Manual Electronics

MeasurementModule TypeCPX−CMIX−M1−1

CPX Terminal

Manual567 054en 0906NH[742 036]

Page 2: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively
Page 3: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

IFesto P.BE−CPX−CMIX−EN en 0906NH

Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Edition en 0906NH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Designation P.BE−CPX−CMIX−EN. . . . . . . . . . . . . . . . . . . . . . .

Order no. 567 054. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

© (Festo AG�&�Co. KG, D�73726 Esslingen, Germany, 2009)Internet: http://www.festo.comE−Mail: [email protected]

The reproduction, distribution and utilization of this docu−ment as well as the comunication of its contents to otherswithout express authorization is prohibited. Offenders willbe held liable for the payment of damages. All rights re−served in the event of the grant of a patent, utility moduleor design.

Page 4: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

II Festo P.BE−CPX−CMIX−EN en 0906NH

PROFIBUS, PROFIBUS−DP,PROFIBUS IO��® are registered trade marks of PROFIBUS International (PI)

DeviceNet�® is a registered trademark of Open DeviceNet VendorAssociation. Inc. (ODVA)

RSLinx, RSLogix,RSNetworx for DeviceNet�® are registered trademarks of Rockwell Software Inc. or

Rockwell Automation

EtherNet/IP�® is a registered trade name of ControlNet International Ltd.and the Open DeviceNet Vendor Association. Inc. (ODVA)

TORX�® is a registered trade name of CAMCAR TEXTRON INC.,Rockford, Ill., USA

Page 5: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

IIIFesto P.BE−CPX−CMIX−EN en 0906NH

Contents

Designated use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Safety note VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Target group IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Required software versions X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Important user instructions XI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Notes on this manual XIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glossary XV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. Overwiev CPX 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 CMIX measuring module 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.1 Connection and display elements of the CMIX 1−3 . . . . . . . . . . . . . . . .

1.1.2 Function of the CMIX 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.3 CMIX in the CPX terminal 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Layout 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2. Fitting and installation 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 General notes on fitting and installation 2−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2 Fitting and removing the CMIX 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Installation of the drive and displacement encoder 2−6 . . . . . . . . . . . . . . . . . . . .

2.3.1 General requirements of the mechanics 2−7 . . . . . . . . . . . . . . . . . . . . .

2.3.2 Drive and displacement encoder 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Mounting the CASM−... sensor interface 2−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5 Electrical installation 2−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.1 Earthing 2−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.2 Axis connection 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.3 Permissible module and string lengths 2−13 . . . . . . . . . . . . . . . . . . . . . .

2.5.4 Sensor interface CASM 2−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.5 Ensuring protection class IP65 2−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.6 Power supply 2−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.6.1 Determining the current consumption 2−17 . . . . . . . . . . . . . . . . . . . . . . .

2.6.2 Power supply arrangement � formation of power zones 2−18 . . . . . . . .

Page 6: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

IV Festo P.BE−CPX−CMIX−EN en 0906NH

3. Commissioning 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Overview / procedure for commissioning 3−3 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2 Notes on the available CPX nodes 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 I/O assignment of the CMIX / address range 3−5 . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 Control byte and status byte assignment 3−6 . . . . . . . . . . . . . . . . . . . .

3.3.2 Data format of actual value and setpoint value 3−9 . . . . . . . . . . . . . . . .

3.3.3 Notes on displaying speed 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Commissioning with various drives/measuring systems 3−11 . . . . . . . . . . . . . . . .

3.4.1 Digital measuring system (DGCI) 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.2 Encoder (DNCI) 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.3 Potentiometer (MLO−..., DSMI) 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.4 Examples 3−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5 Resetting to status as at delivery 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4. Diagnosis 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 Errors of the CMIX 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.1 Error numbers of the CMIX 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.2 Acknowledging errors 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2 Diagnostics via LEDs 4−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2.1 LEDs on the sensor interface 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2.2 LEDs on the measuring system (DGCI only) 4−7 . . . . . . . . . . . . . . . . . . .

4.3 Diagnosis via the display/7−segment display 4−8 . . . . . . . . . . . . . . . . . . . . . . . . .

4.4 Diagnosis via the CPX node 4−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.1 Module output and input data 4−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.2 Status bits of the CPX terminal 4−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.3 I/O diagnostic interface and diagnostic memory 4−11 . . . . . . . . . . . . . .

Page 7: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

VFesto P.BE−CPX−CMIX−EN en 0906NH

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical Data CMIX A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Components and accessories A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2.1 Components with the CMIX A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2.2 Supported drives or measuring systems A−5 . . . . . . . . . . . . . . . . . . . . .

A.3 Characteristic values for various measuring systems A−8 . . . . . . . . . . . . . . . . . .

A.4 Replacing components A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.5 Display with the handheld unit A−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B. Configuration with CPX node B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1 CPX−FEC B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.1 Configuration B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.2 Parameterising the CMIX B−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.3 Save actual configuration as the nominal configuration B−5 . . . . . . . . .

B.1.4 Address assignment B−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.5 Diagnosis B−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2 CPX−FB13 (PROFIBUS−DP) B−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2.1 General configuration information B−12 . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2.2 Configuration with STEP 7 B−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2.3 Parameterisation B−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2.4 Addressing B−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.3 CPX−FB11 (DeviceNet) B−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.3.1 Configuring DeviceNet station properties (EDS) B−24 . . . . . . . . . . . . . . .

B.3.2 Parameterising B−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.3.3 Addressing B−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C. Index C−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 8: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

VI Festo P.BE−CPX−CMIX−EN en 0906NH

Page 9: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

VIIFesto P.BE−CPX−CMIX−EN en 0906NH

Designated use

The CPX−CMIX−C−1−H1 measuring module documented in thismanual is intended exclusively for use in Festo CPX terminalsfor installation in a machine or an automation control system.

In combinaton with a CPX terminal with suitable CPX nodes aswell as suitable drives with measuing system, the CMIXpermits processing of position values of the conected drive inthe CPX node.

The CPX terminal may only be used with the CMIX as follows:

� as specified in industrial applications

� without any modifications by the user. Only theconversions or modifications described in thedocumentation supplied with the product are permitted.

� In faultless technical condition.

� In combination with suitable components(drive/measuring system combinations, see section 1.2).

The limit values specified for pressures, temperatures,electrical data, torques etc. should be observed.

Please comply with the regulations of the workers’ com�pensation insurance association, the German Technical Con�trol Board (TÜV) and the electrical requirements of the VDE orthe corresponding national and local safety regulations.

Page 10: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

VIII Festo P.BE−CPX−CMIX−EN en 0906NH

Safety note

Protection against dangerous movements

WarningHigh acceleration forces at the connected actuators!Unexpected motion can cause collisions and severeinjuries.

Dangerous movements can occur through faultycontrolling of connected actuators, e.g. via:

� unsafe or faulty circuitry or cabling,

� faulty operation of the components,

� faults in the measured value and signal generators,

� faulty or non−EMC−compliant components,

� faults in the higher−order control system.

· Before carrying out assembly, installation andmaintenance work, always switch off the power supplyand compressed air supply.Always make sure that the compressed air supply andpower supply are switched off and locked beforeworking in the machine area.

· Make sure that no persons are in the operating range ofthe drives or any other connected actuators.

· Simply switching off the compressed air supply or loadvoltage are not suitable locking procedures. In the eventof a fault, this could lead to unintentional movement ofthe drive.

· Do not switch on the compressed air supply until thesystem is correctly installed and parameterised.

· If used in safety relevant applications, additionalmeasures are necessary, e.g. in Europe the standardslisted under the EU machine guidelines must beobserved. Without additional measures in accordancewith statutory minimum requirements, the product is notsuitable for use in safety−related sections of controlsystems.

Page 11: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

IXFesto P.BE−CPX−CMIX−EN en 0906NH

Protection from pressurised tubing

CautionDanger of injury through inappropriate handling ofpressurised tubing!

Sudden unexpected movement of the connected actuatorsand uncontrolled movements of loose tubing can causeinjury to human beings or damage to property.

· Do not connect, disconnect or open pressurised tubing.

· The tubes must always be exhausted before removal(release compressed air).

· Use suitable protective equipment (e.g. safety goggles,safety shoes, etc.).

Target group

This description is intended exclusively for technicianstrained in control and automation technology, who haveexperience in installing, commissioning, programming anddiagnosing positioning systems.

Service

Please consult your local Festo Service if you have anytechnical problems.

Page 12: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

X Festo P.BE−CPX−CMIX−EN en 0906NH

Required software versions

Particular software versions for the CPX node are required foroperating the CMIX (versions as at March 2009):

Bus node/FEC Required version 1) Support/Operation

CPX−FEC from Revision 18 (R18) suitable

CPX−FB6 (Interbus) from Revision 22 (R22) on request

CPX−FB11 (DeviceNet) from Revision 20 (R20) suitable

CPX−FB13 (PROFIBUS−DP) from Revision 25 (R25) suitable

CPX−FB14 (CANopen) from Revision 20 (R20) on request

CPX−FB23 (CC−Link) from Revision 19 (R19) on request

CPX−FB32 (EtherNet/IP) from Revision 11 (R11) on request

CPX−FB33 (PROFINET, M12) from Revision 7 (R7) on request

CPX−FB34 (PROFINET, RJ45) from Revision 7 (R7) on request

CPX−FB38 (EtherCat) all on request

CPX−CEC in preparation on request

1) Revisions version (R...) see type plate

Tab.�0/1: Overview of CPX bus node / CPX−FEC

Please also observe the notes on the software status in thedocumentation for the CPX node.

Page 13: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

XIFesto P.BE−CPX−CMIX−EN en 0906NH

Important user instructions

Danger categories

This manual contains instructions on the possible dangerswhich may occur if the product is not used correctly. Theseinstructions are marked (Warning, Caution, etc.), printed on ashaded background and marked additionally with a picto�gram. A distinction is made between the following dangerwarnings:

WarningThis means that failure to observe this instruction mayresult in serious personal injury or damage to property.

CautionThis means that failure to observe this instruction mayresult in personal injury or damage to property.

NoteThis means that failure to observe this instruction mayresult in damage to property.

The following pictogram marks passages in the text whichdescribe activities with electrostatically sensitive compo�nents.

Electrostatically sensitive components may be damaged ifthey are not handled correctly.

Page 14: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

XII Festo P.BE−CPX−CMIX−EN en 0906NH

Marking special information

The following pictograms mark passages in the textcontaining special information.

Pictograms

Information:Recommendations, tips and references to other sources ofinformation.

Accessories:Information on necessary or sensible accessories for theFesto product.

Environment:Information on environment−friendly use of Festo products.

Text markings

· The bullet indicates activities which may be carried out inany order.

1. Figures denote activities which must be carried out in thenumerical order specified.

� Hyphens indicate general activities.

Page 15: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

XIIIFesto P.BE−CPX−CMIX−EN en 0906NH

Notes on this manual

This manual refers to the following versions:

� CPX−CMIX−M1−1 measuring module from ab softwarestatus V 1.0

This manual contains special information on the functioning,mounting, installation and commissioning of the CMIXmeasuring module with associated modules and componentson the axis string (see Tab.�0/2).

Information on controlling, programming and diagnosing of aCMIX with the used CPX node is provided in chapter 3.

Special information on configuration for particular CPX nodesis provided in appendix B.

General basic information on the mode of operation, onfitting, installing and commissioning CPX terminals can befound in the CPX system manual, type P.BE−CPX−SYS−...

General information on operating the Handheld can be foundin the manual for the CPX Handheld, type P.BE−CPX−MMI−1−...

Page 16: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

XIV Festo P.BE−CPX−CMIX−EN en 0906NH

This manual contains information about the followingmodules and components:

Module/Component � Type Description

CPX−CMIX−C−1−H1 CMIX measuring module with 7−segment display as well as aconnection to the sensor interface or measuring system.The CMIX is a CPX module (technology module) in a CPXterminal.

CASM−S−D2−R3CASM−S−D3−R7

Sensor interfaces with connection to the CMIX, for connectingspecial displacement encoders to the axis string:� Analogue, absolute measuring system (potentiometer)� Digital, incremental measuring system

DGCI−...

DGP(L)−... withMLO−POT−...−TLF

DNCI−..., DDPC−...

DNC−... withMLO−POT−...−LWG

DNCM−...

DSMI−...

Permissible drives with displacement encoders: 1)

� Linear drive with permanently installed displacementencoder (digital, absolute)

� Linear drive with external displacement encoder(analogue,�absolute � potentiometer)

� Standard cylinder with integrated displacement encoder(digital, incremental)

� Standard cylinder with external displacement encoder(analogue, absolute � potentiometer)

� Standard cylinder with external displacement encoder(analogue, absolute � potentiometer)

� Semi−rotary drive with integrated displacement encoder.(analogue, absolute � potentiometer)

1) Support for other drives in preparation

Tab.�0/2: Overview of modules and components

Page 17: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

XVFesto P.BE−CPX−CMIX−EN en 0906NH

Glossary

The following product−specific terms and abbreviations areused in this manual:

Term / abbreviation Meaning

0 signal Input or output provides 0 V (also LOW, FALSE or logical 0)

1 signal Input or output provides 24 V (also HIGH, TRUE or logical 1)

Absolute displacementencoder

A displacement encoder with fixed (absolute) assignment of measurementvalues (position, angle, etc.) and measurement units

Axis string The entire collection of all modules and cables connected to the CMIX axisconnection

Bus node Provides the connection to specific fieldbuses. Transmit control signals tothe connected modules and monitor their functioning (as CPX module:CPX bus node)

CPX modules Collective term for the various modules integrated in the CPX terminal

CPX terminal Complete system consisting of CPX modules with or without pneumatics

Drive In this manual, the term �drive" represents linear drives (DGCI, DGP),standard cylinders, positioning drives (DNC, DNCI, DNCM) or swivelmodules (DSMI)

I Digital input From the point of view of the master control system, the CMIX statusoutputs are module input data, see section 3.3

I/Os Digital inputs and outputs

Incrementaldisplacement encoder

A path measuring system in which the measurement variable refers to areference point and is determined by counting equally large measurementsteps (increments)

O Digital output From the point of view of the master control system, the CMIX controlinputs are module output data, see section 3.3

OB / IB Output byte / input byte

Page 18: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Contents and general instructions

XVI Festo P.BE−CPX−CMIX−EN en 0906NH

Term / abbreviation Meaning

Parameters Parameters which must be set with measuring system type potentiometerin order to be operated. These are drive length/swivel angle as well asminimum and maximum position.

PLC/IPC Programmable logic controller/industrial PC

Tab.�0/3: Terms and abbreviations

Page 19: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Overview CPX

1−1Festo P.BE−CPX−CMIX−EN en 0906NH

Chapter 1

Page 20: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

1. Overview CPX

1−2 Festo P.BE−CPX−CMIX−EN en 0906NH

Contents

1.1 CMIX measuring module 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.1 Connection and display elements of the CMIX 1−3 . . . . . . . . . . . . . . . .

1.1.2 Function of the CMIX 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.3 CMIX in the CPX terminal 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Layout 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 21: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

1. Overview CPX

1−3Festo P.BE−CPX−CMIX−EN en 0906NH

1.1 CMIX measuring module

1.1.1 Connection and display elements of the CMIX

The following connection and display elements can be foundon the CMIX:

1 Status LEDs

2 X: Control interface(connection formeasuring system orsensor interface)

3 Identification labels(accessories)

4 3−character display

5 Rating plate see side

1

23

4

5

Fig.�1/1: Connection and display elements of the CMIX

Page 22: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

1. Overview CPX

1−4 Festo P.BE−CPX−CMIX−EN en 0906NH

1.1.2 Function of the CMIX

The CMIX measuring module, in combination with a drive witha displacement encoder, permits recording and furtherprocessing of the absolute position values or speed values ofthe connected drive (see section 1.2).

When an incremental measuring system is used, themeasuring system must be referenced after switch−on.

When a potentiometer measuring system is used, drivelength/swivel angle as well as minimum and maximumposition must be entered.

1.1.3 CMIX in the CPX terminal

The CMIX is integrated into a CPX terminal as a CPX moduleand is controlled by the CPX node (bus node or FEC) via theinternal bus using 6 module output bytes and 6 module inputbytes, see section 3.3.

Information on commissioning the CMIX via the CPX bus nodeor CPX−FEC is provided in chapter 3.

Page 23: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

1. Overview CPX

1−5Festo P.BE−CPX−CMIX−EN en 0906NH

1.2 Layout

To record position, you typically need the followingcomponents (see Fig.�1/2):

1 CPX terminal withCMIX

2 Axis string

3 A sensor interfacewith measuringsystem cable(optional, dependingon the measuringsystem used)

4 Drive withdisplacementencoder (here DNCI asexample)

1 2 3 4

Fig.�1/2: Set−up to record positioning

Specific information on the set−up is provided in chapters �2.

Page 24: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

1. Overview CPX

1−6 Festo P.BE−CPX−CMIX−EN en 0906NH

Page 25: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Fitting and installation

2−1Festo P.BE−CPX−CMIX−EN en 0906NH

Chapter 2

Page 26: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−2 Festo P.BE−CPX−CMIX−EN en 0906NH

Contents

2.1 General notes on fitting and installation 2−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2 Fitting and removing the CMIX 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Installation of the drive and displacement encoder 2−6 . . . . . . . . . . . . . . . . . . . .

2.3.1 General requirements of the mechanics 2−7 . . . . . . . . . . . . . . . . . . . . .

2.3.2 Drive and displacement encoder 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Mounting the CASM−... sensor interface 2−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5 Electrical installation 2−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.1 Earthing 2−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.2 Axis connection 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.3 Permissible module and string lengths 2−13 . . . . . . . . . . . . . . . . . . . . . .

2.5.4 Sensor interface CASM 2−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.5 Ensuring protection class IP65 2−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.6 Power supply 2−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.6.1 Determining the current consumption 2−17 . . . . . . . . . . . . . . . . . . . . . . .

2.6.2 Power supply arrangement � formation of power zones 2−18 . . . . . . . .

Page 27: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−3Festo P.BE−CPX−CMIX−EN en 0906NH

2.1 General notes on fitting and installation

Information about fitting the CPX terminal can be found in theCPX system manual (P.BE−CPX−SYS−...).

NoteThe use of components that have not been approved foroperation with the CMIX may lead to malfunctions.

Use only the special matching components from Festo forsetting up and wiring the system.

When fitting the pneumatic components, observe also thenotes on fitting in the operating instructions supplied and thenotes on installation in this chapter.Only then can you guarantee faultless operation.

Page 28: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−4 Festo P.BE−CPX−CMIX−EN en 0906NH

2.2 Fitting and removing the CMIX

The CMIX is mounted in an interlinking block (see alsosection�2.6) of the CPX terminal, see Fig.�2/1.

Note· Always switch off the power supply before fitting orremoving CPX modules.

NoteThe CMIX contains electrostatically sensitive components.

· Therefore, do not touch any components.

· Observe the handling specifications for electrostaticallysensitive components.

Removal Remove the CMIX as follows:

1. Loosen the four screws of the CMIX with a T10 TORXscrewdriver.

2. Pull the CMIX carefully and without tilting away from thepower rails of the interlinking block.

1 CMIX

2 Interlocking block

3 Contact rails

4 TORX T10 screws

3

4

1

2

Fig.�2/1: Removal/fitting of the CMIX

Page 29: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−5Festo P.BE−CPX−CMIX−EN en 0906NH

Fitting Fit the CMIX as follows:

1. Place the CMIX in the interlinking block. Make sure thatthe grooves with the power contact terminals on thebottom of the CMIX lie above the power rails.

2. Push the CMIX carefully and without tilting as far aspossible into the interlinking block.

3. Tighten the screws at first only by hand. Place the screwsso that the self−cutting threads can be used.

4. Tighten the screws with a TORX screwdriver size T10 withtorque 0.9 ... 1.1 Nm.

The parameterisation is saved in the CMIX. Therefore, afterreplacing a CMIX, check the parameters and, if necessary,repeat the commissioning process; see chapter 3. Observe the instructions in section A.4.

Page 30: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−6 Festo P.BE−CPX−CMIX−EN en 0906NH

2.3 Installation of the drive and displacement encoder

Use the permitted combinations of drives and measuringsystems approved by Festo for the CMIX.

The following drives can be used:

Drive Measuring system Sensorinterface

Design Type Function Typeinterface

Linear drive DGCI Digital, absolute Integrated �

DGP(L) Analogue, absolute MLO−POT−TLF−... CASM−S−D2−R3

Cylinder DNCI,DDPC

Digital, incremental Integrated CASM−S−D3−R7

DNC Analogue, absolute MLO−POT−LWG−... CASM−S−D2−R3

DNCM Analogue, absolute Integrated CASM−S−D2−R3

Semi−rotary drive DSMI Analogue, absolute Integrated CASM−S−D2−R3

Tab.�2/1: Drive overview (as at January 2009)

Further drives, sizes and mounting positions are inpreparation.

Page 31: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−7Festo P.BE−CPX−CMIX−EN en 0906NH

2.3.1 General requirements of the mechanics

NoteConnect the drive, guide, measuring system and load freeof play and flush with each other.

Mechanical play, such as between the cylinder’s piston rodand the mass to be moved, results in worse measurementvalues.

NoteLateral loadings produce false measuring results and maydamage the measuring system.

· Use an external guide for the working load in order toprevent transverse loadings on the drive.

· Use fastening elements which will permanently resist theacceleration forces.

NotePlease observe the notes in the operating instructions forthe axis used. Make sure that:

� the permitted lateral force,

� the permitted longitudinal force,

� the permitted mass moment of inertia,

� the maximum permitted speeds and swivel frequenciesare observed.

Page 32: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−8 Festo P.BE−CPX−CMIX−EN en 0906NH

2.3.2 Drive and displacement encoder

Tab.�2/2 provides notes on mounting the measuring system.

Drive Displacement encoder Mounting instructions

DGCI Permanently installeddisplacement encoder

DGP(L) External displacement encoder oftype MLO−POT−...−TLF

· For safe and quick mounting of the measuringsystem: Use the BB−TLF−DGPL−... mounting kit.

· Mount the measuring system electricallyisolated on the mounting surface using theclamping brackets provided.

When used under difficult environmentalconditions (dusty environment):· Mount the measuring system with the actuator

slide facing downwards. The drip edge on bothsides prevents excessive dirt from forming onthe running surface.

DNCI, DDPC Integrated displacement encoder �

DNC External displacement encoder oftype Type MLO−POT−...−LWG

DNCM External displacement encoderalready mounted on delivery

· Always leave the measuring system mountedon the standard cylinder

· Observe the notes in the operating manual

DSMI Integrated displacement encoder �

Tab.�2/2: Notes on mounting the displacement encoder

Page 33: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−9Festo P.BE−CPX−CMIX−EN en 0906NH

2.4 Mounting the CASM−... sensor interface

Mount the CASM−... sensor interface on an even surface withtwo M4 bolts and one retaining washer each; see Fig.�2/2.The symbol marks the position of the fastening screws.The outer fastening screw serves at the same time forearthing ( 1 ). Tightening torque: 2 Nm.

1 Fastening screw(connect earthing)

S1

S2

1

Fig.�2/2: Mounting the CASM−...

Fastening on H−rails as per EN 60715 is possible withmounting kit type CP−TS−HS35; see Fig.�2/3.

1 H−rail 1

Fig.�2/3: Mounting the CASM−... on H−rails

Page 34: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−10 Festo P.BE−CPX−CMIX−EN en 0906NH

2.5 Electrical installation

The CMIX power supply is provided via the CPX terminal;see�section 2.6.

2.5.1 Earthing

The CMIX earthing is provided via the CPX terminal; see theCPX system description.

Observe the additional earthing measures described below,depending on the components used.

NoteFunctional faults can occur through incorrect or missingearthing.

· Connect the specified earth connections at low impe�dance (short cable with large cross−section) to the earthpotential.

Unless otherwise specified, the earthing conductors musthave:

� a cable cross−section of at least 2.5 mm2

� a cable length as short as possible (typically 20 ... 30 cm).

Sensor interface earthing

When using a sensor interface:

· Make a low−ohm connection between the earthing con�nection of the sensor interface and the earth potential ofthe CPX terminal.

Page 35: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−11Festo P.BE−CPX−CMIX−EN en 0906NH

Earthing the drive/measuring system...

Depending on the drive or measuring system used, thesemust be earthed; see Tab.�2/3.

Drive Description Earthing notes

DGCI Linear drive with permanentlyinstalled displacement encoder

· Make a low−ohm connection (earthing strip)between the flat plug of the displacementencoder and the earth potential!� Flat plug (DIN 46246−2, width: 4.8 mm)

DGP(L) Linear drive with externaldisplacement encoder,type�MLO−POT−...−TLF

· Install the displacement encoder electricallyisolated 1)

DNCI, DDPC

Standard cylinder with integrateddisplacement encoder

· Make a low−ohm connection (short cable withlarge cross−section) between the earthconnection at the cylinder and the earthpotential 1)

A self−tapping screw for fastening an earth strapis supplied with the displacement encoder.

DNC Standard cylinder with externaldisplacement encoder,type�MLO−POT−...−LWG

· Make a low−ohm connection (earthing strapsupplied) between the flat plug of thedisplacement encoder and the earth potential!

DNCM Standard cylinder, externaldisplacement encoder alreadymounted on delivery

No additional earthing required 1)

DSMI Semi−rotary drive with integrateddisplacement encoder

· Make a low−ohm connection (earthing strap)between the earth connection of the DSMI andthe earth potential!

1) Alternatively: Mount the drive on an earthed machine bed.

Tab.�2/3: Notes on earthing the drive and displacement encoder

Page 36: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−12 Festo P.BE−CPX−CMIX−EN en 0906NH

2.5.2 Axis connection

The displacement encoder or a sensor interface (dependingon the measuring system) is connected to the ’X’ axisconnection of the CMIX.

This forms an axis string.

Notes on connecting the modules to the axis connection areprovided in section 2.5.3.

The axis connection pin assignments for the CMIX and sensorinterface or measuring system are shown in Tab.�2/4.

Pin Assignment CMIX X CASM: S1

1 Operating voltage 24 V

2 +24 V load voltage

3 0 V

4 CAN_H

5 CAN_L

Housing Cable shield 1)

1) Connect cable shield to the earth connection at the CASM, for the DGCI, correspondingly to the DGCI housing.

Tab.�2/4: Pin allocation of the axis connections

Page 37: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−13Festo P.BE−CPX−CMIX−EN en 0906NH

2.5.3 Permissible module and string lengths

Maximum permissible cable length of the axis string: 30 m(total length CMIX � sensor interface or measuring system)

Connecting cable Length Type

Connecting cable WS−WD, angled plug angled socket

0.25 m KVI−CP−3−WS−WD−0,25angled plug � angled socket

0.5 m KVI−CP−3−WS−WD−0,5

2 m KVI−CP−3−WS−WD−2

5 m KVI−CP−3−WS−WD−5

8 m KVI−CP−3−WS−WD−8

Connecting cable GS−GD, straight plug straight socket

2 m KVI−CP−3−GS−GD−2straight plug � straight socket

5 m KVI−CP−3−GS−GD−5

8 m KVI−CP−3−GS−GD−8

Connecting piece, for control cabinet feed−through

� KVI−CP−3−SSD

Tab.�2/5: Overview of cables between CMIX, sensor interface, measuring system

Page 38: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−14 Festo P.BE−CPX−CMIX−EN en 0906NH

2.5.4 Sensor interface CASM

The sensor interface type CASM−... has an incoming (S1)connection; see section 2.5.2.

A corresponding input (S2) for connecting the specificdisplacement encoder is also available; see Tab.�2/6.

Drive Displacementencoder

Sensor interface Connecting cable

DGCI permanentlymounted

(no sensor interfacerequired)

KVI−CP−3−...

DNCI, DDPC integrated CASM−S−D3−R7 permanently connected to DNCI/DDPC

DNC external, MLO−POT−...−LWG

NEBC−P1W4−K−0,3−N−M12G5

DSMI Integrated

NEBC−P1W4−K−0,3−N−M12G5

DGP(L) external, MLO−POT−...−TLF

CASM−S−D2−R3

NEBC A1W3 K 0 3 N M12G5DNCM external, fitted on

delivery

NEBC−A1W3−K−0,3−N−M12G5

Tab.�2/6: Overview of sensor interfaces and measuring system cables

In principle, other potentiometers can be used: Observe thefollowing:

� The potentiometer must have a connection resistance of3�...�20�k.

� If the potentiometer has worse values for linearity andtemperature coefficient, the measured value will be lessaccurate.

� To connect it to the sensor interface, you might have tofabricate a special cable.

Page 39: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−15Festo P.BE−CPX−CMIX−EN en 0906NH

CASM−S−D3−R7 Sensor interface for digital, incremental measuring systems,with M12 measuring system connection (socket, 8 pin)

Pin Assignment S2

1 +V�b Sensor (5 V) 7

16

2 0 V16

8

3 Signal sine +5 8

4 Signal sine � 4

3

2

5 Signal cosine �

3

6 Signal cosine +

7 Screening

8 n.c. (not connected)

Housing Earthing connection (FE)

The cable screening is connected to the earthing terminal of thesensor interface.

Tab.�2/7: Pin assignment of connection S2 with theCASM−S−D3−R7

Page 40: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−16 Festo P.BE−CPX−CMIX−EN en 0906NH

CASM−S−D2−R3 Sensor interface for analogue, absolute measuring system(potentiometer), with M12 measuring system connection(socket, 5 pin)

Pin Assignment S2

1 Measuring system housing 3 4

2 n.c. (not connected)2 1

3 Analogue GND (OGND)2 1

5

4 Reference voltage 5 V (REF 5V)

5 Analogue input 0 ... 5 V (INPUT)

Housing Earthing connection (FE)

The cable screening is connected to the earthing terminal of thesensor interface.

Tab.�2/8: Pin assignment of connection S2 with theCASM−S−D2−R3

2.5.5 Ensuring protection class IP65

With a completely installed axis string (all plug connectionsinserted), the CMIX in the CPX terminal conforms to protec�tion class IP65.

NoteIn order to achieve protection class IP65:

· Seal unused connections with the protective capssupplied.

If the axis connection is not used, then seal this using aFLANSCHDOSE (flangesocket), S712 protective cap. You willthen achieve protection class IP65.

Page 41: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−17Festo P.BE−CPX−CMIX−EN en 0906NH

2.6 Power supply

The power supply for the CMIX is provided via the followingconnections on the CPX terminal (interlinking blocks withpower supply):

Interlocking block CPX−EV−S... or CPX−M−EV−S...�(VEL/SEN)

The power supply for the following is provided via theoperating voltage supply for the electronics/sensors(VEL/SEN) of the CPX terminal:

� internal electronics of the CMIX

� connected sensor interface (optional)

� connected displacement encoder.

Interlocking block CPX−EV−V...,�CPX−M−EV−V...,CPX−EV−S... or CPX−M−EV−S... (VVAL)

The CMIX does not need any load supply for the valves(VVAL) of the CPX terminal. But the voltages 0 VEL/SEN and 0 VVAL are connected by theCMIX; see section 2.6.2.

2.6.1 Determining the current consumption

Tab.�2/9 shows current consumption of the CMIX.

Current consumption of the CMIX made up of VEL/SEN ofthe CPX terminal

Typical current consumption dependent on themeasuring system

80 ... 110 mA

Maximum current consumption 110 mA

Tab.�2/9: Current consumption via VEL/SEN of theCPX�terminal

Page 42: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

2. Fitting and installation

2−18 Festo P.BE−CPX−CMIX−EN en 0906NH

2.6.2 Power supply arrangement � formation of power zones

The modular power supply arrangement of the CPX terminalfacilitates the formation of power zones.

Observe the following:

� The CMIX connects the internal contact rails 0 VEL/SEN to 0VVAL of the CPX terminal.This means that the operating voltage for the electronics/sensors (VEL/SEN) of the CPX terminal and the CMIX loadsupply for the valves (VVAL) are thus no longer electricallyisolated.

NoteDamage to components and functional damage!

· At the module position of the CMIX, the same potential(common power unit of connection of the 0�V cables)must be supplied as the operating power supply for theelectronics/sensors (VEL/SEN) and the CPX terminal.

The CMIX always connects the 0 V supply for the elec�tronics with the 0 V supply for the valves. This must benoted when a CPX−GE−EV−V interlinking block is located tothe left of the CMIX because this can remove an intentionalvoltage isolation.

Basic information on the power supply arrangement of theCPX terminal can be found in the CPX system manual.

Page 43: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Commissioning

3−1Festo P.BE−CPX−CMIX−EN en 0906NH

Chapter 3

Page 44: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−2 Festo P.BE−CPX−CMIX−EN en 0906NH

Contents

3.1 Overview / procedure for commissioning 3−3 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2 Notes on the available CPX nodes 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 I/O assignment of the CMIX / address range 3−5 . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 Control byte and status byte assignment 3−6 . . . . . . . . . . . . . . . . . . . .

3.3.2 Data format of actual value and setpoint value 3−9 . . . . . . . . . . . . . . . .

3.3.3 Notes on displaying speed 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Commissioning with various drives/measuring systems 3−11 . . . . . . . . . . . . . . . .

3.4.1 Digital measuring system (DGCI) 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.2 Encoder (DNCI) 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.3 Potentiometer (MLO−..., DSMI) 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.4 Examples 3−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5 Resetting to status as at delivery 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 45: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−3Festo P.BE−CPX−CMIX−EN en 0906NH

3.1 Overview / procedure for commissioning

The following steps must be performed duringcommissioning:

1. Check set−up of the used components on the axis string,if�necessary.

2. Check power supply of the CPX terminal; switch on powersupply.

3. Configure CPX node.

4. Depending on the drive or measuring system used:

� Digital measuring system (e.g. DGCI) No commissioning necessary. A zero point canoptionally be set.

� Encoder (e.g. DNCI): The incremental measuring system must bereferenced after switch−on.

� Potentiometer (e.g. MLO−POT−..., DSMI, DNCM): The min. and max. position value must be set onceand the effective stroke length (max. measurementlength) written in 1/100 mm.

After commissioning:

5. Check function of the CMIX.

Page 46: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−4 Festo P.BE−CPX−CMIX−EN en 0906NH

3.2 Notes on the available CPX nodes

Tab.�3/1 shows an overview of the available CPX nodes thatare suitable for operation with the CMIX (as of March 2009).

Bus node/FEC Support/operation Special instructions

CPX−FEC suitable Appendix B.1

CPX−FB6 (Interbus) on request Not present

CPX−FB11 (DeviceNet) suitable Appendix B.3

CPX−FB13 (PROFIBUS−DP) suitable Appendix B.2

CPX−FB14 (CANopen) on request Not present

CPX−FB23 (CC−Link) on request Not present

CPX−FB32 (EtherNet/IP) on request Not present

CPX−FB33 (PROFINET, M12) on request Not present

CPX−FB34 (PROFINET, RJ45) on request Not present

CPX−FB38 (EtherCat) on request Not present

Tab.�3/1: Note, CPX node

Depending on the bus, up to 9 CMIX can be installed in oneCPX terminal.

General parameterisation instructions are provided in therespective manuals for the CPX node used.

Page 47: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−5Festo P.BE−CPX−CMIX−EN en 0906NH

3.3 I/O assignment of the CMIX / address range

The CMIX is controlled by the CPX node via the internal bususing 6 bytes of output data and 6 bytes of input data.

Byte 4 serves as control or status byte; in bytes 0 ... 3 actualvalue and setpoint value are transferred.

Format 32−bit integer (DINT, int32)

(Control byte CCON B1 = 0)

I/O Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Output data Setpoint value Control byteCCON

reserved

LSB ... ... MSBCCON

Input data Actual value: position or speed Status byteSCON

reserved

LSB ... ... MSBSCON

Tab.�3/2: Module output data of the CMIX with 32−bit integer format

Decimal format

Especially for controls that can only process 16−bit values.

(Control byte CCON B1 = 1)

I/O Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Output data Setpoint value Control byteCCON

Reserved

16 bit before the decimal 16 bit after the decimalCCON

Input data Actual value: position or speed Status byteSCON

Reserved

16 bit before the decimal 16 bit after the decimalSCON

Tab.�3/3: Module output data of the CMIX with decimal format

Page 48: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−6 Festo P.BE−CPX−CMIX−EN en 0906NH

3.3.1 Control byte and status byte assignment

CCON With the control byte (CCON), the number format and outputmode of the CMIX are controlled as well as the performanceof the commissioning functions.

Assignment of the control byte CCON (byte 4)

CCON B7PARAM1

B6PARAM0

B5LOAD_P

B4REF

B3RESET

B2MODE

B1FORMAT

B0UNIT

Parameters Loadpara�meters

Setreferencepoint

Acknowl�edgeerror

Mode Numberformat

Unit

Tab.�3/4: Byte 4 of the module output data of the CMIX: CCON

SCON The status byte (SCON) reports the condition of the CMIX.

Assignment of the status byte SCON (byte 4)

SCON B7ERROR

B6�

B5ACK

B4REF_OK

B3ERROR3

B2ERROR2

B1ERROR1

B0ERROR0

Errors � Para�meter accepted

Refe−rencepoint set

Error code

Tab.�3/5: Byte 4 of the module input data of the CMIX: SCON

Page 49: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−7Festo P.BE−CPX−CMIX−EN en 0906NH

Control byte 4 (CCON)

Bit DE EN Description

B0UNIT

Einheit Unit Unit used, dependent on mode and measuring system.UNIT

Position (B2 = 0) Speed (B2 = 1)

= 0: Increments 1)

= 1: 0.01 mm 2)= 0: Increment/s 1)

= 1: 0.01 mm/s 2)

B1FORMAT

Zahlen�format

Format Number format of the actual and setpoint values.= 0: 32−bit integer= 1: Decimal (2 x 16−bit integer, before the decimal,

after the decimal)

B2MODE

Modus Mode Mode of the output actual values= 0: Actual value is position= 1: Actual value is speed

B3RESET

Fehlerquittieren

Reset Error A positive edge (0 −> 1) resets the error when the cause hasbeen eliminated. The signal must be on at least 20 ms.

B4REF

Nullpunkt/Referenz�punktsetzen

Set zeropoint /referencepoint

With a positive edge (0 −> 1), the current position is set as zeropoint (= reference position for DNCI). The bit can be reset assoon as acceptance is confirmed with ACK = 1 (and for DNCIwith REF_OK = 0).For digital measuring system (DGCI) and potentiometer, thezero point also remains stored after switching on/off.

B5LOAD_P

LadeParameter

Loadparameter

With a positive edge (0 −> 1), the value in the setpoint value isaccepted as parameter corresponding to B6 and B7 (only forpotentiometer). The bit can be reset as soon as acceptance isconfirmed with ACK.

B6PARAM0

Parameter Parameter Bit 7 6 ValueParameter transferred (only potentiometer)

0 0 0 Set effective stroke length in 1/100 mm0 1 1 Accept current position as min pos

B7PARAM1

0 1 1 Accept current position as min. pos.1 0 2 Accept current position as max. pos.1 1 3 � (reserved)

1) Size dependent on measuring system: DGCI (Digital): 5 mDNCI (Encoder): 4.8828 mMLO−..., DSMI (Potentiometer): 0 ... 65535 increments, with respect to the nominal length of themeasuring system (the effective stroke length is not considered).

2) For the potentiometer, the max. position, min. position and effective stroke length or swivel anglemust be entered; see section 3.4.3. For swivel modules, the unit 0.01° is valid correspondingly.

Page 50: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−8 Festo P.BE−CPX−CMIX−EN en 0906NH

Status byte 4 (SCON)

Bit DE EN Description

B0ERROR0

Error code Error code Error code of the error.Bit 3 2 1 0 Value Error

0 0 0 0 0 No error0 0 0 1 1 Measuring system is not present/

B1ERROR1

0 0 0 1 1 Measuring system is not present/defect or communication error or time out (E80)

0 0 1 0 2 Checksum error in the measuring system (E81)

0 0 1 1 3 Under voltage in CMIX module (E52)B2ERROR2

0 0 1 1 3 Under voltage in CMIX module (E52)0 1 0 1 5 Impermissible entry of the

effective stroke length (E84)} 100 � Effective stroke length � 500000

B3ERROR3

� 5000000 1 1 0 6 Undervoltage in the measuring system

(E85)1 0 0 0 8 Measuring system defective (E87)

All other values are reserved.

B4REF_OK

Referenz�punkt gesetzt

Referencepoint set

Status of referencing (or zero point).= 0: Reference position is set.= 1: No reference position set yet.

B5ACK

Parameterüber�nommen

Acknowl�edge Parameter

Confirmation (handshake) of parameter acceptance.= 0: No parameter acknowledgement (LOAD_P = 0)= 1: Parameter acknowledged LOAD_P can be reset to 0

B6�

� � Reserved (= 0)

B7ERROR

Fehler Error Error bit.= 0: No error= 1: Error present; see B0 ... B3

Page 51: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−9Festo P.BE−CPX−CMIX−EN en 0906NH

3.3.2 Data format of actual value and setpoint value

Multiple−byte values are interpreted as standard by the CMIXin the byte order �MOTOROLA (MSB−LSB)". Example, effective stroke length 750 mm:

MOTOROLA (MSB−LSB) � Big Endian

Example 75.000d = 00�01�24�F8h

Byte address 3 2 1 0

Bit no. 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Bin 1 1 1 1 1 0 0 0 0 0 1 0 0 1 0 0 0 0 0 0 0 1 0 1 0 0 0 0 0 0 0 0

Hex F8h 24h 01h 00h

If your control system has to use another byte sequence, youmust take this into account accordingly, e.g.�in yourapplication programs.

CPX parameter �Analogue process value presentation"

Some CPX bus nodes (e.g.�CPX−FB13, FB33, FB34 and FB35)support the global system parameter �Analogue process valuepresentation" (system table function number 4402, bit 7):

� Value �0": INTEL (LSB−MSB) � default

� Value �1": MOTOROLA (MSB−LSB)

INTEL (LSB−MSB) � Little Endian

Example 75.000d = 00�01�24�F8h

Byte address 3 2 1 0

Bit no. 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Bin 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 1 1 1 1 1 0 0 0

Hex 00h 01h 24h F8h

Page 52: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−10 Festo P.BE−CPX−CMIX−EN en 0906NH

3.3.3 Notes on displaying speed

Unit increments

Based on the unit inc, only values without the last 3 digits areoutput.

Unit 0.01 mm/s

With the digital measuring system (DGCI), only speeds thathave no after−decimal places result, since here 5 m is alwayscalculated.

For the potentiometer or encoder (DNCI), after−decimal digitsare putput, since for the potentiometer the effective strokelength is divided by 65535 and for the encoder an incrementis calculated as 4.8828 m.

Page 53: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−11Festo P.BE−CPX−CMIX−EN en 0906NH

3.4 Commissioning with various drives/measuring systems

3.4.1 Digital measuring system (DGCI)

Immediately after switch−on, the measuring system providesthe position value. Commissioning is not necessary.

If needed, the current position can be set as zero point withthe bit REF = 1 in the control byte CCON. Confirmation takesplace via ACK = 1 in the status byte SCON. Negative valuesare output below the zero point, positive values above it.

If a zero point is established, it remains stored even afterswitching on or off.

3.4.2 Encoder (DNCI)

The incremental measuring system must be referenced afterswitch−on.

The current position is accepted as zero point (referencepoint) with setting of the bit REF in the control byte CCON.Confirmation takes place via the bits ACK = 1 and REF_OK = 0in the status byte SCON. Negative values are output belowthe zero point, positive values above it.

Page 54: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−12 Festo P.BE−CPX−CMIX−EN en 0906NH

3.4.3 Potentiometer (MLO−..., DSMI)

At initial commissioning, the min. and max. position valuemust be set once and the effective stroke length (maximummeasurement length) written in 1/100 mm or 1/100°.

If no effective stroke length is written, 100�mm or 100° isused as default setting.

The values remain stored after switching on and off. If theexisting potentiometer is replaced by one with anotherlength, the initial commissioning must be carried out again.

Proceed as follows:

1. For definition of the min. and max. position values, themeasuring system (potentiometer) must be pushedsuccessively into the stroke−limiting mechanical stops ofthe drive or run with compressed air. To accept thepositions, the following bits are set in the control byteCCON:

Min. position: PARAM0 = 1 and PARAM1 = 0} Accept with LOAD_P = 1Max. position: PARAM0 = 0 and PARAM1 = 1} Accept with LOAD_P = 1

With the bit ACK (bit 5), the process is acknowledged witha 1−signal each.

2. If the actual position should be output in millimetres or thespeed in millimetres/second (or correspondingly in de�grees, etc.), the effective stroke length must be measuredand input in 1/100 mm or 1/100°. This requires setting thebit UNIT in the control byte CCON to 1 (Z 1/100 mm).

Measuring errors in the input have a negative effect on themaximum achievable accuracy. This applies especially for the swivel modules, for which thescale used by its nature does not permit measurement in1/100°. That is, an entry of 27000 (32−bit integer) or 270.00(decimal) equals the nominal swivel angle of 270°. But theexact angle between the stops can differ from it.

Page 55: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−13Festo P.BE−CPX−CMIX−EN en 0906NH

The effective stroke length is specified either in the 32−bitinteger or decimal format (depending on the bit UNIT) inthe output data byte 0 ... 3. For the length to be accepted,the bits PARAM0 and PARAM1 must equal 0.

The value is accepted with the bit LOAD_P = 1.Confirmation takes place through the bit ACK = 1 in thestatus byte SCON.

3. A zero point can be defined with the bit REF = 1.Confirmation takes place through the bit ACK = 1. REF_OK is already previously = 0. Negative values are output below the zero point, positivevalues above it.

If a zero point is established, it remains stored even afterswitching on or off.

Generally: Play within the measurement application has a negative effect on the achievable accuracy.

Tip: You can also perform all one−time settings with the CPX−FMT. Fig.�3/4 shows the effective stroke length being written as an example.

Fig.�3/4: Writing the effective stroke length with theCPX−FMT

Page 56: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−14 Festo P.BE−CPX−CMIX−EN en 0906NH

3.4.4 Examples

Potentiometer commissioning

Step 1 Bring measuring system into the lower stroke−limitingmechanical stop of the drive.

Output data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 00000000 00000000 00000000 00000000 01000000 00000000

Hex. 0x00 0x00 0x00 0x00 0x40 0x00

Description Not relevant Bit 6, 7: Min. position Reserved

Input data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 XXXXXXXX XXXXXXXX XXXXXXXX XXXXXXXX 00000000 00000000

Hex. 0xXX 0xXX 0xXX 0xXX 0x00 0x00

Description X: Not relevant Bit 5: No acceptanceBit 7: No error

Reserved

Step 2 Accept lower stop.

Output data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 00000000 00000000 00000000 00000000 01100000 00000000

Hex. 0x00 0x00 0x00 0x00 0x60 0x00

Description Not relevant Bit 5: Accept positionBit 6, 7: Min. position

Reserved

Input data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 XXXXXXXX XXXXXXXX XXXXXXXX XXXXXXXX 00100000 00000000

Hex. 0xXX 0xXX 0xXX 0xXX 0x20 0x00

Description X: Not relevant Bit 5: Pos. acceptedBit 7: No error

Reserved

Page 57: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−15Festo P.BE−CPX−CMIX−EN en 0906NH

Step 3 Bring measuring system into the upper stroke−limitingmechanical stop of the drive.

Output data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 00000000 00000000 00000000 00000000 10000000 00000000

Hex. 0x00 0x00 0x00 0x00 0x80 0x00

Description Not relevant Bit 6, 7: Max. position Reserved

Input data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 XXXXXXXX XXXXXXXX XXXXXXXX XXXXXXXX 00000000 00000000

Hex. 0xXX 0xXX 0xXX 0xXX 0x00 0x00

Description X: Not relevant Bit 5: No acceptanceBit 7: No error

Reserved

Step 4 Accept upper stop.

Output data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 00000000 00000000 00000000 00000000 10100000 00000000

Hex. 0x00 0x00 0x00 0x00 0xA0 0x00

Description Not relevant Bit 5: Pos. acceptedBit 6, 7: Max. position

Reserved

Input data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 XXXXXXXX XXXXXXXX XXXXXXXX XXXXXXXX 00100000 00000000

Hex. 0xXX 0xXX 0xXX 0xXX 0x20 0x00

Description X: Not relevant Bit 5: Pos. acceptedBit 7: No error

Reserved

Page 58: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−16 Festo P.BE−CPX−CMIX−EN en 0906NH

Step 5 Set effective stroke length.

Output data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 01110100 10111101 00000000 00000000 00000001 00000000

Hex. 0x74 0xBD 0x00 0x00 0x01 0x00

Description Effective stroke length setpoint value, example 485 mm (Z�48500d = 0x0000BD74)

Bit 0: Unit 0.01 mmBit 1: Format 32−bit int.Bit 2: Position modeBit 6, 7: Effective stroke

length

Reserved

Input data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 XXXXXXXX XXXXXXXX XXXXXXXX XXXXXXXX 00000000 00000000

Hex. 0xXX 0xXX 0xXX 0xXX 0x00 0x00

Description X: Not relevant Bit 5: No acceptanceBit 7: No error

Reserved

Step 6 Accept effective stroke length.

Output data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 01110100 10111101 00000000 00000000 00100001 00000000

Hex. 0x74 0xBD 0x00 0x00 0x21 0x00

Description Effective stroke length setpoint value, example 485 mm (Z�48500d = 0x0000BD74)

Bit 0: Unit 0.01 mmBit 1: Format 32−bit int.Bit 2: Position modeBit 5: Accept lengthBit 6, 7: Effective stroke

length

Reserved

Page 59: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−17Festo P.BE−CPX−CMIX−EN en 0906NH

Input data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 01110100 10111101 00000000 00000000 00100000 00000000

Hex. 0x74 0xBD 0x00 0x00 0x20 0x00

Description Actual value of current position in 0.01 mm:485 mm (Drive is still at the upper stop)

Bit 5: Par. acceptedBit 7: No error

Reserved

Step 7 Optional: Set zero point.

Output data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 00000000 00000000 00000000 00000000 00010001 00000000

Hex. 0x00 0x00 0x00 0x00 0x11 0x00

Description Not relevant Bit 4: Set zero point Reserved

Input data Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Bit 7 ... 0 00000000 00000000 00000000 00000000 00010000 00000000

Hex. 0x00 0x00 0x00 0x00 0x10 0x00

Description Current position = 0 Bit 4: Accept zero pointBit 7: No error

Reserved

Example decimal format

In the decimal format, all values (position values, effectivestroke length, etc.) are interpreted as follows:

L = 488.02 mm before decimal = 488 (0x01E8)after decimal = 02 (0x0002)

Page 60: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

3. Commissioning

3−18 Festo P.BE−CPX−CMIX−EN en 0906NH

3.5 Resetting to status as at delivery

This is how to reset the CMIX to the condition at delivery:

1. Switch off power supply of the CPX terminal.

2. Remove cable to the measuring system or sensorinterface.

3. Switch on power supply of the CPX terminal.

4. Set the bit LOAD_P in the control byte CCON (0 −> 1, positive edge).

5. Switch off power supply of the CPX terminal.

6. Plug cable back in to the measuring system orsensor�interface.

7. Switch on power supply of the CPX terminal.

The CMIX is back in the delivery condition.

Page 61: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Diagnosis

4−1Festo P.BE−CPX−CMIX−EN en 0906NH

Chapter 4

Page 62: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−2 Festo P.BE−CPX−CMIX−EN en 0906NH

Contents

4.1 Errors of the CMIX 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.1 Error numbers of the CMIX 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.2 Acknowledging errors 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2 Diagnostics via LEDs 4−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2.1 LEDs on the sensor interface 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2.2 LEDs on the measuring system (DGCI only) 4−7 . . . . . . . . . . . . . . . . . . .

4.3 Diagnosis via the display/7−segment display 4−8 . . . . . . . . . . . . . . . . . . . . . . . . .

4.4 Diagnosis via the CPX node 4−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.1 Module output and input data 4−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.2 Status bits of the CPX terminal 4−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.3 I/O diagnostic interface and diagnostic memory 4−11 . . . . . . . . . . . . . .

Page 63: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−3Festo P.BE−CPX−CMIX−EN en 0906NH

4.1 Errors of the CMIX

4.1.1 Error numbers of the CMIX

Errors Errorbits 1)

Description Error handling CPX error

E52 = 3 Undervoltage in CMIXmodule

· Check power supply of theCPX�terminal

105:System error B

E80 = 1 Measuring system isnot present/defectiveor communicationerror or time out

· Check connection cable for theaxis string. Cable fracture? Plug inserted correctly?

108:Error on themeasuringsystem

E87 = 8 Measuring systemdefective 2)

· Check measuring system cable.Cable fracture?Plug inserted correctly?

· Check measuring system.

108:Error on themeasuringsystem

E81 = 2 Checksum error in themeasuring system

Sensor interface is defective.· Check sensor interface, replace or

service, if necessary.

108:Error on themeasuringsystem

E84 = 5 Impermissible entry ofthe effective strokelength 3)

Effective stroke length outside thevalid range, or position at thepotentiometer outside the permittedrange (electric reserve).· Transfer correct effective stroke.· Check installation.

108:Error on themeasuringsystem

E85 = 6 Undervoltagemeasuring system

Logic voltage for CASM too low, e.g.connecting cable for axis string toolong (max. 30�m) or damaged.· Check connection cable for the

axis string; replace if necessary.

108:Error on themeasuringsystem

1) Value of the error bits ERROR0 ... ERROR32) For potentiometer, the error does not have to be acknowledged after its cause is repaired3) 100 � Effective stroke � 500000

Tab.�4/1: Error messages of the CMIX

Page 64: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−4 Festo P.BE−CPX−CMIX−EN en 0906NH

Error numbers on the CPX terminal

All CMIX errors are also signaled as CPX error message 108(measuring system error). This can be examined via the I/Odiagnostic interface, for example.

Function number Module diagnostic data

2008+m*4+1 Module error number

Furthermore, the following errors can occur during the com�missioning phase for the CPX bus node with the parameter�System start" = �saved parameterising and CPX−FEC systemequipment status" or for the CPX−FEC:

Error no. Description Error handling

16 Module code not permitted or incorrectmodule(Handheld: [Module code incorrect]�)� The string allocation stored in the CMIX is

different from the configuration stored inthe CPX bus node or the CPX−FEC

· For the CPX bus node: Change parameter �System start..."to �... default parameterisation andcurrent CPX equipment status"

· With the CPX−FEC: Save the actual configuration as theset configuration using the FSTsoftware

Tab.�4/2: Additional error message of the CPX terminal

4.1.2 Acknowledging errors

Errors can basically only be acknowledged after the cause ofthe error has been rectified.

In order to delete the error:

� acknowledge the error with the RESET_FAULT bit

or

� switch the operating voltage off and then on again.

Page 65: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−5Festo P.BE−CPX−CMIX−EN en 0906NH

4.2 Diagnostics via LEDs

LEDs for diagnosing the CPX terminal are provided on theCMIX as well as on the individual modules at the axisconnection.

The meaning of the LEDs on the modules at the axis stringcan be found in the manual for the relevant module.

LEDs at the CMIX

The light−emitting diodes on the cover indicate CMIX errors.

1 Errors P (red)

2 Power LoadPL (not used) PL

1

2

Fig.�4/1: LEDs at the CMIX

LED Description

Error LED Lights up when CMIX errors occur.

PL Power Load Not used by CMIX

Tab.�4/3: LEDs of the CMIX

Page 66: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−6 Festo P.BE−CPX−CMIX−EN en 0906NH

4.2.1 LEDs on the sensor interface

LEDs on the CASM−S−D2−R3

LED S1 LED S2 Status

green off Ready to operate, without error

green red Initialising via CAN completed

flashes green red 24 V present

off off 24 V not present

green flashes red once Error: Sensor error (supply voltage < 12 V for longer than 15 ms)

green flashes red twice Error: Sensor error (cable break in sensor cable or electrical endposition reached)

green flashes red 3 times Error: Supply voltage (< 17 V for longer than 15 ms)

green flashes red 4 times Error: Communication error (Bus Off state)

LEDs on the CASM−S−D3−R7

LED S1 LED S2 CASM−S−D2−R3 state

green off Ready to operate, without error

green red Initialising via CAN completed

flashes green red 24 V present

flashes green off Not yet referenced

off off 24 V not present

green flashes red once Error: Sensor error

green flashes red twice Error: Sensor cable (cable break in the sensor cable)

green flashes red 3 times Error: Supply voltage (< 17 V for longer than 15 ms)

green flashes red 4 times Error: Communication error (Bus Off state)

Page 67: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−7Festo P.BE−CPX−CMIX−EN en 0906NH

4.2.2 LEDs on the measuring system (DGCI only)

LEDs on the DGCI measuring system

Power LED Error LED Status

green off No error (normal operating status)

off off No power supply

off red Error: Initialising via CAN failed

green red Error: Magnet not recognised or incorrect number of magnets

flashes green flashes red Error: Operating voltage not within permissible range

Page 68: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−8 Festo P.BE−CPX−CMIX−EN en 0906NH

4.3 Diagnosis via the display/7−segment display

The CMIX shows status or diagnostic information directly onthe display/7−segment display.

Possible status information

Display Description

When the power supply is switched on, the firmware version (e.g. 1.03) is displayedfor approx. 1 s

Power supply below the permitted range when switched on.Measuring system power supply still switched off.

In error−free operation, the measuring system type is displayed.

� dGC: Digital measuring system (e.g. DGCI)

� dnC: Encoder (e.g. DNCI)

� POt: Potentiometer (e.g. MLO−..., DSMI)

An error exists (Error). Input bit ERROR supplies a 1−signal.

E52: Undervoltage in CMIX module

E80: Measuring system is not present/defective, communication error or time out

E81: Checksum error in the measuring system.

E84 Impermissible entry of the effective stroke length (100 � Effective stroke � 500000)

E85 Undervoltage measuring system

E87 Measuring system defective

Tab.�4/4: Status information display

Page 69: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−9Festo P.BE−CPX−CMIX−EN en 0906NH

4.4 Diagnosis via the CPX node

Errors in the CMIX or the connected modules are reported tothe CPX bus node as CPX error messages. The followingsections contain the special features of the presentation forthe CPX−specific diagnostic possibilities.

� I/O data module (see section 4.4.1),

� status bits (see section 4.4.2),

� diagnostic memory (I/O diagnostic interface, see section 4.4.3).

4.4.1 Module output and input data

Among other information, the following diagnosticinformation is available via the I/O data module (see section 3.3).

Errors

Error exists The ERROR bit shows that an error is present. With the RESET bit, the error can be acknowledged.

Error number The error number of an existing error is provided in the bitsERROR0 ... 3.

Page 70: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−10 Festo P.BE−CPX−CMIX−EN en 0906NH

4.4.2 Status bits of the CPX terminal

Tab.�4/5 shows the message indicating a CMIX error in theCPX terminal status bits.

Bit Diagnostic informationwith 1−signal

Description Cause of CMIX error

0 Error at valve Module type in whichan error has occurred

1 Error at outputan error has occurred

2 Error at input �

3 Error on analogue module/technology module

Bit 3 is set for all CMIX errors

4 Undervoltage Type of error �

5 Short circuit/overload �

6 Wire break �

7 Other error �

Tab.�4/5: Overview of status bits

Further instructions on the function and content of the statusbits can be found in the CPX system manual.

Page 71: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−11Festo P.BE−CPX−CMIX−EN en 0906NH

4.4.3 I/O diagnostic interface and diagnostic memory

A range of different diagnostic information is accessible viathe I/O diagnostic interface and the diagnostic memory of theCPX terminal.

Diagnostic memory data (Handheld and I/O diagnostic interface)

The specific representation of diagnostic messages of theCMIX in the diagnostic memory of the CPX terminal occurs asshown in Tab.�4/6.

Diagnostic memory data (10 bytes per entry, max. 40 entries) Function no. 1)

Byte Designation Description Value 3488 + n

12345

Days [day]Hours [h]Minutes [m]Seconds [s]Milliseconds [ms]

Time information for the reportederror, measured from the point whenthe power supply was switched on(CPX standard).

0 ... 2550 ... 230 ... 590 ... 590 ... 99 (128 ... 227)

n = 10 * d + 0

6 Module code Module code of the CMIX: 180 0 ... 255 n = 10 * d + 5

7 Module position[Pos]

Module number of the CPX modulethat signaled the error

0 ... 47 n = 10 * d + 6

8 Channel number Bit 7 6 5 ... 0 Description

1 0 0 ... 0 Error in I−channel 0

128(0 ... 255)

n = 10 * d + 7

9 Error number [FN] CPX error number 108 (see section 4.1)

108(0 ... 255)

n = 10 * d + 8

10 Following channels Always 0 for the CMIX 0 (0 ... 63) n = 10 * d + 9

1) d (diagnostic event) [NB] = 0 ... 39; most current diagnostic event = 0

Tab.�4/6: Diagnostic memory data of the CMIX

Instructions on diagnosis with the I/O diagnostic interfacecan be found in the CPX system manual.

Page 72: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−12 Festo P.BE−CPX−CMIX−EN en 0906NH

Example of diagnostic memory entry

Diagnostic memory data Value

Byte Designation Description Dec Hex Bin

12345

Days [day]Hours [h]Minutes [m]Seconds [s]Milliseconds [ms]

Errors were signaled 22.66 ms afterswitching on the power supply (bit 7 in byte 5 is set if this is the firstentry since Power ON).

0d0d0d22d194d

00h00h00h16hC2h

00000000b00000000b00000000b00010110b11000010b

6 Module code Module code of the CMIX: 180 180d B4h 10110100b

7 Module position[Pos]

In this case, the CMIX is CPX moduleNo. 2

2d 02h 00000010b

8 Channel number Bit 7 6 5 ... 0 Description1 0 0 ... 0 Error in I channel

128d 80h 10000000b

9 Error number [FN] CPX error number: 108 108d 6Ch 01101100b

10 Following channels Always 0 for the CMIX 0d 00h 00000000b

Tab.�4/7: Example of diagnostic memory entry

Page 73: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−13Festo P.BE−CPX−CMIX−EN en 0906NH

Diagnostic data of the module (I/O diagnosticinterface)

The specific representation of module diagnostic data (error messages) of the CMIX occurs as shown in Tab.�4/8 andTab.�4/9.

Module diagnostic data: Type of error and location where error arose

Function no. 2008 + m * 4 + 0; m = module number (0 ... 47)

Description Describes where the relevant error occurred.

Bit Bit 0 ... 7 Type of error and location where error arose

Values Bit 7 6 5 ... 0 : Description1 0 00000 : Error in I−channel 0

Tab.�4/8: Type of error and location where error arose

Module diagnostic data: Module error number

Function no. 2008 + m * 4 + 1; m = module number (0 ... 47)

Description Error number

Bit Bit 0 ... 7 Error number

Values 108 CPX error number, (see example Tab.�4/7)

Remark For CMIX error messages, see section 4.1

Tab.�4/9: Module error number

Page 74: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

4. Diagnosis

4−14 Festo P.BE−CPX−CMIX−EN en 0906NH

Additional information

Module code

Function no: 16 + m*16 + 0: Module code: 180

Revision code

Function no: 16 + m*16 + 13 Shows the module version: 0 ... 255 according to the name

plate of the module

Serial number

Function no: 784 + m*4 + 0784 + m*4 + 1784 + m*4 + 2784 + m*4 + 3

Serial number of the module. byte 0: lower nibble = year,

higher nibble = month of the series.bytes 1 ... 3: each nibble contains one digit of the serial

number (BCD encoded)

Page 75: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Technical appendix

A−1Festo P.BE−CPX−CMIX−EN en 0906NH

Appendix A

Page 76: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−2 Festo P.BE−CPX−CMIX−EN en 0906NH

Contents

A.1 Technical Data CMIX A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Components and accessories A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2.1 Components with the CMIX A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2.2 Supported drives or measuring systems A−5 . . . . . . . . . . . . . . . . . . . . .

A.3 Characteristic values for various measuring systems A−8 . . . . . . . . . . . . . . . . . .

A.4 Replacing components A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.5 Display with the handheld unit A−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 77: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−3Festo P.BE−CPX−CMIX−EN en 0906NH

A.1 Technical Data CMIX

General CMIX

General technical data See CPX system manual P.BE−CPX−SYS−...

Product weight (with CPX−GE−EV−S) approx. 240 g

Protection class as per EN 60529, completelyinstalled, plug connector inserted or providedwith protective cap

IP65

Protection against electric shock(protection against direct and indirect contact asper IEC/DIN EN 60204−1)

By means of PELV power circuit(Protected Extra−Low Voltage)

Module code (CPX−specific) 180

Module identifier (in the handheld) CPX−CMIX−M1−1 CMIX Sensor Interface

CMIX power supply

Operating voltage �/�load voltage See CPX system manual P.BE−CPX−SYS−...

CMIX current consumption� from operating power supply

Electronics/Sensors (VEL/SEN)Typ. 80 ... 110 mA at 24 V, max. 110 mA

Electrical isolation� between the operating voltage supply for the

electronics/sensors (VEL/SEN) and the loadvoltage supply for the valves (VVAL)

None

Power failure bridging time 10 ms (for systems with the DGCI, a powerdropout > 1 ms causes error E80)

CMIX measuring system connection

Axis stringNumber of axis strings / Number of axesMax. total length (all cables)Type of axis connection

1 / 130 mSocket M9, 5−pin

Page 78: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−4 Festo P.BE−CPX−CMIX−EN en 0906NH

A.2 Components and accessories

Necessary and useful CMIX accessories: www.festo.com/catalogue/CMIX

Information on drives, and other modules on the axis stringand their accessories, is provided in sections A.2.1 and A.2.2and also in the documentation for the modules used.Information on accessories for the CPX terminal can be foundin the CPX system manual or in the manual for the CPXmodules used.

A.2.1 Components with the CMIX

Tab.�A/1 provides an overview of the components with theCMIX.

Components Description e.g. type

CPX terminal withCMIX measuringmodule

The CMIX makes available the positionor speed data of the connected drive ormeasuring system in the CPX terminal

CPX terminal withCPX−CMIX−M1−1measuring module

Drive with displace�ment encoder, sensorinterface, connectioncables and, if present,additional fixed stops

Permissible drive and displacementencoder (in this example a DGC withMLO−POT−...−LWG) and possibly a sensorinterface (depending on the measuringsystem)

See section A.2.2

Tab.�A/1: Components with the CMIX

Page 79: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−5Festo P.BE−CPX−CMIX−EN en 0906NH

A.2.2 Supported drives or measuring systems

The following tables show show the supported drives ormeasuring systems (as of February 2009).

The external measuring systems can be combinedcorrespondingly with any other drives.

DGCI linear drive

Fig. Components Description Type

Drive withmeasuring system

Linear drive with permanently installeddisplacement encoder (digital, absolute).With integrated connection cable forconnecting to the CMIX

DGCI−...

Tab.�A/2: DGCI linear drive components

DGP(L) linear drive and MLO−POT−...−TLF measuring system

Fig. Components Description Type

Drive Linear drive, can be combined with anexternal displacement encoder via theorder code or as an accessory

DGP(L)−...

Measuring system External displacement encoder (analogue, absolute � potentiometer)

MLO−POT−...−TLF

Connection cablefor the axis string

Connection cable between CMIX andCASM−S−D2−R3

KVI−CP−3−...

Sensor interface Sensor interface for connection to ananalogue absolute displacement encoder(potentiometer) on the axis string

CASM−S−D2−R3

Connection cablefor the measuringsystem

Connection cable between aCASM−S−D2−R3 and an MLO−POT−...−TLF

NEBC−A1W3−K−0.3−N−M12G5

Tab.�A/3: Components with DGP(L) linear drive and MLO−POT−...−TLF measuring system

Page 80: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−6 Festo P.BE−CPX−CMIX−EN en 0906NH

DNCI/DDPC standard cylinder

Fig. Components Description Type

Drive withmeasuring system

Standard cylinder with integrated dis�placement encoder (digital, incremental).With an integrated connection cable forconnection to the CASM−S−D3−R7

DNCI−...DDPC−...

Connection cablefor the axis string

Connection cable between a CMIX and aCASM−S−D3−R7

KVI−CP−3−...

Sensor interface Sensor interface for connection to a digitalincremental displacement encoder on theaxis string

CASM−S−D3−R7

Tab.�A/4: Components with a DNCI/DDPC standard cylinder

DNC standard cylinder and MLO−POT−...−LWG displacement encoder

Fig. Components Description Type

Drive Standard cylinder, which can be combinedwith an external displacement encoderusing accessories

DGP−...

Measuring system External displacement encoder (analogue, absolute � potentiometer)

MLO−POT−...−LWG

Connection cablefor the axis string

Connection cable between CMIX andCASM−S−D2−R3

KVI−CP−3−...

Sensor interface Sensor interface for connection to ananalogue absolute displacement encoder(potentiometer) on the axis string

CASM−S−D2−R3

Connection cablefor the measuringsystem

Connection cable between aCASM−S−D2−R3 and an MLO−POT−...−LWG

NEBC−P1W4−K−0.3−N−M12G5

Tab.�A/5: Components with DNC standard cylinder and MLO−POT−...−LWG displacementencoder

Page 81: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−7Festo P.BE−CPX−CMIX−EN en 0906NH

DNCM standard cylinder

Fig. Components Description Type

Drive Standard cylinder with mounted externaldisplacement encoder LWH (analogue,absolute � potentiometer)

DNCM−...

Connection cablefor the axis string

Connection cable between CMIX andCASM−S−D2−R3

KVI−CP−3−...

Sensor interface Sensor interface for connection to ananalogue absolute displacement encoder(potentiometer) on the axis string

CASM−S−D2−R3

Connection cablefor the measuringsystem

Connection cable between aCASM−S−D2−R3 and a DNCMdisplacement encoder

NEBC−A1W3−K−0.3−N−M12G5

Tab.�A/6: Components with DNC standard cylinder

DSMI semi−rotary drive

Fig. Components Description Type

Drive Semi−rotary drive with integrateddisplacement encoder (analogue,absolute � potentiometer)

DSMI−...

Connection cablefor the axis string

Connection cable between CMIX andCASM−S−D2−R3

KVI−CP−3−...

Sensor interface Sensor interface for connection to ananalogue absolute displacement encoder(potentiometer) on the axis string

CASM−S−D2−R3

Connection cablefor the measuringsystem

Connection cable between aCASM−S−D2−R3 and a DSMI

NEBC−P1W4−K−0.3−N−M12G5

Tab.�A/7: Components with DSMI semi−rotary drive

Page 82: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−8 Festo P.BE−CPX−CMIX−EN en 0906NH

A.3 Characteristic values for various measuring systems

Characteristic values of the digital measuring system (DGCI)

Linearity � ±0.01 % full scale (nominal length).

Repetition accuracy . ±0.01 mm

Hysteresis . 4m

Max. speed of travel 3 m/s

Smallest measurable speed 10 mm/s

Tab.�A/8: Characteristic values for digital measuring system

Characteristic values for encoder (DNCI)

Entire system linearity � ±0.07 mm

Repetition accuracy . ±0.02 mm

Hysteresis . 0.03 mm

Max. speed of travel 1 m/s

Smallest measurable speed 10 mm/s

Tab.�A/9: Characteristic values for encoder

Page 83: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−9Festo P.BE−CPX−CMIX−EN en 0906NH

Characteristic values for potentiometer 100 ... 500 (MLO−POT−...��, DSMI)

Measuring length 100 150 225 300 360 450 500

Linearity (± % of stroke) 0.1 0.09 0.08 0.07 0.06 0.05 0.05

Repetition accuracy (± in mm) 0.01 0.01 0.01 0.01 0.011 0.014 0.016

Max. speed of travel 3 m/s

Smallest measurable speed (mm/s) 3 5 7 9 11 14 15

Temperature coefficient 5 ppm/° C

Tab.�A/10: Characteristic values for potentiometer 100 ... 500

Characteristic values for potentiometer 600 ... 2000 (MLO−POT−...��, DSMI)

Measuring length 600 750 1000 1250 1500 1750 2000

Linearity (± % of stroke) 0.05 0.04 0.04 0.03 0.03 0.03 0.02

Repetition accuracy (± in mm) 0.019 0.023 0.03 0.038 0.046 0.054 0.062

Max. speed of travel 3 m/s

Smallest measurable speed (mm/s) 18 23 31 38 46 53 61

Temperature coefficient 5 ppm/° C

Tab.�A/11: Characteristic values for potentiometer 600 ... 2000

Page 84: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−10 Festo P.BE−CPX−CMIX−EN en 0906NH

A.4 Replacing components

When replacing components, observe the instructions inTab.�A/12.

Replacement Description

... of a CMIX orCPX�terminal

· Zero point Any zero point set is stored in the CMIX and must be reset.

· Effective stroke length and minimum/maximum position: The effective stroke length and minimum/maximum position for the poten�tiometer measuring system type is stored in the CMIX and must be reset.

... of drive ormeasuring system

· Zero point Any zero point set is stored in the CMIX and is retained.

· Effective stroke length and minimum/maximum position:The effective stroke length and minimum/maximum position for the poten�tiometer measuring system type is stored in the CMIX and is retained.

Note, however, that the reference system may change when the drive ormeasuring system is replaced!

... of othercomponents

Identical electrical components, such as the sensor interface, can be replacedwithout further changes.

Tab.�A/12: Replacing components

Page 85: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−11Festo P.BE−CPX−CMIX−EN en 0906NH

A.5 Display with the handheld unit

The following displays are available on the CPX−MMI typehandheld unit.

Representation

The CMIX is displayed as module �CMIX sensor interface" onthe handheld.

Parameters (Menu [Parameters] )

The CMIX does not have any module parameters.

Position value/speed value (Menu [Monitoring/Forcing] )

System Overview _CPX terminal0: ... module ...1: ... module ...2: CMIX sensor interfð3: ... module ...

_____________________________________________________

Diag ßà OK

1 2:CMIX _Monitoring/Forcing (M)Diagnostics (D)Parameters (P)Fail safe (F)Module data (MD)_____________________________________________________

Back OK

2:CMIX:M _ Process stateInpCh 0: 425InpCh 1: 4InpCh 2: 0Outp Ch 2: 0_____________________________________________________

Back Force mode

2

1 [Monitoring/Forcing] menu 2 Input and output channels

Fig.�A/1: Position value/speed display ([Monitoring/Forcing] menu)

With the decimal format and positive values, the value ofinput channel 0 equals the position in whole millimetres, thevalue of input channel 1 the decimal places in 1/100 milli�metres. The values in Fig.�A/1 thus equal the position425.04�mm, for example.

System Overview _CPX terminal0: ... module ...1: ... module ...2: CMIX sensor interfð3: ... module ...

_____________________________________________________

Diag ßà OK

Page 86: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

A. Technical appendix

A−12 Festo P.BE−CPX−CMIX−EN en 0906NH

Information on the CMIX ([Module Data] menu)

The module data of the CMIX is displayed in the[Module�data] menu.

System Overview _CPX terminal0: ... module ...1: ... module ...2: CMIX sensor interfð3: ... module ...

_____________________________________________________

Diag ßà OK 1

2:CMIX _Monitoring/Forcing (M)Diagnostics (D)Parameters (P)Fail safe (F)Module data (MD)

_____________________________________________________

Back OK

2:CMIX :MD _Sensor interfaceType code: 180Revision: 2Serial No: 0x12345678

_____________________________________________________

Back2

1 �Module data" menu 2 Information (scroll using é or ê)

Fig.�A/2: Displaying information with the handheld unit

Module data Description

Type code Module code (CPX−specific, for the CMIX: 180)

Revision Revision status of the CMIX

Serial No Serial number of the CMIX

Tab.�A/13: Module data on the handheld unit

Page 87: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Configuration with CPX node

B−1Festo P.BE−CPX−CMIX−EN en 0906NH

Appendix B

Page 88: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−2 Festo P.BE−CPX−CMIX−EN en 0906NH

Contents

B.1 CPX−FEC B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.1 Configuration B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.2 Parameterising the CMIX B−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.3 Save actual configuration as the nominal configuration B−5 . . . . . . . . .

B.1.4 Address assignment B−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.5 Diagnosis B−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2 CPX−FB13 (PROFIBUS−DP) B−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2.1 General configuration information B−12 . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2.2 Configuration with STEP 7 B−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2.3 Parameterisation B−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2.4 Addressing B−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.3 CPX−FB11 (DeviceNet) B−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.3.1 Configuring DeviceNet station properties (EDS) B−24 . . . . . . . . . . . . . . .

B.3.2 Parameterising B−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.3.3 Addressing B−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 89: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−3Festo P.BE−CPX−CMIX−EN en 0906NH

B.1 CPX−FEC

General information on configuration using the FST isprovided in the CPX−FEC manual (type P.BE−CPX−FEC−...).Detailed information on operating the FST can be found in theFST manual (type P.BE−FST−...).

B.1.1 Configuration

Use Festo Software Tools (FST 4.1 or higher) with theHardware Configurator in order to configure your CPXterminal with CPX−FEC.

To configure the CMIX, this must be in the catalogue of theCPX configurator (CPX terminal / Technology module /CPX−CMIX...). You may require an FST software update for this(CPX configuration update):

è www.festo.com è Downloads è Download Area:Software, Drivers and firmware è Enter search term: CMIX

CautionIf you have connected a CPX terminal to your PC forconfiguration: Test projects and programs at first withoutactive actuators or without compressed air. You will then avoid damage in the test phase.

I/O configuration / CPX configuration

You can create the configuration in the following ways:

� Nominal/actual comparison in the editor mode

� Change to the online mode

� Manual configuration with the Hardware Configurator

The first two methods require the CPX terminal to beconnected and ready for operation. The hardwareconfiguration with the CMIX is automatically recognised.

Page 90: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−4 Festo P.BE−CPX−CMIX−EN en 0906NH

With manual configuration, the CMIX can initially beconfigured without a connection to the CPX terminal.

12

1 Configuration with drag & drop 2 Configured modules in theconfiguration table

Fig.�B/1: Manual configuration of the CPX terminal in the Hardware Configurator

Page 91: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−5Festo P.BE−CPX−CMIX−EN en 0906NH

Input word / Output word addresses

Set the start address of the input words and output words ofthe CMIX.

Module Moduleidentifiers

Allocated addressspace

Remarks

CPX−CMIX sensorInterface

T23 CMIX 3 Input words (6 bytes)3 Output words (6 bytes)

For assignment of theaddresses, see section B.1.4.

Tab.�B/1: CMIX technology module

B.1.2 Parameterising the CMIX

The CMIX does not have any module parameters.

B.1.3 Save actual configuration as the nominal configuration

In order to save the changes permanently, after the changes:

� the actual configuration must be saved as the nominalconfiguration,

� or the project must be loaded into the CPX−FEC(a�program must exist for this).

NoteMake sure that you have supplied taught parameters, orparameters edited via the keyboard or the CPX−MMI, to theCPX configurator.

Page 92: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−6 Festo P.BE−CPX−CMIX−EN en 0906NH

B.1.4 Address assignment

Address assignment example

8DI 2AI4DO

8 O 8 O

1

MPA

2 4 53

1 CPX−FEC

2 Digital I/O modules

3 CMIX technology module

4 Analogue I/O modules

5 MPA1 pneumatics (2 pneumatic modules)

Fig.�B/2: CPX−FEC address assignment example

Loca�tion

Module Inputaddress

Outputaddress

Remarks

0 CPX−FEC 128 128 The outputs are not used

1 8−way digital input module (8DI) 0 � �

2 4−way digital output module (4DO) � 0 �

3 CMIX measuring module (T23) 129 ... 131 129 ... 131 For assignments,see�Tab.�B/3

4 2−way analogue input module (2AI) 64, 65 � �

� MPA pneumatic interface � � Passive module

5 MPA pneumatic module(CPX Typ32 1 8V)

� 32 �

6(CPX−Typ32: 1−8V)

� 33 �

Tab.�B/2: Configuration of address assignment for example Fig.�B/2

Page 93: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−7Festo P.BE−CPX−CMIX−EN en 0906NH

Module output data Module input data

OW Contents Address IW Contents Address

OW129 Setpoint value word 0(VK) 1)

O129.0 ... 15 IW129 Actual value word 0 (VK) 1)

I129.0 ... 15

OW130 Setpoint value word 1(NK) 1)

O130.0 ... 15 IW130 Actual value word 1 (NK) 1)

I130.0 ... 15

OW131 Control byte CCON:

Bit Name0 UNIT1 FORMAT2 MODE3 RESET4 REF5 LOAD_P6 PARAM07 PARAM1

O131.0O131.1O131.2O131.1O131.0O131.1O131.1O131.1

IW131 Status byte SCON:

Bit Name0 ERROR01 ERROR12 ERROR23 ERROR34 REF_OK5 ACK6 �7 ERROR

I131.0I131.1I131.2I131.3I131.4I131.5I131.6I131.7

� (reserved) O131.8 ... 15 � (reserved) I131.8 ... 15

1) For decimal format

OW�/�IW�: output word / input word

Tab.�B/3: Addresses of the CMIX input and output bytes in the example Fig.�B/2

Page 94: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−8 Festo P.BE−CPX−CMIX−EN en 0906NH

B.1.5 Diagnosis

Diagnosis with the Hardware Configurator

With the Hardware Configurator you can carry out a completediagnosis of the CPX terminal. For this, the CPX terminal mustbe connected online to your PC: Diagnostic messages of themodules are displayed directly in the Hardware Configuratorwith an icon on the appropriate module:

1

2

1

1 View current diagnostic message (properties or module entry)

2 View diagnostic memory (context menu)

Fig.�B/3: Warning icon as diagnostic message in the Hardware Configurator

Page 95: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−9Festo P.BE−CPX−CMIX−EN en 0906NH

View current diagnostic message

· Diagnostic message in the Hardware Configurator.

· Display the �Diagnosis" tab of the �Module..." dialog bydouble−clicking or via the [Properties] context menu.

Fig.�B/4: Diagnostic message in the Properties dialog

Page 96: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−10 Festo P.BE−CPX−CMIX−EN en 0906NH

Trace memory

· Display the �Trace−Memory" dialog via the[Trace−Memory] context menu of the HardwareConfigurator.

Fig.�B/5: Tarce memory

Diagnosis with the online control panel

· Select [Online] [Control Panel].

Coded diagnostic information is displayed under �Error":Error type, CPX error number, module number

Fig.�B/6: FST online control panel

Page 97: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−11Festo P.BE−CPX−CMIX−EN en 0906NH

Diagnosis in the user program

You can read out diagnostic information in your user programvia function modules (CFM).

Modules Description

C_STATUS Interrogate diagnostic status

C_TR_rd Read entries in diagnostic memory

C_MD_rd Read module diagnostic data

Tab.�B/4: CFMs for diagnosing the CPX terminal

Error program If a fault occurs during running time, an error number will beentered in the error word (FW). Depending on whether anerror program has been configured, the following applies:

� Error program = 0 (no error program defined): Programs will be stopped.

� Error program > 0: Programs will be stopped and the error program with theentered number will be started.

The following example shows a program for error treatment.Enter it as �Error program" in the register �Run mode" in the�Controller settings".

STEP 1“Wait for fault quitting

IF E0.7 ’Reset FEC ErrorTHEN RESET F ’Error

LOAD V0 TO FW ’Fault wordRESET P63 ’Fault quittingSET P0 ’General – organisational

Fig.�B/7: Sample extract from an error program

Page 98: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−12 Festo P.BE−CPX−CMIX−EN en 0906NH

B.2 CPX−FB13 (PROFIBUS−DP)

General information on configuration is provided in theCPX−FB13 manual (type P.BE−CPX−FB13−...).

B.2.1 General configuration information

Identifier

Module (order code) Module identifiers Occupied bytes IdentifierSiemens / EN 50170

CPX−CMIX−M1−1 (T23)measuring module

CMIX 6 bytes I, 6 bytes O 6AE / 192h

Device master file (GSD file) and icon files

Obtainable from Current GSD files and icon files can be found on the FestoInternet pages at:

è www.festo.com è Downloads è Download Area:Software, Drivers and firmware è Enter search term: CMIX

GSD file You will require one of the following GSD files for the CPXterminal with the CMIX:

� Cpx_059e.gsd (German version)

� Cpx_059e.gse (English version)

Depending on the configuration program used, install theGSD file and the icon files with the aid of the appropriatemenu command or copy the files manually into a particulardirectory of your peripheral/PC.

Page 99: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−13Festo P.BE−CPX−CMIX−EN en 0906NH

B.2.2 Configuration with STEP 7

This manual refers to software version V 5.3.

An appropriate device master file (GSD file) must be installedfor configuration.

Proceed as follows for configuration (see Fig.�B/8):

1. Add a DP master system 1 and the CPX terminal 2 tothe CPX−FB13, as per the instructions.

2. Fill the configuration table with the modules of yourCPX�system.Open the component �Festo CPX−Terminal" in theHardware Catalogue (file \PROFIBUS−DP\Additional FieldDevices\Valves\...) 3�.There are two entries for the CMIX:

Entry Description

CPX−CMIX: 6 Byte E/6 Byte A CMIX with 6 bytes I / 6 bytes O, (occupies 3 bytes of parameterisation data) 1)

1) The maximum number of parameterisation data for the CPX terminal is limited to 234.

3. Assign each of the starting addresses in the �Properties � DP slave" window�4.

This concludes the station selection and configuration.

Page 100: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−14 Festo P.BE−CPX−CMIX−EN en 0906NH

1 2 34

Fig.�B/8: Configuration with STEP7 � Hardware catalogue

Page 101: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−15Festo P.BE−CPX−CMIX−EN en 0906NH

B.2.3 Parameterisation

The CMIX does not have any module parameters.

CPX parameter �Analogue process value presentation"

Some CPX bus nodes (e.g.�CPX−FB13, FB33, FB34 and FB35)support the global system parameter �Analogue processvalue presentation" (system table function number 4402,bit�7):

� Value �0": INTEL (LSB−MSB) � default

� Value �1": MOTOROLA (MSB−LSB)

Fig.�B/9: CPX parameter �Analogue process valuepresentation"

Note the byte order of the actual and setpoint values whenusing the INTEL format; see section B.2.4. General information can be found in section 3.3.2.

Page 102: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−16 Festo P.BE−CPX−CMIX−EN en 0906NH

B.2.4 Addressing

Example: Addresses used as from input/output word 7

8DI 2AI4DO

8 O 8 O

MPA

1 2 3 4 5 6Module no.: 0

EA−Diag.Interf.

I7.0...I8.7

Q7.0...Q8.7

I9.0...I9.7

Q9.0...Q9.3

I10.0...I15.7

Q10.0...Q15.7

I16.0...I19.7

Q16.0...Q16.7

Q17.0...Q17.7

Fig.�B/10: CPX−FB13 address assignment example

No. Module DP identifierSiemens

Addresses

I address O address

0 CPX−FB13 (FB13: DPV1, EA−Diag.Interface) 192 7 ... 8 7 ... 8

1 8−way digital input module (E: CPX−8DE) 8DE 9 �

2 4−way digital output module (A�: CPX−4DA 2x) 8DA � 9

3 CMIX (CPX−CMIX−M1−1) measuring module, for assignments, see Tab.�B/6

192 10 ... 15 10 ... 15

4 Analogue input module (A�: CPX4AE−I) 2AE 16 ... 19 �

� MPA pneumatic interface (passive module) � � �

5 MPA1 pneumatic module (VI VMPA1 FB EMS 8)

8DA � 16

6(VI: VMPA1−FB−EMS−8)

8DA � 17

Tab.�B/5: Input and output addresses for the example, see Fig.�B/10

Page 103: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−17Festo P.BE−CPX−CMIX−EN en 0906NH

Module output data Module input data

QB Contents Address IB Contents Address

QB10 Setpoint value byte 0(LSB)

Q10.0 ... 7 IB10 Actual value byte 0(LSB)

I10.0 ... 7

QB11 Setpoint value byte 1 Q11.0 ... 7 IB11 Actual value byte 1 I11.0 ... 7

QB12 Setpoint value byte 2 Q12.0 ... 7 IB12 Actual value byte 2 I12.0 ... 7

QB13 Setpoint value byte 3(MSB)

Q13.0 ... 7 IB13 Actual value byte 3(MSB)

I13.0 ... 7

QB14 Control byte CCON:

Bit Name0 UNIT1 FORMAT2 MODE3 RESET4 REF5 LOAD_P6 PARAM07 PARAM1

Q14.0Q14.1Q14.2Q14.3Q14.4Q14.5Q14.6Q14.7

IB14 Status byte SCON:

Bit Name0 ERROR01 ERROR12 ERROR23 ERROR34 REF_OK5 ACK6 �7 ERROR

I14.0I14.1I14.2I14.3I14.4I14.5I14.6I14.7

QB15 � (reserved) Q15.0 ... 7 IB15 � (reserved) I15.0 ... 7

Tab.�B/6: Addresses of the CMIX input and output bytes in the example Fig.�B/10 (INTEL format)

The following examples show a variable table each for variousformat and data formats; see also section 3.3.

Page 104: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−18 Festo P.BE−CPX−CMIX−EN en 0906NH

Variable table: actual position, 32 bit integer, MOTOROLA format

Axis is at position 981.60 mmFormat 32−bit integerData format MOTOROLA

Input double word ED100 (ID100)

EW100 (IW100) EW 102 (IW102)

EB100(IB100)

EB101(IB101)

EB102(IB102)

EB103(IB103)

0x00 0x01 0x7F 0x70

MSB LSB

Result

32−bit integer 1

ED100 (ID100)0x00017F7098160 [1/100 mm]

1

Tab.�B/7: Variable table example: actual position, 32 bit integer, MOTOROLA format

Page 105: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−19Festo P.BE−CPX−CMIX−EN en 0906NH

Variable table: actual position, decimal, MOTOROLA format

Axis is at position 981.60 mmDecimal formatData format MOTOROLA

Input double word ED100 (ID100)

EW100 (IW100) EW102 (IW102)

EB100(IB100)

EB101(IB101)

EB102(IB102)

EB103(IB103)

0x00 0x3C 0x03 0xD5 1MSB LSB

1

After the decimal Before the decimal2

Result:2

Before the

decimal 1After the decimal

2

EW102 (IW102)0x03D5981

EW100 (IW100)0x003C60

Tab.�B/8: Variable table example: actual position, decimal, MOTOROLA format

Page 106: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−20 Festo P.BE−CPX−CMIX−EN en 0906NH

Variable table: actual position, 32 bit integer, INTEL format

Axis is at position 981.60 mmFormat 32−bit integerINTEL data format

Input double word ED100 (ID100)

EW100 (IW100) EW102 (IW102)

EB100(IB100)

EB101(IB101)

EB102(IB102)

EB103(IB103)

0x70 0x7F 0x01 0x00

LSB MSB

QB1 writes the input double word intoa marker double word and writes theI�bytes in the right order 1Marker double word MD100

1

MB100 MB101 MB102 MB103

0x00 0x01 0x7F 0x70

LSB MSB

Result:

32−bit integer 1

MD1000x00017F7098160 [1/100 mm]

Tab.�B/9: Variable table example: actual position, 32 bit integer, INTEL format

Page 107: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−21Festo P.BE−CPX−CMIX−EN en 0906NH

Variable table: actual position, decimal, INTEL format

Axis is at position 981.60 mmDecimal formatINTEL data format

Input double word ED100 (ID100)

EW100 (IW100) EW (IW102)

EB100(IB100)

EB101(IB101)

EB102(IB102)

EB103(IB103)

0xD5 0x03 0x3C 0x00

1LSB MSB 1

Before thedecimal

After the decimal 2

QB1 writes the input double word intoa marker double word and writes theI�bytes in the right order

Marker double word MD100

MB100 MB101 MB102 MB103

0x00 0x3C 0x03 0xD5

LSB MSB

After the decimal Before the decimal

Result:

Before the

decimal 1After the decimal

2

MW1020x03D5981

MW1000x003C60

Tab.�B/10: Variable table example: actual position, decimal, INTEL format

Page 108: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−22 Festo P.BE−CPX−CMIX−EN en 0906NH

Variable table: effective stroke, 32 bit integer, MOTOROLA format

Effective stroke of the potentiometer224 mmFormat 32−bit integerData format MOTOROLA

Input in the output data:0x0000578022400

1

21 2

2

AB120(QB120)

AB121(QB121)

AB122(QB122)

AB123(QB123)

0x00 0x00 0x57 0x80

MSB LSB

Tab.�B/11: Variable table example: effective stroke, 32 bit integer, MOTOROLA format

Page 109: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−23Festo P.BE−CPX−CMIX−EN en 0906NH

Variable table: effective stroke, 32 bit integer, INTEL format

Effective stroke of the potentiometer224 mmFormat 32−bit integerINTEL data format

1Input in the output data:0x0000578022400

1

2

1 2

AB120(QB120)

AB121(QB121)

AB122(QB122)

AB123(QB123)

0x80 0x57 0x00 0x00

LSB MSB

Tab.�B/12: Variable table example: effective stroke, 32 bit integer, INTEL format

Page 110: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−24 Festo P.BE−CPX−CMIX−EN en 0906NH

B.3 CPX−FB11 (DeviceNet)

General information on configuration is provided in theCPX−FB11 manual (type P.BE−CPX−FB11−...).

B.3.1 Configuring DeviceNet station properties (EDS)

When starting up a new DeviceNet station for the first time,you must inform your configuration program about certainproperties of the station.

The features of the various slaves are usually administered bythe configuration program in a list or library e.�g. EDS library(EDS for electronic data sheets).

The following possibilities can be used with a CMIX:

� Install an EDS file: Modular EDS. Parameterising of technology modules such as the CMIXis only supported via modular EDS.

� Manually enter the slave features (no parameter settingpossible).

Observe the notes in the manual for the CPX−FB11.

Reference source for EDS files

Reference source Current EDS files, icon files and information on the EDS filescan be found under the following address in Internet:

è www.festo.com è Downloads è Download Area:Software, Drivers and firmware è Enter search term: CMIX

Page 111: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−25Festo P.BE−CPX−CMIX−EN en 0906NH

Installing a modular EDS file

You will require the following files for the CPX terminal:

File type File name Language Description

EDS cpx_chassis.eds English Base file for modular EDS.

EDS cpx_fb11...eds English Provides the communication adapter in theconfiguration program.

EDS cpx_...eds English There is an EDS file for every module type. It contains the information needed forconfiguration and parameterisation.

ICO cpx_...ico � Icon file for representing the CPX terminal ormode in the configuration program.

Tab.�B/13: Configuration files (modular EDS) for the CPX terminal for DeviceNet

Installing modularEDS�files

· Install the files with your configuration program.

You must install at least the Chassis EDS and the EDS files ofthe required modules. Recommendation: Install all EDS files.

Icon files Depending on the configuration program used, you canassign icon files (.ico format) to the CPX terminal or the CPXmodules. The CPX terminal or the modules will then berepresented accordingly in the configuration program.

Notes on installing the EDS files and the icon files can befound in the documentation for your configuration program.

Page 112: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−26 Festo P.BE−CPX−CMIX−EN en 0906NH

B.3.2 Parameterising

The CMIX does not have any module parameters.

B.3.3 Addressing

Assign the I/O addresses of the slave (RSNetworx example)

1. Double−click on the scanner in the network. A dialoguebox will open.

2. With the registers �Input" and �Output", you assign theI/O addresses of the CPX terminal to the PLC operands.

Fig.�B/11: Output address assignment

Page 113: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−27Festo P.BE−CPX−CMIX−EN en 0906NH

Example: scanner 1747−SDN (SLC 500 series)

Addressing for sample terminal with:

� 2 input bytes for status bits (strobed data)

� 11 input bytes, input address from I:1.1.0

� 9 output bytes, output address from O:1.1.0

8DI 2A04DO

8 O 8 O

1

MPA

2 4 53

Module no.: 0 1 2 3 4 5 6

1 CPX−FB11 (with status bits)

2 Digital I/O modules

3 CMIX technology module

4 Analogue I/O modules

5 MPA pneumatics (2 pneumatic modules)

Fig.�B/12: CPX example terminal 3 (address example for scanner 1747−SDN, see Tab.�B/14)

Page 114: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−28 Festo P.BE−CPX−CMIX−EN en 0906NH

Module no. Module Addressing

Input address Output address

0 Fieldbus node CPX−FB11 I:1.1.0 ... I:1.1.15 (for status bits)

1 Digital 8−input module CPX−8DE

I:1.7.0 ... I:1.7.7 �

2 Digital 4−output module CPX−4DA

� O:1.4.0 ... O:1.4.3

3 Measuring module CPX−CMIX−M1−1

I:1.4.0 ... I:1.4.15I:1.5.0 ... I:1.5.15I:1.6.0 ... I:1.6.15

O:1.1.0 ... O:1.1.15O:1.2.0 ... O:1.2.15O:1.3.0 ... O:1.3.15

4 Analogue 2−input moduleCPX−2AE

O:1.2.0 ... O:1.2.15O:1.3.0 ... O:1.3.15

5 MPA1 pneumatic module � O:1.4.8 ... O:1.4.15

6 MPA1 pneumatic module � O:1.5.0 ... O:1.5.7

Tab.�B/14: Addressing example for scanner 1747−SDN

Page 115: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−29Festo P.BE−CPX−CMIX−EN en 0906NH

Module output data Module input data

OW Contents Address IW Contents Address

OW:1.4 Setpoint value byte 0(LSB)

O:1.4.0 ... 7 IW:1.1 Actual value byte 0(LSB)

I:1.1.0 ... 7

Setpoint value byte 1 O:1.4.8 ... 15 Actual value byte 1 I:1.1.8 ... 15

OW:1.5 Setpoint value byte 2 O:1.5.0 ... 7 IW:1.2 Actual value byte 2 I:1.2.0 ... 7

Setpoint value byte 3(MSB)

O:1.5.8 ... 15 Actual value byte 3(MSB)

I:1.2.8 ... 15

OW:1.6 Control byte CCON:

Bit Name0 UNIT1 FORMAT2 MODE3 RESET4 REF5 LOAD_P6 PARAM07 PARAM1

O:1.6.0O:1.6.1O:1.6.2O:1.6.3O:1.6.4O:1.6.5O:1.6.6O:1.6.7

IW:1.3 Status byte SCON:

Bit Name0 ERROR01 ERROR12 ERROR23 ERROR34 REF_OK5 ACK6 �7 ERROR

I:1.3.0I:1.3.1I:1.3.2I:1.3.3I:1.3.4I:1.3.5I:1.3.6I:1.3.7

� (reserved) O:1.6.8 ... 15 � (reserved) I:1.3.8 ... 15

Tab.�B/15: Addresses of the CMIX input and output bytes in the example Fig.�B/12

Page 116: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

B. Configuration with CPX node

B−30 Festo P.BE−CPX−CMIX−EN en 0906NH

Page 117: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

Index

C−1Festo P.BE−CPX−CMIX−EN en 0906NH

Appendix C

Page 118: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

C. Index

C−2 Festo P.BE−CPX−CMIX−EN en 0906NH

Page 119: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

C. Index

C−3Festo P.BE−CPX−CMIX−EN en 0906NH

Numbers

0 signal XV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 signal XV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A

Abbreviations, product−specific XV . . . . . . . . . . . . . . . . . . . . .

Absolute (displacement encoder) XV . . . . . . . . . . . . . . . . . . . .

Acknowledging errors 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Axis string XV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C

CCON 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CMIXAddress range 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Components A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connection and display elements 1−3 . . . . . . . . . . . . . . . . . .

CPX bus node / CPX−FEC X . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Current consumption 2−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D

DiagnosisIn the user program B−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . With the Hardware Configurator B−8 . . . . . . . . . . . . . . . . . .

Diagnostic memory 4−11, 4−13 . . . . . . . . . . . . . . . . . . . . . . . . .

Displacement encoder 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Absolute XV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Incremental XV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Drive XV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Drives A−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 120: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

C. Index

C−4 Festo P.BE−CPX−CMIX−EN en 0906NH

E

ErrorsAcknowledge 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error numbers 4−3, 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G

GSD file B−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H

HandheldDiagnostic memory 4−11, 4−13 . . . . . . . . . . . . . . . . . . . . . . .

I

I/O diagnostic interfaceDiagnostic memory 4−11, 4−13 . . . . . . . . . . . . . . . . . . . . . . .

Important user instructions XI . . . . . . . . . . . . . . . . . . . . . . . . . .

Incremental (displacement encoder) XV . . . . . . . . . . . . . . . . .

Intended use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

L

LEDs 4−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

M

Measuring system 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Measuring systems A−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Modular EDS files B−25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Module diagnostic dataModule error number 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . Number of the first faulty channel 4−13 . . . . . . . . . . . . . . . .

Page 121: CPX Terminal - Festo · (release compressed air). · Use suitable protective equipment (e.g. safety goggles, safety shoes, etc.). Target group This description is intended exclusively

C. Index

C−5Festo P.BE−CPX−CMIX−EN en 0906NH

N

Notes on the manual XIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

P

Pictograms XII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power supply 2−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power supply conceptFormation of power zones 2−18 . . . . . . . . . . . . . . . . . . . . . .

Power zones 2−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

S

Safety note VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SCON 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service IX , X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Status bits 4−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Status information 4−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

T

Target group IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Technical Data A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Text markings XII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .