3
Daikin Gas Tight Joints (DGT) For use with R410A/R32 refrigerant pipes BDGTA An advanced evolution in pipe design Daikin Gas Tight Joints (DGT) combine rubber packing and a screwed metal body, which offer gas-tight and rigid connections without brazing. The patented “leverage method” holds the pipe mechanically, preventing pull-out. The benefits of using DGT Time & labour saving o Simple installation process cuts short the installation time o Cost & time saving with less admin work (hot work permit) and safety (fire watcher) Safety o No brazing required, reducing fire risk o No fire watcher required Quality assurance o No special tools required o No special skills worker required o High quality and consistency of installation The mechanism As the nut turns, the “B” point-of-leverage corns are compressed and encroach the surface of the pipe. When the pull-out force increases, the corns encroach deeper to prevent the pipe from becoming loose. Where can you use the DGT joints? B Force Copper Pipe Refrigerant R32, R410A Refrigerant oil Ether oil Diameter 1/4" ~ 1 5/8" Max. Pressure 43.4 Bar Wall thickness 0.8mm ~ 2mm Min. Pressure -755mmHg Type O (~φ15.9mm) & H (~φ19.1mm) Max. Temperature 130°C Form Coiled pipe & Straight pipe Min. Temperature -45°C Standard ISO 14903 Applicable Fluids Applicable Copper Pipe Pipes to ASTM B280-08, B88-09 (Type L)

Daikin Gas Tight Joints (DGT) - Principal Climate

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Daikin Gas Tight Joints (DGT) - Principal Climate

Daikin Gas Tight Joints (DGT) For use with R410A/R32 refrigerant pipes

BDGTA

An advanced evolution in pipe design Daikin Gas Tight Joints (DGT) combine rubber packing and a screwed metal body, which offer gas-tight and rigid connections without brazing.

The patented “leverage method” holds the pipe mechanically, preventing pull-out.

The benefits of using DGT

• Time & labour saving o Simple installation process cuts short the

installation time o Cost & time saving with less admin work

(hot work permit) and safety (fire watcher) • Safety

o No brazing required, reducing fire risk o No fire watcher required

• Quality assurance o No special tools required o No special skills worker required o High quality and consistency of installation

The mechanism

As the nut turns, the “B” point-of-leverage corns are compressed and encroach the surface of the pipe. When the pull-out force increases, the corns encroach deeper to prevent the pipe from becoming loose.

Where can you use the DGT joints?

B

Force Copper Pipe

Refrigerant R32, R410ARefrigerant oil Ether oil Diameter 1/4" ~ 1 5/8"Max. Pressure 43.4 Bar Wall thickness 0.8mm ~ 2mmMin. Pressure -755mmHg Type O (~φ15.9mm) & H (~φ19.1mm)

Max. Temperature 130°C Form Coiled pipe & Straight pipeMin. Temperature -45°C

Standard ISO 14903

Applicable Fluids Applicable Copper PipePipes to ASTM B280-08, B88-09 (Type L)

Page 2: Daikin Gas Tight Joints (DGT) - Principal Climate

Specifications

Picture Dimensions

Weight (g) ND φ AF (mm) L

(mm)

1/4" (6.4mm) 19 46.2 106

3/8" (9.5mm) 22 51.4 139

1/2" (12.7mm) 23.8 82.3 170

5/8" (15.9mm) 29.7 82.8 236

3/4" (19.1mm) 35 85.5 327

7/8" (22.2mm) 38 93.5 401

1 1/8" (28.6mm) 45 99.5 546

1 3/8" (34.9mm) 51.1 101.5 686

1 5/8" (41.3mm) 58.3 103.5 881

Picture Dimensions

Weight (g) ND φ 1 ND φ 2 AF1

(mm) AF2

(mm) L

(mm)

1/2" (12.7mm)

3/8" (9.5mm) 24 22 62.4 158

5/8" (15.9mm)

1/2" (12.7mm) 29.7 23.8 83.2 220

7/8" (22.2mm)

3/4" (19.1mm) 38 35 87.4 362

1 1/8" (28.6mm)

1" (25.4mm) 45 41.8 94.4 510

Excellent performance

Thanks to the unique double sealing method, the sealing performance is secured over a long period, even under severe conditions of high pressures and extreme temperatures.

Fire free connections

No brazing is needed on site, reducing installation cost and time and increasing the quality of the final installation.

Authorised standards

Full compliance with ISO 14903, proving safety and reliability of the system.

Durable under high pressure

Using the leverage method, the pull-out resistance is more than four times the maximum operating pressure.

Easy Installation

Low torque tightening means installation can completed with only one or two turns of a nut, without any special tools being required (only wrenches or spanners are used).

Page 3: Daikin Gas Tight Joints (DGT) - Principal Climate

3 steps installation method

By using the marking gauge, draw the insertion depth line on the pipe surface.

Insert the pipe until the line disappears.

Tighten the nut until the green indicator disappears.

1. Green indicator should be hidden 2. Be sure to check the position of the depth line by the gauge end tail

1.

2.

3.