Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
Corrosion Protection for Pipelines
Draft Basis of Design Report
Sacramento County Regional Sanitation District (Regional San)
HARVEST WATER PROGRAM
Prepared for: Michael Harrison, PE
Engineering Lead, Harvest Water Program C-PMO
Sacramento Regional County Sanitation District
8521 Laguna Station Road
Elk Grove, CA 95758
Prepared by: Ken Kalemkarian, EIT
Chelsea Teall, PE
Reviewed by: Chris Sheldon, PE
Glenn Willson, PE
Date: October 30, 2020
V&A Project No. 19-0093
Harvest Water Program: Corrosion Protection for Pipelines BODR Introduction
| Project No. 19-0093 | 1
1 Introduction V&A Consulting Engineers, Inc. (V&A) is a corrosion engineering subconsultant to Brown & Caldwell
(B&C) and Carollo on the Capital Program Management Services (C-PMO) team for Sacramento Regional
County Sanitation District’s (Regional San’s) Harvest Water Program. The Harvest Water Program was
developed to meet Regional San’s long-term goals of increasing the production and use of recycled
water. The Harvest Water Program offers multiple benefits, including providing a safe and reliable
supply of tertiary-treated water for agricultural uses, reducing groundwater pumping, supporting habitat
restoration efforts, and providing both near-term and long-term benefits to the Sacramento-San Joaquin
Delta. The facilities to be constructed by this Program will include a recycled water pump station
(approximately 75 MGD at build-out), about 14 miles of transmission pipeline (18- to 66-inch diameter),
25 miles of distribution pipelines and laterals, appurtenant facilities, and potentially a dedicated
recharge basin. The scope of this Basis of Design Report (BODR) includes the transmission and
distribution pipelines, which are shown in Figure 1-1.
The role of the C-PMO is to design and construct facilities that have been planned by the A-PMO, or
Administration Program Management Office. The A-PMO is led by Regional San’s Department of Policy
and Planning. The C-PMO will work closely with the A-PMO to support their continued efforts related to
planning, permitting, end-user coordination, public outreach, etc. The C-PMO will develop a Basis of
Design for the overall system and establish a plan for sequencing the design and construction of the
various system components. The C-PMO will develop and issue separate RFPs for design services for
each of the discrete projects defined by the sequencing plan and will manage those projects throu gh
commissioning.
The first step in designing a corrosion control system is to investigate the soil corrosivity. The methods
used to perform the investigations, detailed results of the investigations, and recommendations for
corrosion control of the proposed pipeline materials shall be summarized in a preliminary design report
for each project. The objectives of the soil corrosivity investigations conducted by each project team
should include the following:
1. Review the results of the in-situ soil resistivity testing performed by the C-PMO, which are
summarized in Section 2 and Appendix A of this BODR
2. Collect and review the results of soil sample resistivity testing
3. Collect and review the results of soil sample chemical analysis
4. Discuss the influence of soil parameters on soil corrosivity towards the proposed pipeline materials
5. Recommend either a cathodic protection (CP) system or corrosion monitoring sys tem for metallic
portions of the pipelines based on the soil corrosivity
A corrosion monitoring system consists of test stations, joint bonds, and insulating joints. A CP system
includes a CP current source in addition to all the elements of a corrosion mo nitoring system. The types
of CP systems are discussed further in Section 3.
One of the primary driving factors for designing the CP system is the current requirement of the p ipeline
to be protected. The current required to protect the pipeline can be determined empirically, if the
pipeline is already installed, or theoretically, if it is not. Since the Harvest Water Program involves
installing new pipelines, the CP current requirement will be estimated using theoretical calculations.
Harvest Water Program: Corrosion Protection for Pipelines BODR Introduction
| Project No. 19-0093 | 2
Once the current requirement is known, the number and type of anodes, rectifier current and voltage,
and other parameters for the CP system are calculated, as discussed in Section 4. Other variables and
components of the CP system design are discussed in this report as well, such as electrical isolation
from foreign metallic structures (Section 5), joint bonds for providing an electrically continuous pipeline
(Section 6), and test stations (Section 7).
Additionally, foreign utilities could accelerate the corrosion of the pipeline regardless of whether the
pipeline is cathodically protected. There are two types of foreign utilities that are of concern: (1) Buried
pipelines with CP and (2) overhead AC transmission lines. The circumstances under which these foreign
utilities are of concern and mitigating measures are discussed in Section 8.
Figure 1-1. Harvest Water Program Transmission and Distribution Pipeline Alignments
Harvest Water Program: Corrosion Protection for Pipelines BODR Soil Corrosivity
| Project No. 19-0093 | 3
2 Soil Corrosivity Soil corrosivity can be estimated based on measured soil properties, such as soil resistivity, pH, and
concentrations of water-soluble chloride, sulfate, and bicarbonate ions.
Soil resistivity is a property that quantifies how strongly soil opposes the fl ow of electric current.
Since corrosion is an electrochemical process accompanied by current flow, it is of primary
importance to measure resistivity when investigating soil corrosivity. A lower soil resistivity value
generally corresponds with a greater degree of electrical activity and a higher corrosion rate.
Lower pH (more acidic) soil tends to prevent the formation of protective oxide layers on the surface
of metallic structures. The formation of a protective layer in high pH environments is referred to as
passivation.
Higher concentrations of ions can break down protective oxide films, reduce the quality of concrete
cover, and decrease soil resistivity in wet weather conditions.
▪ In addition to lowering soil resistivity in wet weather conditions, high concentrations of chloride
ions tend to break down otherwise protective surface oxide films and can promote corrosion of
buried metallic structures and reinforcing steel embedded in concrete.
▪ In addition to reducing soil resistivity in wet weather conditions, high concentrations of sulfate
ions can chemically attack concrete structures and promote corrosion of buried metallic
structures.
▪ Although bicarbonates are not directly aggressive to buried metallic or concrete structures,
higher concentrations tend to decrease soil resistivity and promote corrosion activity.
V&A measured in-situ soil resistivity along the transmission and distribution pipeline alignments to
preliminarily assess the soil corrosivity for the Harvest Water Program. The corrosion enginee r for each
project within the program should perform additional measurements on soil samples collected at the
pipeline depths from borings taken by the project geotechnical engineers to further characterize the
soil. The soil samples should be tested in the laboratory for minimum soil resistivity, pH, and
concentrations of water-soluble chloride, sulfate, and bicarbonate ions.
The methods used to perform the in-situ soil resistivity testing, detailed results of the testing, and
corresponding preliminary soil corrosivity are presented in this section. V&A performed the in-situ soil
resistivity testing from September 8th through October 21st, 2020. Testing was performed at 167
locations along the proposed pipeline alignment to depths of 5, 10, 15, and 20 feet. Measurements
were also taken to a depth of 30 feet at locations where the pipeline will cross rivers, railroads, or other
features requiring the pipeline to be buried deeper.
A map showing an overview of the proposed pipeline alignment featuring the in-situ soil resistivity test
locations is shown in Figure 2-1. Note that not all measurement locations are labeled on Figure 2-1;
however, all points are clearly labeled on the more detailed maps in Appendix B.
Harvest Water Program: Corrosion Protection for Pipelines BODR Soil Corrosivity
| Project No. 19-0093 | 4
Figure 2-1. Project Vicinity Map
Harvest Water Program: Corrosion Protection for Pipelines BODR Soil Corrosivity
| Project No. 19-0093 | 5
2.1 Methods
Soil resistivity is a property that quantifies how strongly soil opposes the flow of electric current. Since
corrosion is an electrochemical process accompanied by current flow, it is of primary importance to
measure resistivity when investigating soil corrosivity. A lower soil resistivity value generally
corresponds with a greater degree of electrical activity and a higher corrosion rate. The methods used
to measure soil resistivity are discussed in this section.
In-situ Soil Resistivity Testing
In-situ soil resistivity testing was performed using the Wenner 4-Pin Method in accordance with
ASTM G57. This test method involves the use of four metallic pins driven into the soil in a straight line at
equidistant spacing. A ground resistance tester is used to discharge alternating current into the soil
from the two outer pins. The current creates a voltage gradient in the soil proportional to the average
resistance of the soil. The voltage drop between the two inner pins is measured, and the resistance of
the soil to a depth equal to the p in spacing is calculated by the meter using Ohm’s Law (“resistance is
equal to voltage divided by current,” or R = V/I). A typical Wenner 4-pin resistivity test setup is
presented in Figure 2-2, and an example setup is shown in Photo 2-1.
Figure 2-2. Soil Resistivity Measurement Setup
Soil Resistance Meter
C1 P1 P2 C2
1.53 Ω Calculate Resistance
Pin
x x x
Pin Spacing
Test Wire
Measure Voltage (V)
Apply Current (A)
Harvest Water Program: Corrosion Protection for Pipelines BODR Soil Corrosivity
| Project No. 19-0093 | 6
Photo 2-1. Example of Wenner 4-Pin Test Setup
The soil resistance value from the meter is recorded, and resistivity of the soil to a depth equal to the
pin spacing is calculated with the following formula:
𝜌 = 2𝜋𝑥𝑅
where ρ = soil resistivity (Ω-cm)
π = 3.14 (approximately)
x = distance between pins (cm)
R = soil resistance, value from meter (Ω)
At the completion of each test, the pin spacing is adjusted and the test is repeated.
Harvest Water Program: Corrosion Protection for Pipelines BODR Soil Corrosivity
| Project No. 19-0093 | 7
Barnes Soil Layer Resistivity Calculations
The soil resistance values from the meter are also used to calculate the resistivity of individual layers of
soil; this procedure is referred to as the Barnes Soil Layer Resistivity Calculations. The relation between
soil resistivity to depth and soil layer resistivity is shown graphically in Figure 2-3.
Figure 2-3. Soil Resistivity to Depth and Soil Layer Resistivity
Individual soil layer resistances (RA-B) are calculated using the following formula:
𝑅𝐴−𝐵 =𝑅𝐴𝑅𝐵𝑅𝐴 − 𝑅𝐵
where RA-B = resistance of soil layer between depth A and depth B (Ω)
RA = soil resistance to depth A, value from meter (Ω)
RB = soil resistance to depth B, value from meter (Ω)
Note that the resistance of the soil layer from grade to 5 feet below grade ( R0-A) is equivalent to
resistance to depth A (RA) and is not calculated using the Barnes Layer formula. Average resistivity of a
layer of soil (ρA-B) is calculated with the following equation:
𝜌𝐴−𝐵 = 2𝜋(𝐵 − 𝐴)𝑅𝐴−𝐵
where ρA-B = average resistivity of soil layer from depth A to depth B (Ω-cm)
π = 3.14 (approximately)
A = depth below grade to top of soil layer (cm)
B = depth below grade to bottom of soil layer (cm)
RA-B = resistance of soil layer between depth A and depth B (Ω)
Layer 0-A (5 feet)
Layer A-B (5 feet)
Layer B-C (5 feet)
Layer C-D (5 feet)
Layer D-E (10 feet)
Soil Layer Resistivity
Depth 0 (0 feet below grade)
Depth A (5 feet below grade)
Depth B (10 feet below grade)
Depth C (15 feet below grade)
Depth D (20 feet below grade)
Depth E (30 feet below grade)
Soil Resistivity to Depth
Harvest Water Program: Corrosion Protection for Pipelines BODR Soil Corrosivity
| Project No. 19-0093 | 8
Interpretation of Soil Resistivity Data
The correlation between resistivity and anticipated corrosion activity of steel is presented in Table 2-1.
Table 2-1. Effect of Resistivity on Soil Corrosivity1
Soil Resistivity
(Ω-cm) Degree of Corrosivity
≤ 500 Very High
501 – 1,000 High
1,001 – 2,000 Moderate
2,001 – 10,000 Mild
> 10,000 Negligible
The interpretation of this correlation varies somewhat among corrosion engineers; however, Table 2-1 is
a generally accepted guide.
2.2 Results and Conclusions
The results of the soil resistivity measurements indicate that soil resistivity is relatively consistent along
the proposed pipeline alignments. In general, the soil at the program location is in the range of 1,000
to 2,500 Ω-cm.
A summary of the in-situ soil resistivity results is presented in Table 2-2 and Table 2-3. The individual
results for each resistivity test location are presented in Appendix A.
Table 2-2. Summary of In-Situ Soil Resistivity Results
Depth
(ft)
Soil Resistivity to Depth (Ω-cm) Layer
(ft)
Resistivity of Layer (Ω-cm)
Average Minimum Maximum Average Minimum Maximum
5 2,327 613 24,513 0 - 5 2,318 613 24,513
10 1,767 594 8,810 5 - 10 1,703 481 7,762
15 1,718 632 6,923 10 - 15 2,058 477 14,676
20 1,679 651 7,009 15 - 20 2,291 440 32,768
30 1,484 1,034 2,356 20 - 30 958 493 1,856
All
Depths
1,863 594 24,513 All Layers 2,063 440 32,768
1 Peabody, A. and Parker, M. “Corrosion Basics, an Introduction,” Ed. By Brasunas, A. NACE International, p. 191 (1984)
Harvest Water Program: Corrosion Protection for Pipelines BODR Soil Corrosivity
| Project No. 19-0093 | 9
Table 2-3. Overall Percentage of Soil Layer Corrosivity
Corrosivity
Percent of Measurements (%) per Soil Layer (feet)
All Layers 0 - 5 5 - 10 10 - 15 15 - 20 20 - 30
Very High 1 0 1 1 1 0
High 16 12 20 18 17 6
Moderate 52 50 57 51 51 44
Mild 30 37 23 29 28 50
Negligible 1 1 0 1 2 0
Conclusion: Based on the results of the in-situ soil resistivity testing, the soil at the program location
ranges from negligibly to very highly corrosive with most soils ranging from mildly to highly corrosive.
2.3 Recommendations
The following recommendations are presented based on the results and conclusions of the soil
corrosivity investigation:
1. Collect and provide laboratory analysis of soil samples at the pipeline depth every 5,000 feet for
minimum soil resistivity, pH, and concentrations of chloride, sulfate, and bicarbonate ions. The soil
samples shall be collected by the project geotechnical engineer at the direction of a Corrosion
Engineer. A Corrosion Engineer is a Registered Professional Corrosion Engineer or a NACE CP4 (CP
Specialist) with a Professional Engineering license in a related discipline. The Corrosion Engineer
shall assess the soil corrosivity to buried metallic piping and provide recommendations for
corrosion protection in a report.
2. Preliminary results indicate that it is likely that cathodic protection (CP) systems will be required on
buried metallic piping and fittings. The CP system or corrosion monitoring system shall be designed
by a Corrosion Engineer.
3. When designing the CP systems, run scenarios for high, low, and typical resistivities to ensure the
CP system can protect the pipelines within all these conditions (to a reasonable degree).
4. A Coatings Specialist shall either prepare or review the coating and lining specifications for metallic
pipelines and fittings. A Coatings Specialist is a Registered Professional Corrosion Engineer or a
NACE CIP3 with a Professional Engineering license in a related discipline. The specified coatings
and linings shall be suitable for the application.
Harvest Water Program: Corrosion Protection for Pipelines BODR General Information About CP
| Project No. 19-0093 | 10
3 General Information About CP
CP is a method of corrosion control that uses an external anode as a current source to impress DC
current through the soil onto a pipeline. CP reverses the flow of corrosion currents that occur when a
pipeline is installed in corrosive soil. The pipeline is made more electronegative with respect to the soil,
and the pipeline becomes the cathode in the corrosion cell. The current flows along the pipeline to the
drain cable to complete the circuit.
The first decision the designer, owner, and operator of the CP system need to make is whether to install
a galvanic anode cathodic protection (GACP) or impressed current cathodic protection (ICCP) system.
There are guidelines for when to use each system type based on soil resistivity and the pipeline current
requirement. In addition, each project has unique requirements to consider.
3.1 GACP System Discussion
Within certain limits, galvanic anodes offer a relatively inexpensive and convenient means of controlling
corrosion. In a GACP system, the anodes are constructed from an active metal, such as magnesium or
zinc. The electric potential available to produce the flow of electric current is limited to the difference in
potential between the galvanic anode and the pipeline. The driving voltage between the anode and the
pipeline results in corrosion of the anode and current flow to the pipeline. The use of galvanic anodes is
usually economical in applications where the pipeline has a lower cathodic protection current
requirement (typically less than 1 A), and the soil resistivity is less than 3,000 ohm-cm.
Galvanic anodes have an insulated copper lead wire connected to the anode at one end. The free end
of the lead wire is terminated in a test station for monitoring. The test station includes a terminal board
with mechanical lugs for terminating the anode lead wires and pipeline drain cable. Installation of a test
station allows the pipeline potential and anode current to be measured and monitored to ensure proper
operation of the system. A schematic showing a GACP system is shown in Figure 3-1.
Harvest Water Program: Corrosion Protection for Pipelines BODR General Information About CP
| Project No. 19-0093 | 11
Figure 3-1. GACP System Schematic
3.2 ICCP System Discussion
Impressed current CP (ICCP) systems use a power source to impress current from an external anode
through the soil to a pipeline. The impressed current anode is constructed from an inert material, such
as graphite or cast iron. A wire from the negative terminal of the power source is connected to the
pipeline and wires from the positive terminal are connected to anodes. A schematic of an impressed
current CP system with a rectifier and anodes in a deep well (one possible anode configuration) is
shown in Figure 3-2.
Power is typically sourced as alternating current (AC) from the electrical grid that is t hen rectified to
direct current (DC). Existing AC power at structures and transformers are used as much as possible.
When possible, rectifiers will be located along access roads or in other areas that provide convenient
access. Alternate power sources can also be used, such as solar systems with photovoltaic panels,
batteries, and charge controllers.
An advantage of an ICCP system over a GACP system is the ability to adjust the amount of protective
current applied to the pipeline and the capability to protect several miles of pipe from one current
source. ICCP systems are generally applicable to situations where AC power is available, the pipeline
has a higher CP current requirement, or soil resistivity is greater than 3,000 oh m-cm.
Harvest Water Program: Corrosion Protection for Pipelines BODR General Information About CP
| Project No. 19-0093 | 12
Figure 3-2. Impressed Current CP System Schematic
3.3 CP Criteria
One criterion used to determine whether a steel or ductile iron pipeline is adequately protected from
corrosion is commonly called the “−850 mV criterion,” which comes from NACE SP0169, Section
6.2.1.3:
"A structure-to-electrolyte potential of −850 mV or more negative as measured with respect to a saturated
copper/copper sulfate (CSE) reference electrode. This potential may be either a direct measurement of the
polarized potential or a current-applied potential. Interpretation of a current-applied measurement requires
consideration of the significance of voltage drops in the earth and metallic paths."
The polarized potential is measured when the cathodic protection current is momentarily interrupted,
which is called the “instant off” potential. An alternate criterion for determining whether a steel or
ductile iron pipeline is adequately protected from corrosion is commonly called the “100 mV shift
criterion,” which comes from NACE SP0169, Section 6.2.1.2:
"A minimum of 100 millivolts of cathodic polarization. Either the formation or the decay of polarization must be
measured to satisfy this criterion."
The 100 mV shift criterion is satisfied if the difference between the " instant off" and the "native"
potential is at least 100 mV. A “native” potential is measured before the application of CP current. Once
the CP system is installed, the pipeline and CP system shall be tested to ensure either the −850 mV
criterion or the 100 mV shift criterion per NACE 0169 is satisfied.
Harvest Water Program: Corrosion Protection for Pipelines BODR CP System Design Calculations Approach
| Project No. 19-0093 | 13
4 CP System Design Calculations Approach
4.1 Theoretical Current Requirement
For new pipelines that have not been installed yet, the current requirement is typically th eoretically
calculated based on the expected pipeline surface area and assumed required current density, which is
dependent upon the pipe material and coating. The theoretical current requirement is calculated using
the following equation:
𝐼𝑆 = 𝜋𝐷𝐿𝐶𝐷𝑆 (1 −𝐶𝐸𝑆100
)
where IS = theoretical current requirement (mA)
D = diameter of piping (ft)
L = length of piping (ft)
CDS = assumed required current density (mA/ft2)
CES = assumed coating efficiency (%)
4.2 Sizing the CP System
When designing a CP system, multiple iterations of calculations must be performed until a design can
be found that has a current capacity that exceeds the current requirement of the pipeline, a voltage
capacity that can discharge the required amount of current, and an anod e life of at least 20 years. An
example of some key equations that are used in the design process are the following.
The required voltage and current output are related to one another along with CP circuit resistance by
Ohm’s Law:
𝑉𝑅 = 𝐼𝐶𝑃𝑅𝐶𝑃
where VR = Required voltage (V)
ICP = CP current output (A)
RCP = CP circuit resistance (Ω)
The CP circuit resistance is the sum of the anode resistance, pipeline resistance, and wire resi stance:
𝑅𝐶𝑃 = 𝑅𝐴 + 𝑅𝑊 + 𝑅𝑆
where RCP = CP circuit current (Ω)
RA = resistance of anodes to remote earth (Ω)
RW = resistance of wires (Ω)
RS = resistance of pipeline to remote earth (Ω)
Harvest Water Program: Corrosion Protection for Pipelines BODR Electrical Isolation
| Project No. 19-0093 | 14
5 Electrical Isolation Metallic pipelines shall be electrically isolated from existing pipes, vaults, and structures. It is important
to electrically isolate the pipelines from these foreign structures because the foreign structures can
drain the CP current (act like a CP current sink). If the structures drain enough CP current from the
pipeline, then the NACE SP0169 CP protection criteria may no longer be achieved, and the pipeline may
not be adequately protected from corrosion. It is also important to isolate new pipelines from old
pipelines because they may have differences in electrochemical potential resulting in galvanic
corrosion. It is recommendation that electrical isolation be designed and installed in accordance with
NACE SP0286, Electrical Insulation of Cathodically Protected Pipelines.
5.1 Insulating Flange Kit
Insulating flange kits refer to flanged joints with insulating components that prevent current passing
from one side of the joint to the other. Insulating flange kits include a gasket that goes between the
flanges, insulating sleeves that prevent the bolt shaft from contacting the flange holes, and insulating
washers that prevent the bolt head and nuts from directly contacting either flange face. Stainless steel
washers are installed along with the insulating washers to provide added strength and distribute load
across the washer.
After the insulating flange kit is installed, it is recommended that the joint be wrapped in petrolatum
wax tape to inhibit current from flowing through the electrolyte and around the join t. The petrolatum wax
tape has the added benefit of providing barrier protection to the electrically isolated stainless steel
fasteners of the joint.
Quality control and care during installation are paramount when using insulating flange kit s, especially
for pipelines with large diameters (such as greater than 42-inches in diameter). Insulating flange kits
have been used successfully on large diameter pipes, but they require careful attention to be installed
correctly. If they are not installed correctly, then there may be electrical shorts, which are oftentimes
found after the pipe has been backfilled.
5.2 Monolithic Insulating Joint
Monolithic insulating joints are factory assembled insulating joints that arrive to the job site as a single
component. This unique design provides proven long-term isolation properties for the joint and should
be considered for large diameter pipelines (over 48-inches in diameter) that are prone to pipeline
settlement. Monolithic insulating joints are designed so that they are either welded into the field piping
during installation or installed via bolted flanges.
Electrical isolation across a monolithic insulating joint is tested before leaving the factory, reducing the
number of electrical shorts found in the field. Monolithic insulating joints typically cost more than
insulating flange kits and have a longer lead time; however, they can be installed at a lower cost, which
makes both types of insulating joint designs competitive alternatives.
Harvest Water Program: Corrosion Protection for Pipelines BODR Electrical Isolation
| Project No. 19-0093 | 15
5.3 Isolation at Casings
Dielectric spacers are used to isolate the casing from the carrier pipe. The casing is often uncoated
bare steel with a large surface area, which poses the risk of draining significant CP current if it
becomes shorted to the carrier pipe. Properly installed and sufficient dielectric spacers typically provide
effective separation distance for metallic isolation.
End seals are used at the casing ends to minimize the risk of an electrolytic short between the pipeline
and casing. Filling the annular space with a high-resistivity grout should be considered if the casing is
below the water line to prevent electrolytic shorts due to water intrusion in the annular space.
Harvest Water Program: Corrosion Protection for Pipelines BODR Joint Bonds
| Project No. 19-0093 | 16
6 Joint Bonds The purpose of joint bonds is to decrease the linear resistance of the pipeline and provide electrical
continuity. A CP system behaves as an electrical circuit; current flows to structures (cathodes) that are
electrically continuous with the anodes. When a pipeline is electrically discontinuous, CP current is
unable to protect the pipeline at locations past the discontinuity because the current has no way of
returning back to the rectifier to complete the CP circuit.
Joint bonds are required for non-welded pipe joints, such as bell-and-spigot, bolted, or mechanically
coupled field joints. Joint bonds should not be installed on insulating joints, which are intention ally
installed to provide electrical isolation at the joint.
Joint bonds typically consist of insulated, stranded, copper wires that are exothermically welded to each
side of the joint. The length, gauge, and number of copper wires at each joint shall be determined by
calculating the acceptable increase in attenuation. Typically, an acceptable amount of increased
attenuation is double the amount of attenuation that would be present for a welded pipeline of the
same dimensions. In practice, this means the electrical resistance at each joint should be less than or
equal to the electrical resistance of one stick of pipe.
Harvest Water Program: Corrosion Protection for Pipelines BODR Test Stations
| Project No. 19-0093 | 17
7 Test Stations The purpose of providing the pipeline with a CP system is to mitigate the harmful effects of external
corrosion due to the soil corrosivity and extend the useful life of the pipeline. Various types of test
stations are used to monitor the performance of the CP system. The pipe-to-soil potentials of the
pipeline can be measured at all of the following types of test stations, whic h is then compared to NACE
criteria for adequate corrosion control to determine the effectiveness of the CP system .
7.1 Monitoring Test Stations (MTS)
MTS are used to measure pipe-to-soil potentials of the pipeline. Two test leads are attached to the
pipeline and terminated in a test station box. The maximum distance between test stations of any type
shall be 1,000 feet, and MTS shall be placed at appropriate intervals between other test station types
to maintain this requirement.
7.2 Insulating Joint Test Stations (IJTS)
IJTS are installed at insulating joints to measure the effectiveness of the insulating joint and ensure it is
functioning properly. IJTS consist of test leads initiating from both sides of the insulating joint and
terminating in a test station box.
7.3 Casing Test Stations (CTS)
CTS are installed at the ends of casings to measure the effectiveness of the isolation between the
carrier pipe and casing. When casings are used, the casing should be electrically isolated from the
carrier pipe. Test leads from the casing and carrier pipe are terminated in a test station box.
7.4 Foreign Pipeline Test Stations (FPTS)
FPTS may be installed at foreign pipeline crossings to measure the electrical interaction between the
project pipeline and the foreign pipeline. The FPTS consists of project pipeline test leads, foreign
pipeline test leads, and galvanic anode test leads terminated in a test station box. If current is
discharging from the project pipeline to the foreign pipeline, then the galvanic anode test leads can be
connected to the project pipeline at the test station box so current will discharge from the anodes
instead of the project pipeline. A neoprene mat should be installed between the project pipeline and
foreign pipeline to increase resistance and reduce current flow through the soil between the pipelines.
7.5 Anode Test Stations (ATS)
ATS are installed where galvanic anodes are cathodically protecting metallic pipelines or metallic
fittings that are associated with PVC pipelines. Test leads from the pipeline or fitting and galvanic
anodes are terminated in a test station box. The current output and open circuit potential of the
galvanic anodes providing CP current should be measured in addition to the pipe -to-soil potentials.
Harvest Water Program: Corrosion Protection for Pipelines BODR Test Stations
| Project No. 19-0093 | 18
7.6 Post-mounted vs. Flush-mounted Test Station Box
All test leads are terminated in either a post-mounted or flush-mounted test station box. It is common to
use post-mounted test stations in rural areas and open fields because they are easier to find and spot
from a distance. Flush-mounted test stations are commonly used in urban environments and along the
sides of roads because they do not create obstacles. In areas where flush -mounted test stations could
easily be covered up (with vegetation, for instance), then post -mounted test stations should be used.
Harvest Water Program: Corrosion Protection for Pipelines BODR Stray Current Mitigation
| Project No. 19-0093 | 19
8 Stray Current Mitigation
8.1 DC Stray Current from Buried Foreign Utilities
Interference occurs when a foreign CP system protecting a foreign pipeline influences the project
pipeline, which is not part of the intended system. The voltage gradient created by the foreign CP anode
bed may cause current to flow onto the project pipeline. This DC stray current returns to the foreign CP
rectifier through the project pipeline, which acts as a low resistance conductor. Current discharge from
the project pipeline may occur where the two pipelines cross or in areas of low resistivity soil. Corrosion
occurs at the point where the current leaves the project pipeline (i.e., current discharges) to return to
the foreign CP rectifier. A schematic of DC stray current influence is shown in Figure 8-1. V&A
recommends installing foreign pipeline test stations (FPTS) at foreign pipeline crossings. Refer to
Section 7.4 for detailed information about the FPTS.
Figure 8-1. DC Stray Current Influence
Most DC stray current problems are generally considered to be a combination of two types of
interference:
1. Anodic interference, which occurs where the project pipeline receives CP current from a foreign
pipeline’s anode bed, and generally occurs where the project pipeline is near the foreign pipeline’s
rectifier. The potential of the project pipeline will be shifted electronegatively in areas of anodic
interference.
2. Cathodic interference, which occurs where the project pipeline is discharging CP current into the
soil to the foreign pipeline, and generally occurs where the project pipeline crosses the foreign
Harvest Water Program: Corrosion Protection for Pipelines BODR Stray Current Mitigation
| Project No. 19-0093 | 20
pipeline. The potential of the project pipeline will be shifted electropositively in areas of cathodic
interference.
8.2 AC Stray Current from Overhead Power Lines
AC stray current effects should be considered when pipelines are installed in close vicinity to overhead
electric transmission facilities. Based on experience, general guidance promotes AC stray current
evaluation when the overhead circuit loading is 69 kV and higher and the buried pipeline is within
2,000 feet of the electric corridor; however, specific conditions can modify this guidance. There are two
primary concerns resulting from AC stray currents:
1. Step touch potentials, which pose a safety hazard to employees working on the pipeline (when
touching valves, test leads, etc.).
▪ Locations with induced voltage of 15 VAC or more are a safety risk. This is commonly referred to
as “step touch potential.” Individuals exposed to pipel ines that may have induced voltages
should safely determine the induced voltage value prior to touching the pipeline or its
components.
2. Pipeline corrosion resulting from induced AC.
▪ AC current density can be calculated when induced AC potential and soil resistivity have been
measured. When AC current density is below 20 A/m2, the risk of pipeline corrosion is minimal.
When AC current density values are above 100 A/m2, pipeline corrosion is likely. Between these
two values, pipeline corrosion risk is indeterminate. It is important to note that AC current
density can be high in locations with very low soil resistivity, and locations with pipeline
corrosion risk can exist with induced AC voltage levels as low as 2 VAC.
▪ Typically, AC related pipeline corrosion risk is higher for pipelines that are well coated (steel
pipelines with dielectric coating) as compared to pipelines with low coating efficiency (mortar
coated pipelines). This is due to AC current discharge from the pipeline that may occur at small ,
focused coating holidays (breaks or damaged coating). This project includes both types of
pipelines.
Induced AC potentials on the pipeline can be measured with a referenc e electrode and a calibrated
multimeter. Typically, maximum induced AC potential on the buried pipeline can be found where the
pipeline deviates from the overhead electric corridor after long lengths of parallel occupancy. The
location of pipeline insulating joints are also areas of concern, and induced AC potential should be
measured on each side of the insulating joint.
The project corrosion engineer should review the plan and profile drawings in addition to google earth
maps to identify locations of AC stray current concern for the pipeline. It is recommended that AC
monitoring test stations be installed at strategic “hot spot” locations where induced AC potential may be
highest. AC monitoring test stations should employ a “dead front” test panel to minimize risk associated
with electrical shock. Induced AC potential can be measured at these test stations after installation to
evaluate the pipeline’s AC corrosion and safety risk. Induced AC potential will vary depending on the
overhead electric transmission circuit loading, which changes within a 24-hour cycle and seasonally.
Following commissioning of the cathodic protection system, testing should be coordinated with the
electric utility provider to capture the maximum induced AC conditions on the pipeline .
AC stray current can be effectively managed with the installation of grounding systems an d solid state
decouplers. These devices allow AC stray current to safely drain from the pipeline while maintaining DC
cathodic protection current. Should AC stray current mitigation be required, decoupler sizing and
grounding system design should be completed by a registered Corrosion Engineer or an experienced
NACE-certified Corrosion Specialist (CP4) after cooperative testing with the electric utility provider.
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-1
Appendix A In-situ Soil Resistivity Data The following data was collected and analyzed by V&A.
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
1 5 1.00 958 0 - 5 1.00 958 High
10 0.51 977 5 - 10 1.04 997 High
15 0.36 1,034 10 - 15 1.22 1,172 Moderate
20 0.28 1,072 15 - 20 1.26 1,207 Moderate
2 5 1.64 1,570 0 - 5 1.64 1,570 Moderate
10 0.62 1,187 5 - 10 1.00 955 High
15 0.43 1,235 10 - 15 1.40 1,344 Moderate
20 0.32 1,226 15 - 20 1.25 1,198 Moderate
3 5 2.11 2,020 0 - 5 2.11 2,020 Mild
10 0.93 1,781 5 - 10 1.66 1,592 Moderate
15 0.51 1,465 10 - 15 1.13 1,081 Moderate
20 0.36 1,379 15 - 20 1.22 1,172 Moderate
4 5 1.23 1,178 0 - 5 1.23 1,178 Moderate
10 0.54 1,034 5 - 10 0.96 922 High
15 0.41 1,178 10 - 15 1.70 1,631 Moderate
20 0.32 1,226 15 - 20 1.46 1,396 Moderate
5 5 0.86 823 0 - 5 0.86 823 High
10 0.39 747 5 - 10 0.71 683 High
15 0.30 862 10 - 15 1.30 1,245 Moderate
20 0.26 996 15 - 20 1.95 1,867 Moderate
30 0.22 1,264 20 - 30 1.43 2,739 Mild
6 5 1.53 1,465 0 - 5 1.53 1,465 Moderate
10 0.82 1,570 5 - 10 1.77 1,692 Moderate
15 0.62 1,781 10 - 15 2.54 2,434 Mild
20 0.46 1,762 15 - 20 1.78 1,707 Moderate
30 0.32 1,839 20 - 30 1.05 2,014 Mild
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-2
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
7 5 0.64 613 0 - 5 0.64 613 High
10 0.34 651 5 - 10 0.73 695 High
15 0.26 747 10 - 15 1.11 1,058 Moderate
20 0.22 843 15 - 20 1.43 1,369 Moderate
8 5 1.08 1,034 0 - 5 1.08 1,034 Moderate
10 0.71 1,360 5 - 10 2.07 1,984 Moderate
15 0.55 1,580 10 - 15 2.44 2,337 Mild
20 0.46 1,762 15 - 20 2.81 2,692 Mild
9 5 2.61 2,499 0 - 5 2.61 2,499 Mild
10 0.59 1,130 5 - 10 0.76 730 High
15 0.27 776 10 - 15 0.50 477 Very High
20 0.17 651 15 - 20 0.46 440 Very High
10 5 1.91 1,829 0 - 5 1.91 1,829 Moderate
10 0.84 1,609 5 - 10 1.50 1,436 Moderate
15 0.49 1,408 10 - 15 1.18 1,126 Moderate
20 0.33 1,264 15 - 20 1.01 968 High
11 5 2.62 2,509 0 - 5 2.62 2,509 Mild
10 1.22 2,336 5 - 10 2.28 2,186 Mild
15 0.68 1,953 10 - 15 1.54 1,471 Moderate
20 0.46 1,762 15 - 20 1.42 1,361 Moderate
12 5 1.18 1,130 0 - 5 1.18 1,130 Moderate
10 0.63 1,207 5 - 10 1.35 1,294 Moderate
15 0.44 1,264 10 - 15 1.46 1,397 Moderate
20 0.33 1,264 15 - 20 1.32 1,264 Moderate
13 5 4.67 4,472 0 - 5 4.67 4,472 Mild
10 1.47 2,815 5 - 10 2.15 2,054 Mild
15 0.65 1,867 10 - 15 1.17 1,116 Moderate
20 0.44 1,685 15 - 20 1.36 1,304 Moderate
30 0.27 1,551 20 - 30 0.70 1,338 Moderate
14 5 0.94 900 0 - 5 0.94 900 High
10 0.61 1,168 5 - 10 1.74 1,664 Moderate
15 0.45 1,293 10 - 15 1.72 1,643 Moderate
20 0.35 1,341 15 - 20 1.58 1,508 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-3
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
15 5 1.01 967 0 - 5 1.01 967 High
10 0.61 1,168 5 - 10 1.54 1,475 Moderate
15 0.44 1,264 10 - 15 1.58 1,512 Moderate
20 0.32 1,226 15 - 20 1.17 1,124 Moderate
16 5 3.21 3,074 0 - 5 3.21 3,074 Mild
10 1.10 2,107 5 - 10 1.67 1,602 Moderate
15 0.48 1,379 10 - 15 0.85 815 High
20 0.36 1,379 15 - 20 1.44 1,379 Moderate
30 0.23 1,321 20 - 30 0.64 1,220 Moderate
17 5 4.21 4,031 0 - 5 4.21 4,031 Mild
10 1.75 3,351 5 - 10 2.99 2,868 Mild
15 0.99 2,844 10 - 15 2.28 2,183 Mild
20 0.65 2,490 15 - 20 1.89 1,812 Moderate
18 5 1.74 1,666 0 - 5 1.74 1,666 Moderate
10 0.71 1,360 5 - 10 1.20 1,149 Moderate
15 0.46 1,321 10 - 15 1.31 1,251 Moderate
20 0.32 1,226 15 - 20 1.05 1,007 Moderate
30 0.25 1,436 20 - 30 1.14 2,189 Mild
19 5 2.01 1,925 0 - 5 2.01 1,925 Moderate
10 0.67 1,283 5 - 10 1.01 962 High
15 0.36 1,034 10 - 15 0.78 745 High
20 0.25 958 15 - 20 0.82 783 High
30 0.18 1,034 20 - 30 0.64 1,231 Moderate
20 5 4.29 4,108 0 - 5 4.29 4,108 Mild
10 1.32 2,528 5 - 10 1.91 1,826 Moderate
15 0.59 1,695 10 - 15 1.07 1,022 Moderate
20 0.37 1,417 15 - 20 0.99 950 High
21 5 1.77 1,695 0 - 5 1.77 1,695 Moderate
10 0.73 1,398 5 - 10 1.24 1,190 Moderate
15 0.46 1,321 10 - 15 1.24 1,191 Moderate
20 0.33 1,264 15 - 20 1.17 1,118 Moderate
22 5 1.61 1,542 0 - 5 1.61 1,542 Moderate
10 0.78 1,494 5 - 10 1.51 1,449 Moderate
15 0.49 1,408 10 - 15 1.32 1,262 Moderate
20 0.38 1,455 15 - 20 1.69 1,621 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-4
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
24 5 2.00 1,915 0 - 5 2.00 1,915 Moderate
10 0.66 1,264 5 - 10 0.99 943 High
15 0.37 1,063 10 - 15 0.84 806 High
20 0.28 1,072 15 - 20 1.15 1,102 Moderate
30 0.21 1,207 20 - 30 0.84 1,609 Moderate
25 5 1.65 1,580 0 - 5 1.65 1,580 Moderate
10 0.73 1,398 5 - 10 1.31 1,254 Moderate
15 0.43 1,235 10 - 15 1.05 1,002 Moderate
20 0.30 1,149 15 - 20 0.99 950 High
26 5 1.41 1,350 0 - 5 1.41 1,350 Moderate
10 0.95 1,819 5 - 10 2.91 2,788 Mild
15 0.62 1,781 10 - 15 1.78 1,709 Moderate
20 0.44 1,685 15 - 20 1.52 1,451 Moderate
30 0.32 1,839 20 - 30 1.17 2,247 Mild
27 5 1.46 1,398 0 - 5 1.46 1,398 Moderate
10 0.93 1,781 5 - 10 2.56 2,453 Mild
15 0.58 1,666 10 - 15 1.54 1,476 Moderate
20 0.59 2,260 15 - 20 * * *
28 5 1.14 1,092 0 - 5 1.14 1,092 Moderate
10 0.63 1,207 5 - 10 1.41 1,348 Moderate
15 0.36 1,034 10 - 15 0.84 804 High
20 0.29 1,111 15 - 20 1.49 1,428 Moderate
30 0.22 1,264 20 - 30 0.91 1,745 Moderate
29 5 1.12 1,072 0 - 5 1.12 1,072 Moderate
10 0.73 1,398 5 - 10 2.10 2,007 Mild
15 0.48 1,379 10 - 15 1.40 1,342 Moderate
20 0.37 1,417 15 - 20 1.61 1,546 Moderate
30 0.28 1,609 20 - 30 1.15 2,205 Mild
30 5 0.72 689 0 - 5 0.72 689 High
10 0.40 766 5 - 10 0.90 862 High
15 0.27 776 10 - 15 0.83 796 High
20 0.24 919 15 - 20 2.16 2,068 Mild
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-5
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
31 5 1.98 1,896 0 - 5 1.98 1,896 Moderate
10 1.05 2,011 5 - 10 2.24 2,141 Mild
15 0.63 1,810 10 - 15 1.58 1,508 Moderate
20 0.45 1,724 15 - 20 1.58 1,508 Moderate
30 0.24 1,379 20 - 30 0.51 985 High
32 5 0.95 910 0 - 5 0.95 910 High
10 0.65 1,245 5 - 10 2.06 1,971 Moderate
15 0.51 1,465 10 - 15 2.37 2,267 Mild
20 0.42 1,609 15 - 20 2.38 2,279 Mild
33 5 1.39 1,331 0 - 5 1.39 1,331 Moderate
10 0.69 1,321 5 - 10 1.37 1,312 Moderate
15 0.46 1,321 10 - 15 1.38 1,321 Moderate
20 0.33 1,264 15 - 20 1.17 1,118 Moderate
34 5 1.43 1,369 0 - 5 1.43 1,369 Moderate
10 0.57 1,092 5 - 10 0.95 908 High
15 0.47 1,350 10 - 15 2.68 2,565 Mild
20 0.30 1,149 15 - 20 0.83 794 High
35 5 1.41 1,350 0 - 5 1.41 1,350 Moderate
10 0.60 1,149 5 - 10 1.04 1,000 Moderate
15 0.38 1,092 10 - 15 1.04 992 High
20 0.29 1,111 15 - 20 1.22 1,172 Moderate
30 0.22 1,264 20 - 30 0.91 1,745 Moderate
36 5 2.28 2,183 0 - 5 2.28 2,183 Mild
10 0.95 1,819 5 - 10 1.63 1,559 Moderate
15 0.55 1,580 10 - 15 1.31 1,251 Moderate
20 0.36 1,379 15 - 20 1.04 998 High
37 5 1.25 1,197 0 - 5 1.25 1,197 Moderate
10 0.67 1,283 5 - 10 1.44 1,383 Moderate
15 0.45 1,293 10 - 15 1.37 1,312 Moderate
20 0.34 1,302 15 - 20 1.39 1,332 Moderate
38 5 0.82 785 0 - 5 0.82 785 High
10 0.47 900 5 - 10 1.10 1,054 Moderate
15 0.34 977 10 - 15 1.23 1,177 Moderate
20 0.28 1,072 15 - 20 1.59 1,519 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-6
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
39 5 1.72 1,647 0 - 5 1.72 1,647 Moderate
10 0.66 1,264 5 - 10 1.07 1,025 Moderate
15 0.37 1,063 10 - 15 0.84 806 High
20 0.29 1,111 15 - 20 1.34 1,284 Moderate
30 0.23 1,321 20 - 30 1.11 2,129 Mild
40 5 1.58 1,513 0 - 5 1.58 1,513 Moderate
10 0.93 1,781 5 - 10 2.26 2,165 Mild
15 0.78 2,241 10 - 15 4.84 4,631 Mild
20 0.29 1,111 15 - 20 0.46 442 Very High
30 0.23 1,321 20 - 30 1.11 2,129 Mild
41 5 1.10 1,053 0 - 5 1.10 1,053 Moderate
10 0.58 1,111 5 - 10 1.23 1,175 Moderate
15 0.38 1,092 10 - 15 1.10 1,055 Moderate
20 0.29 1,111 15 - 20 1.22 1,172 Moderate
42 5 1.45 1,388 0 - 5 1.45 1,388 Moderate
10 0.99 1,896 5 - 10 3.12 2,988 Mild
15 0.82 2,356 10 - 15 4.78 4,573 Mild
20 0.71 2,719 15 - 20 5.29 5,068 Mild
43 5 0.98 938 0 - 5 0.98 938 High
10 0.57 1,092 5 - 10 1.36 1,305 Moderate
15 0.43 1,235 10 - 15 1.75 1,676 Moderate
20 0.37 1,417 15 - 20 2.65 2,539 Mild
44 5 1.94 1,858 0 - 5 1.94 1,858 Moderate
10 0.73 1,398 5 - 10 1.17 1,121 Moderate
15 0.49 1,408 10 - 15 1.49 1,427 Moderate
20 0.37 1,417 15 - 20 1.51 1,447 Moderate
45 5 1.85 1,771 0 - 5 1.85 1,771 Moderate
10 0.94 1,800 5 - 10 1.91 1,830 Moderate
15 0.49 1,408 10 - 15 1.02 980 High
20 0.30 1,149 15 - 20 0.77 741 High
46 5 2.18 2,087 0 - 5 2.18 2,087 Mild
10 0.79 1,513 5 - 10 1.24 1,186 Moderate
15 0.43 1,235 10 - 15 0.94 904 High
20 0.39 1,494 15 - 20 4.19 4,015 Mild
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-7
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
47 5 1.97 1,886 0 - 5 1.97 1,886 Moderate
10 0.86 1,647 5 - 10 1.53 1,462 Moderate
15 0.58 1,666 10 - 15 1.78 1,706 Moderate
20 0.48 1,839 15 - 20 2.78 2,666 Mild
48 5 3.20 3,064 0 - 5 3.20 3,064 Mild
10 1.06 2,030 5 - 10 1.59 1,518 Moderate
15 0.75 2,155 10 - 15 2.56 2,456 Mild
20 0.65 2,490 15 - 20 4.88 4,668 Mild
49 5 1.45 1,388 0 - 5 1.45 1,388 Moderate
10 0.59 1,130 5 - 10 0.99 953 High
15 0.40 1,149 10 - 15 1.24 1,189 Moderate
20 0.23 881 15 - 20 0.54 518 High
50 5 1.31 1,254 0 - 5 1.31 1,254 Moderate
10 0.75 1,436 5 - 10 1.75 1,680 Moderate
15 0.50 1,436 10 - 15 1.50 1,436 Moderate
20 0.37 1,417 15 - 20 1.42 1,363 Moderate
51 5 6.10 5,841 0 - 5 6.10 5,841 Mild
10 1.90 3,639 5 - 10 2.76 2,642 Mild
15 0.95 2,729 10 - 15 1.90 1,819 Moderate
20 0.58 2,222 15 - 20 1.49 1,426 Moderate
52 5 2.36 2,260 0 - 5 2.36 2,260 Mild
10 0.55 1,053 5 - 10 0.72 687 High
15 0.34 977 10 - 15 0.89 853 High
20 0.27 1,034 15 - 20 1.31 1,256 Moderate
53 5 3.41 3,265 0 - 5 3.41 3,265 Mild
10 0.94 1,800 5 - 10 1.30 1,243 Moderate
15 0.74 2,126 10 - 15 3.48 3,330 Mild
20 0.44 1,685 15 - 20 1.09 1,039 Moderate
54 5 2.12 2,030 0 - 5 2.12 2,030 Mild
10 0.83 1,590 5 - 10 1.36 1,306 Moderate
15 0.43 1,235 10 - 15 0.89 854 High
20 0.31 1,187 15 - 20 1.11 1,064 Moderate
56 5 2.63 2,518 0 - 5 2.63 2,518 Mild
10 1.46 2,796 5 - 10 3.28 3,143 Mild
15 0.84 2,413 10 - 15 1.98 1,894 Moderate
20 0.57 2,183 15 - 20 1.77 1,698 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-8
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
57 5 2.37 2,269 0 - 5 2.37 2,269 Mild
10 1.00 1,915 5 - 10 1.73 1,657 Moderate
15 0.82 2,356 10 - 15 4.56 4,362 Mild
20 0.67 2,566 15 - 20 3.66 3,507 Mild
58 5 25.60 24,513 0 - 5 25.60 24,513 Negligible
10 2.19 4,194 5 - 10 2.39 2,293 Mild
15 1.59 4,568 10 - 15 5.80 5,557 Mild
20 0.69 2,643 15 - 20 1.22 1,167 Moderate
59 5 1.75 1,676 0 - 5 1.75 1,676 Moderate
10 0.65 1,245 5 - 10 1.03 990 High
15 0.39 1,120 10 - 15 0.98 934 High
20 0.27 1,034 15 - 20 0.88 840 High
60 5 0.81 776 0 - 5 0.81 776 High
10 0.31 594 5 - 10 0.50 481 Very High
15 0.22 632 10 - 15 0.76 726 High
20 0.18 689 15 - 20 0.99 948 High
61 5 1.43 1,369 0 - 5 1.43 1,369 Moderate
10 0.53 1,015 5 - 10 0.84 806 High
15 0.34 977 10 - 15 0.95 908 High
20 0.25 958 15 - 20 0.94 904 High
62 5 1.75 1,676 0 - 5 1.75 1,676 Moderate
10 0.86 1,647 5 - 10 1.69 1,619 Moderate
15 0.56 1,609 10 - 15 1.61 1,537 Moderate
20 0.43 1,647 15 - 20 1.85 1,774 Moderate
63 5 1.67 1,599 0 - 5 1.67 1,599 Moderate
10 0.69 1,321 5 - 10 1.18 1,126 Moderate
15 0.55 1,580 10 - 15 2.71 2,596 Mild
20 0.45 1,724 15 - 20 2.48 2,370 Mild
64 5 14.30 13,693 0 - 5 14.30 13,693 Negligible
10 4.60 8,810 5 - 10 6.78 6,494 Mild
15 2.41 6,923 10 - 15 5.06 4,847 Mild
20 1.32 5,056 15 - 20 2.92 2,795 Mild
65 5 2.22 2,126 0 - 5 2.22 2,126 Mild
10 1.17 2,241 5 - 10 2.47 2,369 Mild
15 0.80 2,298 10 - 15 2.53 2,422 Mild
20 0.55 2,107 15 - 20 1.76 1,685 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-9
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
66 5 2.76 2,643 0 - 5 2.76 2,643 Mild
10 1.29 2,470 5 - 10 2.42 2,319 Mild
15 1.03 2,959 10 - 15 5.11 4,893 Mild
20 0.84 3,217 15 - 20 4.55 4,360 Mild
67 5 1.50 1,436 0 - 5 1.50 1,436 Moderate
10 0.74 1,417 5 - 10 1.46 1,399 Moderate
15 0.48 1,379 10 - 15 1.37 1,308 Moderate
20 0.37 1,417 15 - 20 1.61 1,546 Moderate
68 5 4.00 3,830 0 - 5 4.00 3,830 Mild
10 1.14 2,183 5 - 10 1.59 1,527 Moderate
15 0.56 1,609 10 - 15 1.10 1,054 Moderate
20 0.46 1,762 15 - 20 2.58 2,467 Mild
69 5 1.95 1,867 0 - 5 1.95 1,867 Moderate
10 0.74 1,417 5 - 10 1.19 1,142 Moderate
15 0.44 1,264 10 - 15 1.09 1,039 Moderate
20 0.32 1,226 15 - 20 1.17 1,124 Moderate
70 5 1.28 1,226 0 - 5 1.28 1,226 Moderate
10 0.67 1,283 5 - 10 1.41 1,346 Moderate
15 0.53 1,523 10 - 15 2.54 2,429 Mild
20 0.42 1,609 15 - 20 2.02 1,938 Moderate
71 5 1.55 1,484 0 - 5 1.55 1,484 Moderate
10 0.68 1,302 5 - 10 1.21 1,160 Moderate
15 0.41 1,178 10 - 15 1.03 989 High
20 0.28 1,072 15 - 20 0.88 846 High
72 5 1.87 1,791 0 - 5 1.87 1,791 Moderate
10 0.58 1,111 5 - 10 0.84 805 High
15 0.34 977 10 - 15 0.82 787 High
20 0.26 996 15 - 20 1.11 1,058 Moderate
73 5 3.44 3,294 0 - 5 3.44 3,294 Mild
10 0.89 1,704 5 - 10 1.20 1,150 Moderate
15 0.51 1,465 10 - 15 1.19 1,144 Moderate
20 0.36 1,379 15 - 20 1.22 1,172 Moderate
74 5 0.81 776 0 - 5 0.81 776 High
10 0.39 747 5 - 10 0.75 720 High
15 0.30 862 10 - 15 1.30 1,245 Moderate
20 0.25 958 15 - 20 1.50 1,436 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-10
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
75 5 1.42 1,360 0 - 5 1.42 1,360 Moderate
10 0.59 1,130 5 - 10 1.01 967 High
15 0.42 1,207 10 - 15 1.46 1,396 Moderate
20 0.35 1,341 15 - 20 2.10 2,011 Mild
76 5 1.65 1,580 0 - 5 1.65 1,580 Moderate
10 0.84 1,609 5 - 10 1.71 1,638 Moderate
15 0.54 1,551 10 - 15 1.51 1,448 Moderate
20 0.46 1,762 15 - 20 3.11 2,973 Mild
77 5 2.75 2,633 0 - 5 2.75 2,633 Mild
10 1.11 2,126 5 - 10 1.86 1,782 Moderate
15 0.78 2,241 10 - 15 2.62 2,512 Mild
20 0.55 2,107 15 - 20 1.87 1,786 Moderate
78 5 1.01 967 0 - 5 1.01 967 High
10 0.61 1,168 5 - 10 1.54 1,475 Moderate
15 0.42 1,207 10 - 15 1.35 1,291 Moderate
20 0.34 1,302 15 - 20 1.79 1,709 Moderate
79 5 1.01 967 0 - 5 1.01 967 High
10 0.47 900 5 - 10 0.88 842 High
15 0.36 1,034 10 - 15 1.54 1,473 Moderate
20 0.33 1,264 15 - 20 3.96 3,792 Mild
80 5 1.92 1,839 0 - 5 1.92 1,839 Moderate
10 0.63 1,207 5 - 10 0.94 898 High
15 0.52 1,494 10 - 15 2.98 2,852 Mild
20 0.44 1,685 15 - 20 2.86 2,739 Mild
30 0.30 1,724 20 - 30 0.94 1,806 Moderate
81 5 2.72 2,605 0 - 5 2.72 2,605 Mild
10 0.64 1,226 5 - 10 0.84 801 High
15 0.45 1,293 10 - 15 1.52 1,451 Moderate
20 0.29 1,111 15 - 20 0.82 781 High
82 5 2.55 2,442 0 - 5 2.55 2,442 Mild
10 0.92 1,762 5 - 10 1.44 1,378 Moderate
15 0.58 1,666 10 - 15 1.57 1,503 Moderate
20 0.40 1,532 15 - 20 1.29 1,234 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-11
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
84 5 2.51 2,403 0 - 5 2.51 2,403 Mild
10 1.40 2,681 5 - 10 3.17 3,031 Mild
15 0.80 2,298 10 - 15 1.87 1,787 Moderate
20 0.52 1,992 15 - 20 1.49 1,423 Moderate
85 5 1.03 986 0 - 5 1.03 986 High
10 0.56 1,072 5 - 10 1.23 1,175 Moderate
15 0.47 1,350 10 - 15 2.92 2,800 Mild
20 0.38 1,455 15 - 20 1.98 1,900 Moderate
86 5 10.37 9,930 0 - 5 10.37 9,930 Mild
10 3.69 7,067 5 - 10 5.73 5,485 Mild
15 1.91 5,487 10 - 15 3.96 3,791 Mild
20 1.35 5,171 15 - 20 4.60 4,409 Mild
87 5 1.40 1,341 0 - 5 1.40 1,341 Moderate
10 0.69 1,321 5 - 10 1.36 1,303 Moderate
15 0.47 1,350 10 - 15 1.47 1,412 Moderate
20 0.35 1,341 15 - 20 1.37 1,313 Moderate
88 5 1.39 1,331 0 - 5 1.39 1,331 Moderate
10 0.81 1,551 5 - 10 1.94 1,859 Moderate
15 0.63 1,810 10 - 15 2.84 2,715 Mild
20 0.46 1,762 15 - 20 1.70 1,632 Moderate
89 5 0.91 871 0 - 5 0.91 871 High
10 0.59 1,130 5 - 10 1.68 1,607 Moderate
15 0.46 1,321 10 - 15 2.09 1,999 Moderate
20 0.37 1,417 15 - 20 1.89 1,811 Moderate
90 5 1.84 1,762 0 - 5 1.84 1,762 Moderate
10 1.27 2,432 5 - 10 4.10 3,926 Mild
15 0.87 2,499 10 - 15 2.76 2,645 Mild
20 0.69 2,643 15 - 20 3.34 3,193 Mild
91 5 8.99 8,608 0 - 5 8.99 8,608 Mild
10 0.70 1,341 5 - 10 0.76 727 High
15 0.52 1,494 10 - 15 2.02 1,936 Moderate
20 0.43 1,647 15 - 20 2.48 2,379 Mild
92 5 2.12 2,030 0 - 5 2.12 2,030 Mild
10 1.04 1,992 5 - 10 2.04 1,955 Moderate
15 0.70 2,011 10 - 15 2.14 2,050 Mild
20 0.53 2,030 15 - 20 2.18 2,090 Mild
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-12
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
93 5 3.78 3,620 0 - 5 3.78 3,620 Mild
10 2.42 4,635 5 - 10 6.73 6,441 Mild
15 1.69 4,855 10 - 15 5.60 5,365 Mild
20 1.20 4,596 15 - 20 4.14 3,963 Mild
94 5 1.05 1,005 0 - 5 1.05 1,005 Moderate
10 0.59 1,130 5 - 10 1.35 1,290 Moderate
15 0.45 1,293 10 - 15 1.90 1,816 Moderate
20 0.42 1,609 15 - 20 6.30 6,033 Mild
95 5 4.52 4,328 0 - 5 4.52 4,328 Mild
10 0.92 1,762 5 - 10 1.16 1,106 Moderate
15 0.43 1,235 10 - 15 0.81 773 High
20 0.31 1,187 15 - 20 1.11 1,064 Moderate
96 5 1.44 1,379 0 - 5 1.44 1,379 Moderate
10 0.65 1,245 5 - 10 1.18 1,135 Moderate
15 0.38 1,092 10 - 15 0.91 876 High
20 0.27 1,034 15 - 20 0.93 893 High
97 5 2.48 2,375 0 - 5 2.48 2,375 Mild
10 0.94 1,800 5 - 10 1.51 1,450 Moderate
15 0.61 1,752 10 - 15 1.74 1,664 Moderate
20 0.50 1,915 15 - 20 2.77 2,655 Mild
98 5 2.19 2,097 0 - 5 2.19 2,097 Mild
10 1.24 2,375 5 - 10 2.86 2,737 Mild
15 0.81 2,327 10 - 15 2.34 2,237 Mild
20 0.56 2,145 15 - 20 1.81 1,737 Moderate
99 5 2.73 2,614 0 - 5 2.73 2,614 Mild
10 1.67 3,198 5 - 10 4.30 4,118 Mild
15 1.07 3,074 10 - 15 2.98 2,852 Mild
20 0.85 3,256 15 - 20 4.13 3,959 Mild
101 5 1.67 1,599 0 - 5 1.67 1,599 Moderate
10 0.84 1,609 5 - 10 1.69 1,618 Moderate
15 0.59 1,695 10 - 15 1.98 1,898 Moderate
20 0.53 2,030 15 - 20 5.21 4,990 Mild
103 5 1.50 1,436 0 - 5 1.50 1,436 Moderate
10 0.63 1,207 5 - 10 1.09 1,040 Moderate
15 0.45 1,293 10 - 15 1.58 1,508 Moderate
20 0.35 1,341 15 - 20 1.58 1,508 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-13
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
104 5 1.44 1,379 0 - 5 1.44 1,379 Moderate
10 0.59 1,130 5 - 10 1.00 957 High
15 0.49 1,408 10 - 15 2.89 2,768 Mild
20 0.44 1,685 15 - 20 4.31 4,129 Mild
105 5 1.67 1,599 0 - 5 1.67 1,599 Moderate
10 0.87 1,666 5 - 10 1.82 1,739 Moderate
15 0.65 1,867 10 - 15 2.57 2,461 Mild
20 0.46 1,762 15 - 20 1.57 1,507 Moderate
106 5 1.07 1,025 0 - 5 1.07 1,025 Moderate
10 0.55 1,053 5 - 10 1.13 1,084 Moderate
15 0.43 1,235 10 - 15 1.97 1,887 Moderate
20 0.35 1,341 15 - 20 1.88 1,801 Moderate
108 5 1.38 1,321 0 - 5 1.38 1,321 Moderate
10 0.65 1,245 5 - 10 1.23 1,177 Moderate
15 0.43 1,235 10 - 15 1.27 1,217 Moderate
20 0.41 1,570 15 - 20 8.81 8,441 Mild
109 5 1.86 1,781 0 - 5 1.86 1,781 Moderate
10 0.95 1,819 5 - 10 1.94 1,859 Moderate
15 0.58 1,666 10 - 15 1.49 1,426 Moderate
20 0.46 1,762 15 - 20 2.22 2,129 Mild
110 5 1.55 1,484 0 - 5 1.55 1,484 Moderate
10 0.67 1,283 5 - 10 1.18 1,130 Moderate
15 0.60 1,724 10 - 15 5.74 5,499 Mild
20 0.47 1,800 15 - 20 2.17 2,077 Mild
111 5 4.45 4,261 0 - 5 4.45 4,261 Mild
10 1.69 3,237 5 - 10 2.72 2,609 Mild
15 1.11 3,189 10 - 15 3.23 3,097 Mild
20 0.88 3,371 15 - 20 4.25 4,067 Mild
113 5 1.38 1,321 0 - 5 1.38 1,321 Moderate
10 0.68 1,302 5 - 10 1.34 1,284 Moderate
15 0.39 1,120 10 - 15 0.91 876 High
20 0.35 1,341 15 - 20 3.41 3,268 Mild
114 5 0.94 900 0 - 5 0.94 900 High
10 0.59 1,130 5 - 10 1.58 1,517 Moderate
15 0.48 1,379 10 - 15 2.57 2,465 Mild
20 0.42 1,609 15 - 20 3.36 3,217 Mild
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-14
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
115 5 6.12 5,860 0 - 5 6.12 5,860 Mild
10 1.64 3,141 5 - 10 2.24 2,145 Mild
15 0.77 2,212 10 - 15 1.45 1,390 Moderate
20 0.48 1,839 15 - 20 1.27 1,220 Moderate
116 5 2.58 2,470 0 - 5 2.58 2,470 Mild
10 0.90 1,724 5 - 10 1.38 1,323 Moderate
15 0.53 1,523 10 - 15 1.29 1,234 Moderate
20 0.41 1,570 15 - 20 1.81 1,734 Moderate
117 5 2.25 2,155 0 - 5 2.25 2,155 Mild
10 0.86 1,647 5 - 10 1.39 1,333 Moderate
15 0.47 1,350 10 - 15 1.04 992 High
20 0.33 1,264 15 - 20 1.11 1,061 Moderate
118 5 1.72 1,647 0 - 5 1.72 1,647 Moderate
10 0.86 1,647 5 - 10 1.72 1,647 Moderate
15 0.76 2,183 10 - 15 6.54 6,259 Mild
20 0.69 2,643 15 - 20 7.49 7,173 Mild
119 5 1.53 1,465 0 - 5 1.53 1,465 Moderate
10 0.66 1,264 5 - 10 1.16 1,111 Moderate
15 0.49 1,408 10 - 15 1.90 1,822 Moderate
20 0.41 1,570 15 - 20 2.51 2,405 Mild
120 5 1.64 1,570 0 - 5 1.64 1,570 Moderate
10 0.78 1,494 5 - 10 1.49 1,424 Moderate
15 0.50 1,436 10 - 15 1.39 1,334 Moderate
20 0.37 1,417 15 - 20 1.42 1,363 Moderate
121 5 3.01 2,882 0 - 5 3.01 2,882 Mild
10 1.29 2,470 5 - 10 2.26 2,162 Mild
15 0.99 2,844 10 - 15 4.26 4,076 Mild
20 0.83 3,179 15 - 20 5.14 4,918 Mild
122 5 2.67 2,557 0 - 5 2.67 2,557 Mild
10 1.29 2,470 5 - 10 2.50 2,390 Mild
15 0.54 1,551 10 - 15 0.93 889 High
20 0.41 1,570 15 - 20 1.70 1,631 Moderate
123 5 0.90 862 0 - 5 0.90 862 High
10 0.68 1,302 5 - 10 2.78 2,664 Mild
15 0.54 1,551 10 - 15 2.62 2,512 Mild
20 0.41 1,570 15 - 20 1.70 1,631 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-15
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
125 5 1.75 1,676 0 - 5 1.75 1,676 Moderate
10 0.65 1,245 5 - 10 1.03 990 High
15 0.39 1,120 10 - 15 0.98 934 High
20 0.27 1,034 15 - 20 0.88 840 High
126 5 1.71 1,637 0 - 5 1.71 1,637 Moderate
10 0.94 1,800 5 - 10 2.09 1,999 Moderate
15 0.55 1,580 10 - 15 1.33 1,269 Moderate
20 0.36 1,379 15 - 20 1.04 998 High
128 5 1.70 1,628 0 - 5 1.70 1,628 Moderate
10 0.96 1,839 5 - 10 2.21 2,112 Mild
15 0.79 2,269 10 - 15 4.46 4,272 Mild
20 0.70 2,681 15 - 20 6.14 5,884 Mild
129 5 1.17 1,120 0 - 5 1.17 1,120 Moderate
10 0.60 1,149 5 - 10 1.23 1,179 Moderate
15 0.43 1,235 10 - 15 1.52 1,453 Moderate
20 0.32 1,226 15 - 20 1.25 1,198 Moderate
130 5 5.14 4,922 0 - 5 5.14 4,922 Mild
10 1.11 2,126 5 - 10 1.42 1,356 Moderate
15 0.72 2,068 10 - 15 2.05 1,962 Moderate
20 0.40 1,532 15 - 20 0.90 862 High
131 5 4.10 3,926 0 - 5 4.10 3,926 Mild
10 1.12 2,145 5 - 10 1.54 1,476 Moderate
15 0.64 1,839 10 - 15 1.49 1,430 Moderate
20 0.33 1,264 15 - 20 0.68 652 High
132 5 3.40 3,256 0 - 5 3.40 3,256 Mild
10 1.20 2,298 5 - 10 1.85 1,776 Moderate
15 0.61 1,752 10 - 15 1.24 1,188 Moderate
20 0.44 1,685 15 - 20 1.58 1,512 Moderate
134 5 3.79 3,629 0 - 5 3.79 3,629 Mild
10 0.94 1,800 5 - 10 1.25 1,197 Moderate
15 0.60 1,724 10 - 15 1.66 1,588 Moderate
20 0.32 1,226 15 - 20 0.69 657 High
135 5 8.97 8,589 0 - 5 8.97 8,589 Mild
10 1.00 1,915 5 - 10 1.13 1,078 Moderate
15 0.66 1,896 10 - 15 1.94 1,859 Moderate
20 0.36 1,379 15 - 20 0.79 758 High
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-16
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
136 5 1.56 1,494 0 - 5 1.56 1,494 Moderate
10 0.85 1,628 5 - 10 1.87 1,788 Moderate
15 0.61 1,752 10 - 15 2.16 2,069 Mild
20 0.50 1,915 15 - 20 2.77 2,655 Mild
137 5 1.63 1,561 0 - 5 1.63 1,561 Moderate
10 0.68 1,302 5 - 10 1.17 1,117 Moderate
15 0.36 1,034 10 - 15 0.77 733 High
20 0.27 1,034 15 - 20 1.08 1,034 Moderate
139 5 2.30 2,202 0 - 5 2.30 2,202 Mild
10 1.61 3,083 5 - 10 5.37 5,139 Mild
15 0.73 2,097 10 - 15 1.34 1,279 Moderate
20 0.54 2,068 15 - 20 2.07 1,987 Moderate
140 5 5.19 4,970 0 - 5 5.19 4,970 Mild
10 1.98 3,792 5 - 10 3.20 3,065 Mild
15 1.07 3,074 10 - 15 2.33 2,229 Mild
20 0.55 2,107 15 - 20 1.13 1,084 Moderate
142 5 1.24 1,187 0 - 5 1.24 1,187 Moderate
10 0.53 1,015 5 - 10 0.93 886 High
15 0.30 862 10 - 15 0.69 662 High
20 0.23 881 15 - 20 0.99 944 High
143 5 3.12 2,988 0 - 5 3.12 2,988 Mild
10 1.01 1,934 5 - 10 1.49 1,430 Moderate
15 0.79 2,269 10 - 15 3.63 3,473 Mild
20 0.66 2,528 15 - 20 4.01 3,841 Mild
144 5 5.05 4,836 0 - 5 5.05 4,836 Mild
10 1.85 3,543 5 - 10 2.92 2,796 Mild
15 1.06 3,045 10 - 15 2.48 2,377 Mild
20 0.96 3,677 15 - 20 10.18 9,744 Mild
145 5 3.13 2,997 0 - 5 3.13 2,997 Mild
10 1.72 3,294 5 - 10 3.82 3,656 Mild
15 0.80 2,298 10 - 15 1.50 1,432 Moderate
20 0.40 1,532 15 - 20 0.80 766 High
146 5 0.76 728 0 - 5 0.76 728 High
10 0.44 843 5 - 10 1.05 1,001 Moderate
15 0.31 891 10 - 15 1.05 1,005 Moderate
20 0.26 996 15 - 20 1.61 1,544 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-17
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
148 5 2.00 1,915 0 - 5 2.00 1,915 Moderate
10 0.59 1,130 5 - 10 0.84 801 High
15 0.35 1,005 10 - 15 0.86 824 High
20 0.29 1,111 15 - 20 1.69 1,620 Moderate
149 5 2.20 2,107 0 - 5 2.20 2,107 Mild
10 1.01 1,934 5 - 10 1.87 1,788 Moderate
15 0.69 1,982 10 - 15 2.18 2,085 Mild
20 0.56 2,145 15 - 20 2.97 2,846 Mild
150 5 3.57 3,418 0 - 5 3.57 3,418 Mild
10 0.67 1,283 5 - 10 0.82 790 High
15 0.45 1,293 10 - 15 1.37 1,312 Moderate
20 0.35 1,341 15 - 20 1.58 1,508 Moderate
151 5 3.18 3,045 0 - 5 3.18 3,045 Mild
10 1.25 2,394 5 - 10 2.06 1,972 Moderate
15 0.87 2,499 10 - 15 2.86 2,740 Mild
20 0.61 2,336 15 - 20 2.04 1,955 Moderate
153 5 5.16 4,941 0 - 5 5.16 4,941 Mild
10 0.99 1,896 5 - 10 1.23 1,173 Moderate
15 0.47 1,350 10 - 15 0.89 857 High
20 0.35 1,341 15 - 20 1.37 1,313 Moderate
154 5 4.40 4,213 0 - 5 4.40 4,213 Mild
10 1.27 2,432 5 - 10 1.79 1,710 Moderate
15 1.00 2,873 10 - 15 4.70 4,504 Mild
20 0.68 2,605 15 - 20 2.13 2,035 Mild
155 5 1.26 1,207 0 - 5 1.26 1,207 Moderate
10 0.84 1,609 5 - 10 2.52 2,413 Mild
15 0.74 2,126 10 - 15 6.22 5,952 Mild
20 0.45 1,724 15 - 20 1.15 1,100 Moderate
156 5 1.64 1,570 0 - 5 1.64 1,570 Moderate
10 0.60 1,149 5 - 10 0.95 906 High
15 0.38 1,092 10 - 15 1.04 992 High
20 0.32 1,226 15 - 20 2.03 1,941 Moderate
157 5 1.29 1,235 0 - 5 1.29 1,235 Moderate
10 0.66 1,264 5 - 10 1.35 1,294 Moderate
15 0.48 1,379 10 - 15 1.76 1,685 Moderate
20 0.35 1,341 15 - 20 1.29 1,237 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-18
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
159 5 1.82 1,743 0 - 5 1.82 1,743 Moderate
10 0.55 1,053 5 - 10 0.79 755 High
15 0.39 1,120 10 - 15 1.34 1,284 Moderate
20 0.27 1,034 15 - 20 0.88 840 High
161 5 2.43 2,327 0 - 5 2.43 2,327 Mild
10 0.89 1,704 5 - 10 1.40 1,345 Moderate
15 0.58 1,666 10 - 15 1.67 1,594 Moderate
20 0.36 1,379 15 - 20 0.95 909 High
163 5 1.49 1,427 0 - 5 1.49 1,427 Moderate
10 0.74 1,417 5 - 10 1.47 1,408 Moderate
15 0.54 1,551 10 - 15 2.00 1,913 Moderate
20 0.52 1,992 15 - 20 14.04 13,444 Negligible
30 0.41 2,356 20 - 30 1.94 3,712 Mild
164 5 2.57 2,461 0 - 5 2.57 2,461 Mild
10 0.89 1,704 5 - 10 1.36 1,304 Moderate
15 0.69 1,982 10 - 15 3.07 2,940 Mild
20 0.62 2,375 15 - 20 6.11 5,852 Mild
165 5 3.45 3,304 0 - 5 3.45 3,304 Mild
10 2.42 4,635 5 - 10 8.11 7,762 Mild
15 2.09 6,004 10 - 15 15.33 14,676 Negligible
20 1.83 7,009 15 - 20 14.71 14,086 Negligible
166 5 1.63 1,561 0 - 5 1.63 1,561 Moderate
10 1.22 2,336 5 - 10 4.85 4,644 Mild
15 1.13 3,246 10 - 15 15.32 14,668 Negligible
20 0.64 2,451 15 - 20 1.48 1,413 Moderate
167 5 1.07 1,025 0 - 5 1.07 1,025 Moderate
10 0.45 862 5 - 10 0.78 744 High
15 0.31 891 10 - 15 1.00 954 High
20 0.23 881 15 - 20 0.89 853 High
168 5 1.14 1,092 0 - 5 1.14 1,092 Moderate
10 0.61 1,168 5 - 10 1.31 1,256 Moderate
15 0.40 1,149 10 - 15 1.16 1,113 Moderate
20 0.29 1,111 15 - 20 1.05 1,010 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-19
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
169 5 1.23 1,178 0 - 5 1.23 1,178 Moderate
10 0.49 938 5 - 10 0.81 780 High
15 0.33 948 10 - 15 1.01 968 High
20 0.24 919 15 - 20 0.88 843 High
170 5 1.74 1,666 0 - 5 1.74 1,666 Moderate
10 0.73 1,398 5 - 10 1.26 1,204 Moderate
15 0.53 1,523 10 - 15 1.93 1,852 Moderate
20 0.42 1,609 15 - 20 2.02 1,938 Moderate
30 0.31 1,781 20 - 30 1.18 2,267 Mild
171 5 1.02 977 0 - 5 1.02 977 High
10 0.58 1,111 5 - 10 1.34 1,287 Moderate
15 0.40 1,149 10 - 15 1.29 1,234 Moderate
20 0.35 1,341 15 - 20 2.80 2,681 Mild
172 5 3.50 3,351 0 - 5 3.50 3,351 Mild
10 1.21 2,317 5 - 10 1.85 1,771 Moderate
15 0.60 1,724 10 - 15 1.19 1,140 Moderate
20 0.39 1,494 15 - 20 1.11 1,067 Moderate
173 5 1.08 1,034 0 - 5 1.08 1,034 Moderate
10 0.59 1,130 5 - 10 1.30 1,245 Moderate
15 0.49 1,408 10 - 15 2.89 2,768 Mild
20 0.40 1,532 15 - 20 2.18 2,085 Mild
174 5 1.19 1,139 0 - 5 1.19 1,139 Moderate
10 0.72 1,379 5 - 10 1.82 1,746 Moderate
15 0.62 1,781 10 - 15 4.46 4,275 Mild
20 0.42 1,609 15 - 20 1.30 1,247 Moderate
175 5 0.97 929 0 - 5 0.97 929 High
10 0.50 958 5 - 10 1.03 988 High
15 0.34 977 10 - 15 1.06 1,017 Moderate
20 0.25 958 15 - 20 0.94 904 High
177 5 1.88 1,800 0 - 5 1.88 1,800 Moderate
10 0.77 1,475 5 - 10 1.30 1,249 Moderate
15 0.45 1,293 10 - 15 1.08 1,037 Moderate
20 0.28 1,072 15 - 20 0.74 710 High
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix A
In-situ Soil Resistivity Data
| Project No. 19-0093 | A-20
Site
Number
Depth
(feet)
Resistance
to Depth
(ohm)
Resistivity
to Depth
(ohm-cm)
Layer
(feet)
Resistance
of Soil Layer
(ohm)
Resistivity
of Soil Layer
(ohm-cm)
Degree of
Corrosivity for
Layer
178 5 2.72 2,605 0 - 5 2.72 2,605 Mild
10 0.67 1,283 5 - 10 0.89 851 High
15 0.39 1,120 10 - 15 0.93 894 High
20 0.29 1,111 15 - 20 1.13 1,083 Moderate
179 5 1.34 1,283 0 - 5 1.34 1,283 Moderate
10 0.54 1,034 5 - 10 0.90 866 High
15 0.39 1,120 10 - 15 1.40 1,344 Moderate
20 0.32 1,226 15 - 20 1.78 1,707 Moderate
30 0.21 1,207 20 - 30 0.61 1,170 Moderate
180 5 1.33 1,274 0 - 5 1.33 1,274 Moderate
10 0.67 1,283 5 - 10 1.35 1,293 Moderate
15 0.44 1,264 10 - 15 1.28 1,227 Moderate
20 0.41 1,570 15 - 20 6.01 5,758 Mild
181 5 2.97 2,844 0 - 5 2.97 2,844 Mild
10 0.85 1,628 5 - 10 1.19 1,140 Moderate
15 0.51 1,465 10 - 15 1.28 1,221 Moderate
20 0.29 1,111 15 - 20 0.67 644 High
183 5 2.92 2,796 0 - 5 2.92 2,796 Mild
10 1.76 3,371 5 - 10 4.43 4,242 Mild
15 0.86 2,470 10 - 15 1.68 1,610 Moderate
20 0.59 2,260 15 - 20 1.88 1,799 Moderate
184 5 1.98 1,896 0 - 5 1.98 1,896 Moderate
10 1.17 2,241 5 - 10 2.86 2,739 Mild
15 0.79 2,269 10 - 15 2.43 2,329 Mild
20 0.57 2,183 15 - 20 2.05 1,960 Moderate
185 5 2.79 2,672 0 - 5 2.79 2,672 Mild
10 1.27 2,432 5 - 10 2.33 2,232 Mild
15 0.93 2,672 10 - 15 3.47 3,326 Mild
20 0.69 2,643 15 - 20 2.67 2,560 Mild
186 5 2.82 2,700 0 - 5 2.82 2,700 Mild
10 1.26 2,413 5 - 10 2.28 2,181 Mild
15 1.12 3,217 10 - 15 10.08 9,652 Mild
20 0.61 2,336 15 - 20 1.34 1,283 Moderate
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-1
Appendix B In-situ Soil Resistivity Maps
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-2
Figure B-1. In-situ Soil Resistivity Map Overview Designating Areas of Detailed Maps by Figure Number
B-2
B-3 B-4
B-5
B-6
B-7
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-3
Figure B-2. In-situ Soil Resistivity Detailed Map
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-4
Figure B-3. In-situ Soil Resistivity Detailed Map
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-5
Figure B-4. In-situ Soil Resistivity Detailed Map
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-6
Figure B-5. In-situ Soil Resistivity Detailed Map
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-7
Figure B-6. In-situ Soil Resistivity Detailed Map
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-8
Figure B-7. In-situ Soil Resistivity Detailed Map
Harvest Water Program: Corrosion Protection for Pipelines BODR Appendix B
In-situ Soil Resistivity Maps
| Project No. 19-0093 | B-9
Figure B-8. In-situ Soil Resistivity Detailed Map