11
1 2551175B Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk Corolla Pack Boilers 503 / 504 & 1000 Series The Corolla Pack Range The Corolla Pack series of condensing, pre-mix, modulating boilers contain multiple heat exchanger modules within a single casing. The range provides boiler outputs from 150kW to 500kW and up to 4000kW in cascade. To simplify installation and maintenance each boiler comes complete with an integrated hydraulic connection kit. The 503/504 Series includes an integrated flue header kit and optional low loss header kit. The 1000 Series includes an integrated low loss header kit and polypropelene flue discharge as standard, with the flue header kit fitted outside of the casing. Featuring efficiency figures as high as 109% nett at (30%) part load, the Corolla Pack has excellent environmental benefits, and far exceeds current requirements for Part L Building Regulations. With sophisticated controls, based on the master and slave principle, the Corolla Pack can manage multiple heating zones and up to 60 boiler modules in cascade. Pre-mix burner The Corolla Pre-mix combustion system comprises of a modulating gas valve integrated with a high performance fan. The system guarantees both a constant gas and air mix under any running condition. The precise mixing of gas and air results in a clean, low temperature flame, which matched with the unique combustion chamber design, provides an immediate exchange of heat. Bi-Metalic heat exchanger The unique high efficiency heat exchanger is equipped with a continuous internal bi-metalic corrugated tube, which is constructed from copper on the water side and stainless steel on the flue side. The heat exchanger also features a refractory plug that retains the heat inside the combustion chamber and forces the flue gases over the coil surfaces to optimise the thermal exchange performance. The micro-flame burner is located at the top in the centre of the heat exchanger with single spark ignition. Features • Hydraulic connection kit within the boiler casing for simplified installation and maintenance • 160 / 200 mm diameter flue header kit • Low loss header kit • Option for LPG Propane • Robust bi-metallic heat exchanger • Flue temperatures of only 3˚C above the return water temperature • Sophisticated controls for management of up to 3 separate heating circuits Corolla Pack 503/504 Boiler

Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. Corolla Pack 503 / 504 series boilers are available with

Embed Size (px)

Citation preview

Page 1: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

12551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Corolla Pack Boilers503 / 504 & 1000 Series

The Corolla Pack Range

The Corolla Pack series of condensing, pre-mix, modulating boilers contain multiple heat exchanger modules within a single casing. The range provides boiler outputs from 150kW to 500kW and up to 4000kW in cascade.

To simplify installation and maintenance each boiler comes complete with an integrated hydraulic connection kit. The 503/504 Series includes an integrated flue header kit and optional low loss header kit. The 1000 Series includes an integrated low loss header kit and polypropelene flue discharge as standard, with the flue header kit fitted outside of the casing.

Featuring efficiency figures as high as 109% nett at (30%) part load, the Corolla Pack has excellent environmental benefits, and far exceeds current requirements for Part L Building Regulations.

With sophisticated controls, based on the master and slave principle, the Corolla Pack can manage multiple heating zones and up to 60 boiler modules in cascade.

Pre-mix burnerThe Corolla Pre-mix combustion system comprises of a modulating gas valve integrated with a high performance fan.

The system guarantees both a constant gas and air mix under any running condition. The precise mixing of gas and air results in a clean, low temperature flame, which matched with the unique combustion chamber design, provides an immediate exchange of heat.

Bi-Metalic heat exchangerThe unique high efficiency heat exchanger is equipped with a continuous internal bi-metalic corrugated tube, which is constructed from copper on the water side and stainless steel on the flue side.

The heat exchanger also features a refractory plug that retains the heat inside the combustion chamber and forces the flue gases over the coil surfaces to optimise the thermal exchange performance.

The micro-flame burner is located at the top in the centre of the heat exchanger with single spark ignition.

Features• Hydraulic connection kit within the boiler casing for simplified installation and maintenance• 160 / 200 mm diameter flue header kit• Low loss header kit• Option for LPG Propane• Robust bi-metallic heat exchanger• Flue temperatures of only 3˚C above the return water temperature• Sophisticated controls for management of up to 3 separate heating circuits

Corolla Pack 503/504 Boiler

Page 2: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

22551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Corolla Pack 503 / 504 series boilers are available with an optional low loss header kit, which is constructed from carbon steel.

The low loss header kit separates the heating plant circulation to maintain a constant flow of water in the boiler independently of losses of load. The kit includes boiler flow and return shut-off valves which enable the system to be worked on without having to empty out the entire heating arrangement.

An optional safety kit is available and includes a fuel valve, thermometric electrical box, manometer, block pressure switch, automatic air vent valve, thermometer and valve with manometer holder.

Corolla Pack 503/504 Series

803

291

220

300

450

Dimensions

Low Loss Header Kit

Page 3: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

32551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Technical specification

FeatureUnit of

measure

Co

rolla

P

ack

503

Co

rolla

P

ack

504

No. boiler modules kW 3 x 50 4 x 50N° EC certification - 0085AQ0713SizesApprox. Shipping weight kg 290 320Water content l 50 55Flow/Return/Gas hydraulic connections (all M) “ 5”- 3”Flue Diameter mm 160Outputs and efficienciesBuilding Regulations Seasonal Efficiency (Gross) % 95Maximum nominal heating input Hi/Hs kW 135/150 188/200Minimum nominal heating input Hi/Hs kW 14.4/16Nominal useful output supplied to the water Hi (80°C - 60°C) kW 132.5 176.6Nominal useful output supplied to the water Hi (50°C - 30°C) kW 145.3 193.6Efficiency at 100% nominal output (80°C - 60°C) (Nett) % 98.2Efficiency at 30% nominal output (80°C - 60°C) (Nett) % 98.7Efficiency at 100% nominal output (50°C - 30°C) (Nett) % 107.7Efficiency at 30% nominal output (50°C - 30°C) (Nett) % 108.7Energy Efficiency marking (Directive 92/42 EEC) Stars ****Output SupplyOutput supply minimum pressure G20/G30/G31 mbar 17/26/25Output supply nominal pressure G20/G30/G31 mbar 20/29/37Nominal pressure gas capacity G20/G30/G31 mc-kg/h 14.3/10.6/10.5 19.0/14.2/14.0Electric power absorbed by the boiler* W 684/255 912/340Nominal supply voltage - 230V 1PH 50HzFuel DataFuel efficiency at nominal output (80°C - 60°C) (Nett) % 98.7Fuel efficiency at nominal output (50°C - 30°C) (Nett) % 108.3Chimney losses with burner on at 100% nominal output (80 - 60°C) % 1.3Chimney losses with burner off % 0.1Case losses with burner on at 100% nominal output % 0.5Maximum heating output flues temperature °C T° return + max 2.5°CMaximum/minimum heating output flues capacity kg/h 220/26 223/26Nominal output flues residual head (sq m for D50mm) Pa/meq 380/25CO2 maximum/minimum heating capacity ppm 9.0/9.0CO maximum/minimum heating capacity (0% O2) ppm 10/80NOx emissions - European Class 5Primary CircuitMin/max settable temperature °C 20/80Max water pressure bar 6Residual hydraulic head at 2000 l/h per unit mca/bar 1.5/15.3Condense hourly production 100% nominal output (50°C - 30°C) gas G20 l/h 20.7 27.6

On Board Electronics (as standard)

N° inputs / N° outputs -8 inputs (4 T° probes, 2 room thermostats,

1 analogical 0-10V, 1 remote control) 5 outputs (3 pumps, 1 mixer valve, 1 alarm)

N° controllable zones as standard - 3 (high T°, low T°, sanitary)Maximum N° of controllable modules in cascade with a master - 60 modulesInterfaceability with other systems - analogical input 0-10V

Technical Details

Page 4: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

42551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Corolla Pack 1000 SeriesDimensions

Up to two Corolla Pack 1000 Series boilers can be installed inline or back-to-back using a 200mm flue header. A maximum of three boilers can be connected inline or back-to-back and this will require a 250mm flue header.

Front view of a single boiler with casing removed showing the four heat exchanger modules.

The illustration above shows 8 Corolla Pack 1004 boilers connected in banks of two to provide a total output of 4000kW.

Page 5: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

52551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Technical specification

FeatureUnit of

measure

Co

rolla

P

ack

1004

Co

rolla

P

ack

1005

Co

rolla

P

ack

1006

Co

rolla

P

ack

1007

No. boiler modules kW 4 x 128 5 x 128 6 x 128 7 x 128

Sizes

Height /Width / Depth 1500 / 1700 / 750 1500 / 3400 / 750 1500 / 3400 / 750 1500 / 3400 / 750

Approx. Shipping weight kg 450 550 675 785

Water content l 130 162.5 195 227.5

Flow/Return/Gas hydraulic connections (all M) “ 5”/ 3”

Flue Diameter mm 4 x D110 5 x D110 6 x D110 7 x D110

Flue Manifold mm D200

Outputs and efficiencies

Maximum nominal heating input Hi/Hs kW 460.0 / 511.2 575 / 639 690 / 766.8 805 / 894.6

Minimum nominal heating input Hi/Hs kW 23.0 / 25.5 28.75 / 31.95 34.5 / 38.34 40.25 / 44.73

Nominal useful output supplied to the water Hi (80°C - 60°C) kW 453.6 567.0 680.4 793.8

Nominal useful output supplied to the water Hi (50°C - 30°C) kW 499.6 624.5 749.4 874.3

Efficiency at 100% nominal output (80°C - 60°C) (Nett) % 98.6

Efficiency at 30% nominal output (80°C - 60°C) (Nett) % 99.2

Efficiency at 100% nominal output (50°C - 30°C) (Nett) % 108.6

Efficiency at 30% nominal output (50°C - 30°C) (Nett) % 109

Energy efficiency marking (Directive 92/42 EEC) Stars ****

Output Supply

Fuels - G20, G30, G31

Output supply minimum pressure - G20 mbar 14

Output supply nominal pressure - G20 mbar 20

Fuel flow rate at nominal pressure G20/G30/G31 mc/h 12.2 / 3.7 / 4.8 15.2 / 4.6 / 6 18.3 / 5.5 / 7.2 21.3 / 6.5 / 8.4

Electric power absorbed by the boiler* kW 1.2 1.5 1.8 2.1

Nominal supply voltage - 230V 1PH 50Hz

Fuel Data

Fuel efficiency at nominal output (80°C - 60°C) (Nett) % 98.7

Fuel efficiency at nominal output (50°C - 30°C) (Nett) % 99.2

Chimney losses with burner on at 100% nominal output (80 - 60°C) % 1.3

Chimney losses with burner off % 0.1

Case losses with burner on at 100% nominal output % 0.5

Maximum heating output flues temperature °C 80°C

Maximum/minimum heating output flues capacity kg/h 183.6 / 56.1 229.5 / 70.2 275.4 / 84.24 321.3 / 98.3

Nominal output flue residual head Pa 600

CO2 maximum/minimum heating capacity % 9% / 9%

CO maximum/minimum heating capacity (0% O2) mg/kWh 23/130

NOx emissions European Class 5 - V (fifth)

Primary Circuit

Min/max settable temperature °C 20 / 80

Max water pressure bar 6

Hydraulic residual head at 4000 l/h per unit mca/bar 1.5 / 15.3

Condense hourly production 100% nominal output (50°C - 30°C) gas G20 l/h 68.8 86.1 103.2 120.4

On Board Electronics (as standard)

N° inputs / N° outputs -8 input (4 T° probes, 2 room thermostat, 1 analogic 0-10 V, 1

remote control)5 output (3 pumps, 1 mixing valve, 1 alarm)

N° controllable zones as standard - 3 (high T°, low T°, DHW heater)

Maximum N° of boilers controlled by the master - 60 units (1004 = 4 units)

Dialog management with others systems -analogical input 0-10V. Optional interfaces available on

request: GSM, etc.

Technical Details

Page 6: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

62551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Typical Plant Layouts 503/504Single Boiler InstallationCorolla Pack 503 - 150kW or 504 - 200kW Output

Page 7: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

72551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Two Boiler InstallationCorolla Pack 503 - 300kW or 504 - 400kW Output

Back-to-Back

In-Line

Typical Plant Layouts 503/504

Page 8: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

82551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Three Boiler InstallationCorolla Pack 503 - 450kW or 504 - 600kW Output

Back-to-Back

In-Line

Typical Plant Layouts 503/504

Page 9: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

92551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Four Boiler InstallationCorolla Pack 503 - 600kW or 504 - 800kW Output

In-Line

Back-to-Back

Typical Plant Layouts 503/504

Page 10: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

102551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Five Boiler InstallationCorolla Pack 503 - 750kW or 504 - 1000kW Output

Back-to-Back

Typical Plant Layouts 503/504

Page 11: Corolla Pack Boilers - Evinox Energy Pack... · 2551175B 2 Evinox Ltd T. +44 (0)1372 722277 E. technical@evinox.co.uk W.  Corolla Pack 503 / 504 series boilers are available with

112551175B

Evinox Ltd T. +44 (0)1372 722277 E. [email protected] W. www.evinox.co.uk

Five Boiler InstallationCorolla Pack 503 - 750kW or 504 - 1000kW Output

In-Line Including Flue

Typical Plant Layouts 503/504