Correlating Committee Note No. 135-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:57:21 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Review use of"actuate" and "activate.” Do "actuate" and "activate" have different meanings? Review usethroughout the document?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
1 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 140-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:24:14 EST 2016
Committee Statement
CommitteeStatement:
Change “UPS” to “ESS” and “Uninterruptible power supply (UPS)” to ”Energy storage systems(ESS)” in all forms and tables in Chapter 7, 14 and Annex A.
The Correlating Committee directs the Technical Committee to review the term “Uninterruptiblepower supply (UPS)” to ”Energy storage systems (ESS).” Correlate text with CI-35.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 41-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 13:46:10 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee has assigned a Task Group to review the use of “visible” vs “visual”throughout the document. The Task Group will be responsible for the development of PublicComments for the entire document.
First Revision No. 2504-NFPA 72-2016 [Global Input]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
3 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 56-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:26:16 EST 2016
Committee Statement
CommitteeStatement:
The following paragraphs are to be reviewed and revised to comply with MOS 1.8.4:
17.4.2
17.6.2.3
17.7.3.3
17.7.3.4
17.7.4.2
17.7.4.3
17.7.5.5.2
17.7.5.6.5.1(A)
17.7.5.6.5.1(B)
17.7.5.6.5.1(C)
17.7.5.6.5.1(D)
17.7.7.4
17.8.1.2
17.8.5.4
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 1.8.4.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
4 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 59-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:35:19 EST 2016
Committee Statement
CommitteeStatement:
The following paragraphs are to be reviewed and revised to comply with MOS 1.8.4:
18.3.3.2
18.4.1.3
18.4.1.4
18.4.1.4.2
18.4.1.4.3
18.4.2.1
18.4.8.2
18.5.1.2
18.5.5.2
18.5.5.4.7
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 1.8.4.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 62-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:40:59 EST 2016
Committee Statement
CommitteeStatement:
The following paragraphs are to be reviewed and revised to comply with MOS 1.8.4:
23.10.2
23.8.3.3
23.8.5.11.1
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 1.8.4
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 64-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:43:29 EST 2016
Committee Statement
CommitteeStatement:
The following paragraphs are to be reviewed and revised to comply with MOS 1.8.4:
24.8.7
24.8.8
24.9.1.1
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 1.8.4.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 65-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:44:44 EST 2016
Committee Statement
CommitteeStatement:
The following paragraphs are to be reviewed and revised to comply with MOS 1.8.4:
26.3.5.2.6
26.4.1
26.4.5.1
26.5.1.5
26.5.2
26.5.3.2
26.6.1.1
26.6.3.3
26.6.4.1.2
26.6.4.1.4
26.6.4.2.1(A)
26.6.4.2.2(A)
26.6.5.1.3(B)
26.6.5.1.6(A)
26.6.5.1.6(B)
26.6.5.2.3
26.6.5.2.6
26.6.6.1
26.6.6.2
The Correlating Committee directs the Technical Committee to review and revise this
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
8 of 134 1/25/2017 2:03 PM
paragraph to comply with MOS 1.8.4.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
9 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 66-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:45:44 EST 2016
Committee Statement
CommitteeStatement:
The following paragraphs are to be reviewed and revised to comply with MOS 1.8.4:
27.1.1
27.5.2.2.5
27.5.2.6.3
27.5.2.6.4
27.5.2.8.6
27.5.3.4.4
27.5.4.2.5
27.5.5.1.1.1
27.5.5.1.2.1
27.5.5.3.1
27.5.5.3.4
27.5.5.3.5
27.6.2.1.10
27.6.2.1.11.2
27.6.3.1.2
27.6.3.2.3.10
27.6.3.2.3.12
27.6.6.10.1
27.6.6.11.4
27.6.6.13.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10 of 134 1/25/2017 2:03 PM
27.6.6.13.3
27.7.1.2.7
27.7.1.4.3
27.7.1.4.4
27.7.1.6.3
27.7.1.6.4
27.7.1.6.4.1
27.7.3.9
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 1.8.4.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
11 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 68-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:50:40 EST 2016
Committee Statement
CommitteeStatement:
The following paragraphs are to be reviewed and revised to comply with MOS 1.8.4:
29.4.8
29.7.2.2
29.9.6.2
29.9.7.7
29.9.8.2.1
29.10.2.3
29.10.4.2
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 1.8.4.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
12 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 74-NFPA 72-2016 [ Global Input ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:22:06 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text in Paragraph 5.The NEC does not use "Section."
First Revision No. 2504-NFPA 72-2016 [Global Input]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
13 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 71-NFPA 72-2016 [ Section No. 3.3.20 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:12:14 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text. The TechnicalCommittee should consider moving the 2nd sentence to Annex A
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
14 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 145-NFPA 72-2016 [ New Section after 3.3.30 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:39:58 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the battery terms providedin 3.3.31. The Technical Committee is to only provide terms used in the document as per MOS1.6.3.3.
First Revision No. 4504-NFPA 72-2016 [New Section after 3.3.30]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
15 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 70-NFPA 72-2016 [ Section No. 3.3.207 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:11:03 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text. The TechnicalCommittee should consider moving the 2nd sentence to Annex A.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
16 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 26-NFPA 72-2016 [ Section No. 7.3.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 21:37:55 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the committee action for 7.3.3.5 is outside the scope ofthe Technical Committee and NFPA 72. The Correlating Committee directs that this text bedeleted.
The Correlating Committee directs the Technical Committee to review the terms “system designer”vs “architect/engineer” for consistency with the use of the term “system designer” as defined andused elsewhere in the code.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
17 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 124-NFPA 72-2016 [ Section No. A.29.8.1.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:34:36 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. In FIGURE7.8.2(g), 9, should 2013 edition be changed to 2019?
First Revision No. 1529-NFPA 72-2016 [Section No. A.29.8.1.4]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
18 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 38-NFPA 72-2016 [ Section No. 10.1.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 13:16:28 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to reinstate 10.1.2. It is important foreach individual chapter to determine applicability of other chapters of the document. Thisqualifying statement is to be included in each chapter for proper context.
First Revision No. 1002-NFPA 72-2016 [Section No. 10.1.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
19 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 154-NFPA 72-2016 [ Section No. 10.3.5 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:55:20 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the values of 0°C (32°F),49°C (120°F) and 30°C (86°F) and transpose values to correlate usage with remainder of Code.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
20 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 36-NFPA 72-2016 [ New Section after 10.4.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 10:32:51 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to consider the use of an exceptionor other positive language to permit other methods. The PI specified upper and lower ranges thatwere different than those in the FR and were not substantiated.
First Revision No. 1017-NFPA 72-2016 [New Section after 10.4.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
21 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 148-NFPA 72-2016 [ Section No. 10.4.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:44:15 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the change made to 10.4.5to ensure the revision did not change the intent of the requirement. Also, revise the text to complywith MOS 3.3.1.2.1.
First Revision No. 1018-NFPA 72-2016 [Section No. 10.4.4]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
22 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 51-NFPA 72-2016 [ Section No. 10.5.3.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:19:32 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text to complywith MOS 3.3.1.2.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
23 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 35-NFPA 72-2016 [ Section No. 10.6.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 10:31:34 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to add annex material to indicate theclassifications are found under NFPA 111, Classification of Stored-Energy Emergency PowerSupply Systems (SEPSS).
The Correlating Committee directs the Technical Committee to review 10.6.4 to add a requiredhead per MOS 1.8.3.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
24 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 52-NFPA 72-2016 [ Section No. 12.3.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:21:05 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text to complywith MOS 3.3.1.2.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
25 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 53-NFPA 72-2016 [ Section No. 12.3.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:22:22 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text to complywith MOS 3.3.1.2.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
26 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 21-NFPA 72-2016 [ New Section after 14.2.2.2.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 18:25:45 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to correlate in regards to theResolve of PI 345. Review/align the terminology for the use of “official correspondence” wherethere is no definition for that term.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
27 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 17-NFPA 72-2016 [ Section No. 14.2.2.2.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 18:19:41 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to correlate in regards to the Resolveof PI 345. Review/align the terminology between deficiency and impairment and clarify the use of“official correspondence” where there is no definition for that term.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
28 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 18-NFPA 72-2016 [ Section No. 14.2.2.2.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 18:21:17 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to correlate in regards to theResolve of PI 345. Review/align the terminology for the use of “official correspondence” wherethere is no definition for that term
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
29 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 134-NFPA 72-2016 [ Section No. 14.4.3.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:54:55 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text of 14.4.3.2(15)(a),14.4.3.2(15)(b), 14.4.3.2(15)(c), 14.4.3.2(15)(d) and 14.4.3.2(17)(l). Review “manufacturer'spublished instructions” vs “published manufacturer's instructions.”
Also, there are several instances of abbreviations in the table, several more use spelled-out terms.The Technical Committee should be consistent throughout.
Also, review use of footnote indicators. Some appear at the beginning of the sentence rather thanat the end. These should be consistent throughout the table.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
30 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 19-NFPA 72-2016 [ Section No. 14.4.3.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 18:23:02 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review Table 14.4.3.2 toestablish frequencies for item 9(4).
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
31 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 20-NFPA 72-2016 [ Section No. 14.4.3.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 18:24:23 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to correlate the requirements forloudspeaker systems between Item 22(2) to Item 30(6).
The Correlating Committee directs the Technical Committee to correlate in regards to the Resolveof PI 345. In A.14.43.2, review/align the terminology for the use of “official correspondence” wherethere is no definition for that term.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
32 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 136-NFPA 72-2016 [ Section No. 17.6.2.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:59:02 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Per MOS2.3.6.3, table and figure notes shall not include requirements.
First Revision No. 2001-NFPA 72-2016 [Section No. 17.6.2.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
33 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 57-NFPA 72-2016 [ Section No. 17.7.3.2.4.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:29:39 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text of17.7.3.2.4.2(4) and 17.7.3.2.4.2(5) to comply with MOS 3.3.1.2.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
34 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 149-NFPA 72-2016 [ Section No. 17.7.3.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:48:26 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Are the terms“pipe” and “piping” the same? Should only one be used?
First Revision No. 2008-NFPA 72-2016 [Section No. 17.7.3.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
35 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 39-NFPA 72-2016 [ Section No. 18.1.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 13:17:53 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to reinstate 18.1.6. It is important foreach individual chapter to determine applicability of other chapters of the document. Thisqualifying statement is to be included in each chapter for proper context.
First Revision No. 2512-NFPA 72-2016 [Section No. 18.1.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
36 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 137-NFPA 72-2016 [ Section No. 18.9.4.7 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:00:12 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text in Table 18.9.4.7.A unit of measure in the column head does not necessitate it be repeated in the table body. Also,see Minimum Character or Symbol Height.
Also, should 75 mm be changed to 70 mm to correlate with Table 14.4.3.2? (2x)
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
37 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 6-NFPA 72-2016 [ Section No. 21.2.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:56:14 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the committee action does not appear to be consistentwith the committee statement. The Correlating Committee directs that the TC clarify the action onthis FR/CI/PI.
910 mm was used instead of 0.9 m and the Technical Committee did not provide substantiationfor adding "where the control circuit is not configured as a Class D circuit" to the requirement.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
38 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 10-NFPA 72-2016 [ Section No. 21.3.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 16:19:44 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the language resulting from the proposed changes isunclear. The Correlating Committee directs that the TC clarify the proposed change.
The word “permitted” appears to be more appropriate than "as specified" in reference to 21.3.9as indicated in the negative comment.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
39 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 9-NFPA 72-2016 [ New Section after 21.3.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 16:17:17 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the committee action is outside the scope of theTechnical Committee. The Correlating Committee directs that this FR/CI/PI be reconsidered foraction within the scope of the committee.
The Technical Committee is requested to review the comments in the ballot.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
40 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 11-NFPA 72-2016 [ Section No. 21.3.13.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 16:22:51 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the committee action is outside the scope of theTechnical Committee. The Correlating Committee directs that this FR/CI/PI be reconsidered foraction within the scope of the committee.
The Technical Committee is requested to review the comments in the ballot.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
41 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 60-NFPA 72-2016 [ Section No. 21.4.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:37:40 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 1.8.4.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
42 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 4-NFPA 72-2016 [ Section No. 21.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:51:36 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the language resulting from the proposed changes isunclear. The Correlating Committee directs that the TC clarify the proposed change.
The Correlating Committee takes note of the negative comment regarding the reference to a notyet published standard and the term FCC vs. building fire command center.
The Correlating Committee directs the Technical Committee to review the italicized terms in 21.6and its Annex to make terms such as “group automatic operation” or “designated as an elevatorgroup” or “group of elevators” in normal text and not italic.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
43 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 5-NFPA 72-2016 [ New Section after 21.7 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:54:32 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to consider the comments in theballot regarding correlation with the requirements of NFPA 13.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
44 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 12-NFPA 72-2016 [ Section No. 23.2.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 16:25:02 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the committee action does not appear to be consistentwith the committee statement. The Correlating Committee directs that the TC clarify the action onthis FR/CI/PI.
The Technical Committee acknowledged the inclusion of CO but they did not indicate why theydid not delete the words "fire alarm" in 23.2.2.1.1 to make the requirement apply to all systems asthe submitter proposed in PI 222.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
45 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 144-NFPA 72-2016 [ Section No. 23.6.1.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:36:57 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text to complywith MOS 3.3.1.2.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
46 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 61-NFPA 72-2016 [ Section No. 23.16.5 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:40:08 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review and revise the terms“Receiver/Transceiver/System Control Unit,” “receiver/transceiver or system control unit” and“transceiver/system control unit” for consistency.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
47 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 63-NFPA 72-2016 [ Section No. 24.3.14.4.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:42:32 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 2.3.3.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
48 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 30-NFPA 72-2016 [ New Section after 26.2.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 10:25:38 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that this FR/CI/PI is outside the scope of the TechnicalCommittee. The Correlating Committee directs the Technical Committee to review section26.2.4.1.5 relative to communication center for inclusion within the scope of the TechnicalCommittee.
First Revision No. 4009-NFPA 72-2016 [New Section after 26.2.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
49 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 31-NFPA 72-2016 [ Section No. 26.3.5.2.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 10:26:31 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs SIG-SSS, SIG-PRO, SIG-TMS and SIG-ECS to correlate toensure consistent use of the terms MFVN and PSTM. SIG-SSS revised the definition for MFVNunder FR 4032 and added "functionally equivalent MFVN" to requirements where the PSTN wasalso referenced. Consideration of correlating with the glossary terms used in the aforementionedrequirement revisions and the test and maintenance sections for DACR, DACT etc.
First Revision No. 4014-NFPA 72-2016 [Section No. 26.3.5.2.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
50 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 32-NFPA 72-2016 [ Section No. 26.3.5.2.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 10:27:54 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs SIG-SSS, SIG-PRO, SIG-TMS and SIG-ECS to correlate toensure consistent use of the terms MFVN and PSTM. SIG-SSS revised the definition for MFVNunder FR 4032 and added "functionally equivalent MFVN" to requirements where the PSTN wasalso referenced. Consideration of correlating with the glossary terms used in the aforementionedrequirement revisions and the test and maintenance sections for DACR, DACT etc.
First Revision No. 4014-NFPA 72-2016 [Section No. 26.3.5.2.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
51 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 33-NFPA 72-2016 [ Section No. 26.6.4.1.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 10:28:59 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs SIG-SSS, SIG-PRO, SIG-TMS and SIG-ECS to correlate toensure consistent use of the terms MFVN and PSTM. SIG-SSS revised the definition for MFVNunder FR 4032 and added "functionally equivalent MFVN" to requirements where the PSTN wasalso referenced. Consideration of correlating with the glossary terms used in the aforementionedrequirement revisions and the test and maintenance sections for DACR, DACT etc.
First Revision No. 4016-NFPA 72-2016 [Section No. 26.6.4.1.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
52 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 34-NFPA 72-2016 [ Section No. 26.6.4.1.5 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 10:29:55 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs SIG-SSS, SIG-PRO, SIG-TMS and SIG-ECS to correlate toensure consistent use of the terms MFVN and PSTM. SIG-SSS revised the definition for MFVNunder FR 4032 and added "functionally equivalent MFVN" to requirements where the PSTN wasalso referenced. Consideration of correlating with the glossary terms used in the aforementionedrequirement revisions and the test and maintenance sections for DACR, DACT etc.
First Revision No. 4017-NFPA 72-2016 [Section No. 26.6.4.1.5]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
53 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 67-NFPA 72-2016 [ Section No. 29.7.1.3.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 11:49:40 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review and revise thisparagraph to comply with MOS 1.8.4.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
54 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 153-NFPA 72-2016 [ Section No. 29.6.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:54:26 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. The Title of29.8.3 was revised by the Technical Committee. The charging paragraph needs to be revised.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
55 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 69-NFPA 72-2016 [ Section No. 29.9.8.2.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:09:55 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review and revise this paragraphto comply with MOS 1.8.4. The Technical Committee should consider moving the sentencedescribing Lb to a list below the describing terms.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
56 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 29-NFPA 72-2016 [ New Section after 29.8.5 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 09:57:01 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to edit 7.1 and 29.1.3 to permitapplicability between Chapters 7 and 29 for the purpose of documentation.
First Revision No. 1526-NFPA 72-2016 [New Section after 29.8.5]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
57 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 80-NFPA 72-2016 [ Section No. A.3.3.56 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:32:33 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review reference in NFPA1221 to A.3.3.17 at the Second Draft.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
58 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 81-NFPA 72-2016 [ Section No. A.3.3.94 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:33:49 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review reference in NFPA1221 to A.3.3.39 at the Second Draft.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
59 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 7-NFPA 72-2016 [ Section No. A.3.3.136.1.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 16:10:56 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the committee action does not appear to be consistentwith the committee statement. The Correlating Committee directs that the TC clarify the action onthis FR/CI/PI.
Figure A.3.3.136.1.1 requires revision to 0.9 m. Update the figure dimensions and documentreferences. The Correlating Committee directs the Technical Committee to review placement ofthe vertical text "w/maximum of 3ft" (add metric).
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
60 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 79-NFPA 72-2016 [ Section No. A.3.3.233 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:31:40 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review reference in NFPA1221 to A.3.3.74 at the Second Draft.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
61 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 82-NFPA 72-2016 [ Section No. A.7.3.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:35:35 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text of A.7.3.3(2) tocomply with MOS 3.3.1.2.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
62 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 83-NFPA 72-2016 [ Section No. A.7.5.3(1) ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:37:42 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text to comply withMOS 2.3.4. Item 4 has a requirement.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
63 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 156-NFPA 72-2017 [ Section No. A.7.8.2(1) ]
Submitter Information Verification
Submitter Full Name: Richard Roux
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Mon Jan 16 14:07:48 EST 2017
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review CI 5047 and itsattachments and add a complete set of completed forms to Annex A.7.8.2(1).
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
64 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 141-NFPA 72-2016 [ Section No. A.10.6.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:25:22 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the term “Uninterruptiblepower supply (UPS)” to ”Energy storage systems (ESS).” Correlate text with CI-35.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
65 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 72-NFPA 72-2016 [ Section No. A.12.2.3.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:13:18 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review ownership of the Annextext. According to the annex text, the paragraph belongs to (SIG-FUN). Review in context to12.2.3.2.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
66 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 125-NFPA 72-2016 [ Section No. A.12.3.6(1) ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:36:30 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text in FIGUREA.12.3.6(1)(c). Per MOS 2.3.6.3, table and figure notes shall not include requirements. Also, theMOS does not permit requirements in the Annex.
First Revision No. 3007-NFPA 72-2016 [Section No. A.12.3.6(1)]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
67 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 73-NFPA 72-2016 [ Section No. A.14.2.9 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:15:06 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text to complywith MOS 2.2.1.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
68 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 43-NFPA 72-2016 [ Section No. A.14.4.3.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Dec 19 15:37:01 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review Table 14.4.3.2. CI 5027text is likely the Annex text for Table 14.4.3.2 Item 9. Review title of Omic vs Ohmic.
Also, The Correlating Committee directs the Technical Committee to review reference in LSC101 to 9.3.2 and 9.3.3 at the Second Draft.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
69 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 150-NFPA 72-2016 [ Section No. A.17.17.2.2.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:50:20 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. The TechnicalCommittee is requested to confirm all metric equivalents as these were not in the original FR.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
70 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 75-NFPA 72-2016 [ Section No. A.18.5.3.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:23:53 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text. In the 2ndparagraph, change “standard” to “code.”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
71 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 76-NFPA 72-2016 [ Section No. A.18.5.5.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:26:05 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text. In the 3rdparagraph, change “standard” to “code.”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
72 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 143-NFPA 72-2016 [ Section No. A.21.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:32:03 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the values of 128 m (420ft) and transpose values to correlate usage with remainder of Code.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
73 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 146-NFPA 72-2016 [ Section No. A.21.6.2.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:41:07 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the document"Incorporating Emergency Messaging Guidance into Practice" as is referenced in this paragraph.It needs to be added as a reference in Annex I.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
74 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 77-NFPA 72-2016 [ Section No. A.21.7.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:27:39 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text. In the 1stparagraph, change “standard” to “code.”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
75 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 8-NFPA 72-2016 [ Section No. A.23.6.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 16:14:19 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee advises that the committee action does not appear to be consistentwith the committee statement. The Correlating Committee directs that the TC clarify the action onthis FR/CI/PI.
Figure A.23.6.1(a) also requires revision to 0.9 m.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
76 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 155-NFPA 72-2017 [ Section No. A.24.3.7 ]
Submitter Information Verification
Submitter Full Name: Richard Roux
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jan 11 11:40:14 EST 2017
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to spell out emerg. svcs. andsys. in Figure A.24.3.7.
FR-527-NFPA 72-2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
77 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 27-NFPA 72-2016 [ Section No. A.24.3.10 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 21:42:02 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs that this FR/CI/PI be reconsidered for correlation with theaction on FR 508. The body of the code deleted reference to UL 2017, the annex did not.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
78 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 147-NFPA 72-2016 [ Section No. A.24.5.14 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:42:30 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the value of 48 in. inFigure A.24.5.14(a) and add the corresponding metric value in parenthesis (xx m).
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
79 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 24-NFPA 72-2016 [ Section No. A.24.5.18.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 21:33:11 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review use of the term “hearing-impaired” vs. “persons who are deaf or hard of hearing” and correlate with FR 1024.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
80 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 78-NFPA 72-2016 [ Section No. A.24.5.22.1.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:28:58 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text. The TechnicalCommittee should consider changing the word "supervisory" to "supervising."
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
81 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 25-NFPA 72-2016 [ Section No. A.24.7 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 21:34:40 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to change Through classified asone-way ECS to be Although classified as one-way ECS for clarity.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
82 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 142-NFPA 72-2016 [ Section No. A.29.2.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:26:44 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review A.29.2.2 and correlatethe structure, presentation order and text with Annex H.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
83 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 152-NFPA 72-2016 [ Section No. A.29.7.8.2.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:52:49 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Should The sourcefor the equation in 29.9.8.2.1 is Stone, W. “Electromagnetic Attenuation in Construction Materials,”National Institute of Standards and Technology, NISTIR 6055, 1997. referenced in A.29.9.8.2.1 bereferenced in Annex I?
First Revision No. 1536-NFPA 72-2016 [Section No. A.29.7.8.2.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
84 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 151-NFPA 72-2016 [ Section No. A.29.10.3.4(9) ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:51:33 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Reference toGottuck and Gottuck 2015 needs to be added to Annex I (possibly Gottuk, E. and D. Gottuk, “Effectof Ceiling Fans on Smoke Alarm Performance,” SUPDET 2016 presentation, Orlando, FL., March3-6, 2015)
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
85 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 84-NFPA 72-2016 [ Chapter B [Excluding any
Sub-Sections] ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:39:17 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text to comply withMOS 1.6.2.4. Any references that are not mandatory but apply to the document are required to beincluded in the last annex in codes and standards.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
86 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 85-NFPA 72-2016 [ Section No. B.2.3.1.4.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:40:46 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. “See initial fuels” in Item 3 which should likely be “see B.2.3.1.4.1(2)” or remove theparenthetical expression.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
87 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 86-NFPA 72-2016 [ Section No. B.2.3.2.3.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:42:05 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “relationships discussed earlier” is vague and the Technical Committeeshould review to provide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
88 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 126-NFPA 72-2016 [ Section No. B.2.3.2.5 [Excluding
any Sub-Sections] ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:37:46 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Should thefigure be revised to indicate fire growth, steady state and decay?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
89 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 138-NFPA 72-2016 [ Section No. B.2.3.2.6.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 16:02:11 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text of TableB.2.3.2.6.2(c). See reference to 92B in footnote. NFPA 92B has been withdrawn. Reference hasbeen deleted from Annex H[I]. Was this table incorporated into 92? If so, the Technical Committeemay want to change the extract citation. If not, 92B needs to be added to I.1.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
90 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 87-NFPA 72-2016 [ Section No. B.2.3.2.6.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:42:55 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The Technical Committee should review “with this guide.”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
91 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 88-NFPA 72-2016 [ Section No. B.2.3.2.6.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:43:50 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The Technical Committee should review reference [8] in this paragraph and correlatewith [8] in B.2.3.2.6.3.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
92 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 89-NFPA 72-2016 [ Section No. B.2.3.2.6.7 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:44:57 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The Technical Committee should review the term “Fastlite” to determine if “FASTLite”is correct.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
93 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 90-NFPA 72-2016 [ Section No. B.2.3.3.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:48:14 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The Technical Committee should review context of the term “ease of” in the 2ndparagraph.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
94 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 91-NFPA 72-2016 [ Section No. B.2.3.4.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:49:02 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The Technical Committee should review to determine if “Critical design assumptions”should be “Critical design features.”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
95 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 92-NFPA 72-2016 [ Section No. B.3.2.1 [Excluding any
Sub-Sections] ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:51:27 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The Technical Committee should review to determine if “The following data” should be“The data listed in B.3.2.1.1 through B.3.2.1.2.”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
96 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 93-NFPA 72-2016 [ Section No. B.3.2.3.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:52:29 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The Technical Committee should review to provide the paragraph number/referencefor “this section” in 2 places.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
97 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 94-NFPA 72-2016 [ Section No. B.3.2.7 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:53:30 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “previous sections” is vague and the Technical Committee should review toprovide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
98 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 95-NFPA 72-2016 [ Section No. B.3.3.1 [Excluding any
Sub-Sections] ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:54:24 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “following method” is vague and the Technical Committee should review toprovide the specific cross reference. It is vague as to what the following method really is. Does thetext mean method in B.3.3.1.1 through B.3.3.1.2?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
99 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 96-NFPA 72-2016 [ Section No. B.3.3.3.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:55:20 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “previous equation” is vague and the Technical Committee should review toprovide the specific cross reference. Should the previous equation be Equation B.3.3.3.2?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
100 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 97-NFPA 72-2016 [ Section No. B.3.3.4.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:57:06 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “preceding correlations” is vague and the Technical Committee should reviewto provide the specific cross reference. What should the preceding correlations be revised to be?Should this refer to a paragraph or formula number?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
101 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 98-NFPA 72-2016 [ Section No. B.3.3.4.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 14:58:47 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “preceding temperature and velocity correlations” is vague and the TechnicalCommittee should review to provide the specific cross reference. What should the precedingtemperature and velocity correlations be revised to be? Should this refer to a paragraph or formulanumber?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
102 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 99-NFPA 72-2016 [ Section No. B.3.3.5.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:00:07 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “previously described” is vague and the Technical Committee should review toprovide the specific cross reference. The term “The equations” is vague and the TechnicalCommittee should review to provide the specific cross reference. Also review “precedingdiscussion.”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
103 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 100-NFPA 72-2016 [ Section No. B.3.3.8.3 [Excluding
any Sub-Sections] ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:01:18 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “following example” is vague and the Technical Committee should review toprovide the specific cross reference. Should it read “An example analysis is provided in B.3.3.8.3.1through B.3.3.8.3.5?”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
104 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 101-NFPA 72-2016 [ Section No. B.3.3.8.3.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:02:01 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “following example” is vague and the Technical Committee should review toprovide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
105 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 102-NFPA 72-2016 [ Section No. B.3.3.8.3.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:03:02 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “preceding design” is vague and the Technical Committee should review toprovide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
106 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 103-NFPA 72-2016 [ Section No. B.3.3.8.3.5 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:04:25 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “previous example” is vague and the Technical Committee should review toprovide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
107 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 104-NFPA 72-2016 [ Section No. B.3.3.8.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:05:31 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “preceding examples” is vague and the Technical Committee should reviewto provide the specific cross reference. Also review “preceding correlations.”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
108 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 105-NFPA 72-2016 [ Section No. B.3.3.9.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:06:36 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “preceding procedure” is vague and the Technical Committee should reviewto provide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
109 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 106-NFPA 72-2016 [ Section No. B.4.1.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:07:40 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “following information” is vague and the Technical Committee should reviewto provide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
110 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 107-NFPA 72-2016 [ Section No. B.4.7.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:08:44 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “following paragraphs” is vague and the Technical Committee should reviewto provide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
111 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 108-NFPA 72-2016 [ Section No. B.4.8.1.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:10:06 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “It” is vague and the Technical Committee should review to provide thespecific cross reference. What does the word it (first word) refer to? Method 1?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
112 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 109-NFPA 72-2016 [ Section No. B.4.8.2.7 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:11:03 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “preceding relation” is vague and the Technical Committee should review toprovide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
113 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 110-NFPA 72-2016 [ Section No. C.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:13:29 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. The term“protected premises Chapter 23” in the 1st paragraph should be a parenthetical reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
114 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 112-NFPA 72-2016 [ Section No. D.2.4.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:17:33 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “see the requirements for measurement point spacing” is vague and theTechnical Committee should review to provide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
115 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 113-NFPA 72-2016 [ Section No. D.2.4.8 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:18:19 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “See the requirements for measurement point spacing.” is vague and theTechnical Committee should review to provide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
116 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 111-NFPA 72-2016 [ Section No. D.2.4.10 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:14:29 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. The term “See also the discussion on the definition of an ADS” is vague and theTechnical Committee should review to provide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
117 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 114-NFPA 72-2016 [ Section No. D.2.5.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:19:55 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. The term“speech satisfactory speech intelligibility” needs to be reviewed.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
118 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 115-NFPA 72-2016 [ Section No. D.2.6.6 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:21:45 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to revise the text to complywith MOS 1.8.3.2.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
119 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 116-NFPA 72-2016 [ Section No. D.3.4 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:22:58 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Should thesubscripted variables be italic for consistency?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
120 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 117-NFPA 72-2016 [ Section No. D.3.6.2 [Excluding any
Sub-Sections] ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:26:06 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. Into paragraph should likely reference to D.3.6.2.1 through D.3.6.2.3.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
121 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 118-NFPA 72-2016 [ Section No. D.3.6.2.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:27:12 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. The term “fastgreater” needs to be reviewed.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
122 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 119-NFPA 72-2016 [ Section No. D.3.6.2.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:28:03 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. There shouldnot be a list of one item.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
123 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 120-NFPA 72-2016 [ Section No. D.4.2.2 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:29:05 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. The term “these”needs to be reviewed. These should likely be D.4.2.2 through D.4.2.8.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
124 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 121-NFPA 72-2016 [ Section No. D.4.2.9 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:29:49 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. ShouldD.4.2.9 be relocated before D.4.2.2?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
125 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 122-NFPA 72-2016 [ Section No. E.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:31:09 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text of Paragraph2. Should 2016 be changed to 2019?
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
126 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 123-NFPA 72-2016 [ Section No. F.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:32:21 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text of Paragraph 1.F1 requires a head. General?
Also, in Paragraph 6, the term “following initiating device circuits” is vague and the TechnicalCommittee should review to provide the specific cross reference.
First Revision No. 3071-NFPA 72-2016 [Section No. F.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
127 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 127-NFPA 72-2016 [ Section No. F.2.3 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:39:07 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Clarify“End-of-line device last device” in Figure 2.3.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
128 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 128-NFPA 72-2016 [ Section No. G.2.2.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:40:33 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text to eliminatevagueness. In Item (10)(f), is there a word missing after ambient? Level? Noise? Also, reviewItem (5), there should not be a list of one item.
First Revision No. 3065-NFPA 72-2016 [Section No. G.2.2.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
129 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 129-NFPA 72-2016 [ Section No. G.3.1.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:45:35 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Needintroductory text for list items. Consider “Message templates for scenario 1 include thefollowing:”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
130 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 130-NFPA 72-2016 [ Section No. G.3.2.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:49:05 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Needintroductory text for list items. Consider “Message templates for scenario 2 include thefollowing:”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
131 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 131-NFPA 72-2016 [ Section No. G.3.3.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:49:52 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Needintroductory text for list items. Consider “Message templates for scenario 3 include thefollowing:”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
132 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 132-NFPA 72-2016 [ Section No. G.3.4.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:51:26 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. G.3.4.1 requires ahead. Also, need introductory text for list items. Consider “Message templates for scenario 4include the following:” Also, the term “listed above” in the note is vague and the TechnicalCommittee should review to provide the specific cross reference.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
133 of 134 1/25/2017 2:03 PM
Correlating Committee Note No. 133-NFPA 72-2016 [ Section No. G.3.5.1 ]
Submitter Information Verification
Submitter Full Name: Dick
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Dec 23 15:52:29 EST 2016
Committee Statement
CommitteeStatement:
The Correlating Committee directs the Technical Committee to review the text. Needintroductory text for list items. Consider “Message templates for scenario 5 include thefollowing:”
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
134 of 134 1/25/2017 2:03 PM