10
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE Transactions on Power Delivery 1 Current Transformer Saturation Prevention using a Controlled Voltage Source Compensator Ehsan Hajipour, Student Member, IEEE, Mehdi Vakilian, Senior Member, IEEE, and Majid Sanaye-Pasand, Senior Member, IEEE Abstract—Current transformer (CT) saturation causes severe distortion in the measured current waveform which may lead to mal-operation of the protective devices. This paper proposes a low-cost, power electronic device to prevent the CT from saturation. The proposed compensator is inserted in series with the relay in the CT secondary circuit and acts as a controlled volt- age source (CVS). The proposed CVS generates a time varying voltage to cancel the voltage developed across the CT burden; therefore, the CT magnetic flux remains almost constant and undistorted during the power system transients. It will be shown that this device can precisely compensate fault current, inrush current, and other probable transient currents despite of its simplicity. The proposed device can be employed to compensate the already in-service CTs connected to non-digital and digital relays. Comprehensive computer simulations are carried out to validate the effectiveness of the proposed compensator. The performance of a sample compensator of this type is validated through special high current laboratory experiments (carried out over several hundred Amperes up to 1.6 kA) and the obtained results illustrate the capability of the proposed compensator to prevent CT saturation. Index Terms—Current transformer (CT), CT compensation, CT saturation, hardware-based compensator. I. I NTRODUCTION T HE accurate and proper performance of protection de- vices is directly related to the correct replication of power system high current waveform in the current transformer (CT) secondary terminal [1]. Consequently, current waveform dis- tortion due to CT saturation significantly threatens the reliable operation of the relays [2], [3]. CT saturation compensation is a safe and effective way to prevent the relays mal-operation. This paper mainly focuses on the saturation compensation of the already in-service CTs which may become undersized over the years due to: i) the unanticipated changes in the power system topology (i.e. transmission line construction) and thus, increase in the power system short circuit capacity [4], ii) implementation of auto-reclosing schemes in an existing power network [5]. In these cases, replacement of the undersized CT is an expensive and undesired solution, where the number of changes during a substation refurbishment needs to be kept minimum [6]. E. Hajipour and M. Vakilian are with the Center of Excellence in Power System Management and Control, Department of Electrical Engi- neering, Sharif University of Technology, Tehran 11365-11155, Iran (e-mail: e [email protected]; [email protected]). M. Sanaye-Pasand is with the Electrical and Computer Engineering School, College of Engineering, University of Tehran, Tehran 14395-515, Iran. He is also with the Control and Intelligent Processing Center of Excellence, Electrical and Computer Engineering School, University of Tehran, Tehran 14395-515, Iran (e-mail: [email protected]). In recent years, the new generation of digital relays is sometimes equipped with a software-based CT saturation detection/compensation unit [2]. This unit detects the inception of a CT saturation incident and tries to prevent the relay inappropriate operation by blocking its trigger command [7] or by reproduction of the distorted samples of the CT output current [8]. Various valuable algorithms have been presented in the literature which focus on the detection of CT saturation [1], [9], [10], and to digitally compensate the CT distorted output [4], [8], [11], [12]. These algorithms can be implemented only into the modern digital relays [13]. In addition, they might not be able to accurately reproduce the input current in all different scenarios. A major part of the already in-service relays are elec- tromechanical, static and initial digital type relays that do not support digital inputs and modern communication protocols. For example, a power system asset analysis implemented by National Grid USA in New York State depicts that over 85% of the relay population in their system are non-digital relays [14]. These types of relays cannot be equipped with the afore- mentioned software-based saturation compensation/detection algorithms. In this case, hardware-based compensation of the CT is a low-cost and effective solution that can be employed. A hardware-based CT compensator is an analog circuit inserted into the CT secondary circuit and prevents the CT from saturation. This type of compensators does not break the analog connection between the CT and the relay and can be employed to compensate a CT which is connected to either non-digital or digital relays. In [15]–[17], different hardware-based algorithms have been proposed to estimate and compensate the CT magnetizing current. These algorithms are only applicable to measurement CTs. In [18], the dc offset component of a CT’s secondary transient current is eliminated by injection of a similar compensating current into the CT secondary winding terminals. A major drawback of this method is the dependence of its performance on accurate estimation of the fault inception instant. Additionally, its performance will be affected by presence of noise [13]. In [5], the CT has been compensated during the dead time of an auto-reclosing scheme. Through the dead time interval, the CT primary winding is open-circuit and therefore, the proposed hardware compensator of [5] could eliminate the CT residual flux employing a bi-directional controlled switching. However, when the fault current is flowing in the power system, the CT primary current is not zero and consequently, the proposed compensator in [5] is not applicable. In [13] and [19], a resistor is dynamically inserted into the CT secondary circuit by a

Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

1

Current Transformer Saturation Prevention using aControlled Voltage Source Compensator

Ehsan Hajipour, Student Member, IEEE, Mehdi Vakilian, Senior Member, IEEE, andMajid Sanaye-Pasand, Senior Member, IEEE

Abstract—Current transformer (CT) saturation causes severedistortion in the measured current waveform which may leadto mal-operation of the protective devices. This paper proposesa low-cost, power electronic device to prevent the CT fromsaturation. The proposed compensator is inserted in series withthe relay in the CT secondary circuit and acts as a controlled volt-age source (CVS). The proposed CVS generates a time varyingvoltage to cancel the voltage developed across the CT burden;therefore, the CT magnetic flux remains almost constant andundistorted during the power system transients. It will be shownthat this device can precisely compensate fault current, inrushcurrent, and other probable transient currents despite of itssimplicity. The proposed device can be employed to compensatethe already in-service CTs connected to non-digital and digitalrelays. Comprehensive computer simulations are carried outto validate the effectiveness of the proposed compensator. Theperformance of a sample compensator of this type is validatedthrough special high current laboratory experiments (carried outover several hundred Amperes up to 1.6 kA) and the obtainedresults illustrate the capability of the proposed compensator toprevent CT saturation.

Index Terms—Current transformer (CT), CT compensation,CT saturation, hardware-based compensator.

I. INTRODUCTION

THE accurate and proper performance of protection de-vices is directly related to the correct replication of power

system high current waveform in the current transformer (CT)secondary terminal [1]. Consequently, current waveform dis-tortion due to CT saturation significantly threatens the reliableoperation of the relays [2], [3]. CT saturation compensation isa safe and effective way to prevent the relays mal-operation.This paper mainly focuses on the saturation compensation ofthe already in-service CTs which may become undersized overthe years due to: i) the unanticipated changes in the powersystem topology (i.e. transmission line construction) and thus,increase in the power system short circuit capacity [4], ii)implementation of auto-reclosing schemes in an existing powernetwork [5]. In these cases, replacement of the undersized CTis an expensive and undesired solution, where the number ofchanges during a substation refurbishment needs to be keptminimum [6].

E. Hajipour and M. Vakilian are with the Center of Excellence inPower System Management and Control, Department of Electrical Engi-neering, Sharif University of Technology, Tehran 11365-11155, Iran (e-mail:e [email protected]; [email protected]).

M. Sanaye-Pasand is with the Electrical and Computer Engineering School,College of Engineering, University of Tehran, Tehran 14395-515, Iran. Heis also with the Control and Intelligent Processing Center of Excellence,Electrical and Computer Engineering School, University of Tehran, Tehran14395-515, Iran (e-mail: [email protected]).

In recent years, the new generation of digital relays issometimes equipped with a software-based CT saturationdetection/compensation unit [2]. This unit detects the inceptionof a CT saturation incident and tries to prevent the relayinappropriate operation by blocking its trigger command [7]or by reproduction of the distorted samples of the CT outputcurrent [8]. Various valuable algorithms have been presented inthe literature which focus on the detection of CT saturation [1],[9], [10], and to digitally compensate the CT distorted output[4], [8], [11], [12]. These algorithms can be implemented onlyinto the modern digital relays [13]. In addition, they might notbe able to accurately reproduce the input current in all differentscenarios.

A major part of the already in-service relays are elec-tromechanical, static and initial digital type relays that do notsupport digital inputs and modern communication protocols.For example, a power system asset analysis implemented byNational Grid USA in New York State depicts that over 85%of the relay population in their system are non-digital relays[14]. These types of relays cannot be equipped with the afore-mentioned software-based saturation compensation/detectionalgorithms. In this case, hardware-based compensation of theCT is a low-cost and effective solution that can be employed.

A hardware-based CT compensator is an analog circuitinserted into the CT secondary circuit and prevents the CTfrom saturation. This type of compensators does not breakthe analog connection between the CT and the relay andcan be employed to compensate a CT which is connectedto either non-digital or digital relays. In [15]–[17], differenthardware-based algorithms have been proposed to estimateand compensate the CT magnetizing current. These algorithmsare only applicable to measurement CTs. In [18], the dcoffset component of a CT’s secondary transient current iseliminated by injection of a similar compensating current intothe CT secondary winding terminals. A major drawback ofthis method is the dependence of its performance on accurateestimation of the fault inception instant. Additionally, itsperformance will be affected by presence of noise [13]. In[5], the CT has been compensated during the dead time of anauto-reclosing scheme. Through the dead time interval, the CTprimary winding is open-circuit and therefore, the proposedhardware compensator of [5] could eliminate the CT residualflux employing a bi-directional controlled switching. However,when the fault current is flowing in the power system, the CTprimary current is not zero and consequently, the proposedcompensator in [5] is not applicable. In [13] and [19], a resistoris dynamically inserted into the CT secondary circuit by a

Page 2: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

2

An

alogue

Interface

Magn

etizing

Bran

ch

i1 i2Rb

Process Unit

vB µ-P

rocessor

The Proposed Compensator

i2

+

-

vC

T

Lb

+

-

CV

S U

nit

VCVS

vC

VS

+

-

Fig. 1. Schematic diagram of the proposed compensator.

power electronic switch, generating a flux to oppose the time-varying flux associated with the decaying dc component of thefault current. In this method, heat dissipation is a factor thatmight hinder its application [1].

It should also be noted that: while, all of the aforementionedhardware-based methods only focus on the CT compensationunder presence of a fault current, this paper opens a newdoor to reproduce other saturated current waveforms, such as:inrush current, harmonically polluted current [11], and evolv-ing faults. This paper employs a low-voltage dc source, fourpower-electronic switches, and a low-cost microprocessor toprevent CT saturation. Using a simple switching strategy, theproposed compensator applies a voltage (equal and opposite tothat of the CT burden) to the CT secondary circuit terminals.Therefore, the voltage across the CT core is kept virtuallyzero and thus, the CT magnetic flux remains almost constantand undistorted. Theoretically, the proposed compensator caninhibit CT saturation independent of the CT primary currentwaveform. In addition, this paper introduces a simple formu-lation to determine the appropriate parameters of the proposedcompensator. The results of a wide range of simulations whichare carried out on an accurate CT model has revealed theefficiency and reliability of the proposed method. Furthermore,the performance of the proposed method is verified against asample protective CT, through experimental results.

II. THE PROPOSED COMPENSATION ALGORITHM

A. Theoretical Background of the Proposed Compensator

The schematic diagram of the proposed compensator struc-ture is illustrated in Fig. 1. The proposed compensator isconnected in series with the CT burden, which consists ofthe CT internal resistance and reactance, the lead equivalentimpedance, and the relay burden. Therefore, the voltage acrossthe CT magnetic core vCT can be obtained as follows:

vCT (t) = vB(t) + vCV S(t) (1)

where vB and vCV S represent the voltage developed across theCT burden and the compensator output voltage, respectively.

In this paper, the compensator output voltage vCV S iscontrolled such that it satisfies the following integral equation:

t∫t0

vCV S(τ)dτ = −t∫

t0

vB(τ)dτ (2)

Therefore, the CT magnetic flux λ(t) can be computed using(1) and (2) through the following relation:

λ(t)−λ(t0)=t∫

t0

vCT (τ)dτ=t∫

t0

[vB(τ) + vCV S(τ)] dτ→

λ(t)−λ(t0)=t∫

t0

vB(τ)dτ +t∫

t0

vCV S(τ)dτ=0→λ(t)=λ(t0).

(3)where λ(t0) represents the CT magnetic flux at t0.

Theoretically, (3) shows that in an ideal operation of theproposed compensator, the CT magnetic flux remains constantover time, independent of the magnitude and waveform of theCT primary current and therefore, the CT will not saturate.This observation is valid for any current waveform suchas symmetrical sinusoidal current, fault current including adecaying dc component, inrush current and combination ofthem.

To implement the aforementioned compensation algorithm,firstly, the CT secondary current i2(t) is sampled by a highprecision current sensor. Then, as shown in Fig. 1, vB(t) canbe calculated as follows:

vB(t) = Rbi2(t) + Lbdi2(t)

dt(4)

where Rb and Lb are the resistance and inductance of the CTsecondary circuit. These parameters can be measured usingthe CVS unit as demonstrated in [20].

The proposed compensator estimates its required outputvoltage vCV S(t) based on the estimated vB(t) and through(2). Afterwards, the proper command is sent to the controlledvoltage source (CVS) unit and it applies vCV S(t) to the CTsecondary circuit terminals.

The following sections describe the proposed hardware ofthe CVS unit and its switching strategy to realize the relationin (2).

B. Hardware Implementation

Fig. 2 depicts hardware implementation of the pro-posed compensator. This hardware consists of a dc voltagesource, four power electronic switches (including freewheelingdiodes), an instant-on switching solid-state relay (IO-SSR),and a microprocessor which manages the switching sequence.To minimize the adverse effect of the power plant noise onthe proper performance of the proposed compensator, it isrecommended to install this device adjacent to the relay inthe substation relay room.

Under normal operating condition of the power system,the proposed compensator is bypassed by the IO-SSR. Thisnormally closed (NC) contactor will prevent occurrence of anyundesired open-circuit in the CT secondary circuit. After thedetection of a transient inception, the microprocessor issuesa control command to open the IO-SSR. Simultaneously, thecompensator which has been already bypassed by the IO-SSR,is inserted into the CT secondary circuit. The typical responsetime of an IO-SSR is less than 1 ms [21], while a CT wouldnot become saturated at least for about 1/6 of cycle (3.3 msfor a 50 Hz power system) after the fault inception [22].

In this paper, the instantaneous current algorithm [23] hasbeen employed for fast fault detection. In this method, atransient inception is detected when 16 consecutive samplesof the CT secondary current i2(t) exceed the CT nominal

Page 3: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

3

Signal Conditioning

VDC

i2

Gates

μProcessor

vC

VS

Control

IO-SSR

Controlled Voltage Source (CVS) Unit

Signal Processing Unit

Fig. 2. Hardware implementation of the proposed compensator.

secondary current (1 A or 5 A). Since this algorithm onlyuses three processor operations (two COMPARE instructions,and one ADD instruction), it can be implemented by usinga fast sampling rate (200 kHz employed in this paper). Atthis sampling frequency, this detection algorithm leads to adelay of 80 µs. It should be noted that during the operation ofthe compensator, the freewheeling diodes across the electronicswitches prevent the CT secondary current from being choppedabruptly [24].

In the proposed compensator, the microprocessor controlsthe CVS output voltage by turning the switches ON or OFF.By proper control of these switches, the microprocessor isable to generate arbitrary voltage pulses with desired widthand magnitude of [−VDC , 0, +VDC].

C. Switching Control Algorithm

Fig. 3 depicts the basic concept of the proposed switchingcontrol algorithm. This figure demonstrates a typical voltagedeveloped across the CT burden vB and its correspondingcompensator output voltage vCV S . As shown in Fig. 3, inthe proposed switching strategy, time is discretized throughapplication of a set of constant steps of ∆Td. At the beginningof each time step ti, a control command δion is sent fromthe microprocessor to the CVS. This command contains: 1)polarity of the desired voltage sgn(δion)=[−1,0,+1] and 2)width of the required pulse |δion| in percentage of ∆Td.

In the proposed switching control, the pulse width is de-termined such that the integral of vCV S(t) over each step of∆Td equals to the integral of vB(t) over the past recent timestep. For example, in Fig. 3, the δ5

on is selected in a way thatA1 equals A2 (A1 = A2). To achieve this, one may estimateδi+1on as follows:

VDCδi+1on ∆Td = −Rb

ti∫ti−1

i2(t)dτ − Lb

ti∫ti−1

di2(τ)

→ δi+1on = −Rb

VDC∆Td

[ti∫

ti−1

i2(t)dτ + Lb

Rb(i2(ti)− i2(ti−1))

](5)

The CT secondary current i2(t) is sampled at a frequencyof fs, 200 kHz in this paper. Therefore, the above integralwould be substituted by a simple trapezoidal rule of integrationdetermination and summation. It should be noted that in this

0 0.5 1 1.5 2 2.50

10

20

30

40

50

v B(V

)

0 0.5 1 1.5 2 2.5

0

-VD

Time (ms)

v CV

S (V

)

Td

t1

t3

t2

t4

1on 2

on 5on

1

2-VDC

ΔTd

Fig. 3. The basic concept of the switching control strategy.

Fault Detector

Com

pare

Switch on CVS unit

Close IO-SSR

CVSv

0

meas.CVSv

refv

NOT

AND

AND

Unhealthy Status

FD

Fig. 4. The proposed logic used to detect the compensator unhealthy status.

paper, the current sensor sampling rate is 200 kHz, while thecompensator output pulses are generated with delay frequencyof fd = 1/∆Td = 25 kHz, as shown in Fig. 3.

As it can be seen in Fig. 3, there is a time delay of∆Td between vCV S(t) and vB(t). In this paper, ∆Td is setto 40 µs. The effect of this time delay on the performanceof the proposed compensation method will be thoroughlyinvestigated in section III-B.

If the magnitude of VDC is not chosen properly, it ispossible to obtain δion > 1, through (5). In this case, δionshould be set to +1, or −1; depending on the sign of δion.A formula is introduced in section III, in order to select theVDC parameter appropriately and to prevent obtaining a valueof δion > 1.

D. Self-Checking Routine

Since the proposed compensator is installed in series withthe CT secondary circuit, it should be ensured that anyprobable failure of its components would not affect the ap-propriate performance of the protection system. Therefore,it is recommended to equip the device with a self-checkscheme. The proposed logic to check the health status of thedevice is depicted in Fig. 4. FaultDetector unit, which wasdescribed earlier, determines the power system condition. Ifpower system operates under normal condition, FD would bezero, otherwise FD = 1.

Under normal operation of the power system (FD = 0),the IO-SSR switch is closed and all of the CVS switches arekept in OFF state. Therefore, the output voltage across the

Page 4: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

4

CVS unit (vmeas.CV S ) would be zero (vmeas.

CV S = vref = 0). Ifoccurrence of any failure causes IO-SSR to open, then, anopen-circuit voltage would appear across the IO-SSR switch.The compensator monitors the CVS output voltage (vmeas.

CV S ),and if any non-zero voltage is observed, it switches theCVS unit ON in order to short the CT secondary circuit.Simultaneously, an alarm signal (Equipment Failure EF asstated in IEC 60044-8 [25]) will be sent to the substationcontrol room.

Under power system fault circumstance (FD = 1), theIO-SSR switch is opened and the CVS unit compensatesthe voltage developed across the CT burden. If any failurethreatens the proper operation of the CVS unit (such as burningof the switches), the measured output voltage of the CVS unit(vmeas.

CV S ) would not be equal to the reference voltage (vref =vCV S) selected by the processor. The processor monitors theCVS output voltage, and if a difference is found between thisvoltage and its reference (vmeas.

CV S 6= vref = vCV S), then theprocessor issues a close command to the IO-SSR and the CVSunit is bypassed. Simultaneously, an alarm signal (EquipmentFailure) will be sent to the substation control room.

As it can be seen, the IO-SSR and the CVS unit backupeach other and therefore, considerably reduce the compensatorprobability of threatening the proper operation of the protec-tion system under an unhealthy status.

III. SELECTION OF THE COMPENSATOR PARAMETERS

It is trivial that if the magnitude of dc voltage sourceVDC is selected equal or larger than the maximum magnitudeof vB(t), then, the proposed compensator can completelycancel the burden voltage at each time step and therefore,CT saturation will be certainly prevented. In this case, theCT magnetic flux remains constant over time. However, itis quite reasonable and practical to design the compensatorin such a way that the CT magnetic flux varies betweenits two saturation limits (positive and negative), and not toexceed these limits. In response, the magnitude of dc voltagesource VDC could be decreased to reduce the compensatorrequirement. To do so, the standard procedure of CT sizingbased on the CT saturation voltage VX is employed in thissection [26].

A. Appropriate Magnitude of DC Voltage Source

For a CT, the saturation voltage VX is defined as that ofsymmetrical voltage across the secondary winding of the CTfor which the peak induction just exceeds the saturation fluxdensity [26]. The CT saturation voltage is a key parameterfor the proper CT sizing. For example, (without using anycompensator) to avoid saturation of a CT due to a fault currentincluding a dc offset component and under a pure resistiveburden, the CT saturation voltage should be higher than theright hand side term of (6), as it is determined in [26]:

VX > Is × Zs

(1 +

X

R

)(6)

where Is is the primary current divided by the CT turns ratio,and Zs is the total secondary burden of the CT. X and R are

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 110

0.2

0.4

0.6

0.8

1

50.65

new oldX XV V

20.36

new oldX XV V

old newX XV V

Fig. 5. Appropriate value of α based on (8).

the primary system reactance and resistance up to the point ofdesired power system fault.

Assume that for an already in-service CT or for a newlyinstalled CT, it is required to increase the CT saturation voltagefrom V old

X to V newX by using the proposed compensator.

Parameter α is defined as follows:

α =VDC√2V new

X

(7)

It is shown in the appendix that the new saturation voltageof the CT would be equal or greater than V new

X , if α satisfiesthe following constraint:

α

[√1− α2

α− π

2− sin−1α

]≤ V old

X

V newX

(8)

Fig. 5 depicts the minimum value of α which satisfies theequality condition of relation (8), while the ratio of V old

X toV newX (the right hand side term in this relation) is varied. Ifα is set to 1, then, the compensator completely cancels theeffect of the voltage developed across the CT burden andconsequently, the CT magnetic flux remains constant overtime. While, If α < 1, then the magnetic flux λ(t) can varyover time, however it would not exceed the CT saturationflux and consequently, the CT will not saturate. In this case,the compensator supports the CT to feed its burden up toits nameplate rating without losing its accuracy. Refer to theappendix for more detailed description.

The steps which should be followed for proper determina-tion of VDC are summarized as follows:

1) The real saturation voltage of the CT is obtained usingits nameplate information or through some proper testsand is represented by V old

X ;2) Based on the power system parameters, and the CT

burden, the required saturation voltage of the CT V newX

(to avoid its saturation) is calculated through (6);3) By solving the equality condition in relation (8), the

minimum acceptable value of α is determined.4) The appropriate value of VDC is calculated as follows:

VDC ≥ α (1 + ε)√

2V newX (9)

where ε represents the error which is introduced intothis computation process by inherent time delay ofthe compensator, as will be discussed in the followingsection.

5) According to IEC 60044-8 [25], the rated auxiliary dc

Page 5: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

5

5 10 15 20 25 30 35 40 450

10

20

30

fd (kHz)

(%

) = 5.03%25 kHz5.03%

df

(kHz)df

%

Fig. 6. The compensation error ε contributed by the compensator time delay(V new

X /V oldX = 4).

power supply voltage of an electronic current trans-former (ECT) can be selected from the standard valuesof 24 V, 48 V, 60 V, 110 V, 220 V. Therefore, thenearest larger value of these standard levels should bechosen as VDC .

B. Proper Value of ∆Td

As it can be seen in Fig. 3, a time delay equal to ∆Td existsbetween the compensator output voltage vCV S and the voltageacross the CT burden vB . It is shown in the appendix that thisdelay will result in an error of ε as follows:

ε = 2V newX

V oldX

sin (πf∆Td) (10)

where f is the power system nominal frequency.Fig. 6 depicts ε versus the delay frequency fd = 1/∆Td

where V newX /V old

X = 4. As it can be seen, through thisequation a delay frequency of 4 kHz results in an error ofabout 31.4%. However, if the frequency is increased, its errorreduces rapidly to a value of about 5.03% in fd = 25 kHz. Inthis paper, the delay frequency is set to 25 kHz (in a 50 Hzpower system) and therefore, ∆Td would be 40 µs. The errorintroduced by this time delay is canceled through choosing aproper value for VDC as in(9).

IV. SIMULATION RESULTS

In this section, several simulations are presented to showthe effectiveness of the proposed compensator. An appropriateCT model, including accurate representation of the magneticcore hysteresis characteristic is developed using the Jiles-Atherton theory [27]. The simulated CT is 300:1-8 VA andits parameters have been provided in [4]. The CT saturationvoltage is V old

X = 205 V. Assume that, in order to avoid CTsaturation it is required to increase the CT saturation voltageto V new

X = 2V oldX = 410 V. Realizing that the delay frequency

fd is set to 25 kHz, the error of ε would be 2.5%. In addition,α is equal to 0.36 according to Fig. 5. Therefore, using (9), therequired voltage magnitude of the dc voltage source is 214.0V, while it is assumed to be 220 V (a standard dc voltagelevel for auxiliary dc power supply in the substations [25]).The CT burden Zb is the CT nominal burden of 8 Ω (withpower factor of 0.8). The current sensor sampling frequencyfs is assumed to be 200 kHz.

-50

0

50

Cur

rent

(A)

-500

0

500

Vol

tage

(V)

40 45 50 55 60 65 70 75 80-2.0

0

2.0

B (T

)

Time (ms)

Bsat

(b)

(a)

(c)

Fig. 7. a) The CT secondary current without (solid line) and with (dashline) compensation, b) vB (dash line) and vCV S (solid line), c) the CTmagnetic flux density without (solid line) and with (dash line) the proposedcompensator.

A. Steady State Analysis

In this section, performance of the proposed compensator isinvestigated during steady state symmetrical ac current injec-tion. The total CT secondary circuit impedance |RCT + Zb|is 9.76 Ω. Therefore, an ac current with the magnitude ofi2 = 42.0 A generates V new

X = 410 V across the CT sec-ondary terminal. Fig. 7 depicts the performance of the CTwith and without the proposed compensator. Fig. 7(a) showsthat without the compensation application, the CT becomesdeeply saturated, while the proposed compensator prevents CTsaturation. Fig. 7(b) depicts the voltage across the CT burdenvB and the compensator output voltage vCV S . As it can beseen, vCV S is in phase with vB and in opposite polarity. Fig.7(c) illustrates the corresponding magnetic flux density B. Asit can be seen, in the compensated CT, the maximum value ofB is about Bsat, which verifies the formulas presented in thepaper appendix, where the value of VDC is chosen in such away to limit the maximum of B to Bsat.

Fig. 8 depicts the CT input/output ratio curve between theRMS of its primary current I ′1 and the RMS of its secondarycurrent I2 under different values of VDC . In an ideal operationof the CT, this curve should follow a straight line of I2=I ′1. As it can be seen in this figure, by variation of VDC ,CT accuracy limit primary current Ial [25] can be arbitrarytuned to avoid the core saturation. Without compensation, theCT accuracy limit primary current is Ioldal = 25.5 A (indicatesa 5P20 CT based on IEC 60044-8 [25]). However, while theVDC parameter is set to 220 V, the CT accuracy limit primarycurrent is increased to Inewal ≈ 2Ioldal = 48.8 A (represents a5P40 CT based on IEC 60044-8 [25]). Therefore, one mayconclude that V new

X = 2V oldX ; as it was requested in the first

stage.

B. Transient Currents Analysis

This section investigates the performance of the proposedcompensator during power system transient currents. A perma-nent fault of 2.5 kA (rms) has a fully offset decaying dc com-ponent, and a time constant of τ = 100 ms has been injected

Page 6: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

6

0 20 40 60 80 1000

20

40

60

80

100

I1' (A)

I 2 (A)

110 VUncomp.220 V VDC

440 V48.8 A

35.2 A

67.1 A

25.5 A

Fig. 8. CT input/output ratio curves when the VDC parameter varies.

50 100 150 2000

1

2

B (T

)

Time (ms)

-200

0

200

Vol

tage

(V)

0

10

20

Cur

rent

(A)

UncompensatedCompensated

idealUncomp.Comp.

(c)

(b)

(a)

Fig. 9. a) The CT secondary current in the presence of a 2.5 kA fault, b)vB(t) (dash line) and vCV S(t) (solid line), c) the CT magnetic flux density.

to the CT primary terminals, as shown in Fig. 9(a). Withoutusing the compensation scheme, the CT experiences a deepsaturation, while the compensator prevents this phenomenon.Fig. 9(b) depicts the compensator output voltage vCV S and thevoltage across the CT burden vB . As it can be seen, in thiscase, the maximum of vB is less than VDC = 220 V (similar toa case of α = 1), therefore, as shown in Fig. 9(c), the proposedcompensator can properly maintain the magnetic flux densityB virtually zero. This observation verifies the effectiveness ofthe proposed switching strategy. A typical full-cycle discreteFourier filter (DFT) has been employed to extract the CTratio error and the CT phase displacement. For the scenarioconsidered here, the maximum CT ratio error and phase errorare less than 0.04%, and 1.4 minutes, respectively.

Fig. 10(a) illustrates a similar fault with a magnitude of 3.5kA. As it can be seen in Fig. 10(b), once α is selected lessthan 1 (0.36 in this study), the compensator lets the CT tosupply its burden, without saturation, up to its nominal rating.Therefore, the CT magnetic flux density deviates from zero;however, it is shown in the appendix that the CT magneticflux would stay certainly below the CT saturation flux λsat.Thus, the CT will not enter its saturation region. In thisscenario, the CT maximum ratio error, and the CT maximum

50 100 150 2000

1

2

B (T

)

Time (ms)

-200

0

200

Vol

tage

(V)

-100

1020

30

Cur

rent

(A)

idealUncomp.Comp.

CompensatedUncompensated

(c)

(b)

(a)

Fig. 10. a) The CT secondary current in the presence of a 3.5 kA fault, b)vB(t) (dash line) and vCV S(t) (solid line), c) the CT magnetic flux density.

phase displacement are less than 0.21%, and 3.6 minutes,respectively.

Fig. 11(a) depicts a complex fictitious scenario to verifythe independence of the proposed compensator from the CTprimary current waveform. In this imaginary case, an inrushcurrent waveform is appeared in the first two cycles of the CTprimary current. Then, a permanent fault is happened. The du-ration of this initial fault assumed to be 2 cycles, followed byan auto-reclosing dead time of 2 cycles. Afterward, the circuitbreakers are closed again and the second fault is experienced.As it can be seen in Fig. 11(b), the proposed compensatoroutput voltage vCV S precisely follows the variation of vB .Fig. 11(c) illustrates how the compensator properly preventsthe CT core from saturation, while without using the proposedcompensator, the CT experiences a deep saturation. In thiscase, the CT maximum ratio error and its phase displacementare less than 0.06%, and 5.2 minutes, respectively. This figuredepicts that the proposed compensation methodology worksproperly while it is independent of the current waveshape(inrush, fault, and combination of them). This promisingfeature distinguishes the proposed compensator from othersavailable in the literature [13], [15]–[19].

V. EXPERIMENTAL RESULTS

In order to show the reliability and effectiveness of the pro-posed compensator, experimental test are also carried out. Thedeveloped compensator consists of: i) a low-cost dsPIC33FMicrochip as the microprocessor, ii) a LA 25-NP LEM Halleffect current sensor with high immunity to external infer-ences, iii) four IRFP3710 IOR fast power MOSFET switchesand, iv) a Siemens V2306 miniature power PCB relay as thenormally closed (NC) IO-SSR contactor. In addition, an AC-DC converter (220 Vac to 24 Vdc) has been employed as thecompensator dc voltage source.

A 300:1 10P5-1VA protective current transformer is chosento be compensated. The CT saturation voltage V old

X is 4.82 Vand it is desired to increase this saturation voltage to V new

X =

Page 7: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

7

0 20 40 60 80 100 120 140 160 1800

1

2

B (T

)

Time (ms)

-200

0

200

Vol

tage

(V)

-10

0

10

20C

urre

nt (A

)

IdealUncomp.Comp.

Comp.Uncomp.

(c)

(b)

(a)

Fig. 11. a) The CT secondary current in an autoreclosing scheme, b) vB(t)(dash line) and vCV S(t) (solid line), c) the CT magnetic flux density.

4V oldX = 19.28 V. The delay frequency is 25 kHz and based on

(10), ε is 5.03%. Through (8), for V oldX /V new

X =0.25, α wouldbe equal to 0.593. Therefore, VDC should be selected greaterthan 17.00 V as presented in (9); which is set to 20 V in theexperiments.

Fig. 12 demonstrates schematic diagram of the implementedtest setup. A regulating transformer and a variable resistorare employed to control the magnitude of the circuit current.The illustrated diode would be inserted only in the transienttests. A large 50:1 short-circuited power transformer is usedto generate high magnitude currents. A clamp-on ammeterand a typical commercial ammeter are used to monitor theRMS of CT primary and secondary currents during the steady-state experiments. In addition, a standard CT is inserted to thehigh current loop to record the primary current wave shapeduring the transient analysis. A digital oscilloscope saves allthe measured data to the in-site laptop. Based on IEC 60044-8[25], for a CT with 1 A secondary rated current and 1 VA ratedpower, the rated burden is 1 Ω. However, in this paper, in orderto investigate the performance of the proposed compensatorunder high degree of the CT saturation, the under-test CTburden is selected to be 6 Ω (purely resistive). By increasingthe CT burden, the required primary current to saturate theCT has been proportionally decreased. The implemented testcircuit is capable of generating steady state sinusoidal currentsup to 1.6 kA.

A. Steady State Experiments

In these experiments, the injected primary current is sinu-soidal. The RMS value of CT primary and secondary currentsare read using a clamp-on ammeter, and a regular ammeter,respectively, as shown in Fig. 12. The obtained input/outputratio curves are depicted in Fig. 13, when the dc voltagesource VDC is set to 20 V, 28 V and 40 V, respectively.Please note that these voltage levels are not in compliance withIEC 60044-8 [25] and just have been selected to investigatethe compensator performance. In addition, Fig. 13 illustrates

Regulating Transformer

220 V

50:1 Transformer

Test CT

High CurrentLoop Burden

CVS Unit

Current Sensor

Switches Gates

Analogue

Interface

dsP

IC33F

J256 USB

Process Unit

I1

I2

Clamp

Standard CT

AAmmeter

R

IO-SSR

Diode(transient test)

Fig. 12. Schematic diagram of the experimental test setup.

TABLE ILABORATORY-MEASURED RATIO ERRORS AND PHASE DISPLACEMENTS

Compensated (VDC = 20 V) UncompensatedI1(A) εr(%) 4ϕ (minutes) εr(%) 4ϕ (minutes)

381 0.81 56.8 3.18 263.8558 1.12 79.2 21.3 1283.4771 0.60 63.4 36.8 1875.6912 0.57 32.6 49.7 2340.8

1098 7.71 131.8 58.1 2628.21353 20.4 337.2 60.2 2806.61398 22.9 354.0 63.1 2927.61569 29.7 476.8 74.1 3010.2

the corresponding results for the uncompensated CT. Table Ireports the CT ratio error (εr), and its phase displacement(4ϕ) ) when the CT is compensated (employing a VDC = 20V) versus the uncompensated CT related parameters.

As it can be seen in Fig. 13, since the CT burden is 6 Ω andthe CT saturation voltage V old

X is 4.82 V, the CT will begin tosaturate in I2 of about 0.8 A (I1 = 240 A) without the proposedcompensator. It is worth mentioning that while the CT burdenis chosen significantly larger than its rated value (6 Ω insteadof 1 Ω), the CT saturates even under its primary rated current(I1=300 A). However, with the proposed compensator, the acsaturation of CT occurred at I1 equal to 1024 A and 1179 Afor VDC equal to 20 V and 28 V, respectively. For VDC = 40V, CT saturation would happen for a current more than themaximum permissible current of the test setup (I1 = 1.6 kA).The new obtained saturation voltages V new

X for VDC = [20 V,24 V, 40 V] are equal to [4.267 V old

X , 4.91 V oldX , >6.25 V old

X ].The CT saturation voltage is successfully increased to 4V old

X

by VDC equal to 20 V, as predicted through (9).The recorded CT secondary currents with and without the

proposed compensator are depicted in Fig. 14, when I1 isequal to 885 A. As it can be seen in Fig. 14(a), withoutthe compensator, CT becomes deeply saturated, while thecompensator prevents the CT core from saturation. Fig. 14(b)represents the voltage across the CT burden vB and thecompensator output voltage vCV S . As it can be seen, vCV S

is in phase with vB but with opposite polarity.A 20 VDC voltage source can prevent the CT from satura-

Page 8: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

8

0 200 400 600 800 1000 1200 1400 16000

1

2

3

4

5

6

I1 (A)

I 2 (A)

Uncomp.

28 V20 V

40 V1024 A

1179 A

240 A

VDC

Fig. 13. Experimentally measured input/output ratio curves without and withthe proposed compensator when the CT burden is 6 Ω.

0 20 40 60 80 1000

-20

0

20

Vol

tage

(V)

Time (ms)

-4-2024

Cur

rent

(A)

IdealUncomp.Comp.

(a)

(b)

Fig. 14. a) The measured CT secondary current without (dash line) and with(solid line) the proposed compensator, b) the recorded voltage across the CTburden vB(t) (dash line) and the compensator output voltage vCV S(t) (solidline).

tion up to 4Ioldal =1024 A. In Fig. 15, a 1360 A symmetrical accurrent is applied to the CT when the compensator dc voltagesource is set to 20, 28, and 40 V, respectively. As it can beseen, 20 V and 28 V dc voltage sources cannot prevent CTsaturation. However, if it is compared with the uncompensatedCT, the depth of CT saturation is noticeably decreased. Thisfigure shows how the compensator prevents CT saturation upto its boundaries, even with improper sizing of VDC .

B. Transient Experiments

In order to verify the performance of the proposed methodduring a transient current injection, a diode is inserted into thepresented circuit in Fig. 12. Therefore, the CT primary currentwould be a half-wave rectified waveform which is similar toa typical inrush current. The regulating transformer is tunedto obtain a primary current with maximum of 650 A. Fig.16 depicts the test setup and a typical recorded signal. Asit can be seen, to achieve a higher current level, the high-current capacity primary conductor has been wound in multi-turns (four turns) around the CT under test.

Fig. 17(a) illustrates the measured currents at the secondaryterminals of both the standard and under-test CTs, withoutthe proposed compensation. As it can be seen, the under-testCT experiences a very deep saturation. Fig. 17(b) depicts theresults of a same test when the under-test CT is compensatedwith the proposed compensator. As it can be seen, the proposed

10 20 30 40 50 60 70 80

-5

0

5

Cur

rent

(A)

Time (ms)

20 V 28 V 40 V Uncompensated

Fig. 15. Performance of the proposed compensator when VDC is selectedless than its proper value.

Standard CT

Under-Test CTClamp

1) Regulating transformer2) 50:1 single-phase power transformer

3) Under test and Standard CTs4) The proposed compensator

5) Digital oscilloscope6) A typical measured transient current

Fig. 16. Transient test setup and a typical recorded signal.

compensator prevents the CT deep saturation. However, theeffect of a very slight saturation can be seen on the CTsecondary current waveform which is due to overlooking theinductance of the CT burden. Fig. 17(c) depicts the voltagemeasured across the CT burden vB and the compensatoroutput voltage vCV S . Note that none of the known hardware-based compensators can perform well in the presence of thepresented transient current. For example, since this currentdoes not have negative half-cycles, dynamically insertion of aresistor [13], [19] could not help to suppress the CT saturation.

VI. CONCLUSIONS

A hardware-based compensator using a controlled voltagesource has been introduced to prevent CT saturation. Thiscompensator cancels the voltage developed across the CTburden and therefore, prevents the CT magnetic flux fromentering its saturation region. Some promising features of theproposed compensation method are summarized as follows:

Page 9: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

9

40 60 80 100 120 140 160 180-20

-10

0

10

Vol

tage

(V)

Time (ms)

0

1

2

Cur

rent

(A)

0

1

2C

urre

nt (A

)

(a)

(b)

(c)

Fig. 17. a) The CT primary (solid line) and secondary (dash line) currentswithout the proposed compensator, b) CT primary (solid line) and secondary(dash line) currents with compensation, c) recorded vB (dash line) and vCV S

(solid line).

• The ability to compensate current signal for both non-digital and digital relays;

• The ability to compensate both in-service and newlyinstalled CTs;

• Eliminating the requirement for replacing the in-serviceCTs with larger ones;

• Preventing false operation of the protective relays due toCT saturation;

• Providing a simple theoretical control strategy with theability to compensate different possible current wave-forms (fault current, inrush current, evolving fault, etc);

• Low-cost hardware preserving a simple hardware struc-ture, while having a set of appropriate design parameters.

The reliability and effectiveness of the proposed compen-sator has been verified through a wide range of simulationstudies. The carried out experimental tests depicts the promis-ing performance of the proposed device.

APPENDIXDERIVATION OF THE FORMULAS FOR THE PARAMETERS

1) Magnitude of VDC: Assume that it is determined toincrease the CT saturation voltage to V new

X . Therefore, themaximum anticipated steady state voltage across the CTburden would be:

vB(t) =√

2V newX sin(2πft) (A.1)

Fig. A.1 depicts this voltage across the CT burden. Assumethat the compensator dc voltage source is equal VDC . Ideally,the compensator output voltage vCSV can cancel vB while it isless than VDC . Therefore, the voltage across the CT magneticcore vCT would be:

vCT (t) =

0 |vB(t)| ≤ VDC

vB(t)∓ VDC |vB(t)| > VDC(A.2)

Fig. A.1 illustrates a typical waveform of vCT . In this figure,θ demonstrates the intersection point of VDC and vB .

0 5 10 15 20

-100

-50

0

50

100

t (rad/s)

Vol

tage

(V

)

2 3

2 2

DCV

DCV

0

0

radωt s

( )Bv t

( ) ( )CT B DCv t v t V

Fig. A.1. The voltage across the CT terminal vCT (t) under ideal compen-sation and steady-state ac current injection.

θ = sin−1

(VDC√2V new

X

)(A.3)

The CT magnetic flux associated with vCT can be eval-uated by integration of (A.2). Here, the CT operates understeady-state condition and due to voltage waveform symmetryλ(2π) = λ(0). Therefore, the maximum CT magnetic fluxλmax can be written as:

λmax =VDC

2πf

[cot θ − π

2+ θ]

(A.4)

It is required to limit this magnetic flux to the CT saturationflux λsat that can be calculated based on the real CT saturationvoltage V old

X through the following relation [26]:

λsat =V oldX√2πf

(A.5)

Considering (A.4) with (A.5), one may conclude (A.6) inorder to avoid CT saturation:

VDC

[cot θ − π

2+ θ]≤√

2V oldX (A.6)

Defining α = VDC/(√

2V newX ), (A.6) can be rewritten as

follows:

α

[√1− α2

α− π

2− sin−1α

]≤ V old

X

V newX

(A.7)

2) Selection of ∆Td: Assume that the compensator outputvoltage vCSV has a time delay equal to ∆Td correspondingto vB . In addition, vB has its maximum foreseen magnitudeas presented in (A.1). Here, the voltage across the CT is:

vCT (t) =√

2V newX [sin (2πft)− sin (2πf (t+ ∆Td))]

→ vCT (t) =√

2V newX cos (2πft) [2 sin (πf∆Td)]

(A.8)Therefore, the CT magnetic flux can be calculated as:

λεmax =

√2V new

X sin (πf∆Td)

πf(A.9)

Considering λsat from (A.5), the error contributed by thetime delay ε can be calculated as follows:

ε =λεmax

λsat= 2

V newX

V oldX

sin (πf∆Td) (A.10)

REFERENCES

[1] B. Schettino, C. Duque, P. Silveria, P. Ribeiro, and A. Cerqueira, “Anew method of current-transformer saturation detection in the presenceof noise,” IEEE Trans. Power Del., vol. 29, pp. 1760–1767, Aug. 2014.

[2] M. Stanbuty and Z. Djekic, “The impact of current transformer saturationon transformer differential protection,” IEEE Trans. Power Del., vol. 30,no. 3, pp. 1278–1287, June 2015.

Page 10: Current Transformer Saturation Prevention using a ...kresttechnology.com/krest-academic-projects/krest... · 2 R b Process Unit v B µ-Processor The Proposed Compensator i 2 + -v

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEETransactions on Power Delivery

10

[3] T. Smith and R. Hunt, “Current transformer saturation effects oncoordinating time interval,” IEEE Trans. Ind. Appl., vol. 49, no. 2, pp.825–831, Mar. 2013.

[4] F. Badrkhani, M. Sanaye-Pasand, M. Davarpanah, A. Rezaei-Zare, andR. Iravani, “Compensation of the current-transformer saturation effectsfor digital relays,” IEEE Trans. Power Del., vol. 26, pp. 2531–2540,Oct. 2011.

[5] E. Hajipour, M. Salehizadeh, M. Vakilian, and M. Sanaye-Pasand,“Residual flux mitigation of protective current transformers used in anauto-reclosing scheme,” IEEE Trans. Power Del., 2015, Early Access.

[6] D. Dolezilek, “Case study: replace substation wiring with rugged fibercommunications,” in IEEE Power Syst. Comf. and Expostion (PSCE),Phoenix, AZ, 2011, pp. 1–8.

[7] W. Rebizant, J. Szafran, and A. Wiszniewski, Digital Signal Processingin Power System Protection and Control. Springer-Verlag, 2011.

[8] N. Chothani and B. Bhalja, “New algorithm for current transformersaturation detection and compensation based on derivatives of secondarycurrents and Newton’s backward difference formulae,” IET Gener.Transm. Distrib., vol. 8, no. 5, pp. 841–850, 2014.

[9] E. dos Santos, G. Cardoso, P. Farias, and A. de Morais, “CT saturationdetection based on the distance between consecutive points in the plansformed by the secondary current samples and their difference-functions,”IEEE Trans. Power Del., vol. 28, no. 1, pp. 29–37, Jan. 2013.

[10] Q. Wu, Z. Lu, and T. Ji, Protective Relaying of Power System UsingMathematical Morphology. Berlin, Germany: Springer-Verlag, 2009.

[11] A. Wiszniewski, W. Rebizant, and L. Schiel, “Correction of currenttransformer transient performance,” IEEE Trans. Power Del., vol. 23,pp. 624–632, Apr. 2008.

[12] E. Hajipour, M. Vakilian, and M. Sanaye-Pasand, “Current transformersaturation compensation for transformer differential relays,” IEEE Trans.Power Del., vol. 30, no. 5, pp. 2293–2302, Oct. 2015.

[13] M. Davarpanah, M. Sanaye-Pasand, and R. Iravani, “Saturation supres-sion approach for the current transformer-Part I: Fundamental conceptsand design,” IEEE Trans. Power Del., vol. 28, no. 3, pp. 1928–1935,July 2013.

[14] “Report on the condition of physical elements of transmission anddistribution systems,” Niagara Mohawk Power Corp., NY, Tech. Rep.CASE 06-M-0878, 30 Sept. 2011.

[15] Q. Xu, A. Refsum, and R. Watson, “Application of external compen-sation to current transformers,” IEE Pro. Sci. Meas. and Technol., vol.143, no. 2, pp. 147–150, Mar. 1996.

[16] D. Slomovitz and H. de Souza, “Shielded electronic current transformer,”IEEE Trans. Instrum. Meas., vol. 54, no. 2, pp. 500–502, Apr. 2005.

[17] A. Baccigalupi and A. Liccardo, “Low-cost prototype for the electroni-cally compensation of current transformers,” IEEE Sens. J., vol. 9, no. 6,pp. 641–647, June 2009.

[18] D. Bradley, C. Gray, and D. O’Kelly, “Transient compensation of currenttransformers,” IEEE Trans. Power App. Syst., vol. PAS-97, no. 4, pp.1264–1271, July 1978.

[19] M. Davarpanah, M. Sanaye-Pasand, and R. Iravani, “Saturation su-pression approach for the current transformer-Part II: Performanceevaluation,” IEEE Trans. Power Del., vol. 28, no. 3, pp. 1936–1943,July 2013.

[20] E. Hajipour and M. Vakilian, “Accurate protection current transformerparameters determination method under high noise immunity,” in 23rdIranian Conf. Elect. Eng. (ICEE), Tehran, Iran, 2015, pp. 1545–1550.

[21] Solid state relays general information, Carlo Gavazzi Company.[Online]. Available: www.carlogavazzisales.com

[22] J. Pan, K. Vu, and Y. Hu, “An efficient compensation algorithm forcurrent transformer saturation effects,” IEEE Trans. Power Del., vol. 19,pp. 1623–1628, Oct. 2004.

[23] M. Ohrstrom, “Fast fault detection for power distribution systems,”Master’s thesis, Royal Institute of Technology (KTH), Stockholm, 2003.

[24] F. de Leon, A. Farazmand, S. Jazebi, D. Deswal, and R. Revi, “Elimina-tion of residual flux in transformers by the application of an alternatingpolarity dc voltage source,” IEEE Trans. Power Del., vol. 30, no. 4, pp.1727–1734, Aug. 2015.

[25] Instrument Transformers- Part 8: Electronic Current Transformers, IECStd. 60 044-8, 2002.

[26] IEEE Guide for the Application of Current Transformers Used forProtective Relaying Purposes, IEEE Std. C37.110, 1996.

[27] U. D. Annakkage, P. G. McLaren, E. Dirks, R. P. Jayasinghe, and A. D.Parker, “A current transformer model based on the Jiles-Atherton theoryof ferromagnetic hysteresis,” IEEE Trans. Power Del., vol. 15, pp. 57–61, Jan. 2000.

Ehsan Hajipour (S’12) received the B.Sc. andM.Sc. degrees in electrical engineering from SharifUniversity of Technology, Tehran, Iran, in 2008 and2010, respectively, where he is currently pursuingthe Ph.D. degree.

His research interests include power system pro-tection, power system optimization, and digital sig-nal processing.

Mehdi Vakilian (M’95-SM’15) received the B.Sc.degree in electrical engineering and the M.Sc. degreein electric power engineering from Sharif Universityof Technology, Tehran, Iran, in 1978 and 1986,respectively, and the Ph.D. degree in electric powerengineering from Rensselaer Polytechnic Institute,Troy, NY, USA, in 1993.

He was with the Iran Generation and TransmissionCompany, Tavanir, Iran, from 1981 to 1983, andthen with Iranian Ministry of Energy from 1984 to1985. Since 1986, he has been with the faculty of

Department of Electrical Engineering of Sharif University of Technology,Tehran. During 2001 to 2003 and since 2014, he has been Chairman of thedepartment. From 2003 to 2004 and for part of 2007, he was on leave ofstudy at the School of Electrical Engineering and Telecommunications of theUniversity of New South Wales, Sydney, Australia. He has been the Directorof the Power System Educational Group in the department for about six years.He is also the Director of a committee in charge of restructuring the ElectricalEngineering Undergraduate Education at Sharif University of Technology,Tehran, from 2007 to now. His research interests are transient modeling ofpower system equipment, especially power transformers; optimum design ofhigh-voltage equipment insulation; monitoring of power system equipmentand their insulation; power system transients; and distribution system studies.

Majid Sanaye-Pasand (M’98-SM’05) received theB.Sc. degree in electrical engineering from TheUniversity of Tehran, Tehran, Iran, in 1988 andthe M.Sc. and Ph.D. degrees in electrical engineer-ing from The University of Calgary, Calgary, AB,Canada, in 1994 and 1998, respectively.

Currently, he is a Professor with the School ofElectrical and Computer Engineering, University ofTehran. His research interests include power systemprotection, control, and transients.