    Data sheet

    SECURITON AG Alpenstrasse 20 CH - 3052 Zollikofen Switzerland T 800454 1 / 4

    MHD 535 Cable Terminator Module CTM 535

    TheCable Terminator ModuleCTM 535 is the terminator module for the temperature sensor cable MHD 535. An MHD 535 system is notoperational without the Cable Terminator ModuleCTM 535.

    The Cable Terminator ModuleCTM 535 contains the temperature-compensated reference current source which is required for the formation of the

    differential current signals used to transmit the sensor values to the Processor UnitPU.

    Construction of the Cable Terminator Module CTM 535

    The Cable Terminator ModuleCTM 535 comprises a plastic enclosure made of glass fiber reinforced polyester containing the electroniccomponents for termination of the sensor bus system. The printed circuit board features a flat-ribbon connector for the direct connection of thesensor cable, and in addition a seven-pole plug-in terminal for connecting the sensor cable via a connecting cable.

    Figure 1: Construction of the Cable Terminator Module CTM 535

    Terminal block for connecting cableCCA 535

    Banana connector

    Flat-ribbon connector Cable entry

    Mounting the Cable Terminator Module CTM 535

    Mounting position of the Cable Terminator ModuleCTM 535

    The Cable Terminator ModuleCTM 535 can be mounted on the X, Y or Z axis.

  • 8/22/2019 CTM535_DS_T800454_en

    2/4

    Data sheet

    2 / 4 T 800454 MHD535

    Figure 2: Drilling plan of the Cable Terminator Module CTM 535

    Selecting the location for the Cable Terminator ModuleCTM 535

    The location should be a site which is not rendered inaccessible by equipment on site (cable ducts, runs etc.) The mounting location is usuallypredetermined by the application in question (application and mounting type of the sensor cable). A minimum distance of 15 cm from parts onsite (control cabinets, alcoves etc.) should be kept on the entry side of the sensor cable.

    Notice

    A minimum distance of half a sensor distance or 10 m connecting cable CCA 535 should be maintained

    between the last sensor and the Cable Terminator ModuleCTM 535.

    Mounting should be carried out, whenever possible, immediately after the last sensor (i.e. without a connecting cable) (grounding concept,inductive coupling). After consultation with the manufacturer and after an accurate design check, remote mounting is also possible.

    Fastening the Cable Terminator ModuleCTM 535

    The Cable Terminator ModuleCTM 535 is fastened using 4 screws. When mounting on cement or masonry in tunnel applications, special nailanchors CMS 511 with stainless steel V4A screws (5/15x35) should be used. A minimum distance of 15 cm from parts on site (controlcabinets, alcoves etc.) should be kept on the entry side of the sensor cable.

    Safety Notice

    For protection against humidity, the enclosed desiccant bag should be left inside the Cable Terminator ModuleCTM

    535.

  • 8/22/2019 CTM535_DS_T800454_en

    3/4

    Data sheet

    MHD535 T 800454 3 / 4

    Technical specifications of the Cable Terminator Module CTM 535

    Figure 3: Dimensioned drawing of the Cable Terminator Module CTM 535

    Module Type Parameter Values Remark

    CTM 535 Operating voltage +10 ... +20 VDC Via sensor/connecting cable of theProcessor UnitPU

    Power consumption approx. 8.5 mA

    Protection class IP65 in accordance with IEC 529 / EN 60529(1991)

    Ambient conditions 3K5 / 3Z1 in accordance with IEC 721-3-3 / EN

    60721-3-3 (1995)

    Temperature range -40 ... +85 C

    Ambient condition humidity

    95 % rel. hum. for a short time without condensation

    70 % rel. hum. constant

    Connection of connecting cable 2.5 mm2maximum

    Connection of sensor cable 8-pole

    Cable entry

    1 x seal insert MHD 535FX

    1 x seal insert MHD 535SD

    1 x seal insert MHD 535HD

    Sensor cable

    1 x seal insert 8 - 5 mm Connecting cable

    Material of enclosure glass-fiber reinforced polyester

    Approval VdS EN54

    Dimensions 75 x 138 x 56 mm incl. cable entries

    Weight approx. 380 g

  • 8/22/2019 CTM535_DS_T800454_en

    4/4

    Data sheet

    MHD535 T 800454 4 / 4Revision: 11/05/09 vbThe product specifications contained in this document are subject to change without notice. Copyright by Securiton

    Danger

    Prior to the implementation and commissioning of an installation, the technical documentation T800469 must be

    observed.

    Connection overview

    An overview of the connection of the various devices can be seen in the tables below.

    Conductor Processor UnitPU Earth Connecting BoxECB 535 Sensor cable module

    Shield Tm 0 Tm 0

    pink Tm 1 Tm 1 Tm 0

    blue Tm 2 Tm 2 Tm 1

    white Tm 3 Tm 3 Tm 2

    gray Tm 4 Tm 4 Tm 3

    green Tm 5 Tm 5 Tm 4

    yellow Tm 6 Tm 6 Tm 5

    brown Tm 7 Tm 7 Tm 6

    Table 1: Overview of connection of connecting cable

    Conductor Processor UnitPU Earth Connecting BoxECB 535 Sensor cable module

    Shield Tm 0/1 Banana connector Banana connector

    Flat-ribbon cable Flat-ribbon connector Flat-ribbon connector Flat-ribbon connector

    Table 2: Overview of connection of sensor cable

    Item numbers of cable module

    Brief description Type Item number

    Earth Connecting BoxECB 535 MECB0000PEFGRST2

    Cable Terminator ModuleCTM 535 Rev G. MCTM00R0PEFGRST2

    Connection and Filter ModuleCFM 535 Rev G. MCFM00R0PEFGRST2

    Protection and Filter ModulePFM 535 Rev G. MPFM00R0PEFGRST2

    Sensor Separator ModuleSSM 535 Rev G. MSSM00R0PEFGRST2