Cooling Towers
SERIESHRFG
DurableCorrosion ResistantCooling Towers
THERMAL PERFORMANCE CERTIFIEDBY THE COOLING TECHNOLOGY INSTITUTE
VALIDATION NO. 00-22-02
REYMSA COOLING TOWERS, INC. has been committed for over 30 years to the Commercial and Industrial Market in providing solutions to their particular cooling needs, always looking out to the total satisfaction of our customers.
This commitment and the experience of our Engineers, combined with supreme quality, premium materials and components used to manufacture our products, gave birth to the “state of the art” HRFG Series by REYMSA Cooling Towers.
Certified by the CTI (Cooling Technology Institute), Certificate Number: 00-22-02 and 100% FRP manufactured in order to provide with the highest performance and longest service life possible, to serve those who demand the best and are also committed to maintaning all producion equipment at its optimum condition.
HRFG SERIES FEATURESAll FRP unitized casing and internal structure
UV Protection for extended life & strength
Optimum Design for all season performance including freezing climates
Fiberglass-Reinforced-Polyamide adjustable pitch Fans
Self extinguish PVC fill & PVC drift eliminator
Direct drive, low speed, TEFC, NEMA fan motors
Low noise operation
No moving internal parts
Fixed distribution nozzles with variable flow rates
Triple-pass PVC Air Inlet Louvers
Large, easily removable access doors
Corrosion resistant strainers.
Single or multiple fan configurations with common sump
FIBERGLASS REINFORCED POLYESTER (FRP) PROPERTIES
An FRP lamination is 5 times lighter than its equivalent of the same size and thickness made from steel. You will also find that if compared against a steel lamination of the same mechanical resistance, the FRP lamination is about half as heavy.
The low coefficient of expansion of the FRP material makes it highly resistant to wide variations of temperature and humidity without showing any deformation. These properties allow REYMSA Cooling Towers to withstand many different types of environments.
Only for appearance purposes, such as dusting or waxing.
It is very easy to perform a minor repair work on the Fiberglass, materials are available all across the country, and the fixing process is as easy as to grind the surface, apply the Polyester Resin which in the form of liquid, one layer of fiberglass cloth and again apply resin. Finally wait until the resin is dried.
LIGHT WEIGHT
STABILITY
ZERO OR NO MAINTENANCE REQUIRED
VERY EASY TO WORK WITH
FRP material is highly resistant to tension and compression stresses as to impact charges as well, making it a frequently used material in structural applications.
As a rule of thumb, it is required for an FRP lamination to be three times thicker than one made from steel in order to have the same mechanical resistance.
A very simple analogy can be used to have a clear understanding of the FRP properties: The Polyester Resin can be seen as the Cement and the Fiberglass as the corrugated bars in the reinforced concrete.
FRP has at least twice the mechanical resistance of HDPE.
There are several types of polyester resin available in the market for different applications and resistances. The highest protection against environmental attacks is reached by using Premium Isophalic Polyester Resin with UV inhibitor in the manufacturing process of all our Cooling Towers. The life of FRP with Premium Isophalic resin is said to be endless, although REYMSA recommends that 30 years are to be considered when making a life-cycle cost analysis.
HIGH MECHANICAL RESISTANCE
GREAT CHEMICAL AND WEATHER RESISTANCE
Great Resistance to Corrosion and many chemical agents. CORROSION RESISTANCE
Maximum Reliability with Efficiency
ALL FIBERGLASS, ONE PIECE, SEAMLESS CONSTRUCTION WITH HIGH MECHANICAL RESISTANCE, LONG LIFE CONSTRUCTION, AND MINIMUM OR ZERO MAINTENANCE, WITHOUT WATER LEAKAGE PROBLEMS
Corrosion resistant.
Major longevity, life expectancy of 30 plus years.
No risk of water leakage, a unique seamless, one piece construction.
Better appearance, aesthetically superior.
Excellent mechanical resistance and stabilty, capable of working in all kinds of environments weathers.
Exterior and interior gelcoat protective layer with UV Inhibitor:
Not affected by corrosive sediments caused by airborne impurities collected in the basin, that require the entire cold water in the basin of galvanized and stainless steel towers to be drained, cleaned and flushed quarterly.
Greater resistance to a wide spectrum of pH´s, total dissolved solids, chlorides and sulfates from the water treatement.
Capacity to endure higher levels of concentration of chlorides in the water for the REYMSA Cooling Tower against a Steel (galvanized and/or stainless) Towers. Typically a Pulsed Power Non Chemical water treatment is able to handle up to 400 ppm of concentration of chlorides in the recirculation water, which means more cycles of concentration and less water losses caused by bleeds or blowdowns.
* Great resistance against :- Environmental attacks on the outside- Agressive chemical conditions of the water
REYMSA COOLING TOWERS, INC.
Durability & Minimum Maintenance
Direct drive transmission that eliminates the use of pulleys, belts and bearings.
Our direct drive eliminates the frequent service required by the V-belt drive transmission that translates into higher operational and maintenance costs. Typically a V-belt drive transmission require a quarterly service for checking and readjusting tension on the belt, lubrication of fan shaft bearings, lubrication of the motor base adjusting screws and drive alignment to ensure maximum belt life.
Also by having less components between the fan and the motor, the risk of a failure causing a sudden stop of the fan,which will cause higher operational water temperatures that may stop the entire air conditioning system, is reduced to a minimum.
REYMSA uses the best fan in the market, manufactured using cast aluminum hubs and adjustable pitch air foil blades molded with engineering thermoplastics.
Blade materials: fiberglass reinforced polyamide, which is spark and corrosive resistant, able to resist high vibration levels and high temperatures. Ambient operating air temperatures may fluctuate from – 50°F to 250°F.
Fan Motors: all our Tower models feature motors that exceed the Cooling Tower duty characteristics. REYMSA Fan Motors are NEMA Premium Efficient, TEFC, 1.15 service factor, 100% cast iron construction for SEVERE DUTY, INVERTER DUTY, and MARINE DUTY applications, EPROXY PAINT, inpro/ seal vbx bearing isolators on both ends of the shaft, brass drain and breather, 6-60 hz variable torque.
DIRECT DRIVE ON ALL OF OUR TOWER MODELS, FOR A MORE RELIABLE OPERATION WITH MUCH LESS SERVICE AND OPERATION COSTS, AND MINIMAL RISK OF A FAILURE
REYMSA COOLING TOWERS, INC.
Maximum Reliability with Efficiency
HIGHEST SURFACE TO VOLUME RATIO PVC FILL FOR SMALLER FOOTPRINTBy having the highest specific surface area ft2/ft3, our fill provides the highest surface area for the heat transfer for all HVAC and most Industrial applications. The PVC compounds used in our fill have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, grease, fats, oils and biological attack. Also has excellent fire rating due to its self-extinguishing characteristics and meets or exceeds Cooling Technology Institute (CTI) PVC materials standard 136.
Hot water manifold manufactured of PVC schedule 40, with PVC welded branches tested at 100 psig., to assure reliability and prevent water leakages that affect the tower efficiency, due to wearing of union gasket as other manufacturers do.
THE MOST RELIABLE HOT WATER DISTRIBUTION SYSTEM
Fixed, non-clogging large orifice nozzles, 2 ½" , N.P.T., largest in the market, manufactured in ABS plastic, able to handle up to 180°F water temperature, with interchangeable internal devices so that water is efficiently and uniformly distributed across the entire fill surface. Nozzle body has threaded connection and it is easy to remove.
NON CLOGGING SPRAY NOZZLES
2½" N.P.T. ABS-Spray Nozzleswith interchangeable
internal devices
REYMSA COOLING TOWERS, INC.
Durability & Minimum Maintenance
REYMSA COOLING TOWERS, INC.
EASY, REMOVABLE, ENVIRONMENTAL FRIENDLY AIR INLET LOUVER DESIGNOur triple pass PVC air inlet louvers are designed to block the direct sunlight to the water, minimize the splash out, and to reduce the noise, while having low pressure drop that results in less fan motor energy consumption. Blocking the direct sunlight and allowing very little light to pass through, the potential of algae growth is reduced, therefore reducing water treatment and maintenance cost. Additional characteristics are its durability by being corrosion-free, and impervious to chemical attacks. PVC is specially formulated for UV resistance, and fire resistance, non-combustible and self extinguishing.
EASY MAINTENANCE AND CLEANING ACCESS
Wide and easy access for monitoring or cleaning the inside of the Tower and the cold water basin by removing the access door or the air inlet louvers.
RemovableAccess Door
RemovableAir inlet Louvers
In Addition to our Guarantee of the Thermal Performance of our Cooling Towers, the HRFG Series are Certified by the Cooling Technology Institute (CTI) according to the Standard Std-201. Validation No. 00-22-02
CTI CERTIFICATION OF THERMAL PERFORMANCE
Maximum Reliability with Efficiency
A family owned Company founded in 1969 who really understands the importance of having satisfied customers to build long term relationships.
Assembly is reduced to placing and bolting the fan cylinder on top of the one-piece body and basin section. No gasket or caulking is required.
The reduced footprint of our Induced Draft, Counterflow design requires less structural base support, and frequently less piping than the crossflow towers.
´
EASY AND ECONOMICAL ASSEMBLY AND INSTALLATION COST
Every single tower is assembled and tested at our factory prior to shipment.
FACTORY TESTS
FRIENDLY, EASY TO DEAL WITH COMPANY
REYMSA COOLING TOWERS, INC.
REYMSA COOLING TOWERS, INC.
Durability & Minimum Maintenance
Automatic Sand Filtration System for Suspended Solids RFS SeriesSweeper Piping for Water FiltrationVibration Isolators Variable Frequency DriveBasket Non-Corrosive Strainers for Outlet Connection (Standard)
OPTIONAL DESIGNS WITH CUSTOMIZED COMPONENTS OR COLORS FOR SPECIAL APPLICATIONS
Special Colors, Designs or Configurations
Sickle Fans for Low Noise applications
Special fills for industrial applications with bigger flutes, vertical design or for higher than 130°F water temperature.
OPTIONAL EQUIPMENT
Sound DeflectorsAccess LadderStainless Steel HandrailVibration Cut off SwitchElectric HeatersElectric Water Level ControlBottom Outlet (Dry Sump)Basin Equalizer ConnectionsStainless Steel Davit SupportSpecial Fan Motor ConstructionStainless Steel Non-Skid Catwalk
Tower casing construction with flame retardant resin according to the ASTM-E84 Standard.
3
7
1
9
10
8
6
11
5
4
2
REYMSA COOLING TOWERS, INC.
Maximum Reliability with Efficiency
Air Inlet Louvers
Basin Section
Water Make up
Cold Water Outlet
Overflow (back side)
Drain (back side)
Purge (back side)
8.
9.
10.
11.
12.
13.
14.
Fan Section
Plenum
Drift Eliminator
Spray Nozzle Manifold
Hot Water Inlet
Body Section
Cellular Fill
1.
2.
3.
4.
5.
6.
7.
Construction Details
REYMSA COOLING TOWERS, INC.
Durability & Minimum Maintenance
Engineering Data
Single Fan Double Fan
A A
A
H H H
L
L
L
L
L
L
Quadruple Fan
* A Nominal TON is defined as 3 GPM of water cooled from 95°F to 85°F with a 78°F entering wet bulb.** Modular sections to be assembled for higher tonage requirements. Minimum two modules. Contact your Rep for proper selection.1. All dimensions, weights and capacities are in inches, pounds and gallons. Physical dimensions of each tower are approximate and are subject to change.2. All double and quadruple models have double fittings and connections.
OverflowCold WaterOutlet
Height W/OFan Drain
MODELL W H
*NominalTons
DIMENSIONSMotorHPPurge
Hot WaterInlet
2426
4353
6175
90107
141155
152169192
163184205
171190210
187203229
210243266
227251278
267291313
281311
343380420
565622
685760840
432477528
486578
HRFG-303115HRFG-303102
HRFG-404103HRFG-404105
HRFG-505103HRFG-505105
HRFG-606105HRFG-606175
HRFG-707175HRFG-707110
HRFG-708175HRFG-708110HRFG-708115
HRFG-709175HRFG-709110HRFG-709115
HRFG-808175HRFG-808110HRFG-808115
HRFG-809175HRFG-809110HRFG-809115
HRFG-810110HRFG-810115HRFG-810120
HRFG-811110HRFG-811115HRFG-811120
HRFG-812115HRFG-812120HRFG-812125
HRFG-714275HRFG-714210
HRFG-816275HRFG-816210HRFG-816215
HRFG-1414475HRFG-1414410
HRFG-1616475HRFG-1616410HRFG-1616415
HRFG-822210**HRFG-822215**HRFG-822220**
HRFG-827210**HRFG-827215**HRFG-827220**
HRFG-1622410HRFG-1622415HRFG-1622420
HRFG-1627410HRFG-1627415HRFG-1627420
WaterMakeup
CONNECTION DIAMETER WEIGHT
OPERATINGSHIPPING
864954
1056
97211561236
198198198
197.5197.5197.5
205205205
209.75209.75209.75
159159159
159.75159.75159.75
2-122-122-12
2-122-122-12
2-1½2-1½2-1½
2-1½2-1½2-1½
2-22-22-2
2-22-22-2
2-82-82-8
2-82-82-8
4-24-24-2
4-24-24-2
2-¾2-¾2-¾
2-¾2-¾2-¾
154001540015400
188701887018870
383903839038390
510805108051080
4-104-154-20
4-104-154-20
3636
4848
6161
7373
8484
969696
110.75110.75110.75
979797
103103103
120.5120.5120.5
103103103
145.5145.5145.5
168168
199.5199.5199.5
175175
199.5199.5199.5
268268268
328328
268268268
328328328
3636
4848
6161
7373
8484
848484
85.7585.7585.75
979797
115115115
979797
138.5138.5138.5
979797
8484
104.75104.75104.75
174174
201201201
98.7598.7598.75
98.7598.75
108108
123123
128128
128128
133133
133133133
134134134
155155155
148148148
155155155
152152152
156156156
133133
160160160
134134
159159159
282282282
301301
9090
9898
9898
9898
9898
989898
989898
118118118
114114114
118118118
114114114
119119119
9898
124124124
9898
123123123
246246246
263263
2½2½
2½2½
44
44
66
666
666
666
666
666
888
888
2-62-6
2-62-62-6
2-82-8
2-102-102-10
1-121-121-12
1-121-12
22
22
22
22
22
222
222
222
222
222
222
222
2-22-2
2-22-22-2
2-22-2
2-22-22-2
1-21-21-2
1-21-2
22
22
22
22
22
222
222
222
222
222
222
222
2-22-2
2-22-22-2
4-24-2
4-24-24-2
2-22-22-2
2-22-2
½½
½½
½½
½½
11
111
111
111
111
111
1½1½1½
1½1½1½
2-12-1
2-12-12-1
2-1½2-1½
2-1½2-1½2-1½
1-1½1-1½1-1½
1-1½1-1½
2½2½
2½2½
44
44
66
666
666
666
666
666
888
888
2-62-6
2-62-62-6
2-82-8
2-82-82-8
1-81-81-8
1-81-8
½½
½½
¾¾
¾¾
¾¾
¾¾¾
¾¾¾
¾¾¾
¾¾¾
¾¾¾
¾¾¾
¾¾¾
2-¾2-¾
2-¾2-¾2-¾
2-¾2-¾
2-¾2-¾2-¾
1-¾1-¾1-¾
1-¾1-¾
727727
10221022
13661366
18901890
25532553
271727172717
291229122912
298629862986
335033503350
354835483548
400240024002
402840284028
46744674
547654765476
93499349
109531095310953
795079507950
94359435
14271427
22342234
31893189
44154415
56245624
623062306230
686368636863
699269926992
808680868086
852285228522
974497449744
996599659965
1081810818
132131321313213
2163721637
264272642726427
194451944519445
2554025540
1.52
35
35
57.5
7.510
7.51015
7.51015
7.51015
7.51015
101520
101520
152025
(2)7.5(2)10
(2)7.5(2)10(2)15
(4)7.5(4)10
(4)7.5(4)10(4)15
(2)10(2)15(2)20
(2)10(2)15
APPROACH
5
6
7
8
10
12
14
16
6
3.15
3.60
4.05
4.50
5.49
6.36
8
2.70
3.03
3.42
3.75
4.50
5.31
6.00
10
2.43
2.73
3.00
3.36
3.96
4.59
5.25
5.91
12
2.49
2.73
3.00
3.60
4.14
4.65
5.25
1
15
2.49
2.70
3.21
3.66
4.14
4.62
1
20
2.40
2.79
3.18
3.60
4.05
1
26
2.55
2.88
3.21
3.60
1
30
2.40
2.76
3.09
3.45
1
35
2.61
2.88
3.21
1
APPROACH 6
3.33
3.78
4.26
4.65
5.70
6.75
8
2.85
3.21
3.75
3.96
4.71
5.55
6.45
10
2.55
2.88
3.18
3.51
4.14
4.80
5.55
6.21
12
2.34
2.61
2.91
3.18
3.78
4.32
4.95
5.55
15
2.37
2.61
2.85
3.33
3.84
4.35
4.85
1
20
2.34
2.55
2.88
3.36
3.81
4.23
1
26
2.31
2.67
3.00
3.39
3.78
1
30
2.55
2.91
3.24
3.63
1
35
2.40
2.73
3.06
3.45
15
6
7
8
10
12
14
16
REYMSA COOLING TOWERS, INC.
Maximum Reliability with Efficiency
R A N G E R A N G E
62 Deg. Wet Bulb60 Deg. Wet Bulb
EXAMPLE:
Select the HRFG Model REYMSA Cooling Tower to cool 1200 GMP of clear water from 95 °F to 85 °F at entering air wet bulb of 78 °F.
STEP 1 RANGE is equal to the temperature differential between the entering water temperature ( T1 ) and the leaving water temperature ( T2). (95 °F - 85 °F ) = 10
STEP 2 APPROACH is equal to the temperature differential between the leaving cool water temperature ( T2 ) and wet bulb temperature ( TWB ). ( 85 °F - 78 °F ) = 7
STEP 3 From Section A: TOWER SELECTION FACTORS; Select the apropriate wet bulb temperature table ( 78 °F ). Select the range column ( 10 ) and in Approach row ( 7 ), the Tower Selection Factor = 4.8
STEP 4 Next, go to Section B: CAPACITY TABLES; Enter the column headed by the “ Tower Selection Factor ” determined from Section A ( 4.8 ) and read down that column to the desired cooling water flow rate equal to or greater than that specified ( 1200 gmp ). Look to the left on the row with the desired cooling water flow and read the corresponding HRFG816215 REYMSA Cooling Tower model to satisfy your requirements.
HRFG SERIES TOWER SELECTION
Sección A: TOWER SELECTION FACTORS
R A N G E
R A N G E
R A N G E
R A N G E
R A N G E
R A N G E
R A N G E
R A N G E
APPROACH
APPROACH
APPROACH
APPROACH
5
5
5
5
6
6
6
6
7
7
7
7
8
8
8
8
10
10
10
10
12
12
12
12
14
14
14
14
16
16
16
16
APPROACH
APPROACH
APPROACH
APPROACH
5
5
5
5
6
6
6
6
7
7
7
7
8
8
8
8
10
10
10
10
12
12
12
12
14
14
14
14
16
16
16
16
6
3.42
3.90
4.35
4.80
5.85
8
2.88
3.30
3.66
4.05
4.80
5.61
6.54
10
2.58
2.91
3.21
3.54
4.23
4.89
5.61
6.36
12
2.40
2.67
2.94
3.24
3.81
4.41
5.04
5.64
2.43
2.67
2.91
3.42
3.96
4.44
5.04
2.40
2.61
3.00
3.48
3.90
4.35
2.37
2.73
3.12
3.54
3.90
2.64
2.97
3.36
3.75
2.49
2.79
3.15
3.54
6
3.54
4.02
4.47
5.01
6.00
8
2.97
3.39
3.75
4.14
4.95
5.79
6.60
10
2.64
2.91
3.30
3.63
4.29
5.01
5.70
6.36
12
2.43
2.73
3.00
3.30
3.90
4.50
5.16
5.85
15
2.49
2.76
2.97
3.54
4.02
4.56
5.16
1
20
2.46
2.70
3.09
3.60
3.99
4.50
1
26
2.43
2.82
3.21
3.63
4.02
1
30
2.31
2.67
3.00
3.39
3.78
1
35
2.55
2.91
3.24
3.63
1
6
3.72
4.26
4.74
5.31
6.36
8
3.21
3.63
3.99
4.41
5.19
6.09
10
2.82
3.15
3.54
3.84
4.59
5.31
6.06
12
2.61
2.91
3.21
3.54
4.17
4.80
5.52
6.15
15
2.37
2.61
2.88
3.12
3.72
4.26
4.80
5.46
20
2.37
2.61
2.82
3.27
3.75
4.26
4.71
1
26
2.37
2.55
2.91
3.36
3.78
4.23
1
30
2.43
2.82
3.21
3.60
3.99
1
35
2.34
2.70
3.03
3.42
3.81
1
6
3.93
4.41
4.95
5.55
6.75
8
3.33
3.75
4.17
4.59
5.52
6.45
10
2.94
3.30
3.69
4.05
4.74
5.58
6.36
12
2.73
3.03
3.39
3.72
4.35
5.04
5.76
6.51
15
2.49
2.91
3.00
3.30
3.90
4.44
5.04
5.70
20
2.25
2.49
2.70
2.94
3.42
3.93
4.41
4.95
26
2.28
2.49
2.70
3.09
3.57
3.99
4.41
1
30
2.40
2.61
2.97
3.39
3.81
4.26
1
35
2.31
2.49
2.85
3.21
3.60
4.02
1
6
4.05
4.56
5.16
5.46
8
3.54
3.96
4.41
4.89
5.82
6.90
10
3.12
3.51
3.90
4.26
5.04
5.91
6.75
12
2.88
3.21
3.54
3.90
4.56
5.34
6.00
15
2.61
2.91
3.21
3.51
4.11
4.65
5.34
5.94
20
2.37
2.61
2.85
3.06
3.60
4.14
4.65
5.28
26
2.40
2.64
2.85
3.30
3.78
4.23
4.74
1
30
2.31
2.52
2.73
3.15
3.60
4.02
4.47
1
35
2.43
2.67
3.00
3.48
3.87
4.32
1
6
4.35
4.95
5.55
6.09
8
3.69
4.14
4.59
5.04
6.00
10
3.27
3.72
4.11
4.47
5.34
6.15
12
3.00
3.42
3.75
4.11
4.80
5.55
6.36
15
2.73
3.03
3.36
3.69
4.32
5.01
5.64
6.36
20
2.52
2.79
3.03
3.30
3.84
4.38
5.04
5.61
26
2.31
2.55
2.79
3.00
3.51
3.93
4.44
5.04
30
2.43
2.67
2.85
3.30
3.78
4.26
4.71
1
35
2.34
2.55
2.79
3.18
3.60
4.05
4.50
1
6
4.38
4.98
5.58
6.15
8
3.78
4.29
4.71
5.25
6.21
10
3.39
3.81
4.23
4.62
5.55
6.36
12
3.12
3.54
3.93
4.26
4.89
5.79
6.60
15
2.82
3.18
3.51
3.78
4.44
5.10
5.79
6.45
20
2.55
2.85
3.09
3.42
3.96
4.50
5.10
5.70
26
2.40
2.64
2.91
3.09
3.60
4.11
4.65
5.16
30
2.28
2.52
2.73
2.94
3.42
3.90
4.35
4.86
35
2.40
2.64
2.85
3.27
3.72
4.17
4.59
1
6
4.47
5.19
5.76
6.90
8
3.84
4.35
4.86
5.34
6.36
10
3.48
3.90
4.32
4.74
5.61
6.60
12
3.18
3.60
3.96
4.32
5.13
5.88
6.75
15
2.91
3.24
3.60
3.90
4.56
5.31
6.00
20
2.67
2.91
3.21
3.48
4.05
4.59
5.22
5.85
26
2.43
2.67
2.91
3.18
3.66
4.14
4.68
5.25
30
2.37
2.58
2.82
3.00
3.54
3.99
4.47
5.04
35
2.28
2.49
2.70
2.91
3.39
3.84
4.29
4.77
20 26 30 3515
REYMSA COOLING TOWERS, INC.
Durability & Minimum Maintenance
63 Deg. Wet Bulb
66 Deg. Wet Bulb
70 Deg. Wet Bulb
73 Deg. Wet Bulb
64 Deg. Wet Bulb
68 Deg. Wet Bulb
72 Deg. Wet Bulb
74 Deg. Wet Bulb
75 Deg. Wet BulbR A N G E
76 Deg. Wet BulbR A N G E
77 Deg. Wet BulbR A N G E
78 Deg. Wet BulbR A N G E
79 Deg. Wet BulbR A N G E
80 Deg. Wet BulbR A N G E
81 Deg. Wet BulbR A N G E
82 Deg. Wet BulbR A N G E
APPROACH
5
6
7
8
10
12
14
16
APPROACH
5
6
7
8
10
12
14
16
6
4.71
5.40
6.00
6.75
8
4.05
4.56
5.10
5.61
6.75
10
3.69
4.14
4.53
5.04
5.91
12
3.42
3.78
4.17
4.56
5.40
6.15
15
3.06
3.45
3.78
4.14
4.80
5.55
6.24
20
2.79
3.09
3.42
3.72
4.29
4.89
5.55
6.15
26
2.61
2.85
3.12
3.42
3.90
4.44
5.04
5.58
30
2.49
2.73
2.97
3.24
3.72
4.26
4.74
5.28
35
2.40
2.64
2.85
3.06
3.60
4.05
4.50
5.10
6
4.62
5.31
5.91
6.45
8
3.96
4.44
5.01
5.52
6.06
10
3.54
3.99
4.41
4.89
5.76
6.66
12
3.27
3.66
4.05
4.41
5.16
6.00
15
3.00
3.36
3.69
4.02
4.71
5.46
6.15
20
2.70
2.97
3.30
3.60
4.17
4.71
5.40
6.00
26
2.52
2.79
3.00
3.30
3.81
4.32
4.86
5.40
30
2.40
2.67
2.88
3.09
3.60
4.05
4.56
5.16
35
2.34
2.55
2.79
2.97
3.36
3.90
4.38
4.89
APPROACH
5
6
7
8
10
12
14
16
APPROACH
5
6
7
8
10
12
14
16
6
4.86
5.55
6.15
8
4.20
4.71
5.28
5.79
10
3.75
4.23
4.59
5.10
6.00
12
3.48
3.87
4.29
4.65
5.52
6.36
15
3.18
3.54
3.87
4.26
4.95
5.70
6.45
20
2.91
3.21
3.51
3.84
4.41
5.04
5.70
6.36
26
2.67
2.91
3.18
3.45
3.99
4.50
5.16
5.76
30
2.55
2.79
3.06
3.30
3.81
4.35
4.86
5.52
35
2.49
2.70
2.94
3.21
3.69
4.17
4.65
5.19
6
5.04
5.70
6.36
8
4.38
4.95
5.52
6.00
10
3.87
4.32
4.80
5.28
6.24
12
3.57
3.99
4.38
4.80
5.67
6.60
15
3.21
3.60
3.93
4.32
5.07
5.85
6.60
20
2.97
3.27
3.60
3.90
4.50
5.19
5.85
6.60
26
2.70
2.97
3.27
3.57
4.11
4.65
5.25
5.85
30
2.67
2.91
3.15
3.45
3.93
4.47
5.04
5.64
35
2.52
2.76
2.97
3.21
3.75
4.26
4.74
5.28
APPROACH
5
6
7
8
10
12
14
16
APPROACH
5
6
7
8
10
12
14
16
6
5.10
5.79
6.51
8
4.44
5.04
5.55
6.15
10
3.93
4.41
4.89
5.40
6.36
12
3.69
4.11
4.50
4.92
5.85
6.75
15
3.36
3.75
4.11
4.44
5.25
6.00
20
3.00
3.36
3.69
3.96
4.59
5.25
5.94
6.75
26
2.82
3.09
3.42
3.69
4.26
4.80
5.46
6.00
30
2.70
2.94
3.21
3.51
4.02
4.59
5.16
5.79
35
2.58
2.88
3.09
3.39
3.90
4.38
4.92
5.52
6
5.28
6.00
6.75
8
4.50
5.10
5.70
6.24
10
4.11
4.56
5.10
5.61
6.60
12
3.78
4.20
4.65
5.10
6.00
15
3.45
3.81
4.20
4.56
5.40
6.15
20
3.09
3.48
3.78
4.14
4.74
5.46
6.09
26
2.85
3.15
3.45
3.75
4.35
4.92
5.55
6.15
30
2.79
3.03
3.33
3.63
4.14
4.68
5.34
5.85
35
2.70
2.94
3.21
3.51
3.99
4.50
5.10
5.64
APPROACH
5
6
7
8
10
12
14
16
APPROACH
5
6
7
8
10
12
14
16
6
5.49
6.15
6.90
8
4.65
5.31
5.88
6.54
10
4.20
4.62
5.16
5.70
6.75
12
3.84
4.32
4.74
5.16
6.15
15
3.54
3.96
4.32
4.71
5.49
6.36
20
3.21
3.57
3.90
4.26
4.89
5.61
6.36
26
2.94
3.24
3.57
3.81
4.41
5.04
5.70
6.36
30
2.85
3.18
3.48
3.75
4.29
4.86
5.49
6.09
35
2.73
3.00
3.30
3.60
4.08
4.65
5.16
5.79
6
5.55
6.33
8
4.74
5.40
6.00
6.60
10
4.26
4.74
5.28
5.79
6.90
12
3.96
4.44
4.89
5.40
6.30
15
3.60
3.99
4.38
4.77
5.64
6.45
20
3.20
3.63
3.93
4.29
5.01
5.70
6.45
26
3.03
3.36
3.69
3.96
4.56
5.25
5.85
6.60
30
2.94
3.21
3.54
3.81
4.35
5.04
5.64
6.21
35
2.85
3.09
3.42
3.63
4.20
4.74
5.34
5.94
REYMSA COOLING TOWERS, INC.
Maximum Reliability with Efficiency
REYMSA COOLING TOWERS, INC.
Durability & Minimum Maintenance
Section B: CAPACITY TABLES GPM
2.4 2.8 3.2 4.83.6 54.4 5.8 6.64 5.4 6.2MODEL SELECTION FACTORS
303115303102404103404105505103505105
606105606175707175707110
708175708110708115709175709110709115
808175808110808115809175809110809115
810110810115810120811110811115811120
812115812120812125714275714210
81627581621081621514144751414410
161647516164101616415
822210822215822220827210827215827220
162241016224151622420162741016274151627420
3639658092113
135161212233
228254288245276308
257285315281305344
315365399341377417
401437470422467
513570630848933
102811401260
648716792730869929
129614321584146017381858
42467593
107131
158187247271
266296336285322359
299333368327355401
368425466398439487
467509548492544
599665735989
1089
119913301470
756834925852
10121083
151216681850170320242166
485286
106122150
180214282310
304338384326368410
342380420374406458
420486532455502556
534582626562622
68476084011301244
137015201680
864954
105697311571237
172819082112194723142474
545997119137169
203241317349
342380432367414461
385428473421457515
473547599512565626
601655704632700
770855945
12711400
154117101890
97210741189109513021391
194421482378219026042782
6065
108133153188
225268353388
380423480408460513
428475525468508573
525608665568628695
668728783703778
855950
105014131555
171319002100
108011931321121714481547
216023862642243328963094
6672118146168206
248294388426
418465528448506564
470523578514558630
578668732625690765
734800861773855
9411045115515541711
188420902310
118813111454133815901701
237626222908267731803402
7278
129159183225
270321423465
456507576489552615
513570630561609687
630729798682753834
801873939843933
10261140126016951866
205522802520
129614311585146017361855
259228623170292034723710
7581
134166191234
281334441484
475528600509575641
534594656584634716
656759831710784869
834909978878972
10691188131317661944
214123752625
135014901651152118071933
270029803302304236143866
8188
145179206253
304361476523
513570648550621692
577641709631685773
709820898767847938
901982
1056948
1050
11541283141819072099
231225652835
145816091782164319522087
291632183564328539044174
8794
156192221272
326388511562
551613696591667743
620689761678736830
761881964824910
1008
9681055113510191127
12401378152320482255
248327553045
156617291915176420982241
313234583830352841964482
93101167205236291
349415546601
589655744632713794
663736814725787887
814942
1031881973
1077
10351128121310891205
13251473162821892410
265429453255
167418492046188622432395
334836984092377244864790
99107177219252309
371441582639
627697792672759846
705784866771837945
86610021097938
10351147
11011200129111591283
14111568173323312566
282631353465
178219672179200823852552
356439344358401547705104
HRFG SERIES SPECIFICATIONS
1. GENERAL
2. PERFORMANCE
3. CONSTRUCTION
4. FILL, DRIFT ELIMINATOR AND LOUVERS
5. HOT WATER DISTRIBUTION SYSTEM
6. FANS
7. MOTORS
8. MANUFACTURER
Furnish and install an induced draft, counter flow, factory assembled, All-Fiberglass Reinforced Polyester (FRP) casing and structure Cooling Tower(s) of ______ cells, as shown on plans. Tower shall be similar and equal in all respects to REYMSA HRFG model ______________.
The tower shall have the capacity to cool _______ GPM of water, from _______ °F Entering Water Temperature, to ______°F leaving water temperature, at a design entering air wet-bulb temperature of _______ °F the performance shall be certified by the Cooling Tower Institute (CTI) in accordance with CTI Certification Standard STD-201. Additionally, the Cooling Tower manufacturer shall guarantee the performance of each cell as installed according to plans.
The entire casing and structure shall be constructed of Fiberglass Reinforced Polyester (FRP). Only a high grade isophalic polyester resin with UV inhibitor shall be used in the manufacturing process. For One and Two Fan units, the entire body and basin shall be constructed in one-piece, seamless, watertight FRP. No side fasteners will be allowed at the sidewalls of the body or the basin. There shall not be any metal support or structure in direct contact with water. For the one and two Fan units, there shall be one or two independent fan cylinders with a motor support to be constructed completely of FRP, no metal motor support shall be allowed; to be mounted on top of the body structure held in place with stainless steel fasteners provided by the manufacturer, no gasket shall be required, and shall include a corrosion resistant protective mesh screen cover to prevent airborne objects into the fan. The Four Fan units shall consist of three sections; the body shall be constituted by two independent, seamless, watertight FRP pieces, held together with stainless steel fasteners on the sides, provided by the manufacturer. The basin shall be constituted by two independent, seamless, watertight FRP pieces, held together by side stainless steel fasteners provided by the manufacturer. Multi-piece walls or sheet metal wall sections will not be allowed. There shall not be any metal support or structure in direct contact with water. The fan cylinder structure shall have a motor support constructed completely of FRP. No metal supports shall be allowed. All three sections shall be held together by perimetral flanges with stainless steel fasteners provided by the manufacturer, no gasket shall be required. The entire One, Two or Four Fan tower shall be designed and constructed to withstand wind pressure of no less than 30 pounds-force per square foot (psf) on external surfaces. The top of the body shall be designed and constructed to withstand a live load of no less than 40 psf in addition to the concentrated loads of the fan or other equipment mounted thereon. The One, Two and Four Fan unit basin shall be equipped with cold water outlet, drain with mesh screen cover, overflow, water make-up, drain equalizer and purge fittings. All drain fittings 3" and smaller shall be NPT and larger than 3" shall be ANSI flange (FRP or PVC). A bottom sump drain shall be available for dry sump installation, if required.
Fill shall be cross corrugated film-type, thermoformed PVC, in sections not to exceed 1' x 1' x 6'. For hot water temperatures higher than 130°F, Aluminum or Polyestyrene fill may be used, as applicable. For Higher water temperatures, drift eliminators shall be thermoformed PVC, in sections not to exceed 1' x 1/2' x 6'. Drift losses shall not exceed 0.005% of the design circulating flow. Louvers shall be thermoformed PVC on all four sides of the tower(s).
The hot water shall enter the body through a single inlet per cell. All interior distribution piping shall be PVC, for industrial applications for higher water temperature, fiberglass or Stainless steel piping may be used as applicable. Water shall be evenly distributed over the fill media by a removable, interchangeable ABS (2 1/2") Spray Nozzles. Nozzles shall each contain internal, interchangeable flow devices to provide an optimal spray pattern with 2 to 10 psig pressure differential.
Fan(s) shall be propeller type, fan blades shall be constructed with Fiberglass Reinforced Polyamide, spark and corrosive resistant with adjustable pitch suitable for high temperature operation up to 250°F. Hub(s) shall be aluminum alloy castings. Fan(s) shall be directly driven. Towers utilizing gear reducers or belt driven units will not be accepted.
There shall be single speed, Totally Enclosed Fan Cooled (TEFC), phase, Hertz, volts. Electric Motor(s), NEMA rated for continued operation at a 1.15 service factor. Each motor shall be horsepower for a total Horsepower at RPM.
The Cooling Tower shall be manufactured by REYMSA COOLING TOWERS, INC
REYMSA COOLING TOWERS, INC.
Toll Free Number 1-866-445-2043
1641 World Trade Center, Millenium Industrial Park Laredo, Tx. 78045Phone (210) 579-4837 Fax (210) 745-1513