APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Page 1 of 10 ATS450, 4/18/12 Proprietary Document
Mechanical Integrity Report for the
CURI Tank 3901-A
at
208 North Palmetto Boulevard
Clemson, South Carolina 29631
Inspection: 26 September 2012
Prepared by: George E. Matthews, E.I.T. Senior Consultant
Reviewed by: Jeremy M. Orr, P.E., C.W.I. Principal Engineer - Manager
Purchase Order Number: CU00134445 ATS Job Number: 187436
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Table of Contents
Page 2 of 10 ATS450, 4/18/12 Proprietary Document
Table of Contents General Information, Background, Equipment Orientation and Access
Page 3
Present Condition and Analysis Page 4 Action Items Page 6 Future Inspections, Personnel Qualifications and Reference Industry Codes and Standards
Page 7
Photographs Page 8 Appendix A: NDE Report Appendix B: Calculations
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
General Information, Background, Equipment Orientation and Access
Page 3 of 10 ATS450, 4/18/12 Proprietary Document
Design Pressure Unknown Design Temperature Unknown Operating Pressure Atmospheric Operating Temperature Ambient
Contents None (out of service)
Specific Gravity 1.0 (used for calculations)
Shell Height / Length 11 feet Diameter 40 feet Manufacturer Unknown Year Constructed Unknown Serial Number Unknown National Board Number Not applicable
Material Unknown Carbon Steel Previous Inspection None Drawing(s) None
NDE Performed by George Matthews (VT) Peter Dudley, Joey Laprade (UTT)
Background This report contains the results of the inspection, analysis and action items regarding the Tank 3901-A. The inspection included an external and internal visual inspection and applicable NDE to the accessible portions of the tank. Equipment Orientation The zero references as discussed in this report were as follows: • The tank was oriented beginning with 0° at the center of the shell manway MW1 and
progressing to 360° in a counter-clockwise direction (refer to the roll-out in Appendix A). • All nozzles and manways were individually oriented with 0° at the top of the individual
nozzle and manway necks (towards the top of the tank) and progressed to 360° in a counterclockwise direction.
Equipment Access No scaffolding was constructed for the inspection. Access for the inspection was provided by a ladder.
Overall View
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Present Condition and Analysis
Page 4 of 10 ATS450, 4/18/12 Proprietary Document
External Present Condition Access was limited due to height and vegetative growth. Coating failure was observed throughout. Minor general surface corrosion was observed throughout in areas of coating failure. A 2”x4” vent was located on the roof. Minor general surface corrosion was observed. A grounding cable was not located. Internal Present Condition The roof and shell were coated. Minor general surface corrosion was observed in areas of coating failure. Access to the floor was completely restricted due to a fiber-reinforced plastic (FRP) liner. Cracking, chipping and delamination of the FRP liner were observed. Analysis The tank was analyzed to API 653 for the operating parameters as provided by the client. A summary of the ultrasonic thickness measurements is located in the Summary of Thickness Measurements table that immediately follows. The completed NDE Report is located in Appendix A. The calculations summary is located in Appendix B. Calculated minimum required thicknesses are exclusive of any corrosion allowance.
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Present Condition and Analysis
Page 5 of 10 ATS450, 4/18/12 Proprietary Document
Summary of Thickness Measurements
0.222 0.207 0.0900.217 0.191 0.1000.210 0.172 0.100
Minimum Measured Thickness (inches)
ComponentPrevious
Thickness (inches)
Average Measured Thickness (inches)
Roof
Legend> 10% Above Minimum Required
Corrosion rates and remaining life calculations cannot be performed until a second set of UT measurements is Nominal thickness could not be determined. No previous inspection data was available.
Shell Course 2Shell Course 1
Corrosion Rate
(inches/year)
Remaining Life
(years)
Minimum Required Thickness (inches)
At Minimum Required or BelowWithin 10% of Minimum Required
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Action Items
Page 6 of 10 ATS450, 4/18/12 Proprietary Document
Action Items The following are the prioritized action items based on the observations and findings at the time of the inspection: No. Item Priority
1 The carbon steel components should be cleaned and coated to prevent further deterioration. 3
2 Proper grounding should be verified or installed 3
Legend
Priority 1 High likelihood and consequence of failure. Critical Code or Standard deficiency. May not be fit for continued service without repair.
Priority 2 Medium likelihood and consequence of failure.
Priority 3 Low likelihood and consequence of failure. Non-critical Code or Standard deficiency. Industry best practice or preventative maintenance. Housekeeping items.
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com Future Inspections, Personnel Qualifications and Reference Industry Codes
and Standards
Page 7 of 10 ATS450, 4/18/12 Proprietary Document
Future Inspections The tank should be externally re-inspected in 5 years and internally re-inspected in 10 years according to API 653. According to the Clemson University Spill Prevention Control and Countermeasure (SPCC) Plan, the tank should be re-inspected within 10 years. Personnel Qualifications Jeremy M. Orr SC PE # 27219
GA, AL, ME, FL, LA, TX, SC, CA registered Professional Engineer; Mechanical Engineer with 13 years experience in inspection, evaluation, repair and design in various industries; AWS CWI, API 653 / 510 / 570 / 580 / 571/ 577 certified; STI certified inspector; NACE coating inspector level I certified; ASNT certified level II VT; SPRAT level I certified rope access technician; ATS certified Level II UTT, MT, PT, VT per SNT-TC-1A; active member of TAPPI, AWS, NACE International, ASME
George E. Matthews GA Registered Engineer-in-Training, Mechanical Engineer with 3 years experience in inspection, evaluation, repair and design in various industries
Jesse B. Showalter GA Registered Engineer-in-Training, Mechanical Engineer with 3 years experience in inspection, evaluation, repair and design in various industries
Peter Dudley ATS certified Level II UTT, MT, PT per SNT-TC-1A Joey Laprade ATS certified Level II UTT, MT, PT per SNT-TC-1A Reference Industry Codes and Standards API 653, Tank Inspection, Repair, Alteration, and Reconstruction Clemson University, Spill Prevention Control and Countermeasure Plan
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Photographs
Page 8 of 10 ATS450, 4/18/12 Proprietary Document
Photo 1: Overall view of the tank.
Photo 2: View of vegetative grown limiting access to tank.
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Photographs
Page 9 of 10 ATS450, 4/18/12 Proprietary Document
Photo 3: Internal view of coated roof.
Photo 4: Internal view of coating failure on manway.
APPLIED TECHNICAL SERVICES, INC.
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Photographs
Page 10 of 10 ATS450, 4/18/12 Proprietary Document
Photo 5: View of chipping of FRP liner
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA
Access was limited due to vegetative growth. Where accessible, minor general surface corrosion was observed at areas of coating failure.
Coating failure was observed throughout.
No access.
Roof
Floor
Shell
Insulation / Coating
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Condition / Comments
Minor general surface corrosion was observed at areas of coating failure.
APPLIED TECHNICAL SERVICES, INC.Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
Component
Appendix A: NDE Report
External Visual Inspection:
ATS460, 4/18/12 3901-A Tank Calculations.xls
Minor general surface corrosion was observed at areas of coating failure.
Not applicable.
Grounding Cable
Weld Seam
Jacket / Coils
Support System
Floor Plate Extension
Notes:
Limited access due to vegetative growth. None located as accessible.
Anchor Bolt / Saddle / Lug
Nozzle / Manway / Repad
Relief / Vent
Limited access. Minor to moderate general surface corrosion was observed on accessible nozzles.
2 NPS 4 vents were located on the roof. Minor general surface corrosion was observed.
Minor general surface corrosion was observed.
Minor general surface corrosion was observed.
None located.
ATS460, 4/18/12 3901-A Tank Calculations.xls
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA
Shell Minor general surface corrosion was observed in areas of coating failure.
Component Condition / Comments
Nozzle / Manway Minor general surface corrosion was observed in areas of coating failure
Floor Cracking, chipping and delamination was observed to the FRP liner in isolated areas.
Roof Minor general surface corrosion was observed in areas of coating failure.
Internal Visual Inspection:
APPLIED TECHNICAL SERVICES, INC.Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Appendix A: NDE Report
ATS460, 4/18/12 3901-A Tank Calculations.xls
Notes:
Baffle / Wear Plate None located.
Agitator / Sparger None located.
Internal Coil Not applicable.
Weld Seam No visible deterioration or damage was observed.
Lining / Coating The roof and shell was coated. The floor had a FRP liner.
Nozzle / Manway Minor general surface corrosion was observed in areas of coating failure.
ATS460, 4/18/12 3901-A Tank Calculations.xls
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA
APPLIED TECHNICAL SERVICES, INC.Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Appendix A: NDE Report
Roof:
Plan View: (AS SEEN FROM ABOVE)
Floor:
Rollout / Nozzle Locations (NOT TO SCALE):
ATS460, 4/18/12 3901-A Tank Calculations.xls
Shell:Elevation View:
ATS460, 4/18/12 3901-A Tank Calculations.xls
Roof:
14.4 0.090
0.090
0.090
0.090
0.249
19.2 0.090 0.209
0.218
0.215
0.211
0.230
0.228
0.090
0.090 0.209
0.090
0.228
0.214
APPLIED TECHNICAL SERVICES, INC.
Distance Across (feet)
Minimum Required Thickness (inches)
0.219 0.215
0.232
0.233
0.217
9.7
19.2
9.7
4.9
0.232
14.4
0.2
Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VACorporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Appendix A: NDE Report
Ultrasonic Thickness Measurements:
0 to 180° Minimum Measured Thickness (inches)
0.217
0.2 0.090 0.241
90 to 270° Minimum Measured Thickness (inches)
4.9 0.090
0.215
0.221
ATS460, 4/18/12 3901-A Tank Calculations.xls
Legend> 10% Above Minimum Required
Within 10% of Minimum Required
At Minimum Required or Below
ATS460, 4/18/12 3901-A Tank Calculations.xls
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Appendix A: NDE Report
APPLIED TECHNICAL SERVICES, INC.
Shell Ultrasonic Thickness Measurements Graph:
7.0
8.0
9.0
10.0
11.0
ATS460, 4/18/12 3901-A Tank Calculations.xls
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0.000 0.100 0.200 0.300 0.400
Hei
ght (
feet
)
Minimum Measured Thickness (inches)
0 90 180 270 45 135 225 315 Minimum Required Thickness
ATS460, 4/18/12 3901-A Tank Calculations.xls
Notes:A Height restriction
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA
> 10% Above Minimum Required
Within 10% of Minimum Required
At Minimum Required or Below
Legend
Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Elevation (feet)
Appendix A: NDE Report
Shell Ultrasonic Thickness Measurements:
APPLIED TECHNICAL SERVICES, INC.
AA
0.202
0.2370.241
0.241
0.232
0.231
0.2300.218
A
0.191
0.210
0.1980.224
0.209
A0.1920.202
0.2132.9 0.1960.203
0.1921.50.2
0° Minimum Measured Thickness (inches)
0.1000.100
0.1970.100
7.26.0
0.2014.3
0.100
0.1000.100
9.6 0.100
5.7 0.1960.201
A
8.4A
0.207
10.8 A
0.1000.1000.100 0.194
0.201
0.2110.209
0.215
0.197
A
0.2220.199
Minimum Required Thickness (inches)
90° Minimum Measured Thickness (inches)
180° Minimum Measured Thickness (inches)
270° Minimum Measured Thickness (inches)
ATS460, 4/18/12 3901-A Tank Calculations.xls
At Minimum Required or Below
ATS460, 4/18/12 3901-A Tank Calculations.xls
Notes:A Height restriction
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA
> 10% Above Minimum Required
At Minimum Required or Below
Shell Ultrasonic Thickness Measurements:
Elevation (inches)
Legend
Within 10% of Minimum Required
AA
10.8 0.100 A A A
0.2409.6 0.100 A A A
0.227 0.2388.4 0.100 0.206 0.206
6.0 0.100 0.203 0.1967.2 0.100 0.206 0.238
5.7 0.100 0.204 0.1960.227
2.9 0.100 0.206 0.197 0.222 0.2054.3
0.1721.5 0.100 0.202 0.1990.2 0.100 0.229 0.216 0.218 0.213
APPLIED TECHNICAL SERVICES, INC.Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Appendix A: NDE Report
0.229 0.244
Minimum Required Thickness (inches)
0.220
315°Minimum Measured Thickness (inches)
0.240 0.239
135°Minimum Measured Thickness (inches)
225°Minimum Measured Thickness (inches)
0.2350.100 0.200 0.195
0.230
45°Minimum Measured Thickness (inches)
ATS460, 4/18/12 3901-A Tank Calculations.xls
At Minimum Required or Below
ATS460, 4/18/12 3901-A Tank Calculations.xls
Notes:A No safe access
B Obstruction / vegetative growth
C Threaded
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA
APPLIED TECHNICAL SERVICES, INC.Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Appendix A: NDE Report
Nozzles / Manways / Reinforcement Ultrasonic Thickness Measurements:
ATS460, 4/18/12 3901-A Tank Calculations.xls
Unknown
Unknown
Unknown
UnknownUnknown
UnknownUnknown
Unknown
UnknownUnknownUnknownUnknownN22 0 240 A
A A None N/AA A None N/A
N20 0 240 AN21 0 240 A
A A None N/AA A None N/A
N18 4 240 AN19 0 240 A
A A None N/AA A None N/A
N16 0 0 BN17 0 240 A
B B None N/AB B None N/A
N14 6 12 BN15 0 0 B
B None N/AB B None N/A
N12 0 0 B BN13 6 12 B B
B B None N/AB None N/A
0 B BNone N/ANone N/A
N11 0 0 B
B BB
BN10 0
N8 0 0 B BN9 0 0
None N/AB None N/A
Unknown
Unknown
UnknownUnknown
UnknownN6 0 0 B B
None N/ANone N/A
N7 0 0 B
B BB
B BUnknown
N4 1 228 CN5 0 0 B
N/A Unknown
N/A UnknownN/A UnknownC C
C NoneNone
CN3 1 228 C
None12 C N/A UnknownN2 2 12 C C C None
C
Nozzle NPS Elevation (inches) Thickness
(inches)
Reinforcement Pad
N1 2
Nozzle Thickness (inches) Internal Projection (inches)0° Scan 180° Width
(inches)
C
ATS460, 4/18/12 3901-A Tank Calculations.xls
Notes:A No safe access
B Obstruction / vegetative growth
C Threaded
Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Appendix A: NDE Report
Nozzles / Manways / Reinforcement Ultrasonic Thickness Measurements:
APPLIED TECHNICAL SERVICES, INC.
ATS460, 4/18/12 3901-A Tank Calculations.xls
Scan
Nozzle Thickness (inches) Reinforcement Pad Internal Projection (inches)
N23 4
0° 180°
240 A A A None N/A
Width (inches)
Thickness (inches)
None N/A
None N/A
None N/A
Unknown
A A
B B
Nozzle NPS Elevation (inches)
N24 0 0MW1 36 B B B
A A A
36
UnknownNone N/A Unknown
MW2 30 36 B UnknownB
30
UnknownMW4 30 240 A UnknownMW3 30 B None N/AB
ATS460, 4/18/12 3901-A Tank Calculations.xls
Flat Roofs
of the tank. Typical nom2 NPS 4 vents were located on the roof. Minor general surface corrosion was observed. per 100 square inch area is 0.090" without repair.
Where:D = Diameter 40 ftH = Bott. Shell Course to Max. Liquid Level 11 ft (1st course)G = Specific GravityS = Max. Allowable Stress (psi)E = Joint Efficiency
5.06.0
1049 Triad Court, Marietta, Georgia, 30062 • (770) 423-1400 Fax (770) 514-3299 • www.atslab.com
Appendix B: Calculations Summary
0.100
Shell Course
APPLIED TECHNICAL SERVICES, INC.Corporate Office: Marietta, GA • Branch Offices: Birmingham, AL • Mobile, AL • Jacksonville, FL • Augusta, GA • Savannah, GA • Louisville, KY • Baton Rouge, LA Shreveport, LA • Wilson, NC • Charleston, SC • Columbia, SC • Greenville, SC • Chattanooga, TN • Memphis, TN • Arlington, VA • Chesapeake, VA • Rockville, VA
API STANDARD 653: Minimum Required Thickness for Welded Roof
Minimum Required Thickness (inches)
API STANDARD 653: Minimum Required Thickness for Welded Shell
Flat roof design thickness depends on the presence of and spacing of rafters and the diameter
Course Height (feet)
0.70
1 0.1002
1.0023595 (remaining courses)23595 (1st & 2nd courses)
SEGHDt )1(6.2
min−
=
ATS460, 4/18/12 3901-A Tank Calculations.xls