20

cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Embed Size (px)

Citation preview

Page 1: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature
Page 2: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature
Page 3: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

cooling tower is-: A heat rejection device, which extracts waste heat to

the atmosphere through the cooling of a water

stream to a lower temperature .

Heat rejection device(cooling tower)

Hot water Cold water

Moist, warm air out

Dry air in

Page 4: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Remove heat from the water discharged from the

condenser so that the water can be discharged to the river

or recirculated and reused .

Page 5: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Cross flow

Cross flow is a design in which the air flow is directed perpendicular to the water flow (see diagram below). Air flow enters one or more vertical faces of the cooling tower to meet the fill material. Water flows (perpendicular to the air) through the fill by gravity .

Page 6: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Counter flow

In a counter flow design the air flow is directly opposite of the water flow (see diagram below). Air flow first enters an open area beneath the fill media and is then drawn up vertically. The water is sprayed through pressurized nozzles and flows downward through the fill, opposite to the air flow.

Page 7: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

3-Induced draft cooling tower.

1-Mechanical cooling tower.

2-natural draft cooling tower.

4-Forced draft cooling tower.

Page 8: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

basic components:

1-Frame and casing: Most towers have structural frames that support the exterior enclosures )casings(, motors, fans, and other components. With some smaller designs, such as some glass fiber units, the casing may essentially be

the frame .

Page 9: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Fill: Most towers employ fills )made of

plastic or wood( to facilitate heat transfer by maximizing water and air contact. Fill can either be

splash or film type .With splash fill, water falls over successive layers of horizontal splash bars, continuously breaking into smaller droplets, while also wetting the fill surface. Plastic splash fill promotes better heat

transfer than the wood splash fill .Film fill consists of thin, closely spaced plastic surfaces over which the water spreads, forming a thin film in contact with the air. These surfaces may be flat, corrugated, honeycombed, or other patterns. The film type of fill is the more efficient and provides same heat transfer in a smaller volume than

the splash fill .

Page 10: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Nozzles:

These provide the water sprays to wet the fill. Uniform water distribution at the top of the fill is essential to achieve proper wetting of the entire fill surface. Nozzles can either be fixed in place and have either round or square spray patterns or can be part of a rotating assembly as found in some circular cross-section

towers .

Page 11: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

FAN:

The fan is directly driven, axial flow type fans are specially designed to ensure AEROFOIL Section throughout the blade length, this ensure energy saving and generates maximum air flow at minimum pitch angle of blades in the cooling towers. Fans are electronically balanced made of light weight Aluminum casting. Fans are durable, corrosion resistant and low

noise delivering high flow .

Page 12: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Motor and gear reducer system

FAN MOTOR:

The motor is totally weatherproof in IP:55 construction, suitable for heated and humid atmosphere. Special low RPM totally enclosed motor of vertical, flange type with enlarged threaded shaft and sealed top is supplied with

the cooling tower .

Page 13: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Drift eliminators :These capture water droplets entrapped in the air stream that otherwise would be lost to the

atmosphere .

Louvers: Generally, cross-flow towers

have inlet louvers. The purpose of louvers is to equalize air flow into the fill and retain the water within the tower. Many counter flow tower designs do not require

louvers .

Cold water basin: The cold water basin, located at

or near the bottom of the tower, receives the cooled water that flows down through the tower and fill. The basin usually has a sump or low point for the cold water discharge connection. In many tower designs, the cold water basin is beneath the entire

fill .

Page 14: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Pumps of cooling tower:

Cooling Tower Spray Pumps Loop Pumps

Page 15: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Natural draft, which utilizes buoyancy via a tall chimney. Warm, moist air naturally rises due to the density differential to the dry, cooler outside air. Warm moist air is less dense than drier air at the same temperature and pressure. This moist air buoyancy produces a current of

air through the tower . This photo shows a single

natural draft cooling tower as used at a European plant. Natural draft towers are typically about 400 ft (120 m) high, depending on the differential pressure between the cold outside air and the hot humid air on the inside of the tower as the

driving force. No fans are used .

The green flow paths show how the water is taken from a river (yellow) to an intake supply basin (green) that the Circ Water Pumps take suction from. The water is then pumped to the Condenser where the water is

heated .The water is then sent to an exit distribution basin where the water then can be returned to the river and/or pumped by the Cooling Tower Pumps to the Cooling Towers then the water returned to the intake supply basin where the water can be reused.

Page 16: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature
Page 17: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

Cooling towers with malfunctions can freeze during very

cold weather. Typically, freezing starts at the corners of a

cooling tower with a reduced or absent heat load .

Increased freezing conditions can create growing

volumes of ice, resulting in increased structural loads .

During the winter, some sites continuously operate

cooling towers with 40 °F water leaving the tower. Basin

heaters, tower drain down, and other freeze protection

methods are often employed in cold climates.

Page 18: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

A mechanical draft tower with a fan at the discharge

which pulls air through tower. The fan induces hot moist

air out the discharge. This produces low entering and

high exiting air velocities, reducing the possibility of

recirculation in which discharged air flows back into the

air intake. This fan/fill arrangement is also known as draw-through .

Page 19: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

A mechanical draft tower with a blower type fan at the intake. The fan forces air into the tower, creating high entering and low exiting air velocities. The low exiting velocity is much more susceptible to recirculation. With the fan on the air intake, the fan is more susceptible to complications due to freezing conditions. Another disadvantage is that a forced draft design typically requires more motor horsepower than an equivalent induced draft design. The forced draft benefit is its ability to work with high static pressure. They can be installed in more confined spaces and even in some indoor situations. This fan/fill geometry

is also known as blow-through.

Page 20: cooling tower is :- A heat rejection device, which extracts waste heat to the atmosphere through the cooling of a water stream to a lower temperature

 

SÉRIE 1800(90 a 1.800m3/h) 

SÉRIE 6000 (200 a 1000m3/h)