Upload
ngokien
View
241
Download
1
Embed Size (px)
Citation preview
Connected Plant
ControlEdge 900IO using PROFINET
R100
___________________________________
Integration Center
User Guide
___________________________________
PMDOC-X364-en-100A
April, 2018
2
DISCLAIMER
This document contains Honeywell proprietary information. Information contained herein
is to be used solely for the purpose submitted, and no part of this document or its contents
shall be reproduced, published, or disclosed to a Thirdparty without the express
permission of Honeywell International Sàrl.
While this information is presented in good faith and believed to be accurate, Honeywell
disclaims the implied warranties of merchantability and fitness for a purpose and makes
no express warranties except as may be stated in its written agreement with and for its
customer.
In no event is Honeywell liable to anyone for any direct, special, or consequential damages.
The information and specifications in this document are subject to change without notice.
Copyright 2018- Honeywell International Sàrl
PMDOC-X364-en-100A 3
Table of contents
1 ABOUT THIS GUIDE............................................................................................................................ 5
1.1 Scope ................................................................................................................................................... 5
1.2 Revision history ................................................................................................................................. 5
1.3 Intended audience............................................................................................................................ 5
1.4 Related documents .......................................................................................................................... 5
2 INTEGRATION CENTER WORK FLOW DIAGRAM & TOP-LEVEL ORDERING BOM ................ 6
3 CABLE DIAGRAM SW TOOL ............................................................................................................ 8
3.1 ThirdParty Module Interface .......................................................................................................... 9
3.2 Customer IO Configuration xls .................................................................................................... 10
3.3 Terminal Block Label:..................................................................................................................... 11
3.4 Output Files ..................................................................................................................................... 12
3.5 BOM (Bill of Material) .................................................................................................................... 13
3.6 Cable Drawing ................................................................................................................................. 15
4 IOCB ................................................................................................................................................. 17
4.1 IOCB1: ............................................................................................................................................... 17
4.2 IOCB2: ............................................................................................................................................... 20
5 THIRDPARTY MODULES AND THEIR INTERFACES DETAILS: ................................................... 23
5.1 Conditions for ThirdParty Modules Usages .............................................................................. 23
5.1.1 SP Code: SP3 ................................................................................................................................24
5.1.2 SP Code: SP4 ................................................................................................................................25
5.1.3 SP Code: SP5 ................................................................................................................................27
5.1.4 Thirdparty Module Cable Drawing ...........................................................................................28
6 RPIM MODULE............................................................................................................................... 30
6.1 RPIM Specification and Features................................................................................................ 31
6.2 P2 Connection Details (To backplane) ...................................................................................... 33
6.3 Power Supply Specs ....................................................................................................................... 35
6.4 RPIM Input Cable drawing ............................................................................................................ 37
6.5 RPIM Module Product Label ........................................................................................................ 38
6.6 RPIM Input Power Connector Label ........................................................................................... 39
7 MIGRATION STEPS.......................................................................................................................... 40
8 SAFETY AND GENERAL GUIDELINES:.......................................................................................... 44
9 EPM BOARD CONVERSION .......................................................................................................... 45
9.1 Prerequisites .................................................................................................................................... 45
9.2 Package Installation....................................................................................................................... 45
PMDOC-X364-en-100A 4
9.3 Conversion Procedure from PLC to ControlEdge 900IO-PROFINET ................................. 48
9.4 EPM Label ........................................................................................................................................ 55
10 TEST AND CERTIFICATION: ............................................................................................................ 56
11 NOTICES............................................................................................................................................ 57
ABOUT THIS GUIDE
PMDOC-X364-en-100A 5
1 About this guide
1.1 Scope
This guide describes conversion of ControlEdge 900IO using PROFINET Integration and
upgrading the Firmware.
1.2 Revision history
Revision Supported Release
Date Description
A 100 April 2018 Initial release of ControlEdge 900IO using
PROFINET Integration Firmware.
1.3 Intended audience
This guide is primarily intended for Honeywell field personnel who install and configure the
product.
1.4 Related documents
NA
INTEGRATION CENTER WORK FLOW DIAGRAM & TOP-LEVEL ORDERING BOM
PMDOC-X364-en-100A 6
2 Integration Center Work Flow Diagram & Top-level ordering
BOM
The following is the Integration Center Work Flow Diagram:
~ThirdParty Module Cable Assembly
Integration Center Work
Flow
(Projects Team & Buyer)
#Redundancy Power Supply Assembly
~HC900ModulesBOM(#51454980)
~ThirdParty Modules BOM & Cable Assembly
~IO Cable Assembly (#51308275)
‘ControlEdge 900 IO using Profinet’ – Integration Center Work Flow
Integration Center Work Flow (Projects Team)
-FAT Testing-
PLC-EPM ModulesVendor
(WELCO)EPM Module-Upgrade
PNIO FW
PLC Rack(8 Slot)Vendor
(Tontek)
PLC PSU ModuleVendor
(SFO)
RPIM
(#51308252)
Vendor
(SFO?)
~IOCableAssembly &
IOCB(#51308254)
Vendor
(Caverion?)
Mechanical Parts
-EPOR1 Mechanical Kit
(#51454978-001)
Vendor
(?)
ThirdParty Modules
BOM(#tbd)OEMs
Module
Testing
PLC IO ModulesVendor
(WELCO)
~ThirdParty Modules
Cable Assembly
(#51308277)
Vendor
(Caverion?)
RPIMCableAssembly x 2
(#51308276)
Vendor
(SFO?)
Mechanical Parts-REDU
PSU Mechanical Kit
(51454979-001)
Vendor
(?)
Verify the Modules
Customer
Wiring Tool
Software
Wiring Diagrams
Date: 05Dec2017
Note:
#For only REDU Power Supply requirements
~Customized Parts
? Preferred vendor OR ISC to finalize
IOCB: I/O Cable Board
RPIM: Redundancy Power Supply Module
BOM
BOM
Diagrams
Verify the Package
Verify the cable Assemblies
according to wiring diagram &
Repack
Verify the Package
Verify the Package
BOM
Buyer
Buyer
Shipment
Field IO Configuration
Field IO Configuration
New Product
Label
INTEGRATION CENTER WORK FLOW DIAGRAM & TOP-LEVEL ORDERING BOM
PMDOC-X364-en-100A 7
The following is the Top-Level Ordering BOM
PMDOC-X364-en-100A 8
3 Cable Diagram SW Tool
Cable Diagram Software Tool is designed to perform migration at module and I/O level.
This tool understands old and new system in detail, and makes appropriate choice of
modules based on predefined conditions and rules. The tool reads a comprehensive
database having details of both old and new system, and provides output files that are
necessary for migration. Below is the block illustration of the Cable Diagram SW Tool:
‘ControlEdge 900 IO using Profinet’ – Cable Diagram SW Tool
RFQ
Customer IO Configuration Details
like Module Type, IO Type and
Field Device details
-To be filled in template xls file
-By Projects Team
Alcont & Control Edge 900 IO
Map Database xls file
-Technology Team
Cable Diagram SW Tool
-Handled by Projects Team
-from Projects team to Buyer
Cable Connection Diagram(Pdf)
Xls file
Xls file
Pdf file
-from Projects team to Buyer
-Control Edge 900 Modules BOM(xls)
-Thirdparty Modules BOM(xls)
-Cable Assembly BOM(xls)
Xls files
Input files to Tool:
• Customer IO configuration xls file
• Alcont & ControlEdge 900IO Module & IO pin map xls file
Output files from Tool:
• Cable connection diagram (for cable harness vendor)
• BOMs (for buyer)
ControlEdge 900IO Modules BOM
ThirdParty Modules BOM
Cable assembly BOM
Steps to perform migration using cable diagram software tool
1. Feed in the customer IO configuration file to the tool.
2. Click required settings:
a. ControlEdge 900IO PSU – AC or DC
b. Optimize – Yes/No
3. Click Migration button.
4. Defined output files will be generated.
CABLE DIAGRAM SW TOOL
PMDOC-X364-en-100A 9
XLS Database Tool User Guide (For tool designer use):
• TableA= Alcont IO Module to ControlEdge 900IO Module map
• TableB= Alcont IO Modules and their pin details
• TableC= ControlEdge 900IO modules and their pin details
• TableD= ThirdParty modules and their pin details
• 'Codes & Guidelines' table to learn about rules & codes to pin map.
• This page explains about 'Cable diagram tool' work flow, input details required to
operate and output files.
NOTE
Cable Connection Diagram is used by Cable Vendor for cable
creation and Projects team for debug purpose.
Honeywell P/N Document Title/Description
51156521 Cable Diagram SW Tool
51308268 Cable Connection Diagram
3.1 ThirdParty Module Interface
Some of the Alcont IO types are not supported by ControlEdge Modules. So, ThirdParty
modules are used to bridge that gap. This kind of IO types are known as special I/O’s in the
SW tool a unique code called ‘SPCode’ is reserved for every ThirdParty module to identify
them in the SW tool. Details of the code and the ThirdParty module are given in below
table.
SPCode Alcont IO
Module Type
Input Description Reason
SP2 MAI MAI channel can have Sink (Passive) or
Source (Active) field device, is field
device source type?, then mark those
I/O with this code
This will
help
introduce
appropriate
PMDOC-X364-en-100A 10
SPCode Alcont IO
Module Type
Input Description Reason
SP3 BOU Does IO have >0.5A load current
requirement? Then mark those I/O with
this code
ThirdParty
Module and
define
connection
diagram SP4 PBI Does I/O require channel to channel
isolation? Then mark those I/O with this
code
SP5 SWI Does I/O require channel to channel
isolation? Then mark those I/O with this
code
3.2 Customer IO Configuration xls
Customer IO configuration has the I/O details of the plant. It is an xls file goes as input to
the tool. Against every IO that is special type (not supported by ControlEdge modules),
needs to be marked in a column as SPx, with this special code, tool is trigged to assign
appropriate ThirdParty modules and also make suitable connection diagram.
Customer IO Configuration File - Example Template:
CABLE DIAGRAM SW TOOL
PMDOC-X364-en-100A 11
NOTE
• Sp1 or Blank means normal IO (Supported by ControlEdge
modules). By default, Cable Diagram Software Tool assigns default
SPCode that is SP1. Project team need to edit this special code to
redefine an I/O that is not supported by ControlEdge modules
(Special Type of IO).
• BOU module supports two types of connection cards, CCCA or
CCCH. Connections are different in both cases; hence it is
important to inform the Cable diagram SW tool for creating
appropriate connection diagram. By default, the tool will assume
CCCH as the connection card for BOU module. Projects team
needs to change it if it is CCCA, with this tool makes appropriate
connection diagram.
3.3 Terminal Block Label:
Terminal block label contains details of Alcont IO slot# and ControlEdge Rack & its slot#.
Refer to drawing: 51308275 for details. This label is located behind the door on terminal
block. It guides service engineer/user to appropriately plug the Terminal Block to
ControlEdge system at one end and the SAMTEC connector to IOCB board (CCC card slot)
on Alcont IO system at the other end.
Similarly, there is a text ‘1’,’2’ written on SAMTECH connector that will be mounted on IOCB
board to interface with Alcont IO System. This happens when more than one CCC/IOCB
needs to be connected to single Control Edge Module.
For example: Two Alcont IO’s BOU (16 Chs) modules connected to one ControlEdge 900’s
DO (32 Chs) module. (Please see the IO cable image).
Details of Terminal Block Label
• Drawing Name: Terminal Block Label
• HPN: 51156518-001
• Size: 2CM x 1CM? (as appropriate to door size and readable)
• Color: White
• Label Content:
AL_Slot#: ASxx (1 to 19) 900IO_Slot#: TR/BRx (TR-1 to 8 or BR-1 to 8)
• Exact Content on Label with example1:
AS1
TR1
• Exact Content on Label with example2:
AS19
PMDOC-X364-en-100A 12
BR8
NOTE
In case if there are two or more SAMTECH connectors connected to one single
terminal block, the SAMTECH connectors are numbered with a marker pen
displaying the slot number on it. This helps in making connection.
3.4 Output Files
Below are list of output files with an example:
“Cable Diagrams for wiring vendor and Field Engineer” are used by Cable harness vendor
for creating cables and Honeywell Field Engineer for debug purpose. These cable
connection diagrams have different columns detailing the module type, channel type, CCC
card pin#, IOCB pin number etc.
For cable connection and mapping, below columns are important:
• Alcont IO Side: ALCModule#, IOCB, WC, WG, IOCBSetting and
IOCBConPin#
• Control Edge Side: PLCModule#, PLCTB and PLCTBPin#
For cable connection below columns to be considered (yellow highlighted):
• Alcont IO Side: WC, WG, IOCBConPin#
• Control Edge Side: PLCTB, PLCTBPin#
Wire column shows the channel level connection map.
CABLE DIAGRAM SW TOOL
PMDOC-X364-en-100A 13
3.5 BOM (Bill of Material)
Cable Diagram Tool generates below listed BOMs.
• ControlEdge 900 Modules BOM
EPOR1 Rack level BOM
Plant Level BOM
• ThirdParty Modules BOM
EPOR1 Rack level BOM
Plant Level BOM
PMDOC-X364-en-100A 14
• Cable assembly BOM
Plant Level BOM
EPOR1 Rack level BOM: This BOM will have items required for rack level. This will be used
to prepare rack level materials/modules/cables for rack by rack migration.
Plant Level BOM: This BOM will have consolidated quantity for one complete plant
migration. This is for buyer to make one comprehensive material purchase plan.
This BOM is for cable vendor for preparing comprehensive purchase plan to stock raw
materials.
Example Output BOMs:
(‘I1’ column is for tool designer use; it will not be part of the BOM)
CABLE DIAGRAM SW TOOL
PMDOC-X364-en-100A 15
3.6 Cable Drawing
Cable Diagram Image
PMDOC-X364-en-100A 16
NOTE
Cable diagram Software (SW) tool: Kindly go through the database xls file
for all details including tool design guidelines.
IOCB
PMDOC-X364-en-100A 17
4 IOCB
IOCB (I/O Cable Board), these boards are used as an interface between Alcont IO CCC card
and ControlEdge 900IO modules. There are two types of IOCB boards to interface with
different types of Alcont IO modules. Details are provided below.
4.1 IOCB1
This board is used along with only MAI module for both, sink and source type of Analog
Inputs. It has two switches (S1 and S2) to make appropriate connection for sink and
source type of Analog current input type. Each switch has 10 positions, totalling to 20
positions. MAI module has 10 channels, and each channel is provided with 2 positions to
make connection for sink or source type. Switch setting is explained below for two types of
configuration.
• Switch Electrical Specifications:
Operating voltage: Max 24V
Operating current per channel: Min=10uA and Max=25mA
Operating temperature: 0 to 60degC
Isolation between channels: None
• Sink Type of Analog Input:
This type of channels can be interfaced to two types of modules at ControlEdge 900 side,
To ThirdParty module
To HLAI module of ControlEdge 900
NOTE
HLAI module needs ground reference for each channel, to offer this, free
pin/connection in the IOCB1 is connected to Ground and extended to HLAI
Module. This setting is not necessary if ThirdParty Module is involved.
IOCB1 setting information is captured in a column named as ‘IOCBSetting’
in Cable diagram file against each IO.
PMDOC-X364-en-100A 18
• Source Type of Analog Input:
This type of channels can be interfaced to ControlEdge 900’s UIO module only.
Switch setting for the same is explained below:
MAI Channel# Switch# Switch Position#
For Sink Type of Field IO
Ch1 S1 1 OFF
S1 2 ON
Ch2 S1 3 OFF
S1 4 ON
Ch3 S1 5 OFF
S1 6 ON
Ch4 S1 7 OFF
S1 8 ON
Ch5 S1 9 OFF
S1 10 ON
Ch6 S2 1 OFF
S2 2 ON
Ch7 S2 3 OFF
S2 4 ON
Ch8 S2 5 OFF
S2 6 ON
Ch9 S2 7 OFF
S2 8 ON
Ch10 S2 9 OFF
S2 10 ON
:
IOCB
PMDOC-X364-en-100A 19
Board Dimension and Layout
PMDOC-X364-en-100A 20
4.2 IOCB2
This board is used with below listed Alcont IO Modules for interface with ControlEdge 900
IO module through CCC cards. This Board has a berg jumper connector for making
required connections based on module and IO type. Supported modules are: ACO, MSI,
SWI, BOU, PBI and PBO. Jumper setting is required only for PBI module when ch-ch
isolation is not required, for all other modules jumper short need to be DNP.
Electrical Specifications
• Operating Voltage: 24V DC or 230V AC
• Operating current per channel: Max=2A for signals connections, 3A for Supply
connections.
• Operating temperature: 0 to 60degC
• Isolation between channels: 600 VAC
P2’s Pins: A2, C2,A4,C4,A30,C30,A32,C32 have 3A of current carrying capacity, advised to
use them as common signals like reference ground, return or supply line. All other pins can
carry max of 2A and should be used for signal connections.
Jumper Settings
Jumper setting to be DNP for all modules except PBI module.
PBI Module: For PBI Module input type, Mount jumper on J1 for a channel as marked SP4
in Customer IO configuration xls , if the jumper short is mounted, ch-ch isolation is lost. If
IOCB
PMDOC-X364-en-100A 21
isolation is required for a particular channel, then the jumper needs to be DNP so to isolate
the return line. Isolated channels are passed through Thirdparty Module.
Read ThirdParty Module section for more details.
DO Module(CCCA Card): For BOU module with CCCA connection card combination, there
is one power supply connection for every BOU channel (2 connections per channel). But,
ControlEdge 900's DO module has 4 common power supply connections for all DO
channels. Hence ICOB2’s J1 jumper shorts all power supply connections on CCCA card
and helps route only 4 wires to ControlEdge 900's DO module to extend power supply from
field wire to Control Edge DO module.
Board Dimension and Layout
PMDOC-X364-en-100A 22
THIRDPARTY MODULES AND THEIR INTERFACES DETAILS
PMDOC-X364-en-100A 23
5 ThirdParty Modules and their Interfaces details
Below list of ThirdParty Modules will be used in Migration.
SL# SP Code HPN DESCRIPTION MPN MFR
1 SP2 51509126-
001
MODULE,MTL
CURRENT
REPEATER, 2CH
MTL5544AS MTL
2 SP3 51509127-
001
MODULE,ISOLAT
ED RELAY
OUTPUT - 2CH,
2A
MTL5526 MTL
3 SP4 51509157-
001
MODULE,SIGNAL
CONVERTER/INS
ULATOR,1CH
ACT20P-
VM-AO-S
WEIDMU
LLER
4 SP5 51509224-
001
MODULE,ISOLAT
ED SWITCH
INPUT, 2CH
MTL5513 MTL
5.1 Conditions for ThirdParty Modules Usages
SPCode: SP2
Alcont IO Module: MAI Module
ThirdParty Module: MTL5544AS (MTL)
Brief Electrical Specification
• Channels: 2
• Supply Voltage: 20 to 35V DC
• Signal Range: 1 to 21.5mA
• Operating temp: -20 to +60degC
• HART: Yes
• Wire: 2.5mm2
Conditions
• SPLCh=SP2 is for Source Type of Field device/active field devices.
PMDOC-X364-en-100A 24
• Check total count of SP2, if >16, then go for 900A16-0101 Module ONLY, if total
Control Edge 900 module count per EPOR1 rack is <=16 at the end of migration.
Else chose this ThirdParty Module.
• SPLCh=SP2 is for MAI Input with sink type IO marked in Customer IO configuration xls.
Wiring Details
There are few fixed connections marked as ‘@’ in the below diagram, this means, wiring
connection to these terminals are predefined and follow them as given in figure. And other
connections with symbol ‘#’ will be defined in cable diagram as per IO configuration, and
make connections accordingly.
Wire dimension and specifications are provided in Drawing:
51308271_Rev00_31Jan2018
Module Connections Diagram:
HC900 Side>><<Field Side
(@)24-(Ground)
(@)24+
Power Supply
# -- Wire connection defined by ‘Cable Diagram SW Tool’
@ --Fixed Connections
(@)24-(Ground)
#
(@)24-(Ground)
#
No Connection
No Connection
(@)24-(Ground)
(@)24-(Ground)
#
#
No Connection
No Connection
Module#: MTL5544AS
5.1.1 SP Code: SP3
Alcont IO Module: BOU Module
ThirdParty Module: MTL5526 (MTL)
Brief Electrical Specifications
• Channels: 2
• Supply Voltage: 20 to 35V DC(This also has loop powered option)
• Relay Off Voltage: <17V
• Relay ON Voltage: >20V
• Relay Max Current: 2A
• Operating temp: -20 to +60degC
• Wire: 2.5mm2
• Use ‘2Ch’ option in Function
THIRDPARTY MODULES AND THEIR INTERFACES DETAILS
PMDOC-X364-en-100A 25
Conditions
SPLCh=SP3 is for BOU output with >0.5A requirements. Choose this module if SP3 is
marked against IO in Customer IO configuration xls.
Wiring Details
There are few fixed connections marked as ‘@’ in the below diagram, this means, wiring
connection to these terminals are predefined and follow them as given in figure. Other
connections with symbol ‘#’ will be defined in wiring diagram as per IO configuration, and
make connections accordingly.
Wire dimension and specifications are provided in Drawing:
51308271_Rev00_31Jan2018
NOTE
Either external power supply can be used to power the module or choose
loop powered mode (since this module is interfaced to DO module at
Control Edge 900 side, it can work with loop powered mode as well)
Module Connections Diagram
# -- Wire connection defined by ‘Cable Diagram SW Tool’
@ --Fixed Connections
Module#: MTL5526
(@)24-(Ground)
(@)24+
Power Supply
(@)24-(Ground)
#
(@)24-(Ground)
No Connection
No Connection
#
#
No Connection
(@)24-(Ground)
No Connection
#
(@)24-(Ground)
HC900 Side>><<Field Side
5.1.2 SP Code: SP4
Alcont IO Module: PBI Module
Thirdparty Module: ACT20P-VM-AO-S (Weidmulluer)
Brief Electrical Specifications
• Channels: 1
• Supply Voltage: 20 to 35V DC or Line voltage
• Input Voltage: 0 to 300 VAC or 0 to 300 VDC
PMDOC-X364-en-100A 26
• Output Voltage: 0 to 10V DC / 0 to 20mA
• Isolation Voltage: 2.2K VAC
• Operating temp: -25 to +65degC
• Wire: 2mm2
Conditions
• SPLCh=SP4 is for PBI with Ch to Ch isolation need. Choose this module if SP4 is
marked against IO in Customer IO configuration xls.
• IOCBSettings for these Channels is displayed in cable diagram, so that the jumper
short is removed on IOCB2 for these channels.
Wiring Details
There are few fixed connections marked as ‘@’ in the below diagram, this means, wiring
connection to these terminals are predefined and follow them as given in figure. And other
connections with symbol ‘#’ will be defined in wiring diagram as per IO configuration, and
make connections accordingly.
Wire dimension and specifications are provided in Drawing:
51308271_Rev00_31Jan2018
NOTE
This module needs to be configured before use, thus require
configuration tools (CBX200 USB & FDT/DTM software) to be procured
from Weidmuller. Or Weidmuller has agreed to ship preconfigured
modules based on request with some additional cost.
Module Connections Diagram
#
#
No Connection
No Connection
#
(@)24-(Ground)
(@)24+
(@)24-(Ground)
Power Supply
HC900 Side>><<Field Side
# -- Wire connection defined by ‘Cable Diagram SW Tool’
@ --Fixed Connections
Module#: ACT20P-VM-AO-S
THIRDPARTY MODULES AND THEIR INTERFACES DETAILS
PMDOC-X364-en-100A 27
5.1.3 SP Code: SP5
Alcont IO Module: SWI Module
ThirdParty Module: MTL5513 (MTL)
Brief Electrical Specifications
• Channels: 2
• Supply Voltage: 20 to 35V DC
• Open collector output on Safe side (Vmax: 35V DC)
• Input is a switch type with no voltage feed to it
• Operating temp: -20 to +60degC
• Switch type input needs resistors if LFD is required
• Wire: 2.5mm2
Conditions
• SPLCh=SP5 is for SWI with Ch to Ch isolation need. Choose this module if SP5 is
marked against IO
• IOCBSettings for these Channels is displayed in cable diagram, so that the jumper
short is removed on IOCB2 for these channels
Wiring Details
There are few fixed connections marked as ‘@’ in the below diagram, this means, wiring
connection to these terminals are predefined and follow them as given in figure. Other
connections with symbol ‘#’ will be defined in wiring diagram as per IO configuration, and
make connections accordingly.
Wire dimension and specifications are provided in Drawing:
51308271_Rev00_31Jan2018
Module Connections Diagram
(@)24-(Ground)
(@)24+
Power Supply
# -- Wire connection defined by ‘Cable Diagram SW Tool’
@ --Fixed Connections
#
#
#
#
#
#
(@)24-(Ground)
Module#: MTL5513
No Connection
No Connection
No Connection
PMDOC-X364-en-100A 28
5.1.4 Thirdparty Module Cable Drawing
51308271-001: This cable is used to connect 24V+ of all modules to Power supply’s ‘+’.
Terminal ‘N’ in the drawing refers to number of connections, which are total number of
modules per EPRO1 rack provided in Thirdparty Module BOM.
51308271-002: This cable is used to connect 24V- of all modules to Power supply’s ‘_’.
Terminal ‘N’ in the drawing refers to number of connections, which are total number of
modules per EPRO1 rack provided in Thirdparty Module BOM.
51308271-003: This is cable between ControlEdge 900 module and control side of the
Thirdparty Module.
51308271-004: This cable is used to make connection between field side of the Thirdparty
module and field connections (IOCBx).
NOTE
Details of preparing these cables are provided in below drawing. Buyer
has to order the cables based on BOM quanity generated by ‘Cable
diagram SW tool’.
THIRDPARTY MODULES AND THEIR INTERFACES DETAILS
PMDOC-X364-en-100A 29
PMDOC-X364-en-100A 30
6 RPIM Module
ControlEdge 900 offers both non-redundant and redundant power supply solution for the
rack. Due to space restriction in EPOR1 rack, redundant power supply solution does not fit
into it. Thus, a new approach is developed for redundant power supply need.
RPIM (Redundant power supply Interface module) is a new design to support redundant
power supply needs within the same size of 8 slot rack. Here are the details.
This design basically has ‘Power supply Oring Circuits’ with same spec as a Control Edge
900’s non-redundant power supply. Externally, this module needs pair of supplies to
source 2 x 5V and 2 x 24V.
Block Diagram
8 Slot-Rack
Din-Rail
5V1
230V/Line PS
5V2 24V1 24V2
RPIM EPM IO1 IO2 IO8
5V
1
5V
2
24
V1
24
V2
5V1n2_Status
245V1n2_Status
RPIM module form-factor is same as ControlEdge 900’s 24V PSU. RPIM PCB is a new
design and all other mechanical parts are re-use from Control Edge PSU module. Hence it
looks like PSU module with a new product label on it.
Sample, RPIM PWA images:
RPIM MODULE
PMDOC-X364-en-100A 31
6.1 RPIM Specification and Features
• Form factor is same as Control Edge 900’s 24V PSU module (900P24-0301)
• Most of the mechanical parts are re-used from ControlEdge 900 24V PSU
• It needs 2 pair of 5V DC and 24V DC Din-rail mountable PSUs. (5V: MDR-60-5,
MEANWELL, 24V: MDR-60-24,MEANWELL)
• 5V
Input Voltage Range: 5V DC Type (4.73 to 5.22V DC, +/-5%)
PMDOC-X364-en-100A 32
Max Operating Current: 8A
Fault Time: 2.4mS
• 24V
Input Voltage Range: 25V DC Type (22.11 to 25.66V DC,+/-5%)
Max Operating Current: 2.1A
Fault Time: 2.4mS
• Operating Temp: 0 to 60degC
• A 10 pins connector has Power supply inputs and status signals on it.
• A 20 pins connector has backplane power supply connections
• There are four green color LEDs to display 4 power supply unit status.
• Status Signals: There are two status signals with different voltages levels referring
to the working status of external power supply rails. Here are the details:
For 5V: Voltage at 5V1n2_STA
If both are OK: 1.24V
If one is OK and other is open: 0.7V
If one is OK and other is short to ground: 0.62V
For 24V: Voltage at 24V1n2_STA
If both are OK: 3.66V
If one is OK and other is open: 1.98V
If one is OK and other is short to ground: 1.83V
P1 Connection details (External Power Supply Connector)
RPIM MODULE
PMDOC-X364-en-100A 33
6.2 P2 Connection Details (To backplane)
Meanwell Power Supply Connection Details for both 5V and 24V:
Line connections
• Earth: Earth Connection
• L: Line
• N: Neutral
Low Voltage Connections
• +V: +5V or +24V
• -V: -5V or -24V
• -V: OV or GROUND
Status
• DC OK Switch output: Status signal
• DC OK LED: Green LED to show the status
Voltage Adjust
• +V ADJ: Voltage can be varied thru this knob.
• For 5V: 5 to 6V
• For 24V: 24 to 30V
PMDOC-X364-en-100A 34
Pin Connection Image
RPIM MODULE
PMDOC-X364-en-100A 35
6.3 Power Supply Specs
Part#: MDR-60-5 and MDR-60-24, Make: Meanwell.
PMDOC-X364-en-100A 36
3D images of External Power Supply mount and wiring reference:
RPIM MODULE
PMDOC-X364-en-100A 37
6.4 RPIM Input Cable drawing
PMDOC-X364-en-100A 38
RPIM Output Cable Drawing:
6.5 RPIM Module Product Label
Drawing Name: RPIM Module Product label
• HPN: 51156519-001
• Size: tbd (please fix the label size based on space availability and the readable font
size)
• Color: White
Guidelines:
• Consider all those listed in orange table and ignore remaining.
• include only CE marking, remove all other
• Retain all other notes that pertaining to this label and its printing needs.
RPIM MODULE
PMDOC-X364-en-100A 39
Label
A RPIM MODULE
B 51454984 (PWA:51156519-176)
C 0 TO 60 DEGC
C1 DATE CODE
J n/a
H SERIAL#: xxxx
K SERIAL NUMBER BARCODE
D
5V1 & 5V2 INPUT: 5VDC TYP (+/‐4%)
24V1 & 24V2 INPUT: 24VDC TYP (+/‐5%)
5VDC OUTPUT: 5VDC TYP (4.73‐5.22VDC @8A)
24VDC OUTPUT: 24VDC TYP (22.11‐[email protected])
6.6 RPIM Input Power Connector Label
Drawing Name: RPIM Input Power Connector Cable
• HPN: 51156519-002 • Size: tbd (please fix the label size based on space availability and the readable font
size)
• Background Color: White, Text: Black, LED area to be transparent.
Label Content
10
9
8
7
6
5
4
3
2
1
5V1
5V1-GND
5V2
5V2-GND
24V1
24V1-GND
24V2
24V2-GND
5V1n2_STA
24V1n2_STA
5V1
5V2
24V1
24V2
PMDOC-X364-en-100A 40
7 Migration Steps
Step 1 & 2
1. Dismantle the EPOR1 rack to remove all Alcont IO module. Bring to the state shown
above.
2. Mount IOCB Boards (Red colored PCB boards).
Step 3 & 4
3. Assemble IOCB SECURING BRACKET.
4. Assemble, BACK PLATE DUAL ControlEdge 900.
MIGRATION STEPS
PMDOC-X364-en-100A 41
Step 5 & 6
5. Assemble Top ControlEdge 900 Rack (without modules in it).
6. Assemble Second ControlEdge 900 Rack (without modules in it).
Step 7 & 8
7. Assemble ControlEdge 900 Modules.
8. Assemble Cables between Control Edge modules and IOCB boards.
PMDOC-X364-en-100A 42
Step 9
9. Module view with open doors and assemble ThirdParty Module Din Rail Bracket
Step 10 & 11
10. Make ThirdParty Module cable connection and secure them as shown in figure.
11. Assemble ThirdParty Modules
MIGRATION STEPS
PMDOC-X364-en-100A 43
Step 12
12. ThirdParty Modules bracket at its closed position. And completely assembled view…
PMDOC-X364-en-100A 44
8 Safety and General Guidelines
Safety Guidelines
• IOCB2 board is fixed with a plastic cover at P2 side as insulator from line/high
voltage. Do not remove it.
• For PBI and PBO modules, IOCB2 board will be handling line voltage. To protect
users from accidental touch to unused/exposed P2 connector, user should insert
dummy connector to insulate exposed pins. Use Part#: 51509141-001 (IPD1-16-
D-K, SAMTEC).
• Follow wire gauge recommendations as per the cable diagrams to avoid damage
due to incorrect cable specification.
General Guidelines
• For below two modules field side power supply connection (either 24V+ or 24V-) are
not part of IOCB cable connections. Hence additional wiring needs to be done to
make connection. For this reason, there is a din-rail mountable terminal block
provided in between two Control Edge 900 racks, kindly use them to make 24V+
and 24V-(Ground) connections as required. Module and connection details are
listed below.
ControlEdge’s DO Module (Equ BOU module in Alcont IO System): DO module
needs 24V- (Ground) connection but same is not present in BOU module. Hence
an external wire connection need to be made, use 20AWG wire gauge for this
purpose.
ControlEdge’s DI Module (Equ SWI module in Alcont IO System): DI module
needs 24V+ connection but same is not present in SWI module. Hence an
separate wire connection need to be made, use 20AWG wire gauge for this
purpose.
In case of two/more Alcont IO modules/Slots interface to one Control Edge 900
Module, use power supply connections from first Alcont IO module to connect to
Control Edge 900 module. Ignore the power supply connection of
second/remaining Alcont IO Module/Slot
In case of two/more Control Edge 900 modules interface to one Alcont IO
Module, use power supply connections from first Control Edge 900 module to
connect to Alcont IO Module/Slot. Remaining/Second Control Edge 900
Module Power supply need to be connected to Terminal Block Distributor
located between Control Edge racks.
EPM BOARD CONVERSION
PMDOC-X364-en-100A 45
9 EPM Board Conversion
This section provides the instructions to convert EPM Board to ControlEdge 900IO-
PROFINET device. The EPM board contains the PLC firmware from factory.
9.1 Prerequisites
The following is the list of software prerequisites:
• Windows7 - 64-bit host ( IP Address of this machine should be 192.168.0.1).
• Required packages as described in section 9.2 Package Installation (that involves
installation of CPMSimulator.exe, ControlEdge Builder release version 140.1-22.0
and firmware files).
9.2 Package Installation
Tools for EPM Board conversion are packaged in folder PNIOFirmwareConversionTool.
1. Go to the package folder and double-click on “ControlEdge 900IO using PROFINET -
Firmware Conversion Tool.msi” to run the installer.
2. Click Next on Welcome InstallShield wizard.
3. Enter User name and organisation information under Customer Information dialog
box and Click Next.
PMDOC-X364-en-100A 46
4. Under Setup Type dialog box, select Complete for complete package installation or
select Custom to choose and install required features and Click Next.
5. Click Install.
EPM BOARD CONVERSION
PMDOC-X364-en-100A 47
6. Click Finish to complete the installation.
7. Once Installation is completed, check the below path for installed packages.
“C:\Program Files\Honeywell\PNIO_FirmwareConversionTool” (in case of 64 bit
machines, the path will be “C:\Program
Files(x86)\Honeywell\PNIO_FirmwareConversionTool”). Under which three subfolder
will be created.
• ControlEdgeBuilder
PMDOC-X364-en-100A 48
• CPMSimulator
• FirmwareFiles
NOTE
ControlEdge Builder can be installed from the below path.
For detailed installation steps on ContolEdge builder, refer to
“ControlEdge Builder installation manual”.
9.3 Conversion Procedure from PLC to ControlEdge 900IO-PROFINET
Conversion of EPM Board from PLC to ControlEdge 900IO-PN involves the following
three steps in sequence:
1. Upgrade PLC Product Firmware (part of package)
Firmware filename: epmv1_prod_signed_external_r ls.pkg.
2. Upgrade PNIO Recovery Firmware (part of package)
Firmware filename: Firmware Image: pn900recovery_emp_pn_mrp_signed_prod.pkg.
3. Upgrade PNIO Product Firmware (part of package)
Firmware filename:
ControlEdge_900IO_using_Profinet_R100.1_Product_Signed.pkg.
Upgrade PLC Product Firmware
To upgrade PLC Product Firmware follow the below steps:
1. Launch CPMSimulator.exe from “ :\Program Files (x86)\Honeywell\ PNIO_FirmwareConversionTool\CPMSimulator” to run CPM simulator.
EPM BOARD CONVERSION
PMDOC-X364-en-100A 49
NOTE
On launching the CPM simulator for the first time Firewall
window pops up. Select the settings for CPM simulator as
below and click Allow access.
2. CPMSimulator simulator windows appears as below.
3. Launch ControlEdge Builder from Start menu.
4. In ControlEdge Builder, click Connect button under ControlEdge Configuration
window to open Connect Controller dialog box.
PMDOC-X364-en-100A 50
5. In Connect Controller dialog box, select IP Address option.
6. Enter following credentials and click Connect .
• IP Address: 127.0.0.1
• User name: Administrator
• Password: Admin@1234
EPM BOARD CONVERSION
PMDOC-X364-en-100A 51
7. Now, Click Upgrade Firmware under Maintenance tab to check the EPM details.
8. In Left Pane, Select EPM and make a note of Boot and Application version.
• Boot Version represents the recovery Image version.
• Application version represents the product Image version.
9. Select Radio button for EPM Module Name. Click Transfer.
PMDOC-X364-en-100A 52
10. Press Browse to select the. pkg file. Select the appropriate .pkg file, Click Open.
Sequence of upgrade is given in section EPM Board Conversion from PLC to
PNIO
11. Check Full Transfer. Click Transfer.
12. Firmware Transfer status screen will appear.
EPM BOARD CONVERSION
PMDOC-X364-en-100A 53
13. On completion of Firmware transfer, Click Upgrade.
14. Click OK on Upgrading Firmware dialog box.
PMDOC-X364-en-100A 54
15. Click Yes to upgrade the firmware.
16. Firmware upgrade status window will appear.
EPM BOARD CONVERSION
PMDOC-X364-en-100A 55
17. EPM board reboots once the upgrade is complete.
18. Close CPMSimulator and ControlEdge Builder.
Now, The Board contains the upgraded firmware version. To verify the new version
follow Step one to nine.
9.4 EPM Label
EPM module needs to be upgraded with PNIO software at Integration center. After the
upgrade this label is to be put on it for identification and for tracking (EPM) PNIO-EPM in
the field.
. This label will also help for tracking (EPM) PNIO-EPM in the field.
Drawing Name: PNIO EPM Label
• HPN: 51121627-001
• Color: White
• Label Content:
HPN: 51121627-001
DATE: xx-xx-xxxx
FW VERSION: xxxx
PMDOC-X364-en-100A 56
10 Test and Certification
IOCB boards have not been evaluated for any certification needs as these are passive
boards used for extending the connections.
IOCB2 has been qualified for 600VAC isolation test.
RPIM Module is tested for CE conformity (IEC: EN61326-1:2013)
NOTICES
PMDOC-X364-en-100A 57
11 Notices
Trademarks
Experion ® Process Knowledge System (PKS) is a registered trademark of Honeywell International Inc. All other brand or product names mentioned in the document are trademarks of their respective owners.
Other trademarks
Trademarks that appear in this document are used only to the benefit of the trademark
owner, with no intention of trademark infringement.
ThirdParty licenses
This product may contain or be derived from materials, including software, of third parties.
The ThirdParty materials may be subject to licenses, notices, restrictions and obligations
imposed by the licensor.
The licenses, notices, restrictions and obligations, if any, may be found in the materials
accompanying the product, in the documents or files accompanying such ThirdParty
materials, in a file named third_party_ licenses on the media containing the product, or at
http://www.honeywell.com/ps/thirdpartylicenses.
Documentation feedback
You can find the most up-to-date documents on the Honeywell Process Solutions support
website at:
http://www.honeywellprocess.com/support
If you have comments about Honeywell Process Solutions documentation, send your
feedback to:
Use this email address to provide feedback, or to report errors and omissions in the
documentation. For immediate help with a technical problem, contact your local
Honeywell Process Solutions Customer Contact Center (CCC) or Honeywell Technical
Assistance Center (TAC).
How to report a security vulnerability
For the purpose of submission, a security vulnerability is defined as a software defect or
weakness that can be exploited to reduce the operational or security capabilities of the
software.
Honeywell investigates all reports of security vulnerabilities affecting Honeywell products
and services.
PMDOC-X364-en-100A 58
To report a potential security vulnerability against any Honeywell product, please follow the
instructions at:
https://honeywell.com/pages/vulnerabilityreporting.aspx
Submit the requested information to Honeywell using one of the following methods:
Send an email to [email protected].
or
Contact your local Honeywell Process Solutions Customer Contact Center (CCC) or
Honeywell Technical Assistance Center (TAC) listed in the “Support” section of this
document.
Support
For support, contact your local Honeywell Process Solutions Customer Contact Center
(CCC). To find your local CCC visit the website, https://www.honeywellprocess.com/en-
US/contact-us/customer-support-contacts/Pages/default.aspx.
Training classes
Honeywell holds technical training classes that are taught by process control systems
experts. For more information about these classes, contact your Honeywell representative,
or see http://www.automationcollege.com.
PMDOC-X364-en-100A
April 2018
© 2018 Honeywell International Sàrl
Honeywell Process Solutions
Contact: Honeywell Oy GTAC P3-DCS
Navitas 1, B-block, 4.kerros
Wredenkatu 2
FI-78250 Varkaus, Finland
Phone: +358 20 752 2000
E-mail: DL HPS_Q_GTAC_P3_DCS