ITEM DETAILSBS EN124:2015 D400 DUCTILE IRON COVERS BADGED
WITH ‘M.O.D. PHEON’ WITH INTEGRATED SECURITY COVER
RapidSTACK - GREY(MADE FROM 150mm DEEP SECTIONS)
NOT REQUIRED
QUANTITY
CHAMBER
BASE
CABLE MANAGEMENT
ACCESS
DUCT ENTRY
STEP IRON
MADE ON SITE - TO BE SPECIFIED
1
6
1
0
2 MINIMUM (ADDITIONAL ASREQUIRED TO BS EN:13101)
2 WAY D400(WHERE DUCTS EXIT PIT IN 2 DIRECTIONS)
FRAME AND COVER
CONCRETE BASE SECTION WITH SUMP AS PER NOTE 6
SECTION A - A
BASE RING CAST INTOCONCRETE BASE
FALL TOWARDS SUMP
FINISHED GROUND LEVEL
GRADE C35 CONCRETE
STEP IRONS
2 No 100mm DIAMETERLONGITUDINAL DUCTSCUT FLUSH PLUSLOCAL DUCTS IFREQUIRED
25
ANCHOR POINT 12mm ØCAST INTO PIT BASE
REFER TO NOTE 6
PLAN VIEW
B
A
B
A
DETECTABLE TAPETERMINATED ON STUD
ANCHOR POINT12mm Ø CAST INTO
STEP IRONS
2 No 100mm DIAMETERLONGITUDINAL DUCTSCUT FLUSH PLUSLOCAL DUCTS IFREQUIRED
GRADE C35 CONCRETE
ANCHOR POINT 12mm ØCAST INTO PIT BASE
DETECTABLE TAPETERMINATION STUD
SECTION B - B60
0 M
IN.
D400 WREKIN DUCTILE IRONCOVER WITH INTEGRATEDSECURITY PLATE
STEP IRONS
TYPE2 WAY B1252 WAY D4004 WAY B1254 WAY D400
CLEAR OPENING
600mm x 600mm600mm x 600mm
1200mm x 600mm1220mm x 675mm
STANDARD DEPTH5 CHAMBER SECTIONS MIN6 CHAMBER SECTIONS MIN6 CHAMBER SECTIONS MIN7 CHAMBER SECTIONS MIN
ADDITIONAL DEPTH INCREMENTS150mm150mm150mm150mm
WEIGHT LOADING12.5 Tonnes40 Tonnes
12.5 Tonnes40 Tonnes
COVER MATERIAL
DUCTILE IRON
DUCTILE IRON
COVER CODEB125D400B125D400
DUCTILE IRON
DUCTILE IRON
10 WAY D400 1300mm x 850mm 7 CHAMBER SECTIONS MIN 150mm 40 Tonnes DUCTILE IRON D400
6 WAY B1256 WAY D400
1200mm x 600mm1220mm x 675mm
6 CHAMBER SECTIONS MIN7 CHAMBER SECTIONS MIN
150mm150mm
12.5 Tonnes40 Tonnes DUCTILE IRON
B125D400
DUCTILE IRON
8 WAY B1258 WAY D400
1200mm x 600mm1220mm x 675mm
7 CHAMBER SECTIONS MIN8 CHAMBER SECTIONS MIN
150mm150mm
12.5 Tonnes40 Tonnes DUCTILE IRON
B125D400
DUCTILE IRON