Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com Copyright © 2019 Southwire Company, LLC. All Rights Reserved SPEC 45058_PSS DIVISION DATE: 10/20/2019 Rev:1.0.01M SPEC 45058 CU 600V PVC Type TC SDN Flexible Control Cable Type TC-SDN ® Control Cable 600 Volt Flexible Strand Bare Copper Conductors, Polyvinyl Chloride (PVC) insulation with nylon sheath THHN/THWN, Black Neoprene Jacket, Oil and Sunlight Resistant 90°C Dry 75°C Wet 5 4 3 2 1 Image not to scale. See Table 1 for Dimensions CONSTRUCTION: 1. Conductors: Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174 2. Insulation: Polyvinyl Chloride (PVC) with nylon sheath THHN/THWN. Color code Method 1 Table 2 with no white or green. 3. Fillers: Polypropylene or paper to form round core 4. Binder: Two mil mylar tape helically applied over core 5. Jacket: Black heavy duty sunlight and oil resistant Neoprene APPLICATIONS AND FEATURES: Southwire SDN (Small Diameter Neoprene) flexible control tray cables 600 Volt are suited for use in industrial power or control circuits where small diameter, flame retardant cables are desired. These cables are suitable for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Southwire SDN cables listed ast THHN/THWN are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC Article 501 and 502. Southwire SDN flexible control cable is CSA listed Type TC and as Control and Instrumentation Cable Type (CIC) SPECIFICATIONS: ASTM B172 - Rope-Lay-Stranded Copper Conductors ASTM B174 - Bunch-Stranded Copper Conductors ASTM B3 - Soft or annealed Copper UL 83 - Thermoplastic Insulated Wires and Cables Type THHN/THWN UL 66 - TFFN Conductors (18 and 16 AWG) UL 1277 - Type TC-ER Standard Power and Control Cables IEEE 1202/FT4 - Vertical Tray Flame Test (70,000 Btu/hr) ICEA S-58-679 Control, Instrumentation and Thermocouple Extension Conductor Identification CSA 22.2 No. 230 - Type TC CSA 22.2 No. 239 - Type CIC SAMPLE PRINT LEGEND: SOUTHWIRE® SDN 12 AWG (3.31mm2) 4/C TC 90C DRY 75C WET SUN RES 600V DIR BUR E75755 (UL) --- CSA CIC/TC 90C DRY 75C WET PVC/N (-40C) 600V SR OIL RES FT4

CU 600V PVC Type TC SDN Flexible Control Cable

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com

Copyright © 2019 Southwire Company, LLC. All Rights Reserved SPEC 45058_PSS DIVISION DATE: 10/20/2019 Rev:1.0.01M

SPEC 45058

CU 600V PVC Type TC SDN Flexible Control CableType TC-SDN® Control Cable 600 Volt Flexible Strand Bare Copper Conductors, Polyvinyl Chloride (PVC) insulation with nylon sheath THHN/THWN, Black Neoprene Jacket, Oil and Sunlight Resistant 90°C Dry 75°C Wet

5 4 3 2 1Image not to scale. See Table 1 for Dimensions

CONSTRUCTION: 1. Conductors: Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B1742. Insulation: Polyvinyl Chloride (PVC) with nylon sheath THHN/THWN. Color code Method 1 Table 2 with no white or

green.3. Fillers: Polypropylene or paper to form round core4. Binder: Two mil mylar tape helically applied over core5. Jacket: Black heavy duty sunlight and oil resistant Neoprene

APPLICATIONS AND FEATURES: Southwire SDN (Small Diameter Neoprene) flexible control tray cables 600 Volt are suited for use in industrial power or control circuits where small diameter, flame retardant cables are desired. These cables are suitable for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Southwire SDN cables listed ast THHN/THWN are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC Article 501 and 502. Southwire SDN flexible control cable is CSA listed Type TC and as Control and Instrumentation Cable Type (CIC)

SPECIFICATIONS:• ASTM B172 - Rope-Lay-Stranded Copper Conductors• ASTM B174 - Bunch-Stranded Copper Conductors• ASTM B3 - Soft or annealed Copper• UL 83 - Thermoplastic Insulated Wires and Cables Type THHN/THWN• UL 66 - TFFN Conductors (18 and 16 AWG)• UL 1277 - Type TC-ER Standard Power and Control Cables• IEEE 1202/FT4 - Vertical Tray Flame Test (70,000 Btu/hr)• ICEA S-58-679 Control, Instrumentation and Thermocouple Extension Conductor Identification• CSA 22.2 No. 230 - Type TC• CSA 22.2 No. 239 - Type CIC

SAMPLE PRINT LEGEND:SOUTHWIRE® SDN 12 AWG (3.31mm2) 4/C TC 90C DRY 75C WET SUN RES 600V DIR BUR E75755 (UL) --- CSA CIC/TC 90C DRY 75C WET PVC/N (-40C) 600V SR OIL RES FT4

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com

Copyright © 2019 Southwire Company, LLC. All Rights Reserved SPEC 45058_PSS DIVISION DATE: 10/20/2019 Rev:1.0.01M

SPEC 45058

Stock Code

Conductor Size

Cond. OD(1)

Num. of Power Cond.

Insulation Thickness

Outer Jacket

ThicknessNominal OD

(5)Nominal Weight

DC Resis-tance @

25°C

+Ampacity NEC 310.15 (B) (16)amps

Min Bend Radius

AWG (strds) inches mils mils inches Lbs/MFT Ω/MFT 60°C 75°C 90°C Inches

569925 18 (16) 0.044 3 20 45 0.283 47 6.66 7 7 7 1.13

569926 18 (16) 0.044 5 20 45 0.334 70 6.66 7 7 7 1.34

569927 18 (16) 0.044 6 20 45 0.360 77 6.66 7 7 7 1.44

569928 18 (16) 0.044 8 20 45 0.387 94 6.66 7 7 7 1.55

571341 18 (16) 0.044 10 20 50 0.417 116 6.66 7 7 7 1.67

569929 18 (16) 0.044 12 20 50 0.442 131 6.66 7 7 7 1.77

569943 18 (16) 0.044 14 20 50 0.486 150 6.66 7 7 7 1.94

571342 18 (16) 0.044 16 20 50 0.511 170 6.66 7 7 7 2.04

569944 18 (16) 0.044 19 20 65 0.515 200 6.66 7 7 7 2.06

571389 18 (16) 0.044 24 20 70 0.651 258 6.66 6 6 6 2.60

569930 18 (16) 0.044 37 20 70 0.740 372 6.66 6 6 6 2.96

569912 16 (26) 0.058 2 20 45 0.302 51 4.18 10 10 10 1.21

571340 16 (26) 0.058 3 20 45 0.313 62 4.18 10 10 10 1.25

569914 16 (26) 0.058 4 20 45 0.341 75 4.18 10 10 10 1.36

569915 16 (26) 0.058 5 20 45 0.372 92 4.18 10 10 10 1.49

569916 16 (26) 0.058 6 20 45 0.402 102 4.18 10 10 10 1.61

569917 16 (26) 0.058 7 20 45 0.402 113 4.18 9 10 10 1.61

569918 16 (26) 0.058 8 20 60 0.457 136 4.18 9 10 10 1.83

570089 16 (26) 0.058 9 20 60 0.487 151 4.18 9 10 10 1.95

569910 16 (26) 0.058 10 20 45 0.454 150 4.18 6 7 9 1.82

569919 16 (26) 0.058 12 20 60 0.524 191 4.18 6 7 9 2.10

570090 16 (26) 0.058 14 20 60 0.569 218 4.18 6 7 9 2.28

569920 16 (26) 0.058 16 20 60 0.598 244 4.18 6 7 9 2.39

569922 16 (26) 0.058 19 20 60 0.632 280 4.18 6 7 9 2.53

569911 16 (26) 0.058 24 20 65 0.690 346 4.18 6 7 8 2.76

569923 16 (26) 0.058 30 20 70 0.745 425 4.18 6 7 8 2.98

569924 16 (26) 0.058 37 20 90 0.876 548 4.18 5 6 7 3.50

+Ampacity based on 310.15 (B) (16) up to and including 2000 volts, not more than 3 current-carrying conductors, ambient 30°C (86°F). Use Table 310.15 (B)(3) (a) for derating more than 3 conductors

All dimensions are nominal and subject to normal manufacturing tolerances

Table 1 – Measurements and Electrical

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com

Copyright © 2019 Southwire Company, LLC. All Rights Reserved SPEC 45058_PSS DIVISION DATE: 10/20/2019 Rev:1.0.01M

SPEC 45058

Stock Code

Conductor Size

Cond. OD Num. of

Power Cond.

Insulation Thickness

Outer Jacket

ThicknessNominal OD

(5)Nominal Weight

DC Resis-tance @

25°C

+Ampacity NEC 310.15 (B) (16)amps

Min Bend Radius

AWG (strds) inches mils mils inches Lbs/MFT Ω/MFT 60°C 75°C 90°C Inches

569931 14 (41) 0.074 3 20 45 0.344 80 2.63 15 15 15 1.38

569932 14 (41) 0.074 4 20 45 0.377 99 2.63 14 15 15 1.51

569933 14 (41) 0.074 5 20 45 0.413 121 2.63 14 15 15 1.65

569934 14 (41) 0.074 6 20 45 0.447 138 2.63 14 15 15 1.79

570091 14 (41) 0.074 8 20 65 0.518 192 2.63 12 15 15 2.07

569935 14 (41) 0.074 10 20 70 0.595 235 2.63 9 11 12 2.38

570092 14 (41) 0.074 12 20 65 0.602 267 2.63 9 11 12 2.41

569936 14 (41) 0.074 16 20 65 0.678 341 2.63 9 11 12 2.71

570094 14 (41) 0.074 24 20 70 0.784 489 2.63 8 9 11 3.14

570095 14 (41) 0.074 37 20 90 0.979 754 2.63 7 8 10 3.92

569937 12 (65) 0.092 3 20 45 0.383 115 1.65 20 20 20 1.53

569938 12 (65) 0.092 4 20 45 0.422 140 1.65 17 20 20 1.69

569940 12 (65) 0.092 5 20 45 0.464 176 1.65 17 20 20 1.86

569941 12 (65) 0.092 6 20 45 0.504 203 1.65 17 20 20 2.02

569942 12 (65) 0.092 8 20 85 0.620 297 1.65 15 18 20 2.48

571313 12 (65) 0.092 12 20 65 0.688 394 1.65 11 13 15 2.75

+Ampacity based on 310.15 (B) (16) up to and including 2000 volts, not more than 3 current-carrying conductors, ambient 30°C (86°F). Use Table 310.15 (B)(3) (a) for derating more than 3 conductors

All dimensions are nominal and subject to normal manufacturing tolerances

Table 1 – Measurements and Electrical