Upload
apsara-wimalasena
View
162
Download
13
Tags:
Embed Size (px)
Citation preview
PRESENT BY GROUP 5
Cooling TowerIntroductioncooling tower is a heat rejection device
When cooling Towers are used, plant efficiency usually drops
Cooling towers are characterized according to air and water interactOpen cooling towers or direct cooling towersClosed cooling towers or indirect cooling towers
Cooling towers are also characterized by the means by which air is moved
natural draftmechanical draft
Counter flow and cross flow cooling towers
•Mechanical draft tower can be divided into two type Cross flow design cooling towers Counter flow design cooling towers
Many of industries use cooling towers they are
Petroleum refineriesPetrochemical plantNatural gas processing plantsfood processing plantssemi-conductor plantsPower plants ,etc……….
Cooling Towers are more cost effective and energy efficient than most other alternatives
Limitations of cooling tower
Cooling towers can not cool the water to very low temperature. It can cool close to the surrounding air temperature
If water is needed to be cooler, a chiller may be better suited to your cooling needs than a cooling tower.
Amcot cooling tower
RBFM976 marly cooling tower
Natural draft cooling tower
Motivair open Draft Cooling Tower
Motivair open draft cooling tower provides evaporative cooling at the lowest cost.
Delta Pioneer Forced Draft Cooling Tower-150 Tons
Fiberglass Cooling Towers deliver long life with minimum maintenance.
Fiberglass Cooling Towers
Tank
Pump Pump
Cooling Tower
Tray
Overhead Tank
Heat Exchanger
Heat in
Heat out
Cooling Tower Operation
Tower Type Induced Draught
Method of water Distribution
Rotating header, in which a series of holes is drilled to distribute the water over the whole surface area of the fill pack
Fill Pack High-quality, rigid vinyl sheet, vacuum formed in a patented, cross-flute configuration. The formed sheets are then assembled into pads and built into the tower, providing a fill pack of great strength and exceptional efficiency as a heat transfer medium
Start up Instructions Check that all electrical and piping connections are tight
and correct.
Remove any dirt and rubbish which may have collected in the catchment tray and sump.
Check lubrication points.
Make certain that sump strainer is in position and is not fouled.
Check fan for correct rotation and air flow.
Adjust Ball-Valve to correct water level in sump.
Filling Material
High-quality, rigid vinyl sheet, vacuum formed in a patented, cross-flute configuration.
The formed sheets are then assembled into pads and built into the tower, providing a fill pack of great strength and exceptional efficiency as a heat transfer medium
Filling Material
Types of Pumps Used
Problems in Cooling Tower
Pollutants in Cooling Tower
Water that is applied in cooling towers, even when this concerns tap water, often contains salts (such as chlorine, sulphates and carbonates), dissolved gases (such as oxygen and carbon dioxide) and metal ions (such as iron and manganese ions). The presence of these pollutants can cause a series of problems.
PROBLEMS
MicroorganismsCorrosion HardnessTDS
MicroorganismsBacteria and other pathogenic mircroorganisms are
present everywhere throughout the environment. They can often be found in cooling tower water.
When cooling towers contain an open recirculation system, microorganisms can spread from air to water
When a significant microbial growth takes place, a slime layer is formed. This contains both organic and inorganic matter. This is called Bio Film.
As a result of bio film formation, microorganisms can attach themselves to surface layers.
This causes microorganisms to no longer be flushed away by cooling tower water.
Corrosion
Corrosion can occur due to,
Dissolved Oxygen Formation of Bio Film
Hardness
Mineral deposits are formed by ionic reactions resulting in the formation of an insoluble precipitate. This precipitate is known as scale.
These deposits are difficult to clean. As these deposits build up, they reduce the efficiency of heat transfer.
Total Dissolved Solids
Total Dissolved Solids (TDS) is a severe problem in cooling water.
It causes Diposites.
Calculation of flow rate
Feed water tank
174
179.4
14.1614.1691
371
Tank in the tray
Calculate the flow rates to calculate the windage loss and energy loss in the cooling tower.
Flow rate of the feed water tank
= 59.49 l/s
Flow rate of the water through cooling tower
= 58.68 l/s
M
W
EC
M- Make-up water in l/s
W- Windage loss of water in l/s
C- Circulating water in l/s
E- Evaporated water in l/s
m1- M*10-3*1000 kg/s
m2- C*10-3*1000 kg/s
t1- Temperature of the feed water tank
t2- Temperature of the circulating water
c- Specific heat capacity
Applying mass balance for cooling tower
M=W+C+E
Assuming that there is no evaporation loss
W= 59.49 l/s - 58.68 l/s
= 0.81 l/s
Applying energy balance
m1ct1=m2ct2+Q
Q= 541296 J/s
Measure the pH
In a cooling tower there can be fouling, corrosion
and scale. pH is one of the key factor which
affecting those problems.
pH of the feed water tank =7.94
pH of the circulating water =7.39
•A less amount of water compared to other industrial applications is used for the cooling tower applications.
•This water contains calcium, magnesium and iron bicarbonates and sulfates
•Water which contains calcium and magnesium ions is called “hard” water.
•If the water contains bicarbonates, the hardness is “temporary”.
•If it contains sulfates hardness is “permanent”.
Hardness
•The term temporary is used with the bicarbonates because calcium and magnesium carbonates precipitate when water with temporary hardness is boiled.
•the removal of temporary hardness by boiling or by precipitation with soaps is not an economical solution to the problem.
•Permanent hardness cannot be removed only by boiling the water, although the solubility of calcium sulfate decreases markedly with increasing temperature
•Hardness of water can be measured in several ways
•easiest and the most accurate method is the titration with a solution of EDTA using Eriochrome Black T (EBT) as the indicator
•The end point is reached when the color changes from red to blue.
•EDTA is an excellent complexing agent.
• EDTA is assigned the formula H4Y;
• The disodium salt (which we use in this titration) is• therefore Na2H2Y and affords the complex forming• ion H2Y2- in an aqueous solution;
• It reacts with all metals in a 1:1 ratio.
M2+ + H2Y2- MY2- + 2H+
The reaction with Ca+ and Mg2+ may be written as:
It is apparent from this equation that the dissociation of the complex will be governed by the pH of the solution.
-O2C CH2
N+ CH2 CH2+N
CH2 CO2-
CH2-O2C
H
CH2CO2
-
H
The structure of H2Y2- ion is given below:
CALCULATIONS (for water in the Sump)
Amount of the water sample taken from the Sump= 50cm3Buffer solution (aq. NH3/NH4Cl) (pH 10) = 2cm3Eriochrome Black T/KNO3 indicator = 30-40 mgStandard EDTA Solution(0.01M) = 2ml
Concentration of Ca2+ & Mg2+ (x) = Molarity of EDTA* V Volume of H2O Sample
= 0.01*2 50
= 0.0004 M
Hardness of water in ppm of CaCO3 = X*molar wt. of CaCO3*1000mg 1mg
= 40
CALCULATIONS (for the tray water)
Amount of the water sample taken from the tray= 50cm3Buffer solution (aq. NH3/NH4Cl) (pH 10) = 2cm3Eriochrome Black T/KNO3 indicator = 30-40 mgStandard EDTA Solution(0.01M) = 1.7ml
Concentration of Ca2+ & Mg2+ (x) = 0.01*1.7 50=0.00034M
Hardness of water in ppm of CaCO3 = 34
TDS
Total amount of all inorganic and organic substances – including minerals, salts, metals, cations or anions
Estimated by measuring the specific conductance of the water
Can use TDS meter
How to measure?
Porcelain dish = W1Porcelain dish after evaporation and cooled = W2Weight of the filter paper after washed, dried and cooled
= W3Weight of the filter paper after filtered cooling tower
water, dried and cooled = W4After removing TSS weight of the filter paper = W5 Flask = M1Flask after evaporation and cooled = M2
Readings we got in the practical
Tank Tray
W1 92.211g 89.112g
W2 92.267g 89.157g
W3 2.123g 2.523g
W4 2.155g 2.546g
W5 2.144g 2.534 g
M1 95.864g 97.336g
M2 95.903g 97.378g
How To Calculate?
TS = W2-W1 TS of Tank = (92.267 - 92.211)g = 0.0560.056 gg TS of Tray = (89.157 - 89.112)g = 0.045 g0.045 g
TSS = W4-W3 TSS of Tank = (2.155 – 2.123)g = 0.032g0.032g TSS of Tray = (2.546 – 2.523)g = 0.023g0.023g
How to Calculate?
VSS = W4 – W5 VSS of Tank = (2.155 – 2.144)g = 0.011g0.011g VSS of Tray = (2.546 – 2.534)g = 0.012g0.012g
TDS = TS – TSS TDS of Tank = (0.056 – 0.032)g = 0.024g0.024g TDS of Tray = (0.045 – 0.023)g = 0.022g0.022g
Another way to Calculate TDS
TDS = M2- M1
TDS of Tank = (95.903 - 95.864)g
= 0.039g
TDS of Tray = (97.378 - 97.336)g
= 0.042g
RESULTS
TDS of Tank = (24mg/50ml)*1000ml = 480mg/l480mg/l
TDS of Tray = (22mg/50ml)*1000ml = 440mg/l440mg/l
TDS of Tank = (39mg/100ml)*1000ml = 390mg/l390mg/l
TDS of Tray = (42mg/100ml)*1000ml = 420mg/l420mg/l
METHODS
Find amount of nutrient in the water (especially nitrogen and phosphorous)
Do a microbial count
APPRATUSFour agar plates
Two 1ml pipettes
10ml pipette
Test tubes
PROCEDURE
PREPARING AGAR PLATESFour Petri dishes were taken and kept them in the
oven 160°C for three hours 1.4g of nutrient and 1g of agar were put into a flask.50ml of distilled water is added sterilized in the autoclave at 121°C for 20miniutes.Agar nutrient medium was poured into Petri dishes by
keeping them in the laminar cabinet near a Bunsen flame.
spreaded all over the dishes and kept them in the cabinet to set.
DILUTING THE SAMPLESTen sterilized test tubes were taken and
labeled9ml of distilled water was put into all test
tubes.1ml of water which is taken from tank was
added to the first test tube and mixed well.1ml from that test tube was taken and added
to the second. As this manner add 1ml up to tenth one.
Same procedure repeated for other sample
COUNT MICRO-ORGANISMS
Fifth and tenth test tubes from each sample (tank and tray) were taken as samples.
1ml of each sample was taken and pore them into agar plates.
spreaded all over the nutrient and kept for 24 hours.
After 24 hours, the plates were observed.
RESULTS
unable to count the number of micro-organisms
thousands of small yellow dots
CONCLUSION
Our diluting factor is 10 -11.
there is a strong microbial contamination
want some treatment immediately.
Summery of the results
Water in the tank pH 7.94
Hardness 40 ppm
TDS 480 mg/l
Microorganisms Strong contamination
pH 7.39
Hardness 34 ppm
TDS 440 mg/l
Microorganisms Strong contamination
Water in the tray
Analyzing…….
The allowed pH range for the cooling tower is 6 – 8.5
Water samples are alkaline.
Congenial to the cooling tower.
Analyzing…….
Obtained hardness values are 34 and 40 ppm
Maximum standard value is 200ppm
No action is essential.
Analyzing…….
TDS values are 480 mg/l and 440 mg/l for the sump and the tray.
It is not a big issue for THIS system.
Analyzing…….
Large amount of microorganisms.
Risk of contaminating by ‘Legionella’.
Biocides have to be used.
Adding Biocides
•to prevent growths of microorganisms
• prevent the growth of Legionella
What we can add?
Various Chemicals
•AWC D-115I: •Isothiazoline based biocide for control of bacteria, algae and fungi.
•AWC D-220: •Quaternary amine based biocide for control of algal, bacterial and fungal slimes.
can use, Cl2, ClO2, Br2, O3 as well
For this system
Among them Cl2 can be used
But must check for suitability
Maintenance
Once a 6 months
Once a month
•Inspect the suction filter and clean
• The header should be checked
thoroughly inspected for corrosion
This is recommended by the manufacturer
But not implemented
Thank You