 6E 19" Patch Panel 110 IDC 1U 44.5x483 1.75x19 UNI

P6E-04804-2U 48 port RJ-45 Unshielded Angled CAT 6E 19" Patch Panel 110 IDC 2U 89x483 3.5x19 UNI

Propagation Delay 2.5 nS max @ 1-250 MHz

Propagation Delay Skew  1.25 nS max @ 1-250 MHz

Current rating 1.5 A max.

Contact resistance  20 mOhm max (per contact) Initial Contact resistance: 2.5 mOhm.

Input/Output resistance  200 mOhm max

Input/Output resistance Unbalance 50 mOhm max

Voltage rating 72 Vdc max

Dielectric strength 1000 Volts rms for 1 minute

Insulation Resistance 100 MegaOhm min @ 500 Vdc

DC Resistance 0.1 Ohm max @ 20C

TCL 28-20·Log(f/100) dB min @ 1-250 MHz

Transfer Impedance N/A

Typical De-Embedded FEXT-Loss Typical De-Embedded Insertion-Loss

Blocks UnitsSize

mm Inch

75

Category 6E Unshielded RJ-45 Copper Angled Patch Panels (Jacks)

Typical De-Embedded Return-LossTransmission and Electrical Specifications

1.00 0.02 85.0 84.0 53.0

4.00 0.02 81.0 75.0 54.0

8.00 0.02 78.0 70.0 56.0

10.00 0.03 77.0 68.0 57.0

16.00 0.03 73.0 58.0 58.0

25.00 0.04 70.0 60.1 60.0

31.25 0.04 68.0 59.0 57.0

62.50 0.05 64.0 53.0 44.0

100.00 0.06 60.0 49.0 34.0

200.00 0.06 55.0 43.0 23.0

250.00 0.08 52.0 41.0 20.0

Min Min MinMaksdB dB dB dB

Insertion Loss NEXT FEXT RL

MHz

FREQ.

www.hescs.com

Page 72: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Blank Keystone-Jack Copper Patch Panels

HCS DataLink Blank RJ-45 Keystone-Jack Copper Patch Panels series includes high quality empty multi-port panels specially designed for structured premise cabling in local area networks (LANs).HCS DataLink blank panels are available with plastic or metal frames, with up to 48 ports and with standard or staggered form.The plastic-frame panels are recommended for use with unshielded jacks, while the metal-frame panels are recommended for use with shielded jacks, in order to provide continuous ground connection even when non-shielded cords are used.The HCS Logo and the DataLink Trademark ensure long lasting high-performance and full compatibilty with all HCS components.

Installation of copper cabling systems in horizontal or vertical environments. 

Description

Applications

76 www.hescs.com

Page 73: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Blank Keystone-Jack Copper Patch Panels

Material of construction - Metal Frame Steel, Aluminum, Aluminum Alloy or Anodized Aluminum.

Paint and Color - Metal Frame Powder paint finish, Black (Grey available upon request)

Connector module holder High impact, Flame-retardant plastic compound, UL 94 V-0.

Material of construction - Plastic Frame High impact, Flame-retardant plastic compound, UL 94 V-0. 

Packaging One unit per box. 

Environmental conditions -40 to +60C at 0-90% RH (Non condensing)

Storage Temperature -20 to +80C

Non Halogen constructions Available upon request.

Ordering Information

HCS P/N Descriptionmm

Size

InchUnshielded

Jack Compatibilty

ShieldedUnits

P00-01610-1U 16 port Keystone Jack Boş 19" Plastik Patch Panel  1u Evet Hayır 44.5x483 1.75x19

P00-01620-1U 16 port Keystone Jack Boş 19" Metal Patch Panel  1u Evet Evet 44.5x483 1.75x19

P00-02410-1U 24 port Keystone Jack Boş 19" Plastik Patch Panel  1u Evet Hayır 44.5x483 1.75x19

P00-02420-1U 24 port Keystone Jack Boş 19" Metal Patch Panel   1u Evet Evet 44.5x483 1.75x19

P00-02430-1U 24 port Keystone Jack Boş 19" Metal Patch Panel 1u Evet Hayır 44.5x483 1.75x19

P00-02450-1U 24 port Keystone Jack Boş 19" Metal Patch Panel   1u Evet Hayır 44.5x483 1.75x19

P00-02460-1U 24 port Keystone Jack Boş 19" Açılı Metal Patch Panel 1u Evet Hayır 44.5x483 1.75x19

P00-02470-1U 24 port Keystone Jack Boş 19" Açılı Metal Patch Panel 1u Evet Evet 44.5x483 1.75x19

P00-03210-2U 32 port Keystone Jack Boş 19" Plastik Patch Panel  2u Evet Hayır 89x483 3.5x19

P00-04810-2U 48 port Keystone Jack Boş 19" Plastik Patch Panel  2u Evet Hayır 89x483 3.5x19

P00-04810-1U 48 port Keystone Jack Boş 19" Plastik Patch Panel 1u Evet Hayır 44.5x483 1.75x19

P00-04820-1U 48 port Keystone Jack Boş 19" Plastik Patch Panel 1u Evet Evet 44.5x483 1.75x19

P00-04860-1U 48 port Keystone Jack Boş 19" Açılı Metal Patch Panel 1u Evet Hayır 44.5x483 1.75x19

P00-04870-1U 48 port Keystone Jack Boş 19" Açılı Metal Patch Panel 1u Evet Evet 44.5x483 1.75x19

Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Integrated full installation accessories ( supplied free of charge), including labels and icons, clip organizers and T-raps- providing a simple and elegant cable termination and identification. Optional plastic front panels - providing custom color selection. Detailed installation manual in English and Turkish - providing clear and comprehensive instructions. Optional back-side cable management with clip organizer and trap connection - providing simple and easy cable handling. High quality metal casing - providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation and maximizing noise immunity. Robust and installer-friendly design - providing reduced installation and operating costs Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

Benefits & Features

General Properties 

77www.hescs.com

Page 74: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Augmented Category 6 Cable Assemblies

Basic Cable Conductor Solid bare annealed copper

Wire Insulation Polyolefin Number of insulated conductors 8, twisted in 4 pairs.

Outer Jacket LS0H Halogen free flame retardant compound.

Standard Jacket Color Light Gray RAL 7035. Other colors available upon request.

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number.

Cable to jack tensile strength 1 Kgf (10N) min.

Pulling force 1 Kgf (10N) max.

Storage Temperature -20 to +80C

Durability 750 mating cycles

Bend radius 8xD.

Temperature operating range -20 to +60C

Flame Tests IEC 60332-1 or IEC 60332-3-24 (flame), IEC 60754 (gas) & IEC 61034 (smoke)

Benefits & Features

Testing every assembly prior to shipment -providing the highest degree of quality assurance. Custom-made designs -providing the exact assembly needed for every job and location. Unique LS0H sleeves -providing limp, easy to re-shape and install assemblies, ideal for data-centers. Exceptional material properties and cable design -providing the highest degree of reliability. High Return Loss and NEXT Loss values -providing low BER (Bit-Error-Rate) in all applications. Extremely high pair-balance and overall cable shield -providing excellent alien crosstalk loss and noise immunity. Revolutionary pair lay scheme -providing an extremely low delay skew. All Category 6A verified components -providing full backward compatibility and interoperability. 100% LS0H assemblies -providing safe usage in high-density and closed location. Unique DoubleSafe™ Quality Assurance Program providing lowest rejection rate available.

Qualifications and Approvals

HCS DataLink 500A Cable assemblies are 100% tested and verified for full compliance with the following standards:

Augmented Category 6 Permanent Link according to ANSI/TIA-568-C.2 Class EA Permanent Link according to ISO/IEC-11801 (2nd Edition) Class EA Permanent Link according to CENELEC EN 50173.

Applications

HCS DataLink 500A cable assemblies support all presently available LAN applications, including the following protocols:

10GBASE-T 10 Gigabit Ethernet ATM 52 1000BASE-T 1 Gigabit Ethernet ATM 25 ATM 155 10BASE-T Ethernet TP-PMD Token Ring 4 Mbps and 16 Mbps 100BASE-T “Fast Ethernet“ Broadband and Baseband Video 100BASE-T2 ISDN Basic and Primary Access 100BASE-T4 1BASE-5 Starlan 100BASE-TX ISALAN Token Ring 100 Mbps ITU V.21 ve X.11

Description

HCS DataLink 500A cable assemblies consist of custom-made LS0H pre-terminated 100 Ohm 4-pair LAN cables bundled together, designed for fast and easy installation in data-centers and other high-density locations.Full conformance to TIA-568-C Category 6A and ISO/IEC 11801 Class EA is guaranteed by the selection of Category 6A officially verified components and by 100% testing of each permanent link inside the bundle prior to shipment. HCS DataLink 500A cable assemblies are bundled with special halogen-free and flame-retardant semi-loose sleeves providing limp and easy-tobend, re-shapeable bundles, which are ideal for tight places and high-density locations. The bundles are marked on both sides with numbered labels for fast and easy identification. HCS DataLink 500A cable assemblies are available in shielded or unshielded versions, in lengths ranging from 5 to 90 meters and with Category 6A, Category 7 or Category 7A cables and are in full compliance with TIA-942, ISO/IEC 24764 and EN 50173-5. The standard cable jacket color is gray (RAL 7035) but other colors available upon request.

Physical and Mechanical Properties

Horizontal CAT 6A, CAT 7 or CAT 7A cables terminated with shielded or unshielded keystone jacks conforming to IEC 60603-7-5.

78 www.hescs.com

Page 75: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Ordering Information

Augmented Category 6 Cable Assemblies

Standard color: Light Gray RAL 7035. To define other colors and constructions use the Modular Cords P/N System Table A=IEC 60332-1 B=IEC 60332-3-24

Typical Transmission Properties

Typical Return LossTypical NEXT Loss

Typical ACR-FTypical PS-NEXT Loss

T6A-HNN3C-LLX Pre-terminated 4x2x23# U/FTP or U/MRTP CAT 6A LSOH cables A NN LL S/UT6A-HNN4C-LLX Pre-terminated 4x2x23# S/FTP CAT 7 LSOH cables A NN LL ST6A-HNN5C-LLX Pre-terminated 4x2x22# S/FTP CAT 7A LSOH cables A NN LL ST6A-HNN6C-LLX Pre-terminated 4x2x23# U/FTP or U/MRTP CAT 6A LSOH cables B NN LL S/UT6A-HNN7C-LLX Pre-terminated 4x2x23# S/FTP CAT 7 LSOH cables B NN LL ST6A-HNN8C-LLX Pre-terminated 4x2x22# S/FTP CAT 7A LSOH cables B NN LL S

T6A-HO63O-5OS Pre-terminated 4x2x23# U/FTP CAT 6A LSOH, Grey cables A 6 5 Yes

T6A-H126O-KOU Pre-terminated 4x2x23# U/MRTP CAT 6A LSOH, Grey cables B 12 9O No

T6A-HO241-A5S Pre-terminated 4x2x23# S/FTP CAT 7 LSOH, Blue cables A 2 15 Yes

T6A-HO478-B8S Pre-terminated 4x2x23# S/FTP CAT 7 LSOH, Yellow cables B 4 28 Yes

T6A-H1253-C5S Pre-terminated 4x2x22# S/FTP CAT 7A LSOH, Green cables A 12 35 Yes

T6A-HO689-D8S Pre-terminated 4x2x22# S/FTP CAT 7A LSOH, Purple cables B 6 48 Yes

79

Examples

ShildLength (m)Number of

CablesBasic CablesHCS P/N FR

www.hescs.com

Page 76: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Indoor/Outdoor Multi-Tight Distribution Fiber Optic Cables

Description

HCS DataLight series includes a complete line of Local Area Network (LAN) fiberoptic cables for high transmission rates including voice, data and video.All HCS DataLight cables are produced and rigorously tested to conform to most international standards.HCS DataLight Indoor/Outdoor Multi-Tight-Distribution (MTD) cable series provides the ultimate solution for all types of installations and application.These cables consist of 4-72 buffered fibers, cabled, served with water-blocking swellable aramid yarns and jacketed with black, UV resistant LS0H compound. HCS DataLight cables fully conform to and provide a substantial margin above all relevant TIA/EIA and IEC standards.Optional fibers available: Multimode 50/125 microns (OM2, OM3 & OM4), 62.5/125 microns and Singlemode fibers.

Applications

HCS DataLight cables can be used for various application including the following:

General purpose all-dielectric indoor LAN cable Distribution to Riser cabling - direct connectorization In-building backbone and riser, optimized for Centralized Cabling (TIA TSB-72) Short distance distribution and trunking  Office wiring

HCS DataLight cables support all presently available LAN applications, including the IEEE802.3z protocols for Gigabit Ethernet, 1000BASE-SX

(Short wavelength Gigabit Ethernet) 1000BASE-LX (Long wavelength Gigabit Ethernet) & IEEE 802.3ae 10GBASE-SR/SW 10GBASE-LX4 (10 Gigabit Ethernet).

Qualifications and Approvals    

HCS DataLight Cables are tested and verified for full compliance with the following standards:

ANSI/TIA/568-C.3 ISO/IEC 11801 (2nd Edition) IEC 60332-1 IEC 60754 CENELEC EN50173 IEC 60793 EIA/TIA-455 IEC 60794

Benefits & Features

Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. Tight or Semi-tight 900 microns buffered fibers - providing easy, fast and trouble-free termination and use of field-installable connectors. All-dielectric construction - providing perfect EMC (Electro Magnetic Compatibility) and total noise immunity. Halogen-free, flame retardant, UV and water resistant construction - providing a single cable suitable for all types of installations. Dry, jell-free longitudinal water blocking - providing easy and clean cable and fiber termination. Crisp and clear color coding - providing positive fiber identification and ease of termination. Descending sequential meter mark - providing easy stock and left-over handling. Smooth, limp and flexible jacket - providing easy and comfortable cable handling. Batch number printed every meter - providing fast retrieval of test results from data-base. A comprehensive product range - providing all state-of-the-art cable constructions. Unique DoubleSafe™ Quality Assurance Program  providing lowest rejection rate available.

80 www.hescs.com

Page 77: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Indoor/Outdoor Multi-Tight Distribution Fiber Optic Cables

Optional Constructions    

HCS DataLight Indoor/Outdoor MTD Cables contain up to 72 color-coded, 0.9 mm tight or semi-tight buffer optical fibers.In 4-24 fiber cables, all fibers are cabled together, reinforced by water-blocking swellable aramid strength yarns and protected with a flame-retardant, UV resistant LS0H Jacket.36 and 72-fiber cables are made of 6-fiber sub units. 48 fiber cables are made of 4-fiber sub-units.The cables fully comply with the EIA/TIA FOTP 82B longitudinal water-blocking test.

Notes:1. The "FO" in the P/N is replaced by the fiber designation selected from the FIBER OPTIONS Table.2.  Packaging options to be discussed with HCS Customer Service.3. The standard jacket color is Black RAL 9005. Other colors available upon request.

HCS P/N Description Short WeightKg/Km

Cal. ValueKj/m

NotesODmm

BufferTensile Strength

N, Max. Long

Ordering Information

MFO-00401 4 Fibers LS0H Black Tight 4.9 960 550 25 460

MFO-00402 4 Fibers LS0H Black Semi-Tight 4.9 960 550 25 460

MFO-00601 6 Fibers LS0H Black Tight 5.8 960 550 34 650

MFO-00602 6 Fibers LS0H Black Semi-Tight 5.8 960 550 34 650

MFO-00801 8 Fibers LS0H Black Tight 6.2 1250 750 43 830

MFO-00802 8 Fibers LS0H Black Semi-Tight 6.2 1250 750 43 830

MFO-01201 12 Fibers LS0H Black Tight 7.4 1250 750 52 1000

MFO-01202 12 Fibers LS0H Black Semi-Tight 7.4 1250 750 52 1000

MFO-02401 24 Fibers LS0H Black Tight 10.3 1500 960 120 2000

MFO-02402 24 Fibers LS0H Black Semi-Tight 10.3 1500 960 120 2000

MFO-03601 36 Fibers LS0H Black Tight 19.7 1500 960 250 4000

MFO-03602 36 Fibers LS0H Black Semi-Tight 19.7 1500 960 250 4000

MFO-04801 48 Fibers LS0H Black Tight 18.9 1500 960 300 4800

MFO-04802 48 Fibers LS0H Black Semi-Tight 18.9 1500 960 300 4800

MFO-07201 72 Fibers LS0H Black Tight 26.3 1500 960 570 9000

MFO-07202 72 Fibers LS0H Black Semi-Tight 26.3 1500 960 570 9000

Basic Fiber As selected from the FIBER OPTIONS Section

Buffer type Tight or Semi-tight

Buffer material PVC or LS0H Halogen free compound or acrylic

Buffer OD 900 microns nom

Strength elements Served swellable aramid yarns, providing longitudinal water blocking

Number of fibers 4-72

Color Code HCS Color Table No. 3 (IEC 60304 Color Code)

Outer Jacket LS0H Halogen free and flame retardant compound

Standard Outer Jacket Color Black RAL 9005. Other colors available upon request

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number

Max. Crush resistance 1000 N in 4-12 fiber cables. 3000 N in 24-72 fiber cables

Short Term Bend Radius 15xOD mm min.

Long Term Bend Radius 10xOD mm min.

Storage Temperature -40 to +70 oC

Temperature operating range -40 to +70 oC

Flame Test UL 1581 VW-1 and IEC 60332-1.

Halogen content in LS0H cables Null

81www.hescs.com

Page 78: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Indoor/Outdoor Single Loose Tube Fiber Optic Cables

Description 

HCS DataLight series includes a complete line of Local Area Network (LAN) fiberoptic cables for high transmission rates including voice, data and video.All HCS DataLight cables are produced and rigorously tested to conform to most international standards.HCS DataLight Indoor/Outdoor Single Loose Tube (SLT) cable series provides outstanding all-dielectric design for both indoor and outdoor installations in harsh conditions.These cables consist of 2-12 color-coded bare fibers (250 microns OD), contained in a single jell-filled loose tube, overall served  with water-blocking swellable aramid yarns or glass yarn and jacketed with black, UV resistant PE or LS0H compound.HCS DataLight cables fully conform to and provide a substantial margin above all relevant TIA/EIA and IEC standards.Optional fibers available: Multimode 50/125 microns (OM2, OM3 & OM4), 62.5/125 microns and Singlemode fibers.

Applications

HCS DataLight cables can be used for various application including the following:

General purpose outdoor LAN cable Campus backbone cable Campus distribution cable

HCS DataLight cables support all presently available LAN applications, including the IEEE802.3z protocols for Gigabit Ethernet, 1000BASE-SX (Short

wavelength Gigabit Ethernet) 1000BASE-LX (Long wavelength Gigabit Ethernet) & IEEE 802.3ae 10GBASE-SR/SW 10GBASE-LX4 (10 Gigabit

Ethernet).

Qualifications and Approvals    

HCS DataLight Cables are tested and verified for full compliance with the following standards:

ANSI/TIA/568-C.3 ISO/IEC 11801 (2nd Edition) IEC 60332-1 IEC 60754 CENELEC EN50173 IEC 60793 EIA/TIA-455 IEC 60794

Benefits & Features    

Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. UV, LS0H and water resistant optional constructions - providing a single cable suitable for indoor and outdoor locations. All-dielectric construction - providing perfect EMC (Electro Magnetic Compatibility) and total noise immunity. Crisp and clear color coding - providing positive fiber identification and ease of termination. Descending sequential meter mark - providing easy stock and left-over handling. Batch number printed every meter - providing fast retrieval of test results from data-base. A comprehensive product range - providing all state-of-the-art cable constructions. Unique DoubleSafe™ Quality Assurance Program  providing lowest rejection rate available.

82 www.hescs.com

Page 79: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Indoor/Outdoor Single Loose Tube Fiber Optic Cables

Ordering Information

HCS P/N Description Notes

Notes:1. The "FO" in the P/N is replaced by the fiber designation selected from the FIBER OPTIONS Table.2.  Packaging options to be discussed with HCS Customer Service.3. The standard jacket color is Black RAL 9005. Other colors available upon request.

Optional Constructions    

HCS DataLight Indoor/Outdoor SLT Cables contain up to 12 color-coded, 250 micron bare optical fibers.All fibers are contained in a single jell-filled loose tube, overall served  with water-blocking swellable aramid yarns and jacketed with black, UV resistant LS0H or PE compound.The cables fully comply with the EIA/TIA FOTP 82B and IEC 794-1-F5 longitudinal water-blocking tests.

Basic Fiber As selected from the FIBER OPTIONS Section

Buffer type None. (Bare, color-coded fibers)

Fibers OD 250 microns nom

Loose tube Single, filled with a Thixotropic gel

Strength elements over the loose tube Served swellable aramid or glass yarns, providing longitudinal water blocking

Number of fibers 2-12

Color Code HCS Color Table No. 3 (ANSI/TIA/EIA-598-A Color Code)

Outer Jacket Heavy duty, UV Resistant LS0H or PE compound

Cable OD 7.0 mm nom.

Standard Outer Jacket Color Black RAL 9005. Other colors available upon request

Standard Surface Marking Includes HCS P/N, cable description, Meter mark and Batch Number

Cable weight 38 Kg/Km nom

Max. Tensile Load - Short term 1000 N

Max. Tensile Load - Long term 500 N

Min. Bending Radius - Short term 140 mm

Min. Bending Radius - Long term 70 mm

Max. Crush resistance 2000 N

Water penetration 3m max @ 24h

Storage Temperature -40 to +70 oC

Temperature operating range -40 to +70 oC

Caloric Value: 800 Kj/m nom.

Halogen Content Null

SFO-00201 2 Fibers All Dielectric LS0H Indoor/Outdoor SLT Black  

SFO-00202 2 Fibers All Dielectric Indoor/Outdoor SLT Black  

SFO-00401 4 Fibers All Dielectric LS0H Indoor/Outdoor SLT Black  

SFO-00402 4 Fibers All Dielectric Indoor/Outdoor SLT Black  

SFO-00601 6 Fibers All Dielectric LS0H Indoor/Outdoor SLT Black  

SFO-00602 6 Fibers All Dielectric Indoor/Outdoor SLT Black  

SFO-00801 8 Fibers All Dielectric LS0H Indoor/Outdoor SLT Black  

SFO-00802 8 Fibers All Dielectric Indoor/Outdoor SLT Black  

SFO-01001 10 Fibers All Dielectric LS0H Indoor/Outdoor SLT Black  

SFO-01002 10 Fibers All Dielectric Indoor/Outdoor SLT Black  

SFO-01201 12 Fibers All Dielectric LS0H Indoor/Outdoor SLT Black  

SFO-01202 12 Fibers All Dielectric Indoor/Outdoor SLT Black

83www.hescs.com

Page 80: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS DataLight series includes a complete line of Local Area Network (LAN) fiberoptic cables for high transmission rates including voice, data and video.All HCS DataLight cables are produced and rigorously tested to conform to most international standards.HCS DataLight Indoor/Outdoor Multi-Loose Tube (MLT) cable series provides outstanding all-dielectric design for indoor and outdoor installations in harsh conditions.These cables consist of 4-288 color-coded bare fibers (250 microns) in up to 24 jell-filled loose tubes.The loose tubes are cabled concentrically around an all dielectric central strength member, water swellable yarns placed between tubes and tubes are wrapped with swellable tape and jacketed with black, UV resistant LS0H compound.HCS DataLight cables fully conform to and provide a substantial margin above all relevant TIA/EIA and IEC standards.Optional fibers available: Multimode 50/125 microns (OM2, OM3 & OM4), 62.5/125 microns and Singlemode fibers.

Benefits & Features

Indoor/Outdoor Dielectric Dry-Core Multi-Loose Tube FiberOptic Cables

Description

Applications

HCS DataLight cables can be used for various application including the following:

Long haul outside plant telephone, CATV and data-transmission cable Direct burial and duct installation cable Campus distribution cable

HCS DataLight cables support all presently available LAN applications, including the IEEE802.3z protocols for Gigabit Ethernet, 1000BASE-SX

(Short wavelength Gigabit Ethernet) 1000BASE-LX (Long wavelength Gigabit Ethernet) &IEEE 802.3ae 10GBASE-SR/SW 10GBASE-LX4 (10 Gigabit

Ethernet).

Qualifications and Approvals    

HCS DataLight Cables are tested and verified for full compliance with the following standards:

ANSI/TIA-568-C.3 ISO/IEC 11801 (2nd Edition) IEC 60332-1 IEC 60754 CENELEC EN50173 IEC 60793 EIA/TIA-455 IEC 60794

Exceptional material properties and cable design - providing a unique Century™ Lifetime Warranty. UV and water resistant construction - providing a single cable suitable for many outdoor locations. All-dielectric construction - providing perfect EMC (Electro Magnetic Compatibility) and total noise immunity. Crisp and clear color coding - providing positive fiber identification and ease of termination. Descending sequential meter mark - providing easy stock and left-over handling. Batch number printed every meter - providing fast retrieval of test results from data-base. A comprehensive product range - providing all state-of-the-art cable constructions. Unique DoubleSafe™ Quality Assurance Program providing lowest rejection rate available.

84 www.hescs.com

Page 81: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Indoor/Outdoor Dielectric Dry-Core Multi-Loose Tube FiberOptic Cables

Cables Optional Constructions  

HCS DataLight Outdoor MLT Cables contain up to 288 color-coded, 250 micron bare optical fibers.4-12 color-coded bare fibers are contained in each jell-filled loose tube.All loose tubes are cabled (with fillers as needed to preserve the cable geometry) around a solid, all dielectric central strength member and the water blocking yarns are placed between tubes.The cable core is water blocking tape-wrapped and jacketed with black, UV resistant LS0H compound.The cables fully comply with the EIA/TIA FOTP 82B and IEC 60794-1-F5 longitudinal water-blocking tests.

Notes:1. The "FO" in the P/N is replaced by the fiber designation selected from the FIBER OPTIONS Table.2. Packaging options to be discussed with HCS Customer Service.3. The standard jacket color is Black RAL 9005. Other colors available upon request.4. Outer jacket is available LS0H. This option can be discussed with HCS Customer Service.

Basic Fiber : As selected from the FIBER OPTIONS Section.

Buffer type: None. (Bare, color-coded fibers).

Fibers OD: 250 microns nom.

Loose tubes: 1-24, filled with a Thixotropic gel.

Central strength member: Rigid, all-dielectric FRP.

Number of fibers: 4-288.

Color Code inside each tube: Color Table No. 4: ANSI/TIA/EIA-598-A Color Code)

Color Code of loose tubes: Per request.

Core filling: Dry, water blocking yarns.

Core wrap: Water blocking tape, providing 100% coverage.

Outer Jacket: LS0H compound.

Standard Outer Jacket Color : Black RAL 9005. Other colors available upon request.

Standard Surface Marking : Includes HCS P/N, cable description, Meter mark and Batch Number.

Max. Tensile Strength - Short term 2500 N.

Max. Tensile Strength - Long term 1300 N.

Min. Bending Radius - Short term 20xCable OD

Min. Bending Radius - Long term 10xCable OD

Repeated bending: 100 Cycles min.

Crush Resistance 2200 N

Storage Temperature : -50 to +70C

Temperature operating range : -40 to +70C

Ordering Information

HCS P/N Description NotesODmm

WeightKg/Km

Fiber/TubeTube

QFO-00411 4 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 1 4 11 115

QFO-00611 6 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 3 2 11 115

QFO-00811 8 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 2 4 11 115

QFO-01211 12 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 3 4 11 115

QFO-02411 24 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 6 4 11 118

QFO-04811 48 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 4 12 11.6 130

QFO-07211 72 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 6 12 11.6 132

QFO-09611 96 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 8 12 13.5 160

QFO-14411 144 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 12 12 17 255

QFO-28811 288 Fibers All Dielectric Dry Core Indoor/Outdoor MLT Black 9+15 12 19.6 330

85www.hescs.com

Page 82: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Fiber Optic Patch Cords and Pigtails

Description

HCS DataLight Patch Cords and Pigtails series provides a full range of high quality assemblies, supporting all state-of-the-art connectors types, including ST, SC, SC/APC FC, FC/APC, LC and MPO. Other types, such as SMA, FDDI, and VF-45 are available upon request.HCS DataLight Patch Cords and Pigtails are available with all fiber types including Singlemode 9/125 microns, Multimode 50/125 microns (OM2, OM3 and OM4) and Multimode 62.5/125 microns fibers in any length required.HCS DataLight Patch Cords and Pigtails are available with different buffer and jacket types and colors, including bare fibers (250 microns), tight buffers (900 microns) or jacketed minicables in Simplex or Duplex (Zip-cord) constructions.HCS DataLight Patch Cords and Pigtails can be custom-made with breakout or MTD cables in multi-fiber constructions.HCS DataLight Patch Cords and Pigtails comply with both major industry standards, ANSI/TIA/568-C.3 (Optical Fiber Cabling Components Standard) and IEC 60874 (Connectors for optical fibers and cables) and they are supported by the DoubleSafe™ QA program as a part of complete HCS cabling system.

Applications

FiberOptic cross connect, patch panels, and distribution point connection. ODF connections. Fiber to the desk connection. Active FiberOptic equipment connection.

Qualifications and Approvals

HCS DataLight components are supported by the DoubleSafe™ QA program as a part of complete HCS cabling system and comply to ANSI/TIA/EIA-568-B.3 (Optical Fiber Cabling Components Standard) and IEC 60874 (Connectors for optical fibers and cables).

Benefits & Features  

Full compliance to industry standards - providing high quality components. Available with all major fiber types - providing a wide range of products. Available with all major connector types, including hybrid constructions - providing a wide range of products. Available in 12 different colors - providing a better compatibility and a wider selection range. Robust design - providing low rejection and replacement rates. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

Note: MM=Multimode, 50/125 and 62.5/125 microns fibers. SM=Singlemode 9/125 microns  fibers.

Connector Type

Connector PartSC SC/APC ST FC FC/APC MT-RJ LC

Technical Specifications - Connectors

MPO

86

Connector Ferrule Zirconia Ceramic Zirconia Ceramic Zirconia Ceramic Zirconia Ceramic Zirconia Ceramic Thermoplastic Ceramic PPS

SM Hizalama Aparat› Zirkon Seramik Zirkon Seramik Zirkon Seramik Zirkon Seramik Zirkon Seramik - Seramik NS

MM Hizalama Aparat› Zirkon Seramik - Metal Zirkon Seramik - - Seramik NS

Boot Polyester Polyester Polyester Polyester Polyester Polyester Polyester Silicone

SM Backbone Aluminum Aluminum Zinc Alloy Aluminum Aluminum Aluminum Aluminum Aluminum

MM Backbone Aluminum - Zinc Alloy Aluminum - Aluminum Aluminum Aluminum

Flame Test UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0

Connector Housing Thermoplastic Thermoplastic Thermoplastic

Nickel Plated ZincNickel Plated Zinc Nickel Plated Zinc Thermoplastic Thermoplastic

Polybutylene

Terephthalate

www.hescs.com

Page 83: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Fiber Optic Patch Cords and Pigtails

Connector Type

Durability Tests - Maximum Attenuation Increase After Test

LCTest

SC SC/APC ST FC FC/APC MT-RJ

Temperature Cycling: -40 to +85C 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 10 cycles

High Temp. Endurance: +85˚C  0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 96 hours

Low Temp. Endurance: -40˚C  0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 96 hours

High Humidity Endurance: %95 RH @ +40˚C 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 96 hours

Vibration Endurance: 10-55 Hz, 1.5 mm. 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB P to P

Tensile Endurance: 0-10 Kgf @ 1 min. 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB

Connection Durability: 1000 cycles 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB 0.2 dB

Notes

Example 1: T63-M0512-30 =>3 meters cord made of a 3.0 mm OD Duplex gray PVC Zip-minicable with tight coated 62.5/125 microns Patch Cord Grade fibers terminated on side A with ST connectors and on side B with SC connectors. Example 2: T91-A0040-15 =>1.5 meters pigtail made of a 250 microns OD bare 9/125 microns Standard Grade fiber (not colored) terminated on one side with FC connector.Example 3: T54-F12HH-B6 => 26 meters cord made of a 12x50/125µ OM3 fibers Ribbon LS0H cable terminated on both sides with Male MPO connectors.

Notes1. Detailed cable specs can be found in the relevant catalog pages.2. Detailed connector specs can be found in the relevant catalog pages. 

0.25

0.9

1.6

1.6

2.0

2.0

1.6x3.3

1.6x3.3

2.0x4.1

2.0x4.1

2.0x4.1

51 50/125 FO standard grade

52 50/125 FO premium grade

53 50/125 FO patch cord grade

54 50/125 FO 10GBE grade

55 50/125 FO Modified 10 GBE grade (150m.)

56 50/125 FO Modified 10 GBE grade (600m.)

61 62.5/125 FO standard grade

62 62.5/125 FO premium grade

63 62.5/125 FO patch cord grade

91 Singlemode FO standard grade

92 Singlemode FO premium grade

93 Singlemode FO ITU-T G.652

94 Singlemode FO ITU-T G.652D

95 Singlemode FO ITU-T G.655

96 Singlemode FO ITU-T G.656

97 Singlemode FO ITU-T G.657

NNTranmission Medium

Basic P/N Length

T

T

#

A

B

C

E

G

K

M

P

R

T

V

X NN AB

ConnectorsColor

-

-

XY

dmCable Type & OD (mm)

Note 2Note 1 Cable OD

Bare fiber

Tight-Buffered Fiber

Simplex PVC

Simplex LS0H

Simplexs PVC

Simplex LS0H

Duplex zip PVC

Duplex zip LS0H

Duplex zip PVC

Duplexs zip LS0H

Duplex zip LS0H + 2x28

AWG TC Cables

00 = Natural

01 = Blue

02 = Orange

03 = Green

04 = Brown

05 = Gray

06 = White

07 = Red

08 = Black

09 = Yellow

10 = Violet

11 = Aqua

1 = ST

2 = SC

3 = SC/APC

4 = FC

5 = FC/APC

6 = MT-RJ

7 = FDDI

8 = LC

9 = VF-45

A=MPO 4F - Female

B=MPO 6F - Female

C=MPO 8F - Female

D=MPO 12F -Female

E=MPO 4F - Male

F=MPO 6F - Male

G=MPO 8F - Male

H=MPO 12F -Male

J=MT-RJ -Male

K=LC-Duplex+Comm.Pin

L=SC-Duplex+Comm.Pin

nn=dm

An=10m+

Bn=20m+

Cn=30m+

Dn=40m+

En=50m+

Fn=60m+

Gn=70m+

Hn=80m+

Kn=90m+

NNFiber Count

NN

X Cable Type & OD (mm)

D Bare Ribbon LS0H cable

F Jacketed Ribbon LS0H cable

H Ruggedized (Trunk) LS0H cable

N ‹ndoor LS0H MTD cable

NN

NN

NN

P/N System - Terminated Modular Fiber Optic Cords

Connector Type

PropertiesSC SC/APC ST FC FC/APC MT-RJ LC

Technical Specifications - Transmission Properties

MPO

SM Attenuation Mean: 0.2 dB Mean: 0.2 dB Mean: 0.2 dB Mean: 0.2 dB Mean: 0.2 dB Mean: 0.2 dB Mean: 0.2 dB Mean:0.35 dB

@ 1300nm Sigma: 0.1 dB Sigma: 0.1 dB Sigma: 0.1 dB Sigma: 0.1 dB Sigma: 0.1 dB Sigma: 0.1 dB Sigma: 0.1 dB Sigma: 0.12dB

MM Attenuation Mean: 0.15 dB Mean: 0.15 dB Mean: 0.15 dB -

Mean: 0.15 dB Mean: 0.15 dB Mean:0.35 dB

@ 1300nm Sigma: 0.05 dB - Sigma: 0.05 dB Sigma: 0.05 dB Sigma: 0.05 dB Sigma: 0.05 dB Sigma: 0.12 dB

SM Return Loss Min: 50 dB Min: 65 dB Min: 50 dB Min: 50 dB Min: 65 dB Min: 50 dB Min: 50 dB Min:55 dB

Mean: 58 dB Mean: 80 dB Mean: 58 dB Mean: 58 dB Mean: 80 dB Mean: 58 dB Mean: 58 dB Mean: 60dB

MM Return Loss Min: 25 dB

- Min: 25 dB Min: 25 dB

- Min: 25 dB Min: 25 dB Min:25 dB

D Max: 0.2 dB Mean: 27 dB Mean: 27 dB D Max: 0.2 dB D Max: 0.2 dB D Max:0.2 dB

SM Connection Dur. D Max: 0.2 dB  D Max: 0.2 dB D Max: 0.1 dB D Max: 0.2 dB D Max: 0.2 dB D Max: 0.2 dB  D Max: 0.2 dB D Max:0.2 dB 

MM Connection Dur. D Max: 0.2 dB  - D Max: 0.2 dB D Max: 0.2 dB - D Max: 0.2 dB D Max: 0.2 dB D Max:0.2 dB 

SM Mating cycles 500  500 500 500 500 500  500 500 

MM Mating cycles 500  - 500 500 - 500  500 400 

Temp. Range -40 to +85C -40 to +85C -40 to +85C  -40 to +85C -40 to +85C  -40 to +85C -40 to +85C -40 to +85C

87

Connector Ferrule Zirconia Ceramic Zirconia Ceramic Zirconia Ceramic Zirconia Ceramic Zirconia Ceramic Thermoplastic Ceramic PPS

SM Hizalama Aparat› Zirkon Seramik Zirkon Seramik Zirkon Seramik Zirkon Seramik Zirkon Seramik - Seramik NS

MM Hizalama Aparat› Zirkon Seramik - Metal Zirkon Seramik - - Seramik NS

Boot Polyester Polyester Polyester Polyester Polyester Polyester Polyester Silicone

SM Backbone Aluminum Aluminum Zinc Alloy Aluminum Aluminum Aluminum Aluminum Aluminum

MM Backbone Aluminum - Zinc Alloy Aluminum - Aluminum Aluminum Aluminum

Flame Test UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0 UL-94 V-0

www.hescs.com

Page 84: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Fiberoptic Pre-Terminated 19" Patch Panels

Description

HCS DataLight Pre-Terminated Fiberoptic Patch Panel series provides a full range of pre-terminated fiber optic patch panels and fiber optic distribution points. HCS DataLight Pre-Terminated Fiber Optic Patch Panels accept 4 cassettes for the different front units. Each cassette consists of factory-terminated fiber optic patching in order to convert the MTP/MPO interface to a standard ST/FC/LC/SC/MT-RJ coupler. HCS DataLight Pre-Terminated Fiber Optic Patch Panels are ideal for mission-critical applications such as Data Centers and Storage Area Networks, where fast installation is a must and MACs are frequent. Factory-terminated optical cassettes ensure the best performance, promising true plug&play application. The robust cable management of the 1U Patch Panel enables up to 5 meters of extra cable to be stored within the panel for future move and change requirements. HCS DataLight patch panels are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling systems. The HCS Logo and the DataLight Trademark ensure long lasting high-performance and full support of all present and emerging applications

Applications

Fiberoptic & copper distribution Fiber to desk applications Central Office equipment Data - Centers

Qualifications and Approvals

HCS DataLight panels are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling systems and comply with the following safety standards:

UL94 V-0 rated plastic materials Zero-halogen in LS0H constructions.

Benefits & Features

Interchangeable modular design for fiber connectors - Providing ultimate flexibility. Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Integrated full installation accessories (supplied free of charge), including clip organizers and T-raps - providing a simple and elegant cable termination and identification. High density 1U 96 port design - providing a compact panel and economical space use. Pre-terminated cassettes - enables true plug&play performance. Top access into the panel - providing easy and comfortable cable management. Easy snap-in removable slack management accessories - providing simple and easy cable handling & storing up to 5 meters of ruggedized trunk ribbon Fiber Optic cable. Detailed installation manual in English and Turkish - providing clear and comprehensive instructions. Optional back-side cable management with clip organizer and trap connection - providing simple and easy cable handling. Robust and installer-friendly design - providing reduced installation and operating costs. Modular and expandable comprehensive product range - providing up to 96 ports in a single panel. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

88 www.hescs.com

Page 85: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Fiberoptic Pre-Terminated 19" Patch Panels

General PropertiesMaterial of construction Steel, Aluminum, Aluminum Alloy or Anodized Aluminum.

Paint and Color Powder paint finish, Black (Grey available upon request)

Connector Capacity 12-24-48 and 96 ports

Pre-terminated panel back connection 12/24 fiber ribbon cable terminated with MPO connector

Cassette capacity 4

Modular front plates 4

Insertion loss (max) MM 50,62.5 and SM:0.90 dB/casette. MM 50 OM3 and OM4 :0.75 dB/casette.

Environmental conditions -40 to +60C at 0-90% RH (Non condensing)

Packaging One unit per box.

Storage Temperature -20 to +80C

Non Halogen constructions Available upon request.

The required fiber type (FO) may be selected from HCS Fiber Options table.

89

Ordering Information

HCS P/N Description UnitsSize mm

mmNotesPortsConnectors

PFO-20001-1U DataLight Fiberoptic Blank Pre-terminated Panel, 19" N/A N/A 1u 44.4x480x400 -

PFO-2M121-1U DataLight Pre-Terminated cassette, 12 ST to 1 MPO ST & MPO 12 1u 44.4x480x400 -

PFO-2M122-1U DataLight Pre-Terminated cassette, 12 SC to 1 MPO SC & MPO 12 1u 44.4x480x400 -

PFO-2M123-1U DataLight Pre-Terminated cassette, 12 FC to 1 MPO FC & MPO 12 1u 44.4x480x400 -

PFO-2M124-1U DataLight Pre-Terminated cassette, 12 MT-RJ to 1 MPO MT-RJ & MPO 12 1u 44.4x480x400 -

PFO-2M125-1U DataLight Pre-Terminated cassette, 12 LC to 1 MPO LC & MPO 12 1u 44.4x480x400 -

PFO-2M245-1U DataLight Pre-Terminated cassette, 24 LC to 2 MPO LC & MPO 24 1u 44.4x480x400 -

www.hescs.com

Page 86: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Premium factory-controlled optical performance - enables flexible system configuration and fast installation. Low Smoke Zero Halogen allows for routing cables in any indoor environment Industry-leading low insertion loss (0.50dB max.) Each and every assembly pre-tested before shipment. Round, flexible outer jacket is easy to bend, route and install. Full compliance to industry standards - providing high quality components. Available with all major fiber types - providing a wide range of products. Robust design - ensuring long life and short replacement rates. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

Benefits & Features

MPO Cable Assemblies

Description

HCS DataLight MPO Assemblies series contain a full range of high quality assemblies factory terminated with MPO connectors. HCS DataLight MPO Assemblies are available with most fiber types including Singlemode 9/125 microns, Multimode 50/125 microns (OM2, OM3 and OM4) and Multimode 62.5/125 microns fibers in any length required.The assemblies are available with different cable types and colors, including bare ribbon cables, jacketed ribbon cables, ruggedized (trunk) ribbon cables and indoor MTD cables, with 12 fibers.HCS DataLight Patch Cords and Pigtails comply with both major industry standards, ANSI/TIA-568-C.3 (Optical Fiber Cabling Components Standard) and IEC 60874 (Connectors for optical fibers and cables) and they are supported by the DoubleSafe™ QA program as a part of complete HCS cabling system.

Applications

Mission critical applications such as Data Centers and Storage Area Networks Applications where fast installation is paramount Environments where moves adds and changes are frequent or managed in-house FiberOptic cross connect, patch panels, and distribution point connection ODF connections Fiber to the desk connection Active FiberOptic equipment connection

Qualifications and Protocol Support

HCS DataLight components are supported by the DoubleSafe™ QA program as a part of complete HCS cabling system and comply to ANSI/TIA-568-C.3 (Optical Fiber Cabling Components Standard) and IEC 60874 (Connectors for optical fibers and cables).HCS DataLight MPO Assemblies are designed to support a variety of high-speed network topologies including:

IEEE 802.3 10G Base-SR/SW 10Gbps IEEE 802.3 1000 Base-SX/LX 1Gbps IEEE 802.3 10G Base-LX4 10Gbps FDDI 100Mbps Fiber Channel 400-M5-SN-1 4Gbps IEEE 802.3 FOIRL 10Mbps Fiber Channel 1200-M5E-SN1 10Gbps IEEE 802.3 10 Base-F 10Mbps Fiber Channel FC-PH 1Gbps ATM 155 Mbps, 622 Mbps, 1.2 Gbps & 2.4 Gbps

Technical Specifications - MPO ConnectorsConnector Housing PET

Connector Ferrule PPS

Boot Silicone

SM Backbone Aluminum

MM Backbone Aluminum

Flame Test UL-94 V-0

Max.Insertion Loss 0.5dB

90 www.hescs.com

Page 87: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

MPO Cable AssembliesTechnical Specifications - Complete Assemblies

SM Attenuation @ 1300nm Mean:0.35 dB Sigma: 0.12dB

MM Attenuation @ 1300nm Mean:0.35 dB Sigma: 0.12dB

SM Return Loss Min:55 dB Mean: 60dB

MM Return Loss Min:25 dB D Max:0.2dB

SM Connection Durability D Max:0.2dB

MM Connection Durability D Max:0.2 dB

SM Mating Cycles 500

MM Mating Cycles 500

Operating Temp. -0 to +70C

Installation Temp. -0 to +70C

Storage Temp. -40 to +70C

Ordering Information

HCS P/N Description Lengthmm Notes

"FO" shall be replaced by the relevant Fiber P/N."X" shall be replaced by the relevant Cable Type."C" shall be replaced by the Jacket Color.

Durability Tests - Maximum Attenuation Increase after test

Temperature Cycling: -40 to +85C 0.2 dB 10 Cycles

High Temp. Endurance: +85C 0.2 dB 96 Hours

Low Temp. Endurance: -40C 0.2 dB 96 Hours

High Humidity Endurance: 95% RH @ +40C 0.2 dB 96 Hours

Vibration Endurance: 10-55 Hz, 1.5 mm 0.2 dB P to P

Tensile Endurance: 0-10 Kgf @ 1 minute 0.2 dB -

Connection Durability: 1000 cycles 0.2 dB -

Test Max. Increase Notes

TFO-X12DD-10C MPO-MPO (Female-Female) 12F LS0H FO Assembly 1.0 -

TFO-X12DD-20C MPO-MPO (Female-Female) 12F LS0H FO Assembly 2.0 -

TFO-X12DD-30C MPO-MPO (Female-Female) 12F LS0H FO Assembly 3.0 -

TFO-X12DD-50C MPO-MPO (Female-Female) 12F LS0H FO Assembly 5.0 -

TFO-X12DD-A0C MPO-MPO (Female-Female) 12F LS0H FO Assembly 10.0 -

TFO-X12DD-A5C MPO-MPO (Female-Female) 12F LS0H FO Assembly 15.0 -

TFO-X12DD-C0C MPO-MPO (Female-Female) 12F LS0H FO Assembly 30.0 -

TFO-X12DD-E5C MPO-MPO (Female-Female) 12F LS0H FO Assembly 55.0 -

TFO-X12DD-H0C MPO-MPO (Female-Female) 12F LS0H FO Assembly 80.0 -

TFO-X12DD-K9C MPO-MPO (Female-Female) 12F LS0H FO Assembly 99.0 -

Note: Please contact HCS Customer Service for polarity method (A,B or C)

91www.hescs.com

Page 88: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Notes: 1. The Fiber two-digit P/N should replace the "FO" letters in the selected HCS P/N2. All transmission values are for cabled fibers3. OFL => Overfilled Bandwidth per TIA/EIA 455-204 & IEC 60793-1-41 for legacy and LED based systems, typically up to 100Mbps.4. EMB=> Effective Modal Bandwidth per TIA/EIA 455-220A and IEC 60793-1-49 for laser based systems up to 10Gbps.

57

Standard GradeOM1 - ISO/IEC 11801TIA-568-C.3

Patch Cord Grade

Standard Grade  OM1 - ISO/IEC 11801TIA-568-C.3

Premium Grade OM2 - ISO/IEC 11801TIA-568-C.3

Patch Cord Grade

Fiber P/N Fiber Type Singlemode FiberGrade & Standard

Standard Grade  OS1 - ISO/IEC 11801TIA-568-C.3

Premium GradeTIA-568-C.3

91

92

63

62

61

53

52

51

1310nm 1383nmMFD

2.8 3.0 0.9 1.1 500 NS 600 NS 0.200±0.02

2.8 3.0 0.8 1.0  600 NS 1200 NS 0.200±0.02

3.0 3.5  1.2 1.5 150 NS 200 NS 0.200±0.02

2.8 3.0 0.8 1.0 1500 2000 500 500 0.200±0.02

2.8 3.0 0.8 1.0 1500 2000 500 500 0.200±0.02

2.3 2.5 0.6 0.8 3500 4700 500 500 0.200±0.015

2.3 2.5 0.6 0.8 3500 4700 500 500 0.200±0.015

3.0 3.5 0.7 1.0  200  NS 600 NS 0.275±0.015

2.6 3.0 0.7 1.0  500  NS 600 NS 0.275±0.015

3.0 3.5 1.2 1.5 150  NS 200 NS 0.275±0.015

54

10G Grade300m OM3 - ISO/IEC 11801EIA/TIA 492AAAC-A A1a.2 - IEC 60793-2-10TIA-568-C.3

Nom Max

62.5/125µmGraded Index

MultimodeOptical Fiber

Nom Max

55

56

10G  Grade NEWBend InsensitiveOM3 - ISO/IEC 11801EIA/TIA-492 AAAC-AA1a.2 - IEC 60793-2-10TIA-568-C.3

10G Grade OM4 - EIA/TIA 492AAADOM4 - ISO/IEC 11801 (Draft)A1a.3 - IEC 60793-2-10

1550nm

Nom Max

ITU-T G.652.Dno water peak

94

95

96

ITU-T G.655Non-zero dispersion shiftedITU-T G.656No water peak non-zero dispersion shifted

50/125µmGraded Index

MultimodeOptical Fiber

9.3/125µmSingle Mode Optik Fiber

0.4 0.5 NS NS 0.4 0.5 9.3±0.5 µm@1310nm

0.33 0.38 NS NS 0.22 0.25 9.3±0.5 µm@1310nm

0.33 0.35 NS NS 0.20 0.22 9.2±0.5 µm@1310nm

0.33 0.35 0.31 0.35 0.20 0.22 9.2±0.5 µm@1310nm

0.33 0.35 NS NS 0.20 0.22 9.6±0.5 µm@1550nm

0.33 0.35 0.35 0.40 0.20 0.22 9.6±0.5 µm@1550nm

0.33 0.35 0.31 0.35 0.20 0.22 9.6±0.5 µm@1550nm

ITU-T G.65293

Premium Grade OM2 - ISO/IEC 11801 EIA/TIA 492AAABA1a.1 - IEC 60793-2-10 TIA-568-C.3

Fiber P/N850nm

Fiber Type Multimode FiberGrade & Standard

Attenuation(dB/Km)

Min. Bandwidth (MHz•Km)

Numerical Aperture

1300nm 850nm 1300nm

Nom Max Nom Max OFL3 EMB4 OFL3 EMB4

ITU-T G.657Bend-insensitive Class B

97

10G  Grade NEWBend InsensitiveOM4 - EIA/TIA-492 AAADOM4 - ISO/IEC 11801A1a.3 - IEC 60793-2-10

92

DataLight Fiber Options

www.hescs.com

Page 89: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Mechanical and Environmental FO Cable Properties

EIA/TIA-455FOTP Number

Tested PropertyCENELEC EN 18700

Test MethodsIEC 60794-1

Test Methods

Tested Property Test Method

Optical and Geometrical Fiber Properties

ITU-T Test Methods EIA/TIA-455 FOTP No.IEC 60793-1

Test MethodsFiber Geometry Transmitted Near Field SM: G.650 Method 2.2.1   A2

MM: G.651 Sec. 1 Method B.3 MM: 58

Spectral Attenuation Cut-Back SM: G.650 Method 2.4.1 SM: 78 C1A

MM: G.651 Sec 2,1 Method B.2 MM: 46

Attenuation and 

Attenuation Uniformity at Backscattering  SM: G.650 Method 2.4.2 61 C1C

Specified wavelengths (OTDR) MM: G.651 Sec 2 Method B.4 59

Numerical Aperture Far-Field Light Distribution MM: G.651 Sec. 1 Method B.4 47 C6

Cutoff Wavelength Transmitted Power SM: G.650 Method 2.3.1, 2.3.3 80, 170. C7A

Mode Field Diameter Variable Aperture SM: G.650 Method 2.1.2 167

Bandwidth Frequency Domain MM: G.651 Sec 3 Method B.2 30 C2B

Chromatic Dispersion Phase Shift SM: G.650 Method 2.5.1 169 C5A

Operating and Pulling Load 33 E1 501

Minimum Bending Radius 33 E1 501

Crush Resistance (Compression) 41 E3 504

Repeated Bending 104 E6 509

93

DataLight Test Methods

www.hescs.com

Page 90: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and
Page 91: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

“ileri Teknoloji Data Center Çözümleri”

SECTION E: Phy-FiXX™ Copper & Fiber Optic Managed Cabling Solutions

DATALINK 250E HCS PHY-FIXX™ MANAGED CATEGORY 6 UNSHIELDED RJ-45 COPPER PATCH PANELS 96-97

DATALINK 500A HCS PHY-FIXX™ MANAGED CATEGORY 6A SHIELDED RJ-45 COPPER PATCH PANELS 98-99

DATALINK 250E HCS PHY-FIXX™ CATEGORY 6 UNSHIELDED RJ-45 OUTLET TERMINATOR. 100

DATALINK 500A HCS PHY-FIXX™ CATEGORY 6A SHIELDED RJ-45 OUTLET TERMINATOR. 101

DATALIGHT HCS PHY-FIXX™ MANAGED 24-PORT DUPLEX LC FIBER PATCH PANELS 102

DATALIGHT HCS PHY-FIXX™ FIBER OPTIC PATCH CORDS 103

HCS PHY-FIXX™ 576 CHANNEL SCANNER 104

HCS PHY-FIXX™ APPLICATION SOFTWARE & LICENSE 105

Page 92: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Phy-FiXX™ Managed Category 6 Unshielded RJ-45 Copper Patch Panels

Application

Nitelikler ve Onaylar

Transmission EMC Safety

96

Benefits & Features

Description

Connectivity Features

Wire size range 22-24 AWG, Solid.

Material of construction CRS (cold rolled steel) 1.52 mm thickness.

Coating and color Black Zinc.

Connector module holder High impact, Flame-retardant plastic compound, UL 94 V-0.

Jack Housing material Zinc Alloy plated bright Ni/Cu

IDC plastic housing Polycarbonate UL94 V-0.

Jack contact material Copper alloy plated with 1.25µm Gold over Nickel.

IDC contact material Copper alloy plated with Matte Tin.

Plug Retention Force 6.8 Kgf (66 N) min.

Jack contact force 100 grams min.

IDC terminations cycles 20 min. using same-gauge wires.

IDC type Gas tight

Jack insertion durability 750 mating cycles

Storage temperature range -20 to +60C

Installation and operation conditions 0 to +50C at 0-90% RH (Non condensing)

Packaging One unit per box.

Shipping weight 560 gr.

General Properties    

Phy-FiXX™ is a revolutionary and advanced physical layer management suit providing enterprises with the ability to manage their Physical Layer infrastructure with a level of visibility & integration unique in the structured cabling industry. Using a combination of software, electronics and structured cabling products, Phy-FiXX™ enables users to track and manage their investment from planning through to design, procurement, installation, moves, adds and changes (MACs) and the eventual upgrade of the infrastructure, thereby spanning its entire lifecycle.HCS Phy-FiXX™ Category 6 unshielded Patch Panels are used within the Phy-FiXX™ System. Each 1U 24 Port Patch Panel has one data bus connection port located on the rear of the panel. The data bus connection port connects the panel to the Phy-FiXX™ scanner via a standard RJ45 patch cord. The patch panel is used by the Phy-FiXX™ system to track connectivity in the patch zone and work area. LED status indicators on the panel show status of connectivity between the panel and the scanner and also provide panel guidance for work orders.The IDC section of the Phy-FiXX™ Patch Panels consist of V-shaped contacts that flex not fatigue when terminated. Each port features a patented spring-loaded shutter. The patch panel works as a conventional patch panel when not connected to the Phy-FiXX™ system.All Phy-FiXX™ patch panels fully conform to and provide a substantial margin above all ANSI/TIA-568-C.2 and ISO/IEC-11801 (2nd Edition) Category 6 component requirements.The HCS Phy-FiXX™ Logo and the DataLink 250E Trademark ensure long lasting high-performance and full support of most present applications.

HCS Phy-FiXX™ DataLink 250E panels are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling system.HCS Phy-FiXX™ DataLink 250E panels are tested at the component level and they comply to the following standards:

Two power status indicators to ensure proper connection of power supply from the scanner. Data bus connection to the Phy-FiXX™ Scanner done with an industry standard RJ45 patch cord. Category 6 field configurable for T568A or T568B wiring options. Integral cable management shelf ensures bend radius compliance. International hardware kit contains both ANSI and metric hardware. Can be terminated using industry standard punch-down tools. Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Supplied with front labeling card index strip - providing simple and elegant port identification. Detailed installation manual in English and Turkish - providing clear and comprehensive instructions. Exceeding Category 6 performance - providing full support to Gigabit Ethernet. Robust and installer-friendly design - providing reduced installation and operating costs. Compatible with 22-24 AWG solid conductors - providing support to a wider range of cabling types.

ANSI/TIA-568-C.1 EN-55022, Class B (Europe) UL94 V-0 rated plastic materials ANSI/TIA-568-C.2 FCC Part 15, Subpart J, Class A (USA) Zero-halogen in LS0H constructions ISO/IEC-11801

HCS Phy-FiXX™ DataLink 250E unshielded copper RJ-45 patch panels are used within the Phy-FiXX™ System for horizontal distribution or equipmentterminations in telecommunications rooms and for interconnection terminations in consolidation points, and they fully support the following protocols:

1GBASE-T Gigabit Ethernet 100BASE-T2 ATM 52 Broadband and Baseband VideoATM 155 100BASE-T4 ATM 25 ISDN Basic and Primary AccessTP-PMD 100BASE-TX 10BASE-T Ethernet 1BASE-5 Starlan100BASE-T "Fast Ethernet" Token Ring 100 Mbps Token Ring 4 Mbps and 16 Mbps ISALAN ITU V.21 ve X.11

LED status indicators on both the panel sides show status of connectivity between the panel and the scanner. LED status indicator on the panel calls for operator action (connect/disconnect patch-cord). LED status indicators on each port calls for operator action (connect/disconnect patch-cord). LED status indicators can be activated and deactivated from a remote location by the network supervisor.

www.hescs.com

Page 93: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

FREQ.

MHz

Typical De-Embedded Return-LossTransmission and Electrical Specifications

Typical De-Embedded FEXT-Loss

Phy-FiXX™ Managed Category 6 Unshielded RJ-45 Copper Patch Panels

Insertion Loss

dB

Max

RL

dB

Min

Typical De-Embedded Insertion-Loss

NEXT

dB

Min

FEXT

dB

Min

1.00 0.02 85.0 84.0 53.0

4.00 0.02 81.0 75.0 54.0

8.00 0.02 78.0 70.0 56.0

10.00 0.03 77.0 68.0 57.0

16.00 0.03 73.0 58.0 58.0

25.00 0.04 70.0 60.1 60.0

31.25 0.04 68.0 59.0 57.0

62.50 0.05 64.0 53.0 44.0

100.00 0.06 60.0 49.0 34.0

200.00 0.06 55.0 43.0 23.0

250.00 0.08 52.0 41.0 20.0

97

Propagation Delay 2.5 nS max @ 1-250 MHz

Propagation Delay Skew  1.25 nS max @ 1-250 MHz

Current rating 1.5 A max.

Contact resistance  20 mOhm max (per contact)

Input/Output resistance  200 mOhm max

Input/Output resistance unbalance 50 mOhm max

Voltage rating 72 Vdc max

Dielectric strength 1000 Volts rms for 1 minute

Insulation Resistance 100 MegaOhm min @ 500 Vdc

DC Resistance 0.1 Ohm max @ 20C

Initial contact resistance 2.5 mOhm

TCL 28-20·Log(f/100) dB min @ 1-250 MHz

Transfer Impedance N/A

Ordering Information

HCS P/N Description T568

P6E-02409-1U 24 port RJ-45 Unshielded CAT 6E 19" Phy-FiXX™ Patch Panel 110 IDC 1u 44x483x92 1.75x19x4.25 UNI

Blocks UnitsSize: Hx/Wx/D

mm Inch

www.hescs.com

Page 94: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Phy-FiXX™ Managed Category 6A Shielded RJ-45 Copper Patch Panels

Applications

Qualifications and Approvals    

Transmission EMC Safety

Benefits & Features

Description

Connectivity Features

Wire size range 22-24 AWG, Solid.

Material of construction CRS (cold rolled steel) 1.52 mm thickness.

Coating and color Black Powdercoat.

Connector module holder High impact, Flame-retardant plastic compound, UL 94 V-0.

Jack Housing material Zinc Alloy plated bright Ni/Cu

IDC plastic housing Polycarbonate UL94 V-0.

Jack contact material Copper alloy plated with 1.25µm Gold over Nickel.

IDC contact material Copper alloy plated with Matte Tin.

Plug Retention Force 6.8 Kgf (66 N) min.

Jack contact force 100 grams min.

IDC terminations cycles 20 min. using same-gauge wires.

IDC type Gas tight

Jack insertion durability 750 mating cycles

Storage temperature range -20 to +60C

Installation and operation conditions 0 to +50C at 0-90% RH (Non condensing)

Packaging One unit per box.

Shipping weight 840 gr.

General Properties    

98

Phy-FiXX™ is a revolutionary and advanced physical layer management suit providing enterprises with the ability to manage their Physical Layer infrastructure with a level of visibility & integration unique in the structured cabling industry. Using a combination of software, electronics and structured cabling products, Phy-FiXX™ enables users to track and manage their investment from planning through to design, procurement, installation, moves, adds and changes (MACs) and the eventual upgrade of the infrastructure, thereby spanning its entire lifecycle.HCS Phy-FiXX™ Category 6A shielded Patch Panels are used within the Phy-FiXX™ System. Each 1U 24 Port Patch Panel has one data bus connection port located on the rear of the panel. The data bus connection port connects the panel to the Phy-FiXX™ scanner via a standard RJ45 patch cord. The patch panel is used by the Phy-FiXX™ system to track connectivity in the patch zone and work area. LED status indicators on the panel show status of connectivity between the panel and the scanner and also provide panel guidance for work orders.The IDC section of the Phy-FiXX™ Patch Panels consist of V-shaped contacts that flex not fatigue when terminated. Each port features a patented spring-loaded shutter. The patch panel works as a conventional patch panel when not connected to the Phy-FiXX™ system.All Phy-FiXX™ patch panels fully conform to and provide a substantial margin above all ANSI/TIA-568-C.2 and ISO/IEC-11801 (2nd Edition) Category 6A component requirements.The HCS Phy-FiXX™ Logo and the DataLink 500A Trademark ensure long lasting high-performance and full support of most present applications.

HCS Phy-FiXX™ DataLink 500A panels are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling system.HCS Phy-FiXX™ DataLink 500A panels are tested as CAT6A/Class EA Channel and they comply to the following standards:

Two power status indicators to ensure proper connection of power supply from the scanner. Data bus connection to the Phy-FiXX™ Scanner done with an industry standard RJ45 patch cord. Category 6A field configurable for T568A or T568B wiring options. Integral cable management shelf ensures bend radius compliance. International hardware kit contains both ANSI and metric hardware. Can be terminated using industry standard punch-down tools. Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Supplied with front labeling card index strip - providing simple and elegant port identification. Detailed installation manual in English and Turkish - providing clear and comprehensive instructions. Exceeding Category 6A performance - providing full support to Gigabit Ethernet. Robust and installer-friendly design - providing reduced installation and operating costs. Compatible with 22-24 AWG solid conductors - providing support to a wider range of cabling types.

ANSI/TIA-568-C.1 EN-55022, Class B (Eurppe) UL94 V-0 dereceli plastik malzemer ANSI/TIA-568-C.2 FCC Subpart F 68.5 (USA) LS0H uygulamalarda 0 helojen ISO/IEC-11801

HCS Phy-FiXX™ DataLink 500A shielded copper RJ-45 patch panels are used within the Phy-FiXX™ System for horizontal distribution or equipmentterminations in telecommunications rooms and for interconnection terminations in consolidation points, and they fully support the following protocols:

1GBASE-T Gigabit Ethernet 100BASE-T2 ATM 52 Broadband ve Baseband VideoATM 155 100BASE-T4 ATM 25 ISDN Basic ve Primary AccessTP-PMD 100BASE-TX 10BASE-T Ethernet 1BASE-5 Starlan100BASE-T "Fast Ethernet" Token Ring 100 Mbps Token Ring 4 Mbps ve 16 Mbps ISALANITU V.21 ve X.11

LED status indicators on both the panel sides show status of connectivity between the panel and the scanner. LED status indicator on the panel calls for operator action (connect/disconnect patch-cord). LED status indicators on each port calls for operator action (connect/disconnect patch-cord). LED status indicators can be activated and deactivated from a remote location by the network supervisor.

www.hescs.com

Page 95: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

FREQ.

MHz

Typical Return-LossTransmission and Electrical Specifications

Typical PS-ACRF

Phy-FiXX™ Managed Category 6A Shielded RJ-45 Copper Patch Panels

IL

dB

Max

RL

dB

Min

Typical PS-NEXT

NEXT

dB

Min

FEXT

dB

Min

1.00 0.1 75.0 75.0 30.0

4.00 0.1 75.0 71.1 30.0

8.00 0.1 75.0 65.0 30.0

10.00 0.1 74.0 63.1 30.0

16.00 0.1 69.9 59.0 30.0

25.00 0.1 66.0 55.1 30.0

31.25 0.1 64.1 53.2 30.0

62.50 0.16 58.1 47.2 30.0

100.00 0.20 54.0 43.1 28.0

200.00 0.28 48.0 37.1 22.0

250.00 0.32 46.0 35.1 20.0

300.00 0.35 42.9 33.6 18.5

400.00 0.40 37.9 31.1 16.0

500.00 0.45 34.0 29.1 14.0

Propagation Delay 2.5 nS max @ 1-500 MHz

Propagation Delay Skew  1.25 nS max @ 1-500 MHz

Current rating 1.5 A max.

Contact resistance  20 mOhm max (per contact)

Input/Output resistance  200 mOhm max

Input/Output resistance unbalance 50 mOhm max

Voltage rating 72 Vdc max

Dielectric strength 1000 Volts rms for 1 minute

Insulation Resistance 100 MegaOhm min @ 500 Vdc

DC Resistance 0.1 Ohm max @ 20C

Initial contact resistance 2.5 mOhm

TCL 28-20·Log(f/100) dB min @ 1-500 MHz

Ordering Information

HCS P/N Description T568

P6A-02409-1U 24 port RJ-45 Shielded CAT 6A 19" Phy-FiXX™ Patch Panel 110 IDC 1u 44x483x92 1.75x19x4.25 UNI

Blocks UnitsSize: Hx/Wx/D

mm Inch

TCL

dB

Min

EL TCL

dB

Min

PS ANEXT

dB

Min

PS AFEXT

dB

Min

40.0 40.0 67.0 67.0

40.0 40.0 67.0 67.0

40.0 40.0 67.0 67.0

40.0 40.0 67.0 67.0

40.0 40.0 67.0 67.0

40.0 40.0 67.0 67.0

38.1 38.1 67.0 67.0

32.1 32.1 67.0 67.0

28.0 28.0 67.0 67.0

22.0 22.0 64.5 61.0

20.0 20.0 62.5 59.0

18.5 18.5 61.0 57.5

16.0 16.0 58.5 55.0

14.0 14.0 56.5 53.0

99www.hescs.com

Page 96: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Phy-FiXX™ Category 6 Unshielded RJ-45 Outlet Terminator.

Description

Applications

HCS DataLink 250E Phy-FiXX™ terminator is entirely transparent to the data channels hence it supports all applications supported by HCS CAT 6 unshielded copper RJ-45 keystone jacks:

1000BASE-T Gigabit Ethernet 100BASE-TX Broadband ve Baseband VideoATM 155 Token Ring 100 Mbps ISDN Basic ve Primary AccessTP-PMD ATM 52 1BASE-5 Starlan100BASE-T "Fast Ethernet" ATM 25 ISALAN100BASE-T2 10BASE-T Ethernet ITU V.21 ve X.11100BASE-T4 Token Ring 4 Mbps ve 16 Mbps

Housing material Flame-retardant thermoplastic compound, UL 94 V-0.

Contacts material Phosphor Bronze plated with Tin matte with Nickel.

Contact force 60 gr min.

Operating life Min. 20 re-terminations.

Environmental conditions -20 to +50C at 0-90%RH (non condensing)

Standard Color Transparent.

Benefits & Features

Electrical properties

Ordering Information

HCS P/N Description T568

K6E-008TR 8P8C RJ-45 Unshielded CAT 6 Outlet Terminator

Unit/pack

24 A&BHCS P/N J6E-00873HCS P/N W6E-008D1HCS P/N W6E-008D2

Compatible with

Contact resistance 2.5 mOhm Insulation

Interface resistance 20 mOhm Initial

Voltage rating 72 Vdc max.

Insulation Resistance 100 MegaOhm min @ 500 Vdc

General Properties    

100

Phy-FiXX™ is a revolutionary and advanced physical layer management suit providing enterprises with the ability to manage their Physical Layer infrastructure with a level of visibility & integration unique in the structured cabling industry. Using a combination of software, electronics and structured cabling products, Phy-FiXX™ enables users to track and manage their investment from planning through to design, procurement, installation, moves, adds and changes (MACs) and the eventual upgrade of the infrastructure, thereby spanning its entire lifecycle.The Phy-FiXX™ Outlet Terminator is used at the work area outlet to allow the Phy-FiXX™ system to monitor the connection of the horizontal cable to the work area outlet. The Phy-FiXX™ Outlet Terminator is effectively a stuffer cap with in-built components that work exclusively in the HCS Phy-FiXX™ solution. It enables the Phy-FiXX™ system to determine circuit integrity to the work area outlet. Communications between the Phy-FiXX™ Outlet Terminator and the Phy-FiXX™ Scanner are transparent to the data channel and operate outside the Ethernet bandwidth. The Phy-FiXX™ system can function independently of the Phy-FiXX™ outlet terminator. However, the terminator provides enhanced functionality in terms of monitoring spare or unused channels.

Confirms circuit integrity between the Phy-FiXX™ patch panel and the work area outlet. Enables monitoring of changes and detects the presence of devices at the outlet. Transparent to the Data Channel. Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

www.hescs.com

Page 97: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Phy-FiXX™ Category 6A Shielded RJ-45 Outlet Terminator.

Description

Applications

HCS DataLink 500A Phy-FiXX™ terminator is entirely transparent to the data channels hence it supports all applications supported by HCS CAT 6A shielded copper RJ-45 keystone jacks:

10BASE-T 10 Gigabit Ethernet 100BASE-T4 Token Ring 4 Mbps ve 16 Mbps1000BASE-T Gigabit Ethernet 100BASE-TX Broadband ve Baseband VideoATM 155 Token Ring 100 Mbps ISDN Basic ve Primary AccessTP-PMD ATM 52 1BASE-5 Starlan100BASE-T "Fast Ethernet" ATM 25 ISALAN100BASE-T2 10BASE-T Ethernet ITU V.21 ve X.11

Benefits & Features

Ordering Information

HCS P/N Description T568

K6A-008TR 8P8C RJ-45 Shielded CAT 6A Outlet Terminator

Units/pack

24 A&BHCS P/N W6A-008D1HCS P/N W6A-008D2

Compatible with

Housing material Flame-retardant thermoplastic compound, UL 94 V-0.

Contacts material Phosphor Bronze plated with Tin matte with Nickel.

Contact force 60 gr min.

Operating life Min. 20 re-terminations.

Environmental conditions -20 to +50C at 0-90%RH (non condensing)

Standard Color Transparent.

Electrical properties

Contact resistance 2.5 mOhm Insulation

Interface resistance 20 mOhm Initial

Voltage rating 72 Vdc max.

Insulation Resistance 100 MegaOhm min @ 500 Vdc

General Properties    

101

Phy-FiXX™, kurumların fiziksel katman altyapı sistemlerini sürekli olarak izleyebilme ve yönetebilmelerine imkân sa¤layan, yapısal kablolama sistemleri endüstrisine eşsiz ve devrim niteli¤inde bir yenilik getiren Fiziksel Katman Yönetim platformudur. Yazılım, elektronik ve yapısal kablolama ürünlerinin mükemmel kombinasyonu sayesinde Phy-FiXX™ kullanıcılarına altyapı yatırımlarını planlama aşamasından başlayarak tasarım, satınalma, kurulum, yer de¤iştirme & ekleme & çıkarma, ve güncelleme de dahil tüm aşamalarını takip etme ve yönetilme imkanı vermektedir.Phy-FiXX™ Priz Terminatörü, prize çekilmiş olan kablonun ba¤lantısını izleyebilmek için Phy-FiXX™ sisteminde kullanılmaktadır.Phy-FiXX™ Priz Terminatorü, HCS Phy-FiXX™ sistemi için özel olarak tasarlanmış, üzerinde entegre bir devre barındıran pasif IDC toz kapa¤ıdır. Phy-FiXX™ sisteminde kullanıcı tarafının durumunu izleme ve yönetimine yardımcı olur. Phy-FiXX™ Priz Terminatör ve Phy-FiXX™ Tarayıcı arasındaki haberleşme Ethernet bant genişli¤inin dışında çalışmaktadır. Phy-FiXX™ sistemi, Phy-FiXX™ Priz Terminatörü olmadan da çalışabilir, ancak özellikle aktif olmayan (yedek olarak ilerde kullanılmak üzere çekilen) data uçlarının durumlarını takip etmekte önemli bir işlevsellik sunmaktadır.

Confirms circuit integrity between the Phy-FiXX™ patch panel and the work area outlet.Enables monitoring of changes and detects the presence of devices at the outlet. Transparent to the Data Channel. Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Unique DoubleSafe™ Quality Assurance Program - providing lowest rejection rate available.

www.hescs.com

Page 98: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

General Properties

Fiber options Single Mode: OS1 & OS2. Multimode: OM1, OM2, OM3 & OM4

Material of construction 16 AWG cold rolled steel

Coating and color Powder coating, black

Adapter shell material Crastin SK602 NC010 (PBT 15% G.F.)

Adapter shell color Natural

Alignment sleeve SM: Zirconia MM: Phosphor-Bronze

Number of terminated fibers 48 (24 Duplex LC)

Installation temperature -40 to +75C

Operating temperature -40 to +75C

Storage temperature -40 to +75C

Packaging One unit per box.

Shipping weight 650 gr.

Phy-FiXX™ Managed 24-Port Duplex LC Fiber Patch Panels

Description

Applications

Qualifications and Approvals

Transmission EMC Safety

Benefits & Features

Connectivity Features

Parts List (Each assembled panel includes the following)

1 x Cable gland 4-8mm M20

4 x Blanking grommet 20mm

1 x Aramid retention post

1 x Open grommet

2 x Fiber support base and clips

International hardware kit

Laser hazard warning label

Instruction sheet

Ordering Information

HCS P/N Description NotesUnitsSize: Hx/Wx/D

mm Inch

PFO-F2401-1U 24 port Single Mode Duplex LC Phy-FiXX™ FO Patch Panel 1u 44.2x484.6x336.6 1.74x19.1x13.25 -

PFO-F2402-1U 24 port Multimode Duplex LC Phy-FiXX™ FO Patch Panel 1u 44.2x484.6x336.6 1.74x19.1x13.25 -

"FO" shall be replaced with the relevant Fiber P/N.

102

Phy-FiXX™ is a revolutionary and advanced physical layer management suit providing enterprises with the ability to manage their Physical Layer infrastructure with a level of visibility & integration unique in the structured cabling industry. Using a combination of software, electronics and structured cabling products, Phy-FiXX™ enables users to track and manage their investment from planning through to design, procurement, installation, moves, adds and changes (MACs) and the eventual upgrade of the infrastructure, thereby spanning its entire lifecycle.HCS Phy-FiXX™ 24-Port Duplex LC FO Patch Panels are used within the Phy-FiXX™ System. Each 1U 24 Port Patch Panel has one data bus connection port located on the rear of the panel. The data bus connection port connects the panel to the Phy-FiXX™ scanner via a standard RJ45 patch cord. The patch panel is used by the Phy-FiXX™ system to track connectivity in the patch zone and work area. LED status indicators on the panel show status of connectivity between the panel and the scanner and also provide panel guidance for work orders.The adapter interface contains 24 duplex LC ports with Single Mode or Multimode options. The patch panel works as a conventional patch panel when not connected to the Phy-FiXX™ system.All Phy-FiXX™ patch panels fully conform to and provide a substantial margin above all ANSI/TIA-568-C.3 and ISO/IEC-11801 (2nd Edition) FO component requirements.The HCS Phy-FiXX™ Logo and the DataLight Trademark ensure long lasting high-performance and full support of most present applications.

HCS Phy-FiXX™ DataLight Duplex LC FO panels are used within the Phy-FiXX™ System for horizontal distribution or equipment terminations in telecommunications rooms and for interconnection terminations in consolidation points, and they fully support most presently available LAN applications, including the IEEE802.3z protocols for Gigabit Ethernet, 1000BASE-SX (Short wavelength Gigabit Ethernet) 1000BASE-LX (Long wavelength Gigabit Ethernet) & IEEE 802.3ae 10GBASE-SR/SW 10GBASE-LX4 (10 Gigabit Ethernet).

HCS Phy-FiXX™ DataLight Duplex LC FO panels are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling system.HCS Phy-FiXX™ DataLight Duplex LC FO panels are tested at the component level and they comply to the following standards:

UL94 V-0 rated plastic materials FCC Subpart F 68.5 UL94 V-0 rated plastic materials ANSI/TIA-568-C UL 1863 & CSA 22.2 ISO/IEC-11801

Two power status indicators to ensure proper connection of power supply from the scanner. Data bus connection to the Phy-FiXX™ Scanner done with an industry standard RJ45 patch cord. Panel options for Single Mode and Multimode fibers, including OS1, OS2, OM1, OM2, OM3 & OM4 Integral slide-out cable management shelf ensures bend radius compliance. International hardware kit contains both ANSI and metric hardware. Recessed mounting provides adequate space for routing patch cords, even in free standing enclosures with the front door closed. Exceptional material properties and design - providing a unique Century™ Lifetime Warranty. Detailed installation manual in English and Turkish - providing clear and comprehensive instructions. Robust and installer-friendly design - providing reduced installation and operating costs.

LED status indicators on both the panel sides show status of connectivity between the panel and the scanner. LED status indicator on the panel calls for operator action (connect/disconnect patch-cord). LED status indicators on each port calls for operator action (connect/disconnect patch-cord). LED status indicators can be activated and deactivated from a remote location by the network supervisor.

www.hescs.com

Page 99: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Phy-FiXX™ Fiber Optic Patch Cords

Description

Applications

Qualifications and Approvals

Belirleyici Özellikler

Transmission Safety

Optical Characteristics

Fiber TypeBW (OFL)

ISO Class@850nm @1300nm @850nm @1300nm

Maks. Att. dB/Km Max. Mated ILdB

Min. RLdB (UPC)

Jacket Color

MM 62.5/125µ OM1 200 500 3.75 1.2 0.3 - Orange

MM 50/125µ OM2 500 500 3.5 1.2 0.3 - Grey

MM 50/125µ OM3 2500 500 3.0 1.0 0.3 - Aqua

MM 50/125µ OM4 3500 500 2.6 0.8 0.3 - Aqua

SM 9/125µ OS1 NA NA 0.5 0.5 0.3 50 Yellow

SM 9/125µ OS2 NA NA 0.5 0.5 0.3 50 Yellow

Ordering Information

HCS P/N Description Lengthm

TFO-VccKK-10 Phy-FiXX™ LC-LC Duplex LS0H FO Cord 1.0 -0+0.1m 18 -TFO-VccKK-20 Phy-FiXX™ LC-LC Duplex LS0H FO Cord 2.0 -0+0.1m 34 -TFO-VccKK-30 Phy-FiXX™ LC-LC Duplex LS0H FO Cord 3.0 -0+0.1m 49 -TFO-VccKK-50 Phy-FiXX™ LC-LC Duplex LS0H FO Cord 5.0 -0+0.1m 83 -TFO-VccKK-A0 Phy-FiXX™ LC-LC Duplex LS0H FO Cord 10.0 -0+0.1m 157 -TFO-VccKK-A5 Phy-FiXX™ LC-LC Duplex LS0H FO Cord 15.0 -0+1.5m 230 -

Tolerance Weightgrams Notes

General Properties

Fiber options Single Mode: OS1,OS2. Multimode: OM1, OM2, OM3 & OM4

Connector type Duplex LC

Durability 200 Insertions min.

Cable OD 2.76 x 6.0 mm

Min. Bend radius 2.8 mm

Cable tensile strength 300N

Number of terminated fibers 2

Installation temperature -20 to +50C

Operating temperature -20 to +50C

Storage temperature -50 to +80C

Packaging One unit per box.

103

Phy-FiXX™ is a revolutionary and advanced physical layer management suit providing enterprises with the ability to manage their Physical Layer infrastructure with a level of visibility & integration unique in the structured cabling industry. Using a combination of software, electronics and structured cabling products, Phy-FiXX™ enables users to track and manage their investment from planning through to design, procurement, installation, moves, adds and changes (MACs) and the eventual upgrade of the infrastructure, thereby spanning its entire lifecycle.HCS Phy-FiXX™ DataLight FO Patch Cords are used to connect Phy-FiXX™ FO panels within the Phy-FiXX™ System. HCS Phy-FiXX™ FO Patch Cords incorporate a monitoring cable along with contact points on the cord connectors that activate the detection mechanism in the Phy-FiXX™ patch panel. When used with the rest of the Phy-FiXX™ system, these patch cords will provide connectivity information to the Phy-FiXX™ system.All Phy-FiXX™ patch cords fully conform to and provide a substantial margin above all ANSI/TIA-568-C.3 and ISO/IEC-11801 (2nd Edition) FO component requirements.The HCS Phy-FiXX™ Logo and the DataLight Trademark ensure long lasting high-performance and full support of most present applications.

HCS Phy-FiXX™ DataLight FO Patch Cords are used to connect Phy-FiXX FO panels within the Phy-FiXX™ System and they fully support most presently available LAN applications, including the IEEE802.3z protocols for Gigabit Ethernet, 1000BASE-SX (Short wavelength Gigabit Ethernet) 1000BASE-LX (Long wavelength Gigabit Ethernet) & IEEE 802.3ae 10GBASE-SR/SW 10GBASE-LX4 (10 Gigabit Ethernet).

HCS Phy-FiXX™ DataLight FO Patch Cords are supported by the Century™ Lifetime Warranty and by the DoubleSafe™ QA program as a part of complete HCS cabling system.HCS Phy-FiXX™ DataLight FO Patch Cords are tested at the component level and they comply to the following standards:

Robust duplex housings protect fibers. Monitoring contact interfaces with Phy-FiXX™ FO Patch panel. All cords available with Single Mode and Multimode fibers, including OS1, OS2, OM1, OM2 & OM3 All cords available with two fibers contained in a single outer jacket. All cords are jacketed with LS0H (Low Smoke Zero Halogen) flexible compound. Exceptional material properties and design - providing a unique Century™ Lifetime Warranty.

ANSI/TIA-568-C.3 ICEA 596 ISO/IEC-11801 UL 1863

www.hescs.com

Page 100: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS Phy-FiXX™ 576 Channel Scanner

Description

Accessories

Standard conformance

Management EMC Safety

Benefits & Features

Electrical & Power properties

Max. power consumption 30 WattsUniversal AC input 110-240VAC, 50-60HzHeat generated 12 BTU/HourInsulation Resistance 100 MegaOhm min @ 500 Vdc

General Properties

Ordering Information

HCS P/N Description

PB PF48 0800 Phy-FiXX™ 576 Channel Scanner 44 483 216 4.0 1U

UnitsDimensions mm

H W DShipping

Weight Kg

Material of construction CRS (cold rolled steel) 1.52 mm thickness.

Coating and color Black powder coated finish

Storage conditions -10 to 60ºC, 10 to 95% Relative Humidity non-condensing

Installation and operation conditions 0 to 50ºC, 15-90% Relative Humidity non-condensing

Packaging One unit per box.

Shipping weight 4 Kg

104

Phy-FiXX™ is a revolutionary and advanced physical layer management suit providing enterprises with the ability to manage their Physical Layer infrastructure with a level of visibility & integration unique in the structured cabling industry. Using a combination of software, electronics and structured cabling products, Phy-FiXX™ enables users to track and manage their investment from planning through to design, procurement, installation, moves, adds and changes (MACs) and the eventual upgrade of the infrastructure, thereby spanning its entire lifecycle.Phy-FiXX™ scanners monitor activity on a Phy-FiXX™ enabled system. Each 1U scanner can be connected to up to 48 patch panels providing monitoring of up to 576separate physical channels. Standard RJ45 patch cords are used as the data bus connection between scanners and patch cords.Phy-FiXX™ scanners can be configured and activated independently of the software. When the Phy-FiXX™ application software is connected to the scanner, the scanner“discovers” active hardware and devices on the network and uploads this information onto the Phy-FiXX™ application software. Scanners monitor the connection state of Phy-FiXX™ channels and pass state change data to the Phy-FiXX™ application software. This triggers Phy-FiXX™’s smart polling function which queries the specific outlet and updates the software. In the event that the Phy-FiXX™ application cannot communicate with a scanner, the scanner records transactions in a queue for later delivery to the Phy-FiXX™ software. Scanners recover from power outages without requiring reconfiguration. Phy-FiXX™ scanners consume little power, which can be critical in power-hungry environments such as Data Centers.

Supports up to 48 patch panels and 576 separate physical channels. Smart polling enables continuous updating of Phy-FiXX™ with minimal impact to the network. Simple scanner configuration Auto discovery of active hardware/devices & automatic database population Mission critical port disconnection alerts Trace to device location High density scanner enables rack space to be maximized Low power consumption with no specific fans or cooling required Automatic Rediscovery/Re-synchronization after outage or system failure Transaction queues record events for later delivery if the scanner is disconnected from the Phy-FiXX application. Scanner can be tested and activated independently of software activation Data bus connection between the scanner and patch panel is via an industry standard RJ45 patch cord

Each scanner is supplied with one International 19-inch mounting kit. A standard IEC 60320 power cord (comprising a power plug and C13 Plug/outlet) is required but not included.

HTTP EN-55022, Class B (Europe) UL 1950 SNMP (read-only) FCC Part 15, Class B (USA) IEC 60950 CSA 950

www.hescs.com

Page 101: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

HCS Phy-FiXX™ Application Software & License

Ordering Information

HCS P/N Description Notes

KSW-A5760 HCS Phy-FiXX™ Application SoftwareKSW-A576M HCS Phy-FiXX Application Software - 1 Year Maintenance KSW-L0960 HCS Phy-FiXX™ 96 Channel Software LicenseKSW-L096M HCS Phy-FiXX 96 Channel Software License - 1 Year Maintenance KSW-L5760 HCS Phy-FiXX™ 576 Channel Software LicenseKSW-L576M HCS Phy-FiXX 576 Channel Software License - 1 Year Maintenance

105

Technical Information

Phy-FiXX™ Software is designed for Windows 32 bit and 64 bit environments and requires a TCP/IP network.The following system requirements are recommended:Server*:Supported Operating Systems: Windows Server 2008 (US English version)Windows Server 2008 R2 (US English version)Server should meet Microsoft’s recommended requirementsDatabase*:Microsoft SQL Server Express 2008Microsoft SQL Server Express 2008 R2Browser Support*:Microsoft Internet Explorer Version 7.0 or higherFirefox Version 3.2 or higherChrome Version 5.0 or higherRecommended screen resolution of 1200 x 800 or betterMicrosoft Silverlight is required on the web browsing device.One year technical support provided with initial software purchase (can be renewed on an annual basis).* HCS recommends Windows Server 2008 R2 and SQL Server Express 2008 R2.

DescriptionPhy-FiXX™ is a revolutionary and advanced physical layer management suit providing enterprises with the ability to manage their Physical Layer infrastructure with a level of visibility & integration unique in the structured cabling industry. Using a combination of software, electronics and structured cabling products, Phy-FiXX™ enables users to track and manage their investment from planning through to design, procurement, installation, moves, adds and changes (MACs) and the eventual upgrade of the infrastructure, thereby spanning its entire lifecycle. Phy-FiXX™ Software is the central data manager for the Phy-FiXX™ system. It manages OSI Layer 1 infrastructure elements and provides instantaneous information to the IT Manager about connectivity on Phy-FiXX™ enabled channels. The software documents planned work orders and detects unplanned (ad hoc) changes to the network. It allows continuous monitoring of the complete physical channel from work area outlet to the active network device. Phy-FiXX™ software automatically monitors all connections and disconnections, identifies and confirms port availability and notifies the IT Manager of all unscheduled or unauthorized network cabling changes. All moves, adds, and changes (MACs) detected on the network are automatically updated in the database. Phy-FiXX™ software is a web based application that enables global network access by an unlimited number of users and provides cost effective and accurate network management.Phy-FiXX™ Reports allow the IT team to extract information contained in the Phy-FiXX™ system about the Layer 1 infrastructure and the assets connected to the infrastructure. Reports include information about assets, work orders, logs, MACs, and connectivity status of Phy-FiXX™ enabled channels.

Phy-FiXX™ 96 and 576 Channel Software Licences are used to enable activation of Phy-FiXX™ panels on Phy-FiXX™ scanners. Channel licenses are installed on the Phy-FiXX™ server. Each 96 Channel licence activates four scanner ports and each 576 Channel licence activates 24 scanner ports. 96 Channel licences are ideal for low density environments where the entire channel capacity of a scanner is not required. Multiple 96 channel licences may be installed on a scanner to provide a solution matching the number of channels served by a scanner. 96 channel licenses can be added incrementally as additional channels are connected to the scanner. Each scanner may have up to six 96 channels licenses or one 576 channel licences installed on it. 96 channel licenses may be added to a scanner at any time

Benefits & Features

Hierarchal view of entire enterprise layer 1 infrastructure Monitoring of all connections/disconnections Drag and drop work orders Work orders for end devices and wire closet patches Guided patching Search feature to easily locate assets and information Event logs for audit trails Assets linkage to building maps Enhanced graphics and mapping features, including Zoom, Pan, Scaling & Mini-map. Tracing feature across all channel elements Unrestricted number of users per license Data import and export capability

www.hescs.com

Page 102: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and
Page 103: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

“ileri Teknoloji Data Center Çözümleri”

Bölüm F:Data Center’lar için Kablo Kanalları ve Yangın Önleyici SistemlerFİBER OPTİK KABLO KANALLARI VE AKSESUARLARI 110-116

ENERJİ VE BAKIR DATA KABLOLARI İÇİN METAL KABLO KANALLARI VE AKSESUARLARI 118-125

YANGINA DAYANIKLI & YANGIN ÖNLEYİCİ ÜRÜNLER 128-134

Page 104: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and
Page 105: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

110-116Fiber Optik Kablo Kanalları ve Aksesuarları

Page 106: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

Fiber Optik Kablo Kanalları ve Aksesuarları

110 www.hescs.com

Uygulamalar

HCS DataLight Fiber Optik Kablo Kanalları ve Aksesuarları, zengin kanal seçenekleri ve aksesuarları ile Data Center uygulamalarında gerekli olan fiber optik kablo kanalı ihtiyacına cevap vermektedir.

Açıklama

HCS DataLight Fiber Optik Kablo Kanalları ve Aksesuarları, Data Center’larda kullanılmakta olan fiber optik kabloların kesintisiz veri iletişimi sağlamaları için zarar görmeden uzun yıllar boyunca performans göstermeleri için özel olarak tasarlanmıştır. Kanalların tamamen pürüzsüz yapısı ve fiber optik kabloların dönüş açılarına göre tasarlanmış dönüş aparatları sayesinde, fiber optik kabloların hasar görmesi engellenmiş olur. Kabinetlere inişler ve bağlantılar için sunulan özel aletler, kanal kesimlerinin ve eklerin çapaksız yapılabilmesini ve daha sonraki montajların risksiz yapılabilmesini mümkün kılar.

Belirleyici Özellikler

π Zengin Kanal Seçenekleri – 50x50, 100x100, 220x100 ve 300x100 olmak üzere dört ayrı ölçüde kanal ve aksesuarları ile, düşük adetli kablolama ihtiyaçları için esnek kablo kanalları mevcuttur.

π Kolay montaj – Kablo kanalları basit bir testere yardımıyla kesilebilir, istenilen yerde ek yapılabilir.

π Hafif yapı – Data Center için minimum ilave yük getirir.

π Halojen free malzeme yapısı – Data Center yangın gereksinimlerine uygunluk sağlar.

π Geniş aksesuar alternatifleri – Köşe dönüş, T ek, düz ek, sonlandırma kapakları gibi birçok yardımcı aksesuar sayesinde montajın kusursuz yapılmasına olanak sağlar.

Page 107: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

111www.hescs.com

Genel Özellikler

Çalışma Sıcaklığı: -40 / +60C 0-90% RH (yoğunlaşmayan)

Depolama Sıcaklığı: -20 / +80C

Standart Renk: Sarı RAL 1021.

Sipariş Bilgileri

HCS P/N Açıklama Ölçü (b) mm NotUzunluk (m)Paket miktarı

(mt/adet)

C00-14A01 Kablo kanalı, düz, kapaklı, 50 mm, PPO LS0H

250 60

60

25 Her ek için 1 adet gereklidir

1

1

C00-14A03 Birleştirme aparatı, 50 mm kanal için, PPO LS0H

-50

C00-14A05 45° dönüş, 50 mm kanal için, PPO LS0H -50

C00-14A04 30° dönüş, 50 mm kanal için, PPO LS0H -50

1C00-14A06 90° dönüş, 50 mm kanal için, PPO LS0H -50

1C00-14A07 30° düşey dönüş, 50 mm kanal için, PPO LS0H

-50

1C00-14A08 90° düşey dönüş, 50 mm kanal için, PPO LS0H

-50

1C00-14A09 90° dikey dönüş, 50 mm kanal için, PPO LS0H

-50

1C00-14A10 Yatay T parçası, 50 mm kanal için, PPO LS0H

-50

1C00-14A11 Düşey T parçası, 50 mm kanal için, PPO LS0H

-50

1C00-14A12 Düşey T parçası, açılıp kapanabilir, 50 mm kanal için, PPO LS0H

-50

1C00-14A13 Dörtlü geçiş ek parçası, 50 mm kanal için, PPO LS0H

-50

20C00-14A15 Yuvarlak Esnek tüp sonlandırma parçası, 50 mm, PPO LS0H

-50

5C00-14A14 Kablo kanalı sonlandırma parçası, 50 mm kanal için, PPO LS0H

-50

C00-14A02 Kablo kanalı, perfore, kapaksız, 50 mm, PPO LS0H

250

Yapım malzemesi: Halojen-free PPO (Polyphenylene oxide) malzeme.

Page 108: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

112 www.hescs.com

HCS P/N Açıklama Ölçü (b) mm NotUzunluk (m)Paket miktarı

(mt/adet)

Kablo kanalı, düz, kapaklı, 100 mm, PPO LS0H

2100

100

100

100

100

100

100

100

100

100

100

100

100

100

100

100

100

100

100

16

16

2 Her ek için 1 adet gereklidir

1

1

Birleştirme aparatı, 50 mm kanal için, PPO LS0H

-

45° dönüş, 100 mm kanal için, PPO LS0H -

30° dönüş, 100 mm kanal için, PPO LS0H -

190° dönüş, 100 mm kanal için, PPO LS0H -

130° düşey dönüş, 100 mm kanal için, PPO LS0H

-

145° düşey dönüş, 100 mm kanal için, PPO LS0H

-

190° düşey dönüş, 100 mm kanal için, PPO LS0H

-

130° dikey dönüş, 100 mm kanal için, PPO LS0H

-

145° dikey dönüş, 100 mm kanal için, PPO LS0H

-

190° dikey dönüş, 100 mm kanal için, PPO LS0H

-

1Yatay T parçası, 100 mm kanal için, PPO LS0H

-

5Yatay çıkış için T parçası, 100 mm kanal için, PPO LS0H

-

C00-14B02

C00-14B04

C00-14B03

C00-14B05

C00-14B06

C00-14B07

C00-14B08

C00-14B09

C00-14B10

C00-14B11

C00-14B12

C00-14B14

1Düşey T parçası, 100 mm kanal için, PPO LS0H

-C00-14B15

1Düşey T parçası, açılıp kapanabilir, 100 mm kanal için, PPO LS0H

-

1Dörtlü geçiş ek parçası, 100 mm kanal için, PPO LS0H

-C00-14B17

C00-14B16

2Kablo kanalı sonlandırma parçası, kapalı, 100 mm kanal için, PPO LS0H

-

2Kablo kanalı sonlandırma parçası, açık, 100 mm kanal için, PPO LS0H

-C00-14B19

C00-14B18

C00-14B13

C00-14B01

Kablo kanalı, düz, kapaksız, 100 mm, PPO LS0H

2

Page 109: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

113www.hescs.com

220

HCS P/N Açıklama Ölçü (b) mm NotUzunluk (m)Paket miktarı

(mt/adet)

Yuvarlak Esnek tüp sonlandırma parçası, 100 mm, PPO LS0H

-100

220

220

220

220

220

220

220

220

220

220

220

220

220

2

8

8

Her ek için 1 adet gereklidir2

1

Kablo kanalı, düz, kapaksız, 220 mm, PPO LS0H

2

30° dönüş, 220 mm kanal için, PPO LS0H -

Birleştirme aparatı, 220 mm kanal için, PPO LS0H

-

145° dönüş, 220 mm kanal için, PPO LS0H -

190° dönüş, 220 mm kanal için, PPO LS0H -

130° düşey dönüş, 220 mm kanal için, PPO LS0H

-

145° düşey dönüş, 220 mm kanal için, PPO LS0H

-

190° düşey dönüş, 220 mm kanal için, PPO LS0H

-

130° dikey dönüş, 220 mm kanal için, PPO LS0H

-

145° dikey dönüş, 220 mm kanal için, PPO LS0H

-

190° dikey dönüş, 220 mm kanal için, PPO LS0H

-

1Yatay T parçası, 220 mm kanal için, PPO LS0H

-

C00-14C01

C00-14C03

C00-14C02

C00-14C04

C00-14C05

C00-14C06

C00-14C07

C00-14C08

C00-14C09

C00-14C10

C00-14C11

C00-14C13

1Yatay çıkış için T parçası, 220 mm kanal için, PPO LS0H

-C00-14C14

1Düşey T parçası, 220 mm kanal için, PPO LS0H

-

1Düşey T parçası, açılıp kapanabilir, 220 mm kanal için, PPO LS0H

-C00-14C16

C00-14C15

1Dörtlü geçiş ek parçası, 220 mm kanal için, PPO LS0H

-

1Dörtlü geçiş ek parçası, redüksiyonlu, 220 mm kanal için, PPO LS0H

-C00-14C18

C00-14C17

C00-14C12

C00-14B20

Kablo kanalı, düz, kapaklı, 220 mm, PPO LS0H

2

220

220

220

220

Page 110: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

114 www.hescs.com

Dörtlü geçiş ek parçası, 300 mm kanal için, PPO LS0H

HCS P/N Açıklama Ölçü (b) mm NotUzunluk (m)Paket miktarı

(mt/adet)

Kablo kanalı sonlandırma parçası, kapalı, 220 mm kanal için, PPO LS0H

-220

220

300

300

300

300

300

50

300

300

300

300

300

300

300

300

-

50

2

2

8

Her ek için 1 adet gereklidir

50 adet konnektörlü kablo geçirilebilir

8

2

Kablo kanalı, düz, kapaklı, 300 mm, PPO LS0H

2

Birleştirme aparatı, 300 mm kanal için, PPO LS0H

-

Kablo kanalı, düz, kapaksız, 300 mm, PPO LS0H

2

145° dönüş, 300 mm kanal için, PPO LS0H -

190° dönüş, 300 mm kanal için, PPO LS0H -

145° düşey dönüş, 50 mm kanal için, PPO LS0H

-

145° düşey dönüş, 300 mm kanal için, PPO LS0H

-

190° düşey dönüş, 300 mm kanal için, PPO LS0H

-

145° dikey dönüş, 300 mm kanal için, PPO LS0H

-

190° dikey dönüş, 300 mm kanal için, PPO LS0H

-

1Yatay T parçası, 300 mm kanal için, PPO LS0H

-

1Yatay çıkış için T parçası, 300 mm kanal için, PPO LS0H

-

C00-14D01

C00-14D03

C00-14D02

C00-14D04

C00-14D05

C00-14D06

C00-14D07

C00-14D08

C00-14D09

C00-14D10

C00-14D11

C00-14D13 1-

C00-14D14 1Dörtlü geçiş ek parçası, redüksiyonlu, 300 mm kanal için, PPO LS0H

-

1Kablo kanalı sonlandırma parçası, kapalı, 300 mm kanal için, PPO LS0H

-

C00-14E01

C00-14D15

150mm esnek tüpe yan çıkış aparatı, yuvarlak, PPO LS0H

-

150mm kablo kanalı için T yan çıkış aparatı, PPO LS0H

-C00-14E02

C00-14D12

C00-14C19

C00-14C20 Yuvarlak Esnek tüp sonlandırma parçası, 220 mm, PPO LS0H

-

300

Page 111: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

115www.hescs.com

50

HCS P/N Açıklama Ölçü (b) mm NotUzunluk (m)Paket miktarı

(mt/adet)

50 mm kablo kanalı için 90° düşey yan çıkış aparatı, PPO LS0H

-50

100

100

100

100'den 50'ye

220'den 100'e

300'den 100'e

220'den 100'e

220'den 100'e

50

88

50

-

220

1

1

1

50 adet konnektörlü kablo geçebilir

150 adet konnektörlü kablo geçebilir

80 adet konnektörlü kablo geçebilir

2

1

220 mm kablo kanalı için 90° düşey yan çıkış aparatı, PPO LS0H

-

100 mm kanaldan 50 mm kanala geçiş aparatı, PPO LS0H

-

100 mm Yanal Yükseklikli Kanal Üstünden Çıkış aparatı, PPO LS0H

-

1220 mm kanaldan 100 mm kanala geçiş aparatı, PPO LS0H

-

1300 mm kanaldan 100 mm kanala geçiş aparatı, PPO LS0H -

1220 mm kanaldan 100 mm kanala geçiş aparatı, sol, PPO LS0H

-

1220 mm kanaldan 100 mm kanala geçiş aparatı, sağ, PPO LS0H

-

2Esnek yuvarlak tüp, 50 mm, PPO LS0H 2

2Esnek yuvarlak tüp, 100 mm, PPO LS0H 2

0.35Kare esnek tüp, 80 mm, PPO LS0H 0.35

1Çıkış rampası, PPO LS0H -

10Montaj parçası 50 mm kanal için, 304 derece paslanmaz çelik

-

C00-14E04

C00-14E06

C00-14E05

C00-14E07

C00-14E08

C00-14E09

C00-14E10

C00-14E11

C00-14E12

C00-14E13

C00-14E14

C00-14E16

10Montaj parçası 100 mm kanal için, 304 derece paslanmaz çelik

-C00-14E17

10Montaj parçası 220 mm kanal için, 304 derece paslanmaz çelik

-

10Montaj parçası 300 mm kanal için, 304 derece paslanmaz çelik

-C00-14E19

C00-14E18

1Kesme aleti, 50 mm ve üzeri kanallar için -

1Kesme aleti, 100 mm ve üzeri kanallar için -C00-14E21

C00-14E20

C00-14E15

C00-14E03

100 mm kablo kanalı için 90° düşey yan çıkış aparatı, PPO LS0H

-

100

300

-

-

Page 112: DATA CENTER Challenge - Aeropress · Enviromental monitoring and management in your Data Center provides you visibility and control of vital parameters which ensures your uptime and

116 www.hescs.com

HCS P/N Açıklama Ölçü (b) mm NotUzunluk (m)Paket miktarı

(mt/adet)

Testere ağzı --

-

-

-

1

1

1Ayaktan kontrollü delik açma aleti, 100,220 ve 300 mm kanallar için

-

1Ayaktan kontrollü delik açma aleti, 100,220 ve 300 mm kanallar için, taşıma çantası ile

-

- 1Manuel delik açma aleti, 100,220 ve 300 mm kanallar için -C00-14E24

C00-14E26

- 1Manuel&hidrolik destekli delik açma aleti, 100,220 ve 300 mm kanallar için -C00-14E25

C00-14E27

C00-14E22

C00-14E23 50 mm kanallar için delik açma aleti -