Upload
others
View
23
Download
1
Embed Size (px)
Citation preview
Controller with internal GSM/GSM-R GPRS modem MCL 5.10 R
User Manual Version 1.0
UAB NAVITUS LT, Lithuania 2018
2
This user manual serves as a description of MCL 5.10 controller of automated reading of electricity metering units produced by UAB NAVITUS LT ("the Manufacturer"). Please read this document before starting the installation and operation of the controller. The manufacturer provides no warranties to the controllers if they are damaged as a result of failure to observe the requirements provided in this manual or technical certificate of the controller or due to the breach of occupational safety requirements. The manufacturer reserves the right to change or modify the information provided in this document without any advance notice. It is prohibited to multiply, copy, handover or publish this document in full or in part without having a written consent of UAB NAVITUS LT.
Revision history
Document version Date Modifications, comments
1.0 05/01/2016 First revision
3
1.1. Content
1.2. NOTATIONS AND ACRONYMS ................................................................................................. 4
1.3. SAFETY INSTRUCTIONS ........................................................................................................... 5
2. FUNCTIONALITY AND INSTALLATION ......................................................................................... 6
2.1. GENERAL INFORMATION ......................................................................................................... 6
2.2. SUPPORTED COMMUNICATION PROTOCOLS ....................................................................... 6
2.3. METHODS OF COMMUNICATION WITH CONTROLLER......................................................... 6
3. THE MAIN MODULES OF CONTROLLER MCL 5.10 ..................................................................... 7
4. TECHNICAL SPECIFICATIONS ...................................................................................................... 8
4.1 DESCRIPTION OF INDICATORS ..................................................................................................... 8
5. INTERFACE CONTACT TERMINALS ............................................................................................. 9
5.1. CONTROLLER INSTALLATION MANUAL ..............................................................................10
SIM card insertion ...............................................................................................................................11
Place of installation .............................................................................................................................11
Connection of antenna ........................................................................................................................11
Connection of controller power supply ...............................................................................................11
5.2. INTERFACES FOR CONNECTION OF CONFIGURATION OF METERING UNITS ...............12
5.2.1. CONNECTION OF METERING UNITS WITH RS485 INTERFACE .....................................12
5.2.2. CONNECTION OF METERING UNITS WITH CL (CURRENT LOOP) INTERFACE ...........13
6. MCL 5.10 CONFIGURATION MENU .............................................................................................15
9 MCL 5.10 PROPERTIES ....................................................................................................................15
9.1 SAFETY ...........................................................................................................................................15
9.2 USERS .............................................................................................................................................16
9.3 APN ..................................................................................................................................................16
9.4 AUTOMATIC REBOOT ...................................................................................................................16
9.5 SMS ..................................................................................................................................................16
9.5.1 SMS CONFIGURATION ...............................................................................................................16
9.6 SOFTWARE UPDATES ...................................................................................................................16
9.6.1 AUTOMATIC SOFTWARE UPDATE ...........................................................................................16
9.6.2 MANUAL SOFTWARE UPDATE .................................................................................................16
9.7 BYTE W. TIMEOUT IN X BYTES ...................................................................................................17
10 MANUFACTURER'S WARRANTIES ...............................................................................................17
CONTACT INFORMATION ...................................................................................................................18
ANNEX 1 CONTROLLER MCL 5.10 MENU .........................................................................................19
ANNEX 2 CONFIGURATION OF "HYPERTERMINAL" SOFTWARE .................................................23
ANNEX 3 INSTALLATION OF CONTROLLER'S USB INTERFACE TO COMPUTER .......................27
4
1.2. Notations and acronyms
AC / DC Alternating Current / Direct Current
APN Access Point Name
CL Current Loop
CLin Current Loop Input
CSD Circuit Switched Data
DLMS Device Language Message Specification
EMC Electromagnetic Compatibility
GPRS General Packet Radio Service
GSM Global System for Mobile Communications
ISP Internet Service Provider
IMEI International Mobile Equipment Identity
LED Light Emitting Diode
LiPo Lithium Polymer Battery
PC Personal Computer
PIN number SIM Card Number (Personal Identification Number)
SIM Subscriber Identity Module
TCP/IP Transmission Control Protocol/Internet Protocol
VPN Virtual Private Network
URL Uniform Resource Locator
5
1.3. Safety instructions
Before installing the controller, it is necessary to read the installation manual and technical requirements set forth in this document.
Only the persons with adequate qualification can perform the installation, removal and configuration of the controller. When installing and operating the controller, it is necessary to observe the "Rules for the Installation of Electrical Equipment" (Vilnius, 2007).
All equipment connected with the controller must meet the requirements of EN 60950-1:2006 or other safety standards applicable to such equipment (electricity meters).
The controller must be installed only in the places with limited access. It should be accessible only to the persons servicing this device.
It is prohibited to open and disassemble the frame of the controller. There are no replaceable parts inside the controller. Electricity may be present in some parts even if the controller is disconnected from the power source!
When replacing or connecting communication cables, SIM card or antenna, the supply voltage must be disconnected at all times.
6
2. Functionality and installation
2.1. General information
MCL 5.10 controller ("the Controller") is used in automated electricity, heat and other energy resources reading devices for data transfer to remote data collection centre. The controller does not store, does not analyse and does not interpret the meters or their data. The controller can be fitted with internal lithium polymer battery to send a report on the loss of voltage to the data centre.
The transfer of data to remote centres is performed by GSM and GSM-R network CSD/GPRS technologies, transparent or TCP/IP protocols.
Attention! The functionality provided below depends on the modification of controller and the additional needs of the client, therefore, not all functions can be realised in a specific product.
2.2. Supported communication protocols
The controller supports two-way communication for data exchange (data readings and configuration) by using DLMS/COSEM, LST EN 62056-31:2001 or LST EN 62056-21:2001 (fixed communication 300...19,200 baud, 8N1 or 7E1 bytes) communication protocols.
2.3. Methods of communication with controller
RS485 electric interface is used for data reading from meters (speed of baud rate 300 ... 19,200, 8N1 or 7E1 bytes). The controller is configured locally by using RS232, USB interfaces or remotely - via sms messages or GPRS. The controller can operate either as TCP/IP server (enable connections) or as a client (to initiate connection).
2.4 Installation and electricity power sources
The controller can be installed under the cover of electricity meter produced by Elgama Elektronika or on a 35 mm DIN rail. The correct installation of controller is confirmed by LED indicators. The controller is powered from the external electricity power source. Attention! There is a possibility to connect by using USB cable, however, in such case, the GSM modem of controller, will not function, therefore, it is recommended to use such method of supply only for local configuration. The controller has an additional electricity source - lithium-polymer battery (450 mAh) to be used for sending reports on the loss of voltage to remote data centres.
2.5 Updates of hardware and configuration of parameters The hardware of controller can be updated and the controller itself can be configured both locally (via RS232 or USB interface) and remotely (via GPRS) by using the tools provided by the manufacturer. Subject to the settings, each time it is turned on, the controller can connect to the indicated server and check if there is a newer version of hardware. Due to software used for work with controller or hardware updates, please contact the manufacturer according to contact information provided on the last page of the manual.
2.6 Monitoring of mobile network communication
The controller periodically tries to download a small amount of GPRS data from the network. In case of failure to download, the controller relaunches the GSM modem. In case of launch, subject to the model of modem, the controller tries to connect to the highest possible (for example, 3G) network and verifies the intensity of connection. If the signal is weaker than the limit set in the control unit, the controller connects to the lower connection (e.g. 2G/GPRS). The controller automatically connects to the highest possible connection only after the reset.
7
2.7 Automatic search for network supplier The controller MCL 5.10 can be provided with ID numbers of SIM card suppliers and attribute network settings to each of them individually. In case of insertion of SIM card and connection of controller by using an external power source, the system verifies if the ID number of SIM card supplier meets the ID numbers of each of the entered suppliers in the controller. If so, the controller automatically starts the use of parameters attributed to such provider.
2.8 Reporting system (Plug & Play) The controller can download the reports received from the metering unit. In case of receipt of report, the controller transfer all the received data to the http servers indicated in the settings and also adds its own information (IMEI, IP).
2.9 Time synchronisation The controller synchronises the time and date with GSM network provider - it is necessary for the register of entries and system audit. The time zone of controller is determined and changed in the settings.
3. The main modules of controller MCL 5.10
The main controller modules:
a) Communication interfaces - one or several - are selected according to the modifications table. The purpose of interfaces and parameters is provided in Table 4.
b) Internal 450 mAh lithium polymer battery is used to ensure that the report on the loss of voltage is sent or data transfer function is supported.
The battery is charged from internal or external power source of the controller. - In case of loss of supply voltage, the controller is supplied from the battery and a report is sent to the system about the loss of voltage. The service to which the report is sent is indicated in Device Configuration menu item "AC fault report address". In case of sending of report, the controller automatically switches off and then on again only after the supply voltage is restored. After the expiry of the useful life of the battery, it can be replaced without performing the soldering works.
c) SMA type connection for antenna. External magnetic GSM antenna with 2 ... 5m long cable can be ordered together with the controller. Antenna can be 2.5 ... 11 dBi directional amplification.
d) GSM-R/GPRS modem module supporting up to 10 sessions at one time.
GSM/GPRS modem
GSM/GPRS frequencies 850/900/1800/1900 Mhz
GSM-R frequency Data Transfer / Receipt 876–880 MHz / 921-925 Mhz
Network IPv4
Power class Multi-slot class 10, CS1-CS4, Class B
Data transfer speed up to 85.6 kb/s
Number of GSM/GPRS sessions at the same time 8
Number of uplink ports 2
CSD up to 9.6kb/s
SIM card interface 1,8 / 3,3 V
Antenna connection type SMA (50Ohm)
3G modem
UMTS / EDGE frequencies 850/900/1800/1900/2100 Mhz
Power class Multi-slot class 12, MCS1-9, Class B
Data transfer speed HSUPA cat 6, up to 5.76 Mb/s UL
HSDPA cat 8, up to 7.2 Mb/s DL
WCDMA PS up to 384 kb/s DL/UL
EDGE multi-slot class 12, up to 236.8 kb/s DL/UL
8
4. Technical specifications
Power supply
Supply voltage 90V – 264V AC, 50/60 Hz
Used power < 2.5W (6VA)
Uninterrupted power supply source
LiPo 450mAh battery Stand-by duration - approx. 5 hours, duration of full functionality - 2 hours.
Communication interfaces
20mA current loop (for connection of metering units)
Parameters according to LST EN 62056-21, 2-wire connection Number of connected metering units up to 3 (15V open current loop) Data transfer speed 300 ... 19,200 baud
20mA passive current loop (for connection of scanning device) Parameters according to LST EN 62056-21, 2-wire connection Data transfer speed 300 ... 19,200 baud
RS485 (for connection of metering units) Number of connected metering units - up to 32 2-wire connection (A, B) Data transfer speed 300 ... 19,200 baud
RS232 (for connection/configuration of reading unit/connection of metering units)
3-wire connection (Txd, Rxd, GND) Data transfer speed 2,400 ......19,200 baud
RS485 (for connection/configuration of reading unit) 2-wire connection
Data transfer speed 300 ... 19,200 baud
Galvanic isolation:
20 mA passive current loop <-> remaining interfaces
500V RMS, 1 minute (=1,000V DC)
Environmental conditions, other
Operating temperatures -30 . . .+50 оС Storage temperatures -40 . . .+70 оС Frame Plastic, IP30 Relative humidity 5 ... 95 %, non-condensing Dimensions Weight
93 x 68 x 37mm 100
4.1 Description of indicators
The controller has two LED indicators on the front that are visible at 160 degree angle.
9
* The levels of indicators of signal strength can be changed by menu settings. The strength of signal is updated every 20 seconds.
5. Interface contact terminals
The controller has two RJ25 type connectors for the connection of interfaces - X1 and X2 as well as mini USB interface. In the usual case (unless the order is different), the controller is completed with 25cm length cables used for connection of interfaces; their purpose is marked on the wires (“CL”, “RS485”, “CLIN”). The values of interface signals are provided below.
Fig. 1.1. X1 and X2 connections
LED1: Indication of activity of interfaces and charging of battery
Data exchange; Active interface:
"Current Loop" - request / response Blinking Red
RS485 - request / response Blinking blue
„CLIN“/RS232 - request / response Blinking Green
"Current loop" open circuit Solid Red
Indication of status and signal strength
The controller is not registered in GPRS network / no SIM card
Red long flashes (1s)
The controller is not registered in GPRS network (call waiting mode); Indicated signal strength:*
-113 to -82dBm or less Blinking Red
-81dBm to -70dBm Blinking blue
-69dBm to -51dBm or more Blinking Green
GPRS data transfer session; ("answering the call")
Fast blinking of respective colour
10
Table 1.1. X1 and X2 connection signals
PIN Signal direction Comments, description
- X1 -
1 GND - Configuration interface (RS232)
2 RS232 TXd Out Configuration interface (RS232)
3 RS232 RXd In Configuration interface (RS232)
4 CL - In/Out Interface for connection of metering units (CL)
5 CL + In/Out Interface for connection of metering units (CL)
6 CLIN_BLOCK In Connection of signal with GND to reconnect RS232 to Menu mode (for configuration)
- X2 -
1 Reserved -
2 Reserved
3 RS485 B In/Out Interface for connection of metering units (RS485)
4 RS485 A In/Out Interface for connection of metering units (RS485)
5 CLIN + In/Out Interface for connection of external controller (CLIN)
6 CLIN - In/Out Interface for connection of external controller (CLIN)
5.1. Controller installation manual
Only the servicing persons with adequate qualification can perform the installation, removal and configuration of the controller. When connecting and installing the controller it is necessary to observe the safety regulations. Installation is performed as follows:
Configuration of controller (if necessary)
SIM card insertion
Installation of controller
Connection of antenna and communication interfaces
Connection of power supply
After the connection of power supply, the light emitting diodes should go on on the controller (the controller starts to register to GSM network). The meanings of LEDs are provided in the table.
NOTE. Subject to the quality of connection, registration to GSM/GPRS network can last up to 60 seconds.
Verification of indications and data transfer to remote data centre.
Contact the responsible employee by phone to check the connection between server and connected controller. The session of reading of data of connected electricity metering units is necessary. Indicator 2 ("Communication interfaces") should blink during the connection session. The meanings of indicator are provided in the table.
11
SIM card insertion
PIN number of SIM card should be disabled.
Make sure to disconnect the power supply when inserting or changing SIM card.
SIM card holder is under SIM card cover on the controller installation side. No special tools are necessary to open the SIM card cover.
Opening of SIM cover:
1 – slide cover 2 – remove cover
SIM card and controller electronic components are sensitive to electrostatic discharge. Avoid flexing and scratching of the SIM card. Avoid unnecessary contact with SIM card holder contacts, controller board or other electronic components.
Place of installation
The controller has to be installed in a territory that is not accessible to unauthorised persons. The possibility to access the controller should be provided to the service persons only.
The controller is usually fitted under the cover of electricity metering unit or close to the
electricity metering unit. If the controller is fitted near the metering unit, a 35 mm DIN rail should be used for that. The mounting position (horizontal or vertical) is not important and can be optional.
Before the installation of controller please check if the manufacturer seals are not damaged, if there are no damages on the frame, its connections and cables. Connection of antenna
The controller has SMA connection for connection of antenna. 3 dBi magnetic installation antenna with 2m-long cable is provided in product packaging (by default; special antenna models can be supplied upon request). Connection of controller power supply
The controller can be supplied with power from alternate (50/60Hz) or direct voltage power source of the rated voltage of 110 - 230 V. 2-wire cable with cable ends prepared for connection and
12
soldered is used for power supply.
The controller's power supply is connected via the automatic switch fitted near the device (Fig. 4.4) !
Requirements for the automatic switch SF: - operating voltage 230VAC; - current from 1 to 6 A, recommended B characteristics; - should have a gap of at least 3 mm between the contacts; - the device has to be easily accessible and fitted close to the controller.
Wiring diagram of power source
5.2. Interfaces for connection of configuration of metering units
5.2.1. Connection of metering units with RS485 interface
Subject to modification, the controller can have RS485 interface. This interface can be physically connected with 32 metering units. Interface conductions cannot be longer than 1,000m. It is recommended to use twisted pair cable 2 x 0.5mm2 or 2 x 0.64mm2; a screen signal cable can also be used, for example, LIYCY 2 x 0.5mm2, J-Y(St)Y 1 x 2 x 0.6mm2. In case of connection of more than one metering unit to RS485 interface, RS485 network should be of "line" and not "star" or other type, i.e. RS485 interface cable should stretch from one metering unit to another without long branching. The connection of metering units to RS485 is provided in Fig. 5.6. IMPORTANT. Polarity should be observed! (“A” and “B”).
brown L (phase)
“N” blue N (zero)
13
Connection of metering units to MCL 5.10 via RS485 interfaces.
5.2.2. Connection of metering units with CL (current loop) interface
Subject to modification, controller MCL 5.10 can have one 20 MA current loop interface which can be connected with up to 3 metering units. The metering units are connected to the controller's current loop in series and form a closed circuit. The connection of metering units to the current loop is provided in Fig. 4.6.
Fig. 1.2. Connection of metering units to MCL 5.10 via current loop interfaces.
Maximum length of conductors of current loop can be up to 2,000 m. However, the longer the
14
lines, the lower is the possible speed of data transfer. In case of long conductors (>100m), it is recommended to install additional surge protectors (PROTECT 10 type). It is recommended to use twisted pair cable 2 x 0.5mm2 or 2 x 0.64mm2; a screen signal cable can also be used, for example, LIYCY 2 x 0.5mm2 , J-Y(St)Y 1 x 2 x 0.6mm2. In case of correct connection of current loop interface, the voltage on the terminals of each metering unit current loop has to be 3.5 ... 4V (without data transfer), whereas the measured voltage on the controller CL leads (11-12 contacts) has to be 3.5...4V, multiplied by the number of connected metering units. Accordingly, in case of connection of 2 metering units on the controller CL leads - the voltage will be 7-8V.
15
6. MCL 5.10 configuration menu
MCL 5.10 can be configured by using computer terminal. Information on how to configure "HyperTerminal" software is provided in Annex 1. When "HyperTerminal" (hereinafter referred to as terminal) is prepared, the settings menu will be opened to the terminal by pressing button <Esc> three times. In some modifications, before opening menu, it is requested to enter the password of device. In such case, only if correct password is entered, menu is opened to configure the settings of the device. Menu illustration is provided in Fig. 5.1.
Important! Load or reload controller menu by pressing ESC button (in keyboard) 3 times.
Fig. 1.3. Illustration of MCL 5.10 main menu window
Symbol “-->” indicates the selection of menu item; by pressing <ENTER> or <> button the selected menu item is activated. The options of menu item are changed by pressing <↓> and <↑> buttons. If the user enters the configuration mode and performs no settings for 60 seconds, the message "Exit terminal mode" will be shown and menu will be closed. In order to stay in the menu mode, it is necessary to choose item "EXIT" or <> button. Controller menu hierarchy is provided in Fig. 6.1. More detailed explanation of each menu is provided in the annex.
9. MCL 5.10 properties
Controller MCL 5.10 menu hierarchy and items are provided in Annex 1 "Controller MCL 5.10 Menu". The main functionality is described below.
9.1 Safety
Controller configuration menu is protected by passwords that are set to protect from unauthorised
16
connection and configuration.
9.2 Users
Four-level users are presented to the client: Admin. Controller administrator. Can change password for the user, public and own. Factory password: admin. User. Has restricted rights to review and change certain parameters. Factory password: user. Public. Has restricted rights to review parameters. Where necessary, different passwords can be provided to users when making the controller by default.
9.3 APN
APN names and parameters (GSM supplier / network ID, DNS, etc.) for each APN are entered by administrator or imported via sms and can be accessed by using configuration menu. Each individual APN has different numbers and IP address lists for control, reports and any other APN can be configured manually.
9.4 Automatic reboot
Controller configuration enables the setting of interval in minutes when to reboot the controller automatically if it is not in use.
9.5 SMS
Subject to APN it is possible to set the list of permitted numbers to accept parameter settings by SMS or send periodic SMS messages with controller status, SIM ID, signal strength, IP address.
9.5.1 SMS configuration
Syntax of SMS configuration is provided below. Important! Commands should be sent by using small caps. Maximum size of sms message - 160 symbols. SMS command syntax starts with command smscmd or change of configuration smscfg:<keyword>:<parameters or command key=value;><parameters or command key=value;>Important!Symbols ( ; = ) cannot be used in the parameter's value. E. g.: smscfg:dev_userpassword=PA:SS;=WORD; value not possible. Example: “smscfg:dev_rebootperiod=1000;smscmd:sendreport;smscfg:dev_userpassword=asd;” Other: “smscfg:dev_rebootperiod=1000;dev_userpassword=cccc;smscmd:sendreport;” Subject to command, the controller responds to the change of parameters with a similar line:
Ok;ok;ok; OR
Error;ok;error; If the controller cannot recognise the command, the reply will be: “No valid command”. The total list of commands is provided in Annex 1.
9.6 Software updates
Software can be updated automatically or manually.
9.6.1 Automatic software update
In case the automatic software update is set, after reboot the controller will start automatic sending of software from the IP address provided according to the inserted SIM card.
9.6.2 Manual software update
Subject to the client's equipment, modification, other settings, the controller can also be updated manually via remote GSM/GPRS, or RS485, RS232 by direct connection to the controller.
17
9.7 Byte w. timeout in X bytes
Time interval after the receipt of the last package byte after the deadline of which the package is forwarded and processed.
10. Manufacturer's warranties
UAB "ELGAMA SISTEMOS" warrants that the materials and components used in the production of the controller as well as performed assembly, tuning works are free of defects and the production employees performed their duties with due quality. The guarantee is also applied to the technical specifications of the product. The manufacturer hereby warrants that in case of disconnection of its produced controllers or other equipment of the same purpose of use and their reconnection, the entire information contained in the meters will remain unchanged and will be available for acceptance and analysis. The period of warranty service of controller is provided in its technical certificate. Warranty obligations are only valid if the user observes the following rules:
the installation of controller is performed by the Manufacturer or his authorised representative or the Manufacturer provides a written consent to the legal person to perform installation works by providing him with complete technical documentation for the installation;
avoids termination and short circuit in the communication lines connecting the controller with the metering units or other controllers, also avoids their short-term and long-term connection with telephone, electricity and other communication lines that do not belong to the system;
when changing the electricity meters in the system, their configuration or layout in the system, it is necessary to inform system producer hereof and to receive his consent as well as mandatory software updates/modifications (in case of change of metering units connected to the system);
avoids damage to the controller box seals and stickers.
18
Contact information
In case of any problems related to the installation or use of our equipment and in case of lack of necessary information in this document, please contact us by e-mail: [email protected].
Manufacturer:
UAB NAVITUS LT Visorių g. 2 LT-08300 Vilnius, Lithuania Telephone: +370 5 237 8000 Fax: +370 5 237 5018 Technical information: [email protected]; Sales and other information: [email protected]. www.navitus.lt
19
Annex 1. Controller MCL 5.10 Menu
Menu item Description SMS command (smscfg:)
0 EXIT Exit terminal mode
1 Device configuration
0 RETURN Back to the main menu
1 Menu language of [Public] Menu language dev_menulanguagepublic
2 Menu language of [User] Menu language dev_menulanguageuser
3 Menu language of [Admin] Menu language dev_menulanguageadmin
4 Menu language of [SuperAdmin]
Menu language dev_menulanguagesuperadmin
5 Device reboot period 0.
Reboot time value in minutes. If there are no queries coming via GPRS during specified time, controller will automatically reboot. After each GPRS query by reboot time is set to initial value
dev_rebootperiod
6 Firmware update mode Auto / Manual firmware download and update
dev_fwupdatemode
7 User password Password. If password is not set, it displays "none"
dev_userpassword
8 Admin password Password. If password is not set, it displays "none"
dev_adminpassword
9 AC fault report address Voltage loss report sending server, e.g.: http://10.0.0.1/services?
dev_acfaultreportipport
10 ModBus slave ID Change MoBus slave ID number (1 … 255)
modbus_slaveid
11 Run firmware update Manually run firmware update
12 Reboot Restarts the controller immediately after pressing <Enter> key
smscmd:reboot;
2 Wireless “in” configuration
0 RETURN Back to the main menu
1 Request to proceed timeout
During the specified time the received request has to be send to a meter (through RS485/RS232 out), if it times out the request will be discarded
ingprs_requestproceedtmo
2 Byte w. timeout in X bytes
Timeout value defined in byte transfer time (it depends on baud rate) multiplied by this setting value. Timeout is set after each received byte in frame. If timeout expires after last received byte, the frame is accepted. This setting is for RS485 out interfaces
3 Idle timeout
4 Connection check period ingprs_gprsconncheckperiod
5 Signal indication level 1-2 LED2 signal level indication settings ingprs_signalindlevel1
6 Signal indication level 2-3 LED2 signal level indication settings ingprs_signalindlevel2
3 RS232 IN configuration
0 RETURN Back to the main menu
1. Request to proceed timeout
During the specified time the received request has to be send to a meter (through RS485/RS232 out), if it times out the request will be discarded
in1_requestproceedtmo
2. Data rate RS232 IN baud rate configuration in1_baudrate
3. Data bits Define data bit quantity in1_databits
4. Stop bits Define stop bit in1_stopbits
5. Parity Define parity in1_parity
20
6. Byte wait timeout Timeout value defined in byte transfer time (it depends on baud rate) multiplied by this setting value. Timeout is set after each received byte in frame. If timeout expires after last received byte, the frame is accepted. This setting is for RS485 out interfaces
in1_bytescounttmo
7. Service answer delay Service answer delay in1_serviceanswdelaysendtmo
4. CLin configuration
0. RETURN Back to the main menu
1. Request to proceed timeout
During the specified time the received request has to be send to a meter, if it times out the request will be discarded
in2_requestproceedtmo
2. Data rate RS232 IN baud rate configuration in2_baudrate
3. Data bits Define data bit quantity in2_databits
4. Stop bits Define stop bit in2_stopbits
5. Parity Define parity in2_parity
6. Byte wait timeout Timeout value defined in byte transfer time (it depends on baud rate) multiplied by this setting value. Timeout is set after each received byte in frame. If timeout expires after last received byte, the frame is accepted.
in2_bytescounttmo
7. Service answer delay Service answer delay in2_serviceanswdelaysendtmo
5. RS485 OUT configuration
0. RETURN Back to the main menu
1. Request to proceed timeout
During the specified time the received request has to be send to a meter (through RS485/RS232 out), if it times out the request will be discarded
out2_eventproceedtmo
2. Data rate RS485S out baud rate configuration out2_baudrate
3. Data bits Define data bit quantity out2_databits
4. Stop bits Define stop bit out2_stopbits
5. Parity Define parity out2_parity
6. Byte wait timeout Timeout value defined in byte transfer time (it depends on baud rate) multiplied by this setting value. Timeout is set after each received byte in frame. If timeout expires after last received byte, the frame is accepted. This setting is for RS485 out interfaces
out2_bytescounttmo
7. Answer wait timeout Time for waiting data (answer) in RS485 out, after the request has been sent
out2_answerwaittmo
8. Next request pause Time for waiting for the next frame in RS485 out, after one frame has been received
out2_serviceanswdelaysendtmo
9. Answer buffer size Answer buffer size out2_answerbuffersize
10. Service answer delay Service answer delay out2_serviceanswdelaysendtmo
6. CLout configuration
0. RETURN Back to the main menu
1. Request to proceed timeout
During the specified time the received request has to be send to a meter, if it times out the request will be discarded
out1_eventproceedtmo
2. Data rate RS485S out baud rate configuration out1_baudrate
3. Data bits Define data bit quantity out1_databits
4. Stop bits Define stop bit out1_stopbits
5. Parity Define parity out1_parity
6. Byte wait timeout Timeout value defined in byte transfer time (it depends on baud rate) multiplied by this setting value. Timeout is set after
out1_bytescounttmo
21
each received byte in frame. If timeout expires after last received byte, the frame is accepted. This setting is for CL out interfaces
7. Answer wait timeout Time for waiting data (answer) in CL out, after the request has been sent
out1_answerwaittmo
8. Next request pause Time for waiting for the next frame in CL out, after one frame has been received
out1_serviceanswdelaysendtmo
9. Answer buffer size Answer buffer size out1_answerbuffersize
10. Service answer delay Service answer delay out1_serviceanswdelaysendtmo
7. Protocol IEC62056-21 configuration
0. RETURN Back to the main menu
1. Enable IEC62056-21 Enable IEC62056-21 p1107_enable
2. Break before session start Break before session start p1107_breakduration
3. Initial data rate Initial data rate p1107_initialbaudrate
4. Baud rate switch relay (ACK rq)
Baud rate switch relay (ACK rq) p1107_switchbaudratedelay
5. Answer buffer size Answer buffer size p1107_answerbuffersize
6. Session timeout Session timeout p1107_sessiontmo
7. Pause before next session
Pause before next session p1107_nextsessionpause
8. Enable error reporting Enable error reporting p1107_enableerrorreporting
8. SIM card configuration
0. RETURN Back to the main menu
1. PIN for SIM card Pin code simpin
9. Provider settings
1. 0. RETURN Back to the main menu
2. 1. Provider identification
3. 0. RETURN Back to the main menu
4. 1. Provider Code GSM Provider/Network ID pr1_providercode
5. 2. Provider Name GSM Provider/Network name pr1_providername
6. 2. Provider SMS configuration
7. 0. RETURN
8. 1. Ph1 number for SMS reporting
Report sms to this number pr1_sms_reportnum1
9. 2. Ph2 number for SMS reporting
Report sms to this number pr1_sms_reportnum2
10. 3. IP for UDP reporting IP address for UDP reporting pr1_upd_reportip1
11. 4. Port number for UDP report
Port number for UDP report pr1_upd_reportport1
12. 5. Ph1 number for config Listen to this number for instructions pr1_sms_allowednum1
13. 6. Ph2 number for config Listen to this number for instructions pr1_sms_allowednum2
14. 3. Provider FTP configuration
15. 0. Return
16. 1. FTP server IP FTP server IP address pr1_ftp_serverip
17. 2. FTP server name FTP server name pr1_ftp_servername
18. 3. FTP username FTP login username for firmware download
pr1_ftp_username
22
19. 4. FTP password FTP login password for firmware download
pr1_ftp_password
20. 5. FTP TCP/IP port FTP TCP/IP port pr1_ftp_port
21. 4. Provider GPRS configuration
22. 0. Return
23. 1. User name GPRS network username pr1_gprs_username
24. 2. Password GPRS network password gprs_password
1. 3. APN Access point name gprs_apn
2. 4. TCP/IP listen port TCP/IP port gprs_tcpiplistenport
3. 5. Authentication protocol Authentication protocol pr1_gprs_protocol
4. 6. DNS server DNS server address pr1_dnsserveraddr
5. 7. TCP/IP server port TCP/IP server port pr1_gprs_tcpipserverport
6. 5. Provider network mode
7. 0. Return
8. 1. Network radio mode Network mode: 2G or 3G pr1_rat_selected
14. Passive client
9. 0. Return
10. 1. Passive client enabled Enable passive client gprs_passiveclientenabled
11. 2. Passive client IP1 Ip address gprs_passiveclientip1
12. 3. Passive client PORT1 Port number gprs_passiveclientport1
13. 4. Passive client IP2 Ip address gprs_passiveclientip2
14. 5. Passive client PORT2 Port number gprs_passiveclientport2
15. 6. Passive client IP3 Ip address gprs_passiveclientip3
16. 7. Passive client PORT3 Port number gprs_passiveclientport3
15. Diagnostics 17. 0. RETURN Back to the main menu.
18. 1. SIM card IP The physical device address on the GPRS TCP / IP network = Device SIM card IP address (if the card has a static IP address)
19. 2. Active provider Indicates which Provider’s (1….6) SIM card is present
20. 3. Signal quality GSM signal quality
21. 4. IMEI IMEI is displayed only when SIM card is present
22. 5. GSM registration status GSM registration status
23. 6. Modem GPRS status Modem GPRS status
24. 7. Network mode Network mode
25. 8. SIM Status Status of the SIM card
26. 9. Battery voltage Battery voltage
27. 10. Battery charging Battery charging
28. 11. Start battery test Start battery test
29. 12. Battery test status Battery test status
30. 13. Read log Read log
23
Annex 2. Configuration of "HyperTerminal" software Configuration is performed by using software "HyperTerminal" (Fig. 1, Fig. 2) or any other
analogous software enabling the connection to the controller via RS232 or USB interface. If the computer operates on Windows Operating system, "HyperTerminal" software can be downloaded from: http://downloads.elgsis.com/hyperterm.zip, the files in the downloaded archive have to be opened to the general directory and it is necessary to launch "hyperterm.exe". COM interface settings for configuration are independent from settings for data reading and shall be set as follows: 9600 (2400, 9600, 19200, etc. subject to the speed of
controller interface) bits per second, parity - none, 8 data bits, 1 stop bit, flow control - none.
Fig. 1. Enter new connection name
Fig. 2. Choose the interface to which MCL is connected
Fig. 3. Choose interface settings
24
After pressing "OK" in dialogue window "COM Properties" (Fig. 3), the settings are set on "Auto detect"
by default (Fig. 4). Replace them with respective values: 1. Press button "Disconnect" as shown in Fig. 5; 2. Press button "Properties" as shown in Fig. 5; 3. Press button "Configure" as shown in Fig. 6; 4. Press button "OK" as shown in Fig. 7; 5. Make sure that other connection settings are set as shown in Fig. 6 and Fig. 7; 6. Press button "OK" as shown in Fig. 8; The settings should change to 9600 8-N-1 as shown in Fig. 9.
Fig. 4.
Fig. 5.
25
Fig. 6.
Fig. 7.
26
Fig. 8.
Fig. 9.
27
Annex 3. Installation of controller's USB interface to computer
To use controller's USB interface, it is necessary to install a respective driver to the computer.
The controller needs USB cable driver "STM32 Virtual COM Port Driver". The driver can be downloaded from:http://downloads.elgsis.com/files/mcl5ip/PF257938.zipor manufacturer of the driver: http://www.st.com/web/en/catalog/tools/PF257938. When installing the driver, please remember to choose the respective driver subject to the platform of computer it is installed to - 32 bits or 64 bits and follow the instructions:
1. Choose 32 or 64 byte platform and launch
After the driver is installed, connect the USB cable and go to system settings (device manager).
28
29
2. Select STM32 device and press Update Driver Software
3. Press Browse my computer...
30
4. Press Let me pick from a list...
5. Select type: Portsand press NEXT
6. Select STMicroelectronics and press NEXT
31
7. Press YES
8. Installation completed
9. Please find the port named STMicroelectronics - it is a connected USB connection with controller. Note
the identification number of COM port, it will be necessary for the connection.