Upload
sunilkumarece
View
271
Download
5
Embed Size (px)
Citation preview
INTRODUCTION
Faults in DC systems are caused by
the malfunction of the equipment and controllers
The failure of insulation caused
by external sources such as
lightning ,pollution etc…
In a converter station
Valves are the most critical
equipment needed to
be protected
CONVERTER FAULTSTypes of Converter Faults
Faults due to malfunctions of valves and controllers
Arc backs
Arc through
Misfire
Quenching or Current Extinction
Short Circuits in converter station
Commutation Failure
ARC BACKSIn this phenomena
the valve losses its
capability to block in the
reverse direction
Hence conduction
takes place in reverse
direction also
This is non-self clearing fault
When this fault is detected we need to block the converter
valves and open the
backup AC breaker
This can be eliminated by using a bypass valve placed
across converter
bridge on the valve sideThe bypass
valve has higher current
rating than ordinary valves
ARC THROUGHIt is the failure to block a valve during a scheduled non conduction
period
A malfunction in the gate pulse generator can fire a valve which is actually not supposed to conduct, but is forward biased
This malfunction is mainly because of failure of a) Negative grid pulse b) early occurrence of positive grid pulse
This fault mainly takes place at inverter station
MISFIRE
This takes place
when the required
gate pulse is missing and the
incoming valve fails to ignite
This can occur in
both rectifier
and inverter stations,
but effects
are more in
inverter
Effects are
commutation
failure and arc through. This is a
self clearing
fault
CURRENT EXTINCTION
This takes place when the current through a valve reaches a value
less than the holding current
This fault may cause
overvoltage's to take place in the
valve
COMMUTATION FAILURE It is nothing but the failure of the completion of
commutation before the reversal of commutating voltage takes place.
The minimum value of extinction angle is defined by
Ƴ=180-α-µ The overlap angle is a function of the commutation
voltage and the DC current. The reduction in voltage or increase in current or
both can result in an increase in the overlap angle and reduction of Ƴ below Ƴmin.
This gives rise to commutation failure.
Consider the circuit shown above. Assuming initially valves 1 and 2 are conducting. Now because of increased DC current or decreased
AC voltage or any case valve 1 fails to extinguish. Therefore valve1 carries full link current and the
current in valve 3 becomes zero. Hence valve 3 extinguishes and valve 1 continues
its conduction .
Next when valve 4 fires the short circuit of the bridge takes place as valves in the same arm conducts.
This causes the voltage across valve 5 to be negative hence it does not conducts.
Valve 4 gets extinguished and valve 6 is fired next.
Hence the normal operation is retained back.
Therefore it can be said that single commutation failure is self clearing.
The effects of single commutation failure are, There is no AC current for the period in which the two
valves in an arm are left conducting. The bridge voltage remains zero for a period exceeding
1/3 of a cycle, during which the DC current tends to increase.
Double commutation failure can also takes place in a converter station.
A commutation failure in a bridge can cause several sequence commutation failures in the series connected bridges.
Hence the initial rate of rise of current has to be sufficiently limited by connecting the smoothing reactor in the circuit.
SHORT CIRCUIT IN A BRIDGE
This fault has very low probability of occurrence.
As the valves are kept in a valve hall with air conditioning.
They may sometime occur because of flashover in bushings.
This fault mostly occurs in rectifiers.
PROTECTION AGAINST OVER CURRENTS
It provides basic protection against faults in a converter
It compares
the rectified
current on the valve
side of converter
transformer to DC
current on line side
smoothing reactor
This is used as backup. The
level of overcurrent
required to trip must be set higher than
VGP to avoid tripping
This is mainly used to detect
the ground faults, such as neutral faults.
The faults producing overcurrents are classified into 3 categories: The first one being line faults. They occur
frequently and can be controlled by controlling the current.
The second being the internal faults. They cause high overcurrents. These are infrequent.
The third fault may be commutation failure at inverters. They occur quite frequently.
PROTECTION AGAINST OVER VOLTAGES
The sources of over voltages in converter station are:
Switching operations
Lightning strokes
Sudden load rejection
Resonance between filter and system when suppressing lower order harmonics.
Symmetrical faults in AC yard
Errors in voltage control
Converter faults
SWITCHING OPERATIONS
These over voltages are of short duration.
Switching surges are on account of circuit breaker operation while switching inductive and capacitive loads.
Protection schemes:
Using surge absorbers with circuit breakers.
Using SF6 breakers.
LIGHTNING STROKES
The primary cause of this over voltage is lightning strikes.
These occur for a very short duration but causes more damage to the system.
Protection schemes:
Using surge arresters and spark gaps.
Using overhead ground wire.
With the help of neutral grounding.
OTHER FAULTS
Sudden load rejection,resonance,symmetrical faults in AC yard and other causes temporary over voltages in the system.
This occurs at power frequency and lasts for a few seconds.
Protection schemes:
Using surge over voltage relays and circuit breakers.
Using fast acting static VAR sources.
Using On Load Tap Changers.
SURGE ARRESTERS
It is a device connected between a conductor and ground, to protect the equipments against high voltage surges.
It is also known as lightning arrestors.
It diverts the lightning or switching surges from the equipment towards the ground.
Under normal operating voltage, the impedance offered by a surge arrester is very high.
As the current always chooses the low resistance path equipment can perform in normal operation.
SURGE ARRESTERS CONTD…
When an over voltage occurs it causes the drop in the impedance of surge arrester.
Thus the flow now will be through the surge arrester rather than the main path.
Two types of arresters are there: Gapless arresters Zinc oxide arresters
Zinc oxide arrester is widely used as they have high energy absorbing capability.
SMOOTHING REACTORS
It is a high inductance coil connected in series with the converter to reduce the ripple current on the DC side of the system.
Basically the DC current from the rectifier has harmonic components called ripple.
As SR is in series with rectifier whole load current flows through it.
Then their magnitude is reduced and current becomes smoother.
CORONA ON DC LINES
The phenomena of hissing sound, violet glow accompanied with the production of ozone gas due to ionization of air surrounding the conductor, when voltage gradient exceed a particular value is called corona.
In DC transmission system, due to the discharge a current pulse is generated resulting in increase in power loss.
The effects of corona are: Radio Interference Audible Noise Space charge field
RADIO INTERFERENCE It is also known as radio influence.
It occurs in the band region of 0.5 to 1.6Mhz.
In HVDC lines, RI effect is more in positive conductor rather than in negative conductor.
It is expressed in millivolts per meter.
Mathematically it is expressed asRI=25+10logn+10logr+1.5(g-go)
In negative conductors the value of radio interference is lower by 20dB.
AUDIBLE NOISE The corona discharges from the conductor produce
compressions and rarefactions that are propagated through the medium as acoustical energy.
The portion of the acoustical energy spectrum that lies within the sonic range is perceived as audible noise.The sound level is expressed in decibels'.
It is defined as dB=20log(P/Pr)
where P= measured sound pressurePr= reference pressure level
The positive polarity conductor is the primary source of AN.