16
Cooling towers

Cooling Towers

Embed Size (px)

Citation preview

Cooling towers

AbstractThe objective of this experiment was to explore various operating conditions of a Hilton Bench Top Cooling Tower H892 and to analyse its performance associated at each condition. the influence of varying cooling load, water flow rate and air flow rate on the performance was investigated. The experiment involved keeping two of the three variables constant while varying the third during each run by isolating the influence of each mvariable in operation. Data , such as the water temperature and air pschrometric properties at various points, was collected and manipulated into parameters useful in analyzing the operation of the cooling tower. The most important parameter is the efficiency. The steady flow equations ( energy and mass balances) were employed inorder to investigate the forms of water lost from the system and to provide an insight on the amount of energy transferred between phases under different conditions. It was determined that the maximum efficiency was achieved at-----------------------------------------------------------------------at a cooling load of ----------------for the case where ----------is kept constant and the----------------is varied. It was therefore concluded that optimum cooling is achieved when--------------------

Table of contents Abstract Table of contents 1. Introduction

2. Theory Cooling tower fundamentals Cooling tower terminology Mass balance analysis Energy balance analysis Psychrometry 3. Experimental Apparatus Cooling tower preparation Experimental procedure Precautions

4. Results Approach temperature Temperature range Efficiency Mass balance Energy balance 5. Discussion 6. Conclusion 7. References 8. Appendices

IntroductionA cooling tower is a rejection device, which emits waste heat to the atmosphere through the cooling of a water stream to a lower temperature. The type of heat rejection in a cooling tower is termed evaporative in that it allows a small portion of water to be cooled to evaporate into moving air stream to provide significant cooling to the rest of that water stream. Cooling occurs as a result of direct heat transfer by conduction and convenction between two phases. The heat from the water stream is transferred to the air stream raising the air temperature and its relative humidity and this is discharged to the atmosphere. Humidification processes are frequently carried out to control the cooling and the recovery of water by contacting it with low humidity air. It is therefore common practice for chemical engineers to intergrate cooling towers into plant design to remove all unwanted heat from process streams. the cooled water produced by the cooling tower may then be distributed throughout the whole plant for various cooling purposes using heat exchangers. The conservation of water, for both economic and environmental reasons is thus promoted. the Hilton Bench tower uses the counter- current evaporating method ( also known as wet cooling method). This method is widely used when cooling heated water in industries. When the heated water comes into contactwith air, a large heat of water allows a high heat transfer from the water to the air with little water evaporating into the air , hence the water is conserved. An advantage of this is that heated water can be cooled down to the inlet wet-bulb temperature of the air. The purpose of conducting the experiment was to investigate the influence of varying the cooling load, water flow rate and air flow rate on the performance of the cooling tower and to determine all end state properties of the air and water from charts and tables. Experiments were performed at different cooling loads of 0.5kW, 1.0kW and 1.5kW at constant air and water flow rates. Also the influence of varying the flow rate on the performance of the tower was analysed by perfoming experiments at constant cooling loads and at orifice differential of-------. The ssame approach was taken when analyzing the tower performance at differe air flow rates, constant water flow rate of 40g/s and cooling load.

TheoryCooling towers fall into two main sub-divisions: natural draft and mechanical draft. ( coulson et.al . (1999)) Mechanical draft cooling towers are much more widely used and these towers utilize large fans to force air through circulated water. The water falls downward over fill surfaces which help increase the contact time between the water and the air. This helps maximize heat transfer between the two.conversely, the natural draught cooling tower uses buoyancy through a tall chimney. Warm , moist air naturallyrises due to the density difference to that of dry, cooler outside air.warm moist air is less dense than drier air at the same pressure.the moist air buoyancy produces a current of air through the tower, thus the natural draught cooling tower does not require the aid of any mechanical devices to induce tha air flow. One of the important mechanical draught cooling towers is the forced draught cooling tower. This tower follows a simple operation, atmospheric is forced vertically through the tower through the use of a fan, while the water flows down through gravity.this produces countercurrent flow in the cooling tower. Included in the coling tower structure is packing which serves the purpose of increasing the surface area of contact between the air and water allowing more efficient cooling. The mechanicaldrught cooling tower produces greater coolingthan the natural draught cooling tower and occupies less space. Mechanical draught cooling towers are generally used for achiving higher cooling or for capacity considerations, however they are utilized due to economic considerations( such as costs) when compared to natural draught cooling tower.

temperature range /Cooling Range This is the difference between the temperature of the water entering and that leaving the cooling tower.

T

range

= T water-inlet

T water- outlet

Changes in water and air flow-rates adveserly affect the temperature range. According to Hill and Stanford, 1967,by increasing the air flow rate in the cooling tower, an increase in the temperature range is expected since a higher flow-rate of air increases the contact time of water to less himidfied air which increases the mass transfer driving force. Increasing the water flowrate has the inverse effect, lowering the temperature range and evaporative cooling by increasing the exposure of water to a more humidified air. Therefore it can be seen that as temperature range increases so does the performance of the cooling tower.

ApproachThe difference between the temperature of the cold water leaving the tower and the wet-bulb temperature of the air is known as the approach.

T

approach

= T water- outlet

T wet bulb air

The approach fixes the operating temperature of the tower and is a most important parameter in determining both tower size and cost. The smaller the approach temperature, the higher the performance of the cooling tower under the operating conditions. For optimum efficiency of the cooling tower, the approach temperature would ideally be zero since it is not possible for the air to coolthe water any further than the wet bulb temperatureof the incoming air. However, in practice it is impossible to achieve a zero approach temperature as inorder to achieve this, the tower should be infinitelt tall. Cooling towers are thus not designed to operate with an approach temperature below 2.80C and it is generally accepted that an approach temperature of 5.50Cis attainable. ( Mccabe et al, 2005).

Wet and dry bulb temperatureWet-Bulb Temperature - The lowest temperature that water theoretically can reach by evaporation. Wet-Bulb Temperature is an extremely important parameter in tower selection and design and should be measured by a psychrometer.

Temperature can be measured with two thermometers simultaneously - one with a wet bulb and one with a dry bulb- in order to determine the relative humidity of the surrounding air. This method was used historically by meteorologists, but we will use it extensively in this experiment to measure the water concentration in the air. If the air is saturated with water vapor (100% relative humidity), then the wet bulb and dry bulb temperatures be equal. If the relative humidity is less than 100%, then the wet bulb temperature will be lower due to evaporation of water from the surrounding wrap. To obtain an accurate wet bulb temperature, it is important to make sure that the wet bulb reaches steady state under the conditions of air flow and relative humidity. The relative humidity is determined by looking at wet-bulb and dry-bulb temperatures on a psycrometric chart.

Water loss due to driftThe water entrained in the air flow as fine droplets and discharged to the atmosphere is defined as drift ( Mckelvey and Brooke, 1959). Drift loss does not include water lost by evaporation.

m waterdrift = m watermakeup

m waterevap

thus, the mass of water evaporated can be determined by taking the difference between the mass flow rate of water in the air entering the cooling tower and the mass flowrate of water in the air leaving the tower. Using psychometry the following equation is obtained

mwater

evap

= mdry air (Y1air

outlet

Y1air

inlet)

the psychometric chart is used to determine the absolute humidity and the specific volume at the respective dry bulb and wet bulb temperatures of the inlet and outlet air.

Heat Load The amount of heat to be removed from the circulating water through the tower. Heat load is equal to water circulation rate (gpm) times the cooling range times 500 and is expressed in BTU/hr. Heat load is also an important parameter in determining tower size and cost.

Pumping HeadThe pressure required to pump the water from the tower basin, through the entire system and return to the top of the tower.

Make-UpThe amount of water required to replace normal losses caused by bleedoff, drift, and evaporation. It is the amount of water required to compensate for the loss of water due to evaporation and losses due to drift during the normal operation of the cooling tower. This can be further expressed by the equation given below

m make up = m evapmmake up

m drift

is the mass flow rate of make-up water (kg/s)

m m

evap drift

is the mass flow rate of evaporated water (kg/s) is the mass flow rate of water lost due to drift (kg/s)

Bleed Off (Blowdown)The circulating water in the tower which is discharged to waste to help keep the dissolved solids concentrating in the water below a maximum allowable limit. As a result of evaporation, dissolved solids concentration will continually increase unless reduced by bleed off.

Efficiency of the towerThis is defined as the ratio betweenthe range and the ideal range(i.e the difference between the cooling water inlet temperature and the ambient wet bulb temperature). The cooling tower efficiency can be expressed as

=where is cooling tower efficiency Ti is the inlet temperature of water to the tower (oC , oF ) To is the outlet temperature of water from the tower (oC , oF ) Twb is the wet bulb temperature of air (oC , oF )

Energy Balance on the Cooling TowerHeat transfer is occurring primarily in the load tank, where the water is brought up to the feed temperature. A small amount of heat is also lost to the surroundings by radiation/conduction/convection. Work is done on the water by the pump. Energy is transferred along with mass loss, because dry air enters, and humid air leaves.

Q = the rate of heating added to the system

P = rate of work done by the pump on the waterHexit = rate of enthalpy loss in exiting vapor Hentry = rate of enthalpy gain due to entering air and entering water from make-up tank Now let's set up the energy equation for the portion of the process illustrated at the right:

Q + P = H exit Hentrydefining some mass flow rates and enthalpies:

at steady state

[work done on system] = [energy loss due to enthalpy change]

me the rate of (liquid) water addition from the "make-up" tank ma the mass flow rate of air ms the mass flow rate of steamhda the specific enthalpy of (dry) air hs the specific enthalpy of steamsubscript A -------- entering the chamber subscript B -------- leaving the chamber The energy balance equation is now written:

Q + P = (mahda + mshs)B (mahda + mshs)A mE hEsteam/air leaving steam/air entering water entering from make-up tank

Mass Balance on the Cooling TowerConservation of mass gives us the following simple equations at steady state: Air in = air out

( ma )A = ( ma )B

Water in = water out

(ms) A + mE = (ms )BThis equation simply says that the mass flow rate of water entering the system (because the entering air is humid) plus the mass flow rate of water entering from the make-up tank equals the mass flow rate of water leaving the system as vapor/steam. The ratio of water vapor to air can be determined if the humidity is known.