27
Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu 1 , Robert G. Hunsperger 2 , Michael J. Chajes 3 , Associate Member, ASCE, Kevin J. Folliard 4 , and Eric Kunz 5 ABSTRACT: Corrosion of steel cables and reinforcing steel in concrete structures is a major cause of structural deterioration. The current methods for corrosion detection suffer from several significant drawbacks. In this paper, a nondestructive evaluation technique is developed that is capable of determining the location and severity of corrosion of embedded or encased steel rebar and cables. This technique utilizes time domain reflectometry (TDR), which has been traditionally used to detect electrical discontinuities in transmission lines. By installing a sensor wire along side steel reinforcement, the reinforcement can be modeled as an asymmetric, twin-conductor transmission line. Physical defects of the reinforcement, such as abrupt pitting corrosion, general surface corrosion, and grouting voids, will change the electromagnetic properties of the line. They can be modeled analytically, and identified using TDR. TDR measurement results from several fabricated bridge cable sections with built-in defects are reported. Based on the initial results, the TDR corrosion detection method has proven to be more robust than the existing methods because it allows one to detect, locate and identify the extent of corrosion damage. KEYWORDS: corrosion detection, nondestructive evaluation, time domain reflectometry (TDR), transmission line INTRODUCTION The corrosion of steel cables and reinforcing steel in concrete represents one of the leading causes of durability problems affecting the civil infrastructure. Reinforced, prestressed, and post-tensioned concrete structures have all suffered significantly from corrosion damage, especially in aggressive environments. One of the most challenging aspects of this durability problem is the detection of corrosion of steel cables used in bridges. The National Cooperative Highway Research Program (NCHRP) has identified a concern regarding the structural 1 Grad. Res. Asst., Dept. of Electrical and Computer Engineering, Univ. of Delaware, Newark, DE 19716. 2 Prof., Dept. of Electrical and Computer Engineering, Univ of Delaware, Newark, DE 19716. 3 Assoc. Prof., Dept. of Civ. and Envir. Engrg., Univ of Delaware, Newark, DE 19716. 4 Asst. Prof., Dept. of Civ. Engrg., Univ of Texas, Austin, TX 78712. 5 Industry Representative, 6 Oak Road, Elkton, MD 21921.

Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Corrosion Detection of Steel Cables Using Time Domain

Reflectometry

By Wei Liu1, Robert G. Hunsperger2, Michael J. Chajes3, Associate Member, ASCE, Kevin J. Folliard4, and

Eric Kunz5

ABSTRACT: Corrosion of steel cables and reinforcing steel in concrete structures is a major cause of structural

deterioration. The current methods for corrosion detection suffer from several significant drawbacks. In this paper, a

nondestructive evaluation technique is developed that is capable of determining the location and severity of corrosion

of embedded or encased steel rebar and cables. This technique utilizes time domain reflectometry (TDR), which has

been traditionally used to detect electrical discontinuities in transmission lines. By installing a sensor wire along side

steel reinforcement, the reinforcement can be modeled as an asymmetric, twin-conductor transmission line. Physical

defects of the reinforcement, such as abrupt pitting corrosion, general surface corrosion, and grouting voids, will

change the electromagnetic properties of the line. They can be modeled analytically, and identified using TDR. TDR

measurement results from several fabricated bridge cable sections with built-in defects are reported. Based on the initial

results, the TDR corrosion detection method has proven to be more robust than the existing methods because it allows

one to detect, locate and identify the extent of corrosion damage.

KEYWORDS: corrosion detection, nondestructive evaluation, time domain reflectometry (TDR), transmission line

INTRODUCTION

The corrosion of steel cables and reinforcing steel in concrete represents one of the leading causes of

durability problems affecting the civil infrastructure. Reinforced, prestressed, and post-tensioned concrete structures

have all suffered significantly from corrosion damage, especially in aggressive environments. One of the most

challenging aspects of this durability problem is the detection of corrosion of steel cables used in bridges. The

National Cooperative Highway Research Program (NCHRP) has identified a concern regarding the structural

1 Grad. Res. Asst., Dept. of Electrical and Computer Engineering, Univ. of Delaware, Newark, DE 19716. 2 Prof., Dept. of Electrical and Computer Engineering, Univ of Delaware, Newark, DE 19716. 3 Assoc. Prof., Dept. of Civ. and Envir. Engrg., Univ of Delaware, Newark, DE 19716. 4 Asst. Prof., Dept. of Civ. Engrg., Univ of Texas, Austin, TX 78712. 5 Industry Representative, 6 Oak Road, Elkton, MD 21921.

Page 2: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

integrity of steel components used in cable-stayed bridges (NCHRP 1986). While visual inspection is an effective

method for detecting corrosion in some types of structures, it cannot be used for embedded or encased steel cables,

such as those used in cable-stayed bridges. A nondestructive method to determine the location and extent of

corrosion-induced damage is needed.

Several indirect electromagnetic nondestructive corrosion detection methods have been developed.

Electromagnetic methods are based on the fact that the high-strength steel cables are very good electrical

conductors. Mechanical damage to the cable will change its electrical properties. One can use resistance

measurement, potential measurement (utilizing electrochemical reaction due to active corrosion) (Wietek and Kunz

1995), or magnetic inductance scanning to detect corrosion (Zahn and Bitterli 1995). To date, these methods have

had varying degrees of success in detecting the presence of corrosion, but all have disadvantages, and many are

uneconomical. One common drawback to these methods is that the location and nature of the corrosion is very

difficult to determine.

In this paper, a nondestructive evaluation technique for detecting damage in steel rebar and cables using

time domain reflectometry (TDR) is described. The method being developed has the advantage over existing

methods in that it can detect, locate, and identify the extent of corrosion.

TDR is a well-established technique in the field of electrical engineering that has been used for many years

to detect faults in transmission lines (Hewlett-Packard 1988). It involves sending an electrical pulse along the

transmission line and using an oscilloscope to observe the echoes. Any discontinuity will cause a reflection. From

the transit time, magnitude, and polarity of the reflection, it is possible to determine the spatial location and nature of

the discontinuity. TDR has also been used in some other fields such as geotechnical engineering and mining. Typical

applications of TDR include soil moisture measurements (Topp et al. 1994), water level changes (Hokett et al.

1994), and rock mass deformation (Dowding et al. 1989).

There are obvious similarities between bridge cables and transmission lines. The bridge cable can be

modeled as an asymmetric, twin-conductor transmission line by applying a sensor wire along with the cable (Bhatia

Page 3: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

et al. 1998). Physical defects of the bridge cable, such as abrupt pitting corrosion, general surface corrosion, and

voids in the grout, will change the electromagnetic properties of the line. These defects, which can be modeled as

different kinds of discontinuities, can be detected by TDR.

ANALYTICAL MODELS

Modeling Bridge Cables

Time domain reflectometry is traditionally used in the field of electrical engineering to detect

discontinuities in a transmission line. A transmission line is a wave guiding system along which electromagnetic

waves can travel. It typically has at least two parallel conductors. Examples are telephone lines and television

cables. The key difference between transmission lines and conventional circuits is the size. A transmission line can

be miles long. Therefore, it is long compared to the signal wavelength. As a result, signals cannot travel

instantaneously from one end to the other, as there will be a propagation delay. For a thorough analysis of the wave

propagation in a transmission line, one needs to solve Maxwell's equations with boundary conditions imposed by the

physical nature of the system under investigation. It is also possible to represent a line by the distributed parameter

equivalent circuit and discuss wave propagation in terms of voltage and current.

A bridge cable is a good conductor embedded in a dielectric (grout). By applying a sensor wire along side

the steel cable, the twin-conductor transmission line geometry is obtained (see Figure 1). However, there are still

some important differences between this system and the classic transmission line. First, the two conductors have

different diameters. Next, they are embedded in concrete and encased in a tube; this imposes a complicated

boundary condition. However, if the dimension of the concrete grout is much larger than the dimension of the steel

cable and the sensor wire, one can assume these two conductors are in a uniform concrete medium, i.e., the

influence of the tube is neglected. This simplification will not appreciably affect the analysis since the

electromagnetic field is concentrated between the two conductors and does not significantly extend through the

grout to the tube.

Page 4: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

A distributed parameter model is used to study the wave propagation in this transmission line. The

distributed parameter equivalent circuit is shown in Figure 2. It possesses a uniformly distributed series resistance R,

series inductance L, shunt capacitance C, and shunt conductance G. (R, L, C, and G are defined per unit length.) By

studying this equivalent circuit, several characteristics of the transmission line can be determined.

The transmission line equations can be obtained by applying Kirchhoff's voltage and current laws to the

distributed equivalent circuit. They are given by

in which v and i are the instantaneous values of the line voltage and current at an arbitrary point z. They are

functions of time t and position z. For the sinusoidal steady-state condition, v and i are given by Vejωt and Iejωt

respectively, where V and I are the amplitudes of the voltage and current at the point z. The radian frequency, ω, is

given by ω=2πf, where, f is frequency in Hz. Making these substitutions, and eliminating I, the following differential

equation results

where

and γ is the propagation constant that defines the phase shift β and attenuation α per unit length. The velocity at

which the voltage travels down the line can be defined in terms of β:

β

ω=pv

( )( ) VVCjGLjRzV 22

2

γωω =++=∂∂

( )( )CjGLjRj ωωβαγ ++=+=

∂∂+−=

∂∂

∂∂+−=

∂∂

tvCGv

zi

tiLRi

zv

(1)

(2)

(3)

(4)

(5)

Page 5: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

V and I are related by

where Z0 is the characteristic impedance of the line. It is given by

Distributed Parameters

To study the electrical properties of the cable, it is desirable to obtain the distributed parameters associated

with the cable. The capacitance per unit length is calculated by considering the electric field of two parallel infinitely

long straight line charges of equal and opposite uniform charge densities. The equipotential surfaces are cylinders

with axes parallel to the line charges. If a perfectly conducting cylinder is placed in any equipotential surface, the

electric field will not be disturbed. By placing the two conductors in two equipotential surfaces, and calculating the

potential difference, the capacitance per unit length of the line is obtained to be (Liu 1998)

Since L and C are related by LC=µε (the product of permeability and permittivity), one can get inductance

per unit length from the expression

The resistance per unit length R has two parts, Ra and Rb, which are the resistance of the bridge cable and

sensor wire respectively. To calculate the resistance at high frequency, skin effects must be taken into account.

When the operating frequency is f, the resistance of the transmission line is

−−

=−

abbad

C

2cosh

2222

1

πε

−−= −

abbadL

2cosh

2

2221

πµ

0ZVI =

CjGLjR

Zωω

++

=0

(6)

(7)

(8)

(9)

Page 6: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

+=+=

baba

baf

RRRσσπ

µ 114

where, σ is the conductivity of the conductor.

Characteristic Impedance

At very high frequencies R increases as the square root of f, whereas ωL increases directly as f, and the ratio

R/ωL decreases as the square root of f. It will be useful to consider the case of a single 7-wire prestressing strand

(a=0.635cm), the sensor wire being used (b=0.05cm), and a typical distance between them (d=3.175cm). At

f=50MHz, the ratio R/ωL is 1.08×10-2, which is negligible compared with unity; it will clearly become still more

negligible at higher frequencies. This result, which is based on reasonably realistic data, shows that R+ jωL ≈ jωL in

the frequency range of TDR operation. For grout with low water content, the conductance is quite small.

Additionally, there is an isolating layer of plastic insulation around the sensor wire. Therefore, the conductance G

can be considered to be zero, and G/ωC will therefore be approximately zero. Under these circumstances the

characteristic impedance is given to a high degree of accuracy by the simplified expression

Upon substituting for C and L the following expression for Z0 results

The characteristic impedance of the line is a function of a, b, and d. Note that b is much smaller than a and

d (see Figure 1), and it remains the same value along the line. However, the radius of the steel cable, a, may be

changed if corrosion occurs. A plot of characteristic impedance Z0 versus the radius of the bridge cable a is shown in

Figure 3.

When b<<d,

CL

CjGLjR

Z ≈++

=ωω

0

−−= −

abbadZ

2cosh

21 222

10 ε

µπ

(10)

(11)

(12)

Page 7: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

This expression has a negative value, which means that the characteristic impedance will increase for a

small decrease of a as shown in Figure 3. Since radius a always decreases at a corrosion site, corrosion will cause

higher characteristic impedance. This change of impedance can be detected by time domain reflectometry.

It is also noticed that dZ0/da depends on the value of d2-a2. When the sensor wire is close to the steel cable,

d2-a2 is small, and dZ0/da is large. In this case, the characteristic impedance will have a greater change for the same

decrease of a, and hence the TDR method will be more sensitive.

Time Domain Reflectometry

Time domain reflectometry can be used to detect discontinuities in a transmission line. It involves sending

an electrical pulse along a transmission line and using an oscilloscope to observe the echoes returning back from the

system being tested.

A time domain reflectometer is usually configured as shown in Figure 4. The pulse generator generates a

fast rising step wave or pulse. This wave is launched into the transmission line. A high impedance oscilloscope is

connected to monitor the wave.

The wave travels down the transmission line at vp, the velocity of propagation. At every point that the

excitation signal crosses, the transmission line equations must be obeyed. For a line terminated by a load Zl, if Zl is

different from Z0, the transmission line equations are not satisfied unless a second wave is considered to originate at

the load and propagate back up the line, i.e., a reflection is generated at this point. The ratio of reflected voltage to

the incident voltage is defined as voltage reflection coefficient, Γ , and is related to Zl and Z0 by the equation

22

220 1

21

adad

adadZ

−+−≈

εµ

π

0

0

ZZZZ

VV

l

l

i

r

+−

==Γ

(13)

(14)

Page 8: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

The reflected wave is superimposed on the incident wave. However, they are separated in time. This time,

T, is the transit time from the monitoring point to the mismatch and back again. Therefore, the distance from the

monitoring point to the mismatch is calculated to be D=vpT/2.

Modeling different types of corrosion

In order to utilize TDR to detect corrosion, the damage sites of a bridge cable need to be modeled as

electrical discontinuities in a transmission line. Several physical defects are of great interest when considering the

durability of bridge cables. Among them are abrupt pitting corrosion, general surface corrosion, and voids in the

grout.

• Pitting corrosion

Pitting corrosion is a serious defect characterized by severe localized damage. It greatly reduces the cross-sectional

area of the steel cable, and the localized impedance should increase abruptly if pitting corrosion occurs. Note that

pitting corrosion is not uniform and hence, the shape will not be circular. An equivalent radius needs to be used to

calculate the localized impedance. When the length of pitting corrosion is small compared to the wavelength of the

excitation signal, it can be modeled as a lump inductor in series with the line. From the discussion of TDR in the

previous section, a positive reflection from the site of pitting corrosion is expected. The reflection amplitude gives

indications of the severity of the damage. The location of the corrosion site is obtained from the transit time.

• Surface corrosion

Surface corrosion tends to reduce the radius of the cable on the order of a few percent over a part of length of the

line. Its length is longer than the wavelength of the excitation signal. Therefore, it is modeled as a section of

transmission line with slightly increased characteristic imp edance. A small positive reflection in the TDR waveform

indicates the beginning of a surface corrosion site, while a negative step denotes the end. The extent and length of

the corrosion can be determined from the magnitude and duration of the reflection, respectively.

Page 9: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

• Voids in grout

Although a void in the grout will not change the strength of the reinforcing cable, it leaves a section of the cable

vulnerable to corrosion. The characteristic impedance also depends on ε, which is the dielectric constant of the

system. A void in the grout will change this dielectric constant since the contents of the void, usually air and some

water, have different electrical properties. Voids tend to reduce the dielectric constant and therefore increase the

characteristic impedance. Also, voids will also change the velocity of propagation in the transmission line.

EXPERIMENTAL APPROACH AND RESULTS

A thorough theoretical analysis of the problem has been presented. The model involves representing the

bridge cable as an asymmetric, twin-conductor transmission line by applying a sensor wire along with the cable. The

distributed parameters of the transmission line can be calculated from the geometry and material parameters of the

cable. Physical defects of the bridge cable change the electromagnetic properties of the line and are modeled as

different kinds of discontinuities, which can theoretically be detected by TDR. The following focuses on an

experimental study at verifying the use of TDR.

Sample Fabrication

For the present study, several 1-meter and 3-meter steel strand and rebar specimens with built-in defects

were used to study the ability of TDR to detect pitting corrosion. The pitting corrosion was simulated by locally

grooving the rebar specimens or severing several wires of a strand specimen. Preliminary testing was performed on

both grouted and ungrouted specimens. The steel specimen was placed in the center of a PVC pipe with the plastic –

insulated monitoring wire wound around it. To increase the applicability of the laboratory testing, a typical grout

used in cable-stayed bridges was used. The TDR measurements were also made on bare specimens. Without the

grout, the dielectric constant changed, thus changing the velocity of propagation. On the other hand, the relative

magnitude of the impedance difference did not change. As a result, it was found that damage detection for the

ungrouted specimens was very similar to that of grouted specimens. Because the researchers have access to the

corrosion site when measuring specimens that are not embedded in concrete, such specimens are more convenient to

Page 10: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

use to study the electromagnetic properties of the simulated corrosion. As a result, only bare specimens were used to

investigate several aspects related to TDR damage detection.

The specific specimens used are listed in Table 1.

Instrumentation

TDR measurements can be made either using an oscilloscope/pulse generator combination or using a

commercially available TDR tester. An inexpensive time domain reflectometer can be assembled using a

conventional oscilloscope and a general-purpose pulse generator. A functional block diagram for a typical time

domain reflectometer is shown in Figure 4. A Tektronix 2245A 100MHz oscilloscope and an Interstate Electronics

Corporation P25 pulse generator were used in some of the early experiments. The pulse generator can generate

pulses as narrow as 10ns. However, the electrical length of the 1-meter samples is around 10ns. A narrower pulse is

desirable to avoid the overlap of the transmitted and reflected pulses. Additionally, the peak distortion of the pulse

generator is also a limiting factor. If the reflections from corrosion sites have a magnitude of the same order as the

peak distortions, it may be difficult to identify them.

Major oscilloscope companies, such as Hewlett-Packard and Tektronix, have all built dedicated TDR

instruments or oscilloscopes that include TDR capabilities. TDR results discussed in this paper were obtained using

the Hewlett-Packard 54750A digitizing oscilloscope with Hewlett-Packard 54753A single ended TDR plug-in. This

system has a built-in step generator that generates a 40ps rise time, 200mV step pulse. The rise time, Tr, is the time

required for the voltage to rise from 10 percent to 90 percent of the final value. Theoretical analysis shows that Tr is

an important factor in determining whether or not a small mismatch can be detected.

Experimental Results

The steel cable specimens were connected to the time domain reflectometer through standard 50Ω coaxial

cables. The far end of the steel cable sample was connected to a terminating resistive load. A pulse was then sent

Page 11: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

down the sample and the reflections were viewed on the oscilloscope. The terminating load was changed from an

open to a short to determine where the end of the sample was. The propagation velocity was then calculated.

Figure 5 shows the TDR reflection from a 3-meter steel rebar sample (specimen 1). This sample has one

simulated 50% pitting corrosion site 1.55m from the front end. The pitting corrosion was simulated by circularly

grooving the rebar and removing 50% of its cross-sectional area. The TDR measurement was made on the bare

specimen (without grout). The first step in the waveform corresponds to the generation of the step wave (A). The

wave is launched into a coaxial cable, which is used to connect the sample to the measuring system. The

characteristic impedance of this coaxial cable is 50Ω . However, the sample has higher impedance. As a result, there

is a positive reflection at the beginning of the sample (B). At the end of the sample, the wave goes up because the

line is terminated by an open circuit (D). Right in the middle of the sample there is a simulated corrosion site. A

positive reflection from that site is observed at location (C). The time interval between points B and D is 23.0ns,

which gives a propagation velocity of 2.61×108 m/s, i.e. about 87% of speed of light. The location of the damage

site is accurately determined as 1.58m from point B since TC - TB =12.1ns. The accuracy of the distance

measurement can be further improved with better coaxial cable-to-specimen connections.

TDR can not only locate the corrosion, but also reveal the severity of corrosion. Figure 6 shows TDR

returns from two seven-wire strand steel cable samples (specimen 3 and 4). The steel cables are 0.95m long and

1.27cm in diameter. Corrosion was simulated by cutting several strands. The damage was produced over a 7.5cm

length, 44cm from the end of the sample. The first marker indicates the initial reflection from the front of the

sample, and the third marker indicates the reflection from the end of sample 9.94ns later. The propagation velocity is

1.91×108 m/s. The second marker indicates the reflection from the simulated corrosion site. Note that accurate

location is identified. Experimental results indicate that the magnitude of the reflection depends on the severity of

the damage. The sample on the right has severe damage in which six strands are severed, while the other sample has

two severed strands.

Another advantage of TDR is its ability to deal with multiple discontinuities. Figure 7 shows the TDR

reflection from a 3-meter steel rebar sample (specimen 2). The sample has a simulated 70% pitting corrosion site

Page 12: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

one meter from the end of the sample and a simulated 40% pitting corrosion site a meter further down. The

simulated pitting corrosion is a circular groove 1.2cm in length. The two markers in Figure 7 indicate the pulse

reflections from the damage sites. Both of them are detected through a single measurement. The reflections are small

because the damage extends over only a short length. Even though the reflections are relatively small, if compared

to the signal from an undamaged specimen, it is clearly identifiable.

Characteristic impedance also depends on the cable-to-wire distance. The closer the two conductors, the

more sensitive the measurement will be. This effect is shown in Figure 8. In the figure, the distance d is the distance

between the sensor wire and the strand (see Figure 1). The reflection is stronger when the sensor wire is close to the

severed strand. This result is consistent with the theoretical analysis.

Laboratory experiments also indicate that the TDR measuring system must have a small system rise time to

produce acceptable results. TDR measurements were made on the 1-meter seven-wire strand cable sample with two

strands severed at the middle with rise times varying from 500ps to 3ns. When Tr is greater than 2ns, the 7.5cm long

breakage of two strands at the center point is not detectable as shown in Figure 9.

In field applications for more complex structures like an actual bridge, noise, energy loss, and wave

dispersion can be problematic for TDR measurements. Testing of the prestressed girders in the field has indicated

that energy loss and wave dispersion are not significant.

Whether in the lab, or in the field, small amounts of random noise will be present. To deal with this, one

can repeat measurements and average the results to effectively mask the noise. In fact, the TDR results shown in

Figure 5 through Figure 9 are the average results of 16 measurements. Another kind of noise in the signal can be

created by

• electric field disturbance caused by steel components near the cable being tested,

• variations in d, the distance between the steel cable and the sensing wire, since the characteristic impedance

depends on d.

Page 13: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

The noise magnitude can be relatively large. However, once the concrete element is instrumented, the location of the

steel components causing noise, and the distance d between the steel cable and sensing wire will remain unchanged.

Therefore, the noise will be repeatable. Differential TDR measurement can be used to effectively distinguish

corrosion sites from repeatable noise. If several TDR measurements are made for the same cable over a long time

period, the later TDR results should be identical to the former ones except for the corrosion sites. A differential

comparison of stored signals with newly measured ones can reveal corrosion that occurred between the two

measurements. The differential TDR method has been tested experimentally. Figure 10 shows TDR results obtained

from a 1-meter seven-wire strand sample (specimen 5). This sample has two severed strands over a 4.0cm length,

48cm from the front end of the sample. From waveform 1, it is hard to tell whether or not the sample is damaged and

where the damage is. However, if this waveform is differentially compared with waveform 2, which is the TDR

return obtained from the same sample when it did not have any electrical discontinuities, the damage site can be

easily identified. Currently this differential TDR method is being used to monitor prestressed concrete bridge girders

for Bridge 8F in Fredrica, Delaware (Liu et al. 2001).

Using External Sensor Wire to Detect Corrosion

The discussion to this point has been limited to a sensor wire in grout. In this case the sensor wire is very

close to the steel cable and d2-a2 is very small. The characteristic impedance is very sensitive to the change of the

radius a according to equation 13. Although the internal sensor wire makes the TDR measurement more sensitive, it

is not practical for existing structures.

For detecting corrosion in existing structures, a sensor wire can be placed outside the concrete grout as long

as the wire is parallel to the steel cable and the distance d is not too large. This method is very easy to use, however,

the biggest disadvantage of the external sensor wire is that the TDR measurement is less sensitive, as mentioned

above.

For corrosion that reduces the radius of a single strand (0.635cm) by 22.5 percent to 0.492cm, the

characteristic impedance will change from 51.9Ω to 68.0Ω if an internal sensor wire is applied. However, for an

Page 14: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

external sensor wire, the change of impedance is only 134.4Ω - 128.8Ω=5.6Ω . Surface corrosion and small pitting

corrosion may not be detectable under this circumstance. However, there is no big difference between internal and

external sensor wires if a (radius of the steel cable) is small. It means that the external sensor wire can be used to

detect serious corrosion as well as the internal wire. This fact is of great significance because it allows the evaluation

of existing structures.

CONCLUSIONS

A novel nondestructive evaluation technique for detecting damage in steel cables and reinforcing steel in

concrete structures using time domain reflectometry (TDR) has been developed and demonstrated. Both analytical

models and laboratory tests have been used to demonstrate the effectiveness of TDR in locating and characterizing

simulated corrosion sites. Based on the work, the following results have been shown:

1. The system (steel strand/rebar and sensor wire) can be modeled as a transmission line and evaluated

analytically. Experimental results showed that the analytical model gave an accurate prediction of the

characteristic impedance of the sample.

2. TDR can detect the location of damage sites on a steel strand or reinforcing bar and provide indications as to the

severity of the damaged region.

3. TDR measurements can be used for both new and existing structures. External sensing wires applied outside of

the protective sheathing can be used for already existing structures, but with reduced measurement sensitivity.

The TDR nondestructive evaluation technique need not be limited to the application of bridge cables or

reinforcing steel. It can also be applied to other structures that utilize steel to detect and locate hidden corrosion

damage or other defects such as fatigue cracks.

ACKNOWLEDGMENTS

This work was supported in part by the National Science Foundation under grant CMS-9700164 and the

Delaware Transportation Institute under grant No.929.

Page 15: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

APPENDIX. REFERENCES

Bhatia, S. K., Hunsperger, R. G., and Chajes, M. J. (1998). “Modeling Electromagnetic Properties of Bridge Cables

for Non-destructive Evaluation.” Proc. of Int. Conference on Corrosion and Rehabilitation of Reinforced

Concrete Structures, Orlando, Florida.

Dowding, C. H., Su, M. B., and O’Connor, K. M. (1989). “Measurement of Rock Mass Deformation with Grouted

Coaxial Antenna Cables.” Rock Mechanics and Rock Engineering, v.22, No. 1, pp.1-23.

“Time Domain Reflectometry Theory" (1998). Hewlett-Packard Application Note 1304-2, Hewlett-Packard

Company, Palo Alto, Calif.

Hokett, S.L., Russell, C.E., and Gillespie, D.R. (1994). “Water Level Detection During Drilling Using Time Domain

Reflectometry”, Proc. of Symposium and Workshop on Time Domain Reflectometry in Environmental,

Infrastructure, and Mining Applications, Evanston, Illinois.

Liu, W. (1998). "Nondestructive Evaluation of Bridge Cables Using Time Domain Reflectometry." Master’s thesis,

University of Delaware.

Liu, W., Hunsperger, R. G., Chajes, M. J., Li, D., and Kunz, E. (2001). “Nondestructive Corrosion Monitoring of

Prestressed HPC Bridge Beams Using Time Domain Reflectometry”, Proc. of TRB 80th Annual Meeting,

Washington, DC.

“Nondestructive Methods for Field Inspection of Embedded or Encased High Strength Steel Rods and Cables.”

(1986). Final Report, NCHRP Project 10-30, Manchester, England.

Topp, G.C., Zegelin, S.J., White, I. (1994). “Monitoring Soil Water Content Using TDR: an Overview of Progress”

Proc. Of Symposium and Workshop on Time Domain Reflectometry in Environmental, Infrastructure, and

Mining Applications, Evanston, Illinois.

Wietek, B. and Kunz, E. (1995). “Permanent Corrosion Monitoring for Reinforced and Prestressed Concrete

Structures." Proc. of IABSE Symposium, San Francisco, Calif.

Zahn, F. A. and Bitterli, B. (1995). "Developments in Non-Destructive Stay Cable Inspection Methods", Proc. of

IABSE Symposium, San Francisco, Calif.

Page 16: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Table 1 Specimens used in the experiment.

Specimen Type Length Damages Sites

1 rebar 3-m 50% at 1.55m

2 rebar 3-m 70% at 1.0m, 40% at 2.0m

3 strand 0.95-m 2 severed wires 7.5 cm wide at 0.44m

4 strand 0.95-m 6 severed wires 7.5 cm wide at 0.44m

5 strand 0.95-m 2 severed wires 4.0 cm wide at 0.48m

Page 17: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 1. Twin-conductor transmission line geometry of a bridge cable with sensor wire,

where a is the radius of the steel cable, b is the radius of the sensor wire, and d is the center-to-

center distance between the cable and wire.

Steelcable

Sensor wire

Grout

Tube

a

b d

Page 18: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Z Z+ ∆ Z

R ∆ Z L ∆ Z

G ∆ Z C ∆Z

Z+ 2∆ Z

R ∆ Z L ∆ Z

G ∆ Z C ∆Z

Figure 2. Distributed parameter equivalent circuit of a transmission line

Page 19: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 3. Characteristic impedance as a function of radius a, where d=0.80cm, b=0.03cm

Page 20: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 4. Functional block diagram for a typical time domain reflectometer

Pulse Generator

Oscilloscope

Transmission LineZl

Load

Page 21: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 5. TDR return of a 3-meter rebar sample (specimen 1). The sample has 50% pitting corrosion in the middle.

AB C

D

Page 22: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 6. TDR returns from 95cm seven-wire strand cable samples (specimen 3 and 4).

Six Severed Strands Two Severed Strands

Page 23: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 7. TDR returns from 3-meter reinforcing steel sample (specimen 2).

Page 24: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 8. TDR returns from 1-meter seven-wire strand cable sample, where d1<d2<d3.

1dd =

2dd = 3dd =

Page 25: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 9. Comparison of TDR returns with different rise time Tr. The sample is 0.95m long and has two

severed strands at 0.44m.

Tr=500ps Tr=1.0ns

Tr=2.0ns Tr=3.0ns

Page 26: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

Figure 10. TDR results obtained from a 95cm seven-wire strand sample before (waveform 2) and after (waveform 1)

a simulated damage is made to the sample. The differential comparison in the bottom reveals the damage site.

Page 27: Corrosion Detection of Steel Cables Using Time Domain ...hunsperg/corrosion/ASCE2002.pdf · Corrosion Detection of Steel Cables Using Time Domain Reflectometry By Wei Liu1, Robert

LIST OF FIGURES

Figure 11. Twin-conductor transmission line geometry of a bridge cable with sensor wire, where a is the radius of

the steel cable, b is the radius of the sensor wire, and d is the center-to-center distance between the cable and wire.

Figure 12. Distributed parameter equivalent circuit of a transmission line

Figure 13. Characteristic impedance as a function of radius a, where d=0.80cm, b=0.03cm

Figure 14. Functional block diagram for a typical time domain reflectometer

Figure 15. TDR return of a 3-meter rebar sample (specimen 1). The sample has 50% pitting corrosion in the middle.

Figure 16. TDR returns from 95cm seven-wire strand cable samples (specimen 3 and 4).

Figure 17. TDR returns from 3-meter reinforcing steel sample (specimen 2).

Figure 18. TDR returns from 1-meter seven-wire strand cable sample, where d1<d2<d3.

Figure 19. Comparison of TDR returns with different rise time Tr. The sample is 0.95m long and has two severed

strands at 0.44m.

Figure 20. TDR results obtained from a 95cm seven-wire strand sample before (waveform 2) and after (waveform 1)

a simulated damage is made to the sample. The differential comparison in the bottom reveals the damage site.