  • CX-1010INSTALLATION/WIRING GUIDE

    SK1659 Rev A

  • Page 1

    Installation / Wiring Guide

    ConfigurationMountingWiring

    Inputs

    Outputs

    Serial Communications

    Analog IO (Optional)Mounting

    Wiring

    DeviceNet (Optional)Logic Control

  • Page 2

  • Page 3

    CONFIGURATION

    This section will show you how to re-configure the CX-1010 for electrical compatibility. Complete thisprocedure prior to installation. This procedure does not require power to complete.

    The area that is involved in re-configuring the CX-1010 is the AC Power Input Voltage switch. This switchis located in an external location on the CX-1010. You will not be required to access the interior of theCX-1010.

    Figure 1 (page 5) illustrates the location of this switch.

  • Page 4

    WARNING

    You will damage the CX-1010 if youapply 230 VAC to the AC Power inputwhile the AC Power Input Voltage switchis in the 115 V position.

    CONTREX

    menupage

    page

    statuspar

    parcodeset

    help7

    8

    94

    5

    61

    2

    3clear

    0

    .enter

  • Page 5

    The AC Power Input Voltage switch is located on the rear of the CX-1010. The default configuration for theAC Power Input Voltage switch is 115 VAC.

    To re-configure for 230 VAC Input, move the switch from the 115V position (up) to the 230V position(down).

    Figure 1 AC Power Input Voltage Switch

    RS 485SERIALCOMM.

    +12 V AUX150 mA MAX

    FI_1A

    FI_1A

    FI_1B

    FI_1B

    COM

    FI_2A

    FI_2A

    FI_2B

    FI_2B

    COM

    RI_1

    RI_2

    USE COPPER WIRE ONLY.SELECT WIRE SIZE ACCORDING TO AMPACITYFOR 60/75 C WIRETIGHTEN TERMINALS TO 5 IN/LB

    J5

    DI_0

    DI_1

    COM

    DI_2

    DI_3

    DI_4

    DI_5

    COM

    DI_6

    DI_7

    DI_8

    DI_9

    COM

    DI_10

    DI_11

    DI_12

    DI_13

    COM

    DI_14

    DI_15

    J7

    FRE

    QU

    EN

    CY

    INP

    UTS

    RE

    G. I

    NP

    UTS

    DIG

    ITA

    L IN

    PU

    TS

    DIGITALOUTPUTS

    CONTROLOUTPUTTO DRIVE

    ACPOWERINPUT

    J6

    TD/RD+

    TD/RD

    COM

    +V_D0

    D0_0

    D0_1

    D0_2

    D0_3

    D0_4

    D0_5

    D0_6

    D0_7

    COM

    C0_SIG

    C0_COM

    L1

    L2/NEUT

    GND/PE

    INPUT VOLTAGE:115/230 VAC

    INPUT CURRENT:0.1 AMP

    INPUT FREQUENCY:50/60 HZ

    115V

    115V

    230V

    115V(default)

  • Page 6

    3.6"(9.1 cm)

    7.2"(18.3 cm)

    7.7"(19.6 cm)

    *6.3"(16.3 cm)

    4.0"(10.2 cm

    )

    DOOR PANEL(3.65" .03" 9.27 .07cmCUTOUT (

    CUTOUT7.25" .03"

    18.41 .07 cm ( )

    CONTREX

    menu page

    pagestatus

    par

    par

    codeset

    help

    78

    9

    45 6

    1 23

    0

    . enter

    * From the rear of the door panel to the back of the connectors

    clear

    Figure 2 CX1010 Cutout Dimensions and Mounting Guide

  • Page 7

    MOUNTING

    This section contains instructions for mounting the CX1010 in the door panel of an industrial electricalenclosure. The CX1010 is packaged in a compact 1/2 DIN vertical instrument enclosure that mounts easilyin the door of your industrial electrical enclosure. The CX-1010 meets the NEMA 4 and the IP65 standards.To ensure compliance with these standards, enclose the CX-1010 in a Nema 4 or IP65 industrial electricalenclosure.

    To mount the CX1010:

    1) The industrial electrical enclosure that will house the CX1010 must conform to the followingenvironmental conditions:

    Temperature: 0 - 55 degrees C (Internal enclosure temperature)

    Humidity: 0 - 95% RH non-condensing

    Environment: Pollution degree 2 macro - environment

    Altitude: To 3300 feet (1000 meters)

    2) The dimensions for the door panel cutout are 3.65"+ .03" x 7.25 +.03" (9.27 x 18.41cm). Seefigure 2. Allow two inches of clearance on both sides of the cutout and four inches ofclearance on the top and bottom of the cutout for mounting clamp attachments, wire routingand heat convection.

    3) Insert the CX1010 through the door panel cutout until the gasket and bezel are flush with thedoor panel (see figure 2).

    4) Slide the two mounting clamp bars into the slots that are located on either side of the CX1010. See figure 2. Tighten the mounting screws until the CX1010 is mounted securely inthe electrical enclosure. Do not overtighten.

  • Page 8

    * Power for frequency input sensors may be supplied by J5, pin 1. Total current should not exceed 150 mA .

    TD / RD +

    TD/ RD

    COMMON

    RS485SERIALCOMMUNICATIONSINTERFACE

    J1

    1

    2

    3

    TD / RD +

    TD/ RD

    COM

    RS

    485

    SE

    RIA

    L C

    OM

    M

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    R

    R

    R

    R

    R

    R

    ZERO SPEED

    HI SPEED ALARM

    LOW SPEED ALARM

    DEV ALARM 1

    DEV ALARM 2

    BATCH DONE

    CNTL OUT DIR

    DRIVE ENABLE

    EXTERNAL

    DC

    POWER

    SUPPLY

    (50V MAX)

    +

    R

    R

    J2+V_DO

    DO_0

    DO_1

    DO_2

    DO_3

    DO_4

    DO_5

    DO_6

    DO_7

    COM

    DIG

    ITA

    L O

    UT

    PU

    TS

    1

    2

    J3SIGNAL INPUT

    DRIVE COMMON

    CO

    NT

    RO

    LO

    UT

    PU

    TT

    O D

    RIV

    E

    CO_SIG

    CO_COM

    MOTOR DRIVE

    1

    2

    3

    1

    2

    3

    J4

    AC

    PO

    WE

    RIN

    PU

    T

    L1

    L2/NEUT

    GND/PE

    115 VACL1

    NEUT

    GND/PE

    230 VACL1

    L2

    GND/PE

    + 12V PWR

    A

    A

    B

    B

    COMMON

    J5

    NC

    NC

    LEAD

    QUADRATUREDIFFERENTIALSENSOR

    * + 12V_AUXFI_1A

    FI_1A

    FI_1B

    FI_1B

    COM

    FI_2A

    FI_2A

    FI_2B

    FI_2B

    COM

    RI_1

    RI_2

    FR

    EQ

    UE

    NC

    Y IN

    PU

    TS

    A

    A

    B

    B

    COMMON

    + 12V PWR

    FEEDBACK

    QUADRATUREDIFFERENTIALSENSOR

    CX-1010

    RE

    G IN

    DIG

    ITA

    L INP

    UT

    S

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    DI_0

    DI_1

    COM

    DI_2

    DI_3

    DI_4

    DI_5

    COM

    DI_6

    DI_7

    DI_8

    DI_9

    COM

    DI_10

    DI_11

    DI_12

    DI_13

    COM

    DI_14

    DI_15

    J7BLOCKSELECT ABLOCKSELECT B

    BLOCKSELECT C

    SETPOINT DIR

    INCREMENTBATCH COUNT

    RESET BATCHCOUNT

    REMOTESCROLL UP

    REMOTESCROLL DOWN

    FSTOP

    RSTOP

    HSTOP

    RUN

    JOG FWD

    JOG REV

    KEYPAD LOCKOUT

    NC

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    J6

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    FUSES

    1 A150 V

    Figure 3 CX1010 General Wiring

  • Page 9

    WIRING

    This section contains the input, output and serial communications wiring information for the CX1010.Please read this section prior to wiring the CX1010 to ensure that you make the appropriate wiringdecisions.

    NOTE: The installation of this motor control must conform to area and local electrical codes. See TheNational Electrical Code (NEC,) Article 430 published by the National Fire Protection Association,or The Canadian Electrical Code (CEC). Use local codes as applicable

    Use a minimum wire gauge of 18 AWG.

    Use shielded cable to minimize equipment malfunctions from electrical noise and terminate theshields at the receiving end only.

    Keep the AC power wiring (J4) physically separated from all other wiring on the CX1010. Failureto do so could result in additional electrical noise and cause the CX1010 to malfunction.

    Inductive coils on relay, contactors, solenoids that are on the same AC power line or housed in thesame enclosure should be suppressed with an RC network across the coil.

    A hand operated supply disconnect device must be installed in the final application. The primarydisconnect device must meet EN requirements.

    Install an AC line filter or isolation transformer to reduce excessive EMI noise, such as line notchesor spikes, on the AC power line.

    DANGER

    Hazardous voltages.Can cause severe injury, deathor damage the equipment.The CX1010 should only be installed by aqualified electrician.

  • Page 10

    INPUTS

    NOTE: The installation of this motor control must conform to area and local electrical codes. Refer to page9 before you begin wiring.

    AC Power Input(J4 pins 1, 2,3)The CX1010 operates on either a 115 VAC - 10% +15%, 0.250 Amp., 50/60 Hz or a 230 VAC -10% +15%,0.125 Amp, 50/60 Hz. Use the separate 3 pin connector(J4) for the power connection.

    * Fuse L1 for 115 VAC applications. Fuse L1and L2 for 230 VAC applications. Use 1 Amp250 normal blow fuses.

    Figure 4 AC Power Input

    L1

    Neutral (115 VAC)or L2 (230 VAC)

    GND/PE

    1

    2

    3

    J4

    *

    *

    WARNING

    You will damage the CX-1010 if you apply230 VAC to the AC Power inputwhen the AC Power Input Voltage switchis in the 115 V position.

  • Page 11

    Lead Frequency(J5 pins 1, 2, 4, 5, 6)Frequency Input 1

    The LEAD FREQUENCY Input acts as the lead signal when the CX1010 is in the Follower mode. Thewiring for the LEAD FREQUENCY is determined by the sensor. Figures 5 through 8 illustrate the wiring forthe various sensors.