Coupling HVAC system with environmentally friendly refrigeration system in food store
F.M.Visconti, M.Orlandi, D.Mazzola
Epta S.P.A
Clima 2016 – Aalborg May 25
CLIMA 2016 - AALBORG May 25
Coupling HVAC+R system
Adaptive Cabinet Control
Fully exploit the capabilities of shopping mall
overall systems and iBEMS to interact with
refrigeration plant
EPTA activity in CommONEnergy
CLIMA 2016 - AALBORG May 25
System description:
• Horizontal BLDC inverter driven compressor;
• Water condensed and inverter water cooled.
System advantages:• INVERTER AND ELECTRONIC EXPANSION VALVE: adaptation to changing cooling demand;• CHARGE REDUCTION AND FACTORY TEST: each cabinet is tested in factory;• RELIABILITY: each cabinet has its own unit;• CLOSED SHELL FOR THE COMPRESSOR UNIT: quitness in the store.
CO2 Water Loop system
CLIMA 2016 - AALBORG May 25
VARIABLE SPEED COMPRESSOR
August 2015.
Running percentage of compressor in three vertical LT cabinets
CO2 Water Loop system
CLIMA 2016 - AALBORG May 25
Thermal zoning
Radiant panels (floor or
ceiling) as an energy
saving alternative to full
air HVAC
CLIMA 2016 - AALBORG May 25
Location: Horwich, United Kingdom
700 m2 store
250 m2 sale area
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
WINTER TIME = Full heat recovery
In winter time Optimized trascritical CO2 plant allows 100%
heat recovery to provide store heating without the need of
additional heat sources.
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
Traditional solution Epta solution
The optimized transcritical CO2 system
WINTER TIME
Refrigeration
HVAC+EPTA
HVAC+R
CLIMA 2016 - AALBORG May 25
Gas cooler, used only in summer time
Door heatingHX 1
WINTER TIME
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
Gas cooler, used only in summer time
Door heating
Cassette and primary air heating
HX 1
HX 2
WINTER TIME
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
Gas cooler, used only in summer time
Door heating
Cassette and primary air heating
HX 1
HX 2
HX 3
Self cooling
WINTER TIME
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
SUMMER TIME
In summer time the same plant provides the necessary
cooling amount for refrigeration and for A/C with parallel
compression.
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
The optimized transcritical CO2 system
SUMMER TIME
Traditional solution Epta solution
Refrigeration
HVAC+EPTA
HVAC+R
CLIMA 2016 - AALBORG May 25
Gas cooler, used only in summer time and mid season
Store cooling
SUMMER TIME
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
In synthesis:
1) allows 100% heat recovery to provide store heating
without the need of additional heat from other sources;
2) give multi temperature heat recovery circuits to satisfy
different thermal loads;
3) allows store cooling without an external plant
4) allows plant control based on input from various thermal
sources, thus optimizing total efficiency
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
Optimized transcritical booster CO2 systemAdaptive control of thermal load using CO2 pressure variation
CLIMA 2016 - AALBORG May 25
HX 1
HX 2
HX 3
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
Cassette
Primary air
Door curtain
Optimized transcritical booster CO2 system
CLIMA 2016 - AALBORG May 25
Adaptive air flow
Radiation
CLIMA 2016 - AALBORG May 25
Air flow reduced in off-design (field) condition allows saving energy
Adaptive air flow
CLIMA 2016 - AALBORG May 25
SMART Grids are part of our future
Smart Appliances
CLIMA 2016 - AALBORG May 25
• http://www.eco-smartappliances.eu/
• EPEE* asked to include Commercial Refrigeration as “Smart Appliances”
Smart Appliances
*European Partnership for Energy and the Environment
CLIMA 2016 - AALBORG May 25
Household refrigeration
300 Million unit (EU 28) - > 50- 300 W
Smart Appliances, preparatory study*
*Preparatory study on Smart Appliances (Lot 33), 2015
CLIMA 2016 - AALBORG May 25
Commercial refrigeration
13 Million Unit (EU 28) - > 300 – 5000W
Smart Appliances, preparatory study*
*Preparatory study on Smart Appliances (Lot 33), 2015
CLIMA 2016 - AALBORG May 25
Smart Appliances
But the architecture is complex
And involves a lot of subjects
at various levels
Will be the challenge
for the next future
CLIMA 2016 - AALBORG May 25
Demand-response for refrigeration
Dynamic balance between energy demand and response.
Flattening energy peaks(e.g. store cold during night and use during day)
CLIMA 2016 - AALBORG May 25
Renewable energy overgeneration
Demand-response for refrigeration
Dynamic balance between energy demand and response.
Fast adapting to energy cost
CLIMA 2016 - AALBORG May 25