31
continuos power protection availability 28 March 2011 1 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA TM Conceptpower DPA

Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

Embed Size (px)

Citation preview

Page 1: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

continuos power protection availability

28 March 2011 1

Newave unique MODULAR power protection concept for mission critical applications

CONCEPTPOWER DPATM

Conceptpower DPA

Page 2: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 2

Content

• Newave Modular Concept

Highlights Safe Swap Modules Parallel Architecture Scalability & Flexibility

• Benefits

• Options

• Conclusion

Newave Modular Concept

Scalable up to 1.5 MVA

Scalable up to 1.5 MVA

Page 3: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 3

Highlights

• Decentralized Parallel Architecture (DPA)

• Flexibility/Scalability

• High Quality

• High Power Density

• Safe-Swap Modules

Newave Modular Concept

Page 4: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 4

Battery

InverterBooster

Static Switch

Rectifier

The Conceptpower DPA TM Modules are fully independent and are composed of all major hardware and firmware building blocks:

• CPU (Central Processing Unit)

• All power circuits (rectifier, inverter, battery charger)

• Static switch and static switch control

• Power Management Control Panel

Control unitDisplay

Safe Swap Modules

Page 5: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 5

Safe-swap: hot insertion and removal of modules from ahost system without removing power.

In a redundant Power Protection SystemSafe-swap is achieved only if amodule may be added or replacedWithout interrupting the power to the Load and w/o having to transferthe load to the raw mains (by-pass).

High availability of power protection systems Safe scaling-up of system Easy fault recovery

Safe Swap Modules

Page 6: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 6

MX – Modules DPA (S2)

CL

AS

SIC

FR

AM

E

50kV

A

TR

IPL

E F

RA

ME

15

0kV

A

UP

GR

AD

E

FR

AM

E 2

50kV

A

24kW/30kVA 32kW/40kVA 40kW/50kVA

Safe-Swap DPA ModelsSystem Power up to 1200 kW by 30 modulesin parallel

Size : 663x225x720mm (WxHxD

43.1 kg 45.3kg 46.8 kg

Newave Modular Concept

730x800x1975240 bl. x 7/9AhMax. 379kg w/obatteries

730x800x1975Batteries externalMax. 439kg

730x800x1650280 bl. x 7/9AhMax. 309 kg w/obatteries

Page 7: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 7

Power Protection Parallel Architectures

Parallel System Architectures are designed to increase Power Protection Availability, which cannot be achieved by STANDALONE UPS’S.

These two architectures differ by the level of decentralization of their building blocks.

There are two basic Power Protection Parallel Architectures available today:

Parallel Architecture

• Central Parallel Architecture (CPA) and

• Decentralized Parallel Architecture

(DPA)TM

Page 8: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 8

In a Centralized Parallel Architectures the system is composed of common system building blocks:Centralized Parallel

Architecture (CPA)(Legancy Modular UPS)

REDUNDANT HOT-SWAP-POWER-UNIT

REDUNDANT HOT-SWAP-POWER-UNIT

REDUNDANT HOT-SWAP-POWER-UNIT

• CPU

The only Decentralized Parts are the Power Units.

CENTRALPROCESSING UNIT

CENTRAL CONTROL PANNEL

CENTRAL STATIC BYPASS SWITCH

CRITICAL LOADCRITICAL LOAD

MAINS 1MAINS 1 MAINS 2MAINS 2

CENTRAL BATTERY PACKS

Single point of failure describes any part of the system that can, if it fails, cause an interruption of required service. This can be as simple as a process failure or as catastrophic as a computer system crash.

• Control Panel

• Static Bypass Switch

• Battery

Parallel Architecture

Page 9: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 9

DPA

STATIC BP SWITCH

DPA POWER

UNIT

DPA CENTRAL PROCESSING

UNIT

DPA CONTROL PANNEL

CRITICAL LOADCRITICAL LOAD

MAINS 1MAINS 1 MAINS 2MAINS 2

DPA

STATIC BP SWITCH

DPA POWER

UNIT

DPA CENTRAL PROCESSING

UNIT

DPA CONTROL PANNEL

DPA

STATIC BP SWITCH

DPA POWER

UNIT

DPA CENTRAL PROCESSING

UNIT

DPA CONTROL PANNEL

DPA BATTERY

PACKS

DPA BATTERY

PACKS

DPA BATTERY

PACKS

Decentralized Parallel Architecture (DPA)DPATM from NEWAVE

Decentralized Parallel Architecture (DPA)TM was designed to distribute virtually the entire UPS Hardware and Software into modules in order to reduce the Single Points of Failures (SPOF). DPA includes distributed

• Control Panel

• CPU

• Power Unit

• Static bypass switch

• Separate Batteries

and

Parallel Architecture

Page 10: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 10

• Multi Master and Slave Technology through a simplified BUS Communication

• Full redundancy on inverter

Exclusively Decentralized Parallel Architecture (DPA)TM

• Each critical building block is decentralized

> No critical Single Point of Failure

• Full redundancy on Static Bypass Switch (SBS)

• Back Feed protection integrated or optional

Parallel Architecture

DPA

STATI C BP SWI TCH

DPA POWERUNI T

DPA CENTRAL PROCESSING

UNI T

DPA CONTROL PANNEL

CRITICAL LOAD

MAINS 1 MAINS 2

DPA

STATI C BP SWI TCH

DPA POWERUNI T

DPA CENTRAL PROCESSING

UNI T

DPA CONTROL PANNEL

DPA

STATI C BP SWI TCH

DPA POWERUNI T

DPA CENTRAL PROCESSING

UNI T

DPA CONTROL PANNEL

DPA BATTERY

PACKS

DPA BATTERY

PACKS

DPA BATTERY

PACKS

DPA

STATI C BP SWI TCH

DPA POWERUNI T

DPA CENTRAL PROCESSING

UNI T

DPA CONTROL PANNEL

CRITICAL LOAD

MAINS 1 MAINS 2

DPA

STATI C BP SWI TCH

DPA POWERUNI T

DPA CENTRAL PROCESSING

UNI T

DPA CONTROL PANNEL

DPA

STATI C BP SWI TCH

DPA POWERUNI T

DPA CENTRAL PROCESSING

UNI T

DPA CONTROL PANNEL

DPA BATTERY

PACKS

DPA BATTERY

PACKS

DPA BATTERY

PACKS

Page 11: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 11

Static Bypass Switch (SBS) Redundancy

To achieve highest level of availability in Multi-Module configurations it is essential that also the SBS be redundant .

DC/AC SBS

AC/DC

DC/AC SBS

AC/DC

DC/AC SBS

AC/DC

CRITICAL APPLICATION

MAINS POWER SUPPLY

In the event of a SBS-short-circuit the input contactor opens and isolates the SBS short….

The Critical Application remains on reliable inverter supply and will not switch to raw mains supply.

Exclusively Decentralized Parallel Architecture (DPA)TM

Parallel Architecture

Page 12: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 12

In-line contactors for Rectifier andBypass-Input for “back feed protection” .....increased service personnel safety

DC/AC SBS SBS SBS

CRITICAL APPLICATION

MAINS POWER SUPPLY

DC/AC DC/AC

BATT BATT BATT

AC/DC AC/DC AC/DC

In the event of a mains failure or a SBS-short there is a risk of VOLTAGE HAZARD for service personnel that might be working on UPS…

BACK FEED PROTECTION

Exclusively Decentralized Parallel Architecture (DPA)TM

Parallel Architecture

Page 13: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 13

TIER II DATA CENTRE

UPS 2

CoolingSystem

UPS 1

Distrib

utio

nBo

ard

Large space required : expensive

Large cables : expensive

Lower efficiency : high losses

Dedicated cooling system: expensive

Redundancy far from load • INITIAL INVESTMENT COST….. HIGH• TCO....... HIGH.

Right Sizing ??

Scalability & Flexibility

Page 14: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 14

Modular UPS design (pay as you growth)

Simpler and less expensive cabling

Redundancy close to point of use

Reduced floor space utilization

No dedicated cooling system

Easy to service - replacement modules

High speed of deployment

• INITIAL INVESTMENT COST… LOWER• TCO....... LOWER

Distrib

ution

Board FREE SPACE - NO UPS ROOM REQUIRED

O O O

O O O

O O O

O O O

O O O

O O O

TIER II DATA CENTRERight Sizing with Modules!!

Scalability & Flexibility

Page 15: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 15

Po

we

r [k

VA

]

Year

200 kVA

1 2 3 4 5

100 kVA

60

300 kVA

400 kVA

Load Curve

Expected Critical Load = 200kVA

200kVA 200kVA 200kVA

Exp. Critical Load = 200kVA

50kVA Module

50kVA Module50kVA Module

Standalone Configuration

Modular Configuration

500 kVA

600 kVA

WITH MODULARDESIGN, WASTED ENERGY DURING YEARS IS REDUCED !

Pay as you grow…

50kVA Module

50kVA Module

Rightsizing of the Power Protection System Over Time

Page 16: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 16

Scalability brings Flexibility

Benefits

Page 17: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

Rapid RecoveryModularity

28 March 2011 Conceptpower DPA 17

RecognitionRemote

Monitoring

Proactive Maintenance

Local Service Support

Continuous Power Protection Availability

High AvailabilityContinuous

Operation

Double Conversion Topology

Class VFI-SS–111

Fault Tolerance Redundancy

In Business Critical Applications a new availability strategy with near-zero-downtime is required to reduce the risk of threat to the business….the: Continuous Power Protection Availability

High Availibility

To achieve near-zero downtime and avoid very costly consequences of disruption of Mission Critical Applications, advanced Modular Power Protection Architectures with High Availability must be employed.

MTBF MTTR

Benefits

Page 18: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 18

Conceptpower DPA-Module

Safe-Swap Module

• Safe-Swap Modular design, minimize

service and maintenance costs

• MTTR reduction maximize your power

protection availability

• No need of skilled personnel on site

• Non need of spares, only modules for an

easy fault recovery

EnhancedServiceability

Benefits

Page 19: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 19

Eff

icie

ncy

(%

)

Load (%)

Energy Saving…Energy Saving…

9091

9293

94

95

96

97

25% 50% 75% 100%

Flat Efficiency

Results in low losses at PARTIAL and FULL load.Redundant UPS Systems operate typically at 25-75% of the rated load.

Other Modular UPS efficiency

Reduced TCO

BenefitsBenefits

Page 20: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 20

Benefits – Flat efficiency – Reduced TCO

Page 21: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 21

Benefits:• No phase compensation

filter required

• Respect power grid regulations

• Energy savings

Advanced Booster PFC circuit to provide near-unity Input PF even with partial loads.

0.5

0.6

0.7

0.8

0.9

1

25% 50% 75% 100%

Load %)

Inp

ut

PF

(%

)

Input Power Factor versus load

Reduced TCO

Benefits

Page 22: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 22

UNIQUE ELECTRICAL

PERFORMANCE

Benefits:• No gen-set oversized

required• Small

cable/fuses/breakers size

• No extra heating of transformers

Input Distortion THDI versus load

3.4

3.02.7

3

Load (%)

TH

D I

(%)

Advanced Booster PFC circuit to provide Flat THDI Curve even with partial loads.

Reduced TCO

Benefits

0

1

2

3

4

25% 50% 75% 100%

Page 23: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 23

BladeSever = Leading PF

No UPS oversize required

0

5

10

15

20

25

-0.75 -0.80 -0.85 -0.90 -0.95 1.00 0.95 0.90 0.85 0.80 0.75 0.70 0.65

- 0.90

Po

wer

(kW

)

Blade Servers have leading Power Factors andTherefore require adequate power from UPS

Conceptpower DPA provides full rated powerfrom 0.9-leading to 0.8-lagging power factor

0.801.00

CONCEPTPOWER DPATM

Blade Server Friendly Power

Benefits

Page 24: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 24

UPS’ integration with external environment

Benefits

Page 25: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 25

Blade Server – Friendly Technology (No need for UPS Power Derating)Output PF (0.8)

Reduced Harmonic Injection to Mains (No need for GENSET over-sizing)

Input THD i = < 3% (Flat THD i curve)

Reduced size of Cables and Fuses (Installation Cost Saving)

Unity Input PF=0.99 (Flat PF curve)

Small foot-print (Expensive floor-space saving)

High Power Density (342kW / m2)

Ease of handling ONE/TWO Technicians (Ease of Maintenance and Service)

Reduced weight (24kW =43.1kg, 32 kW =45.3kg 40kW=46.8kg)

Todays BENEFITSFEATURES

High Efficiency (Flat Efficiency Curve)

Energy Saving (Reduced Losses and Cooling Energy)

Back Feed protection Increased Service Personnel Safety

Summary

Benefits

Page 26: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 26

Options

• Battery charger 13 A

• Cold/black Start

• Synchro Kit

DPA modules (S2)

Page 27: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 27

Newave modular concept offers a new way of

thinking when conceiving a Data Centre

Conclusion

Scalable up to 1.5 MVA

Scalable up to 1.5 MVA

Page 28: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 28

1. Optimize capital investment and available space Pay-as-you-grow solution lowers your capital costs and increases utilization rates, while

innovative rack-based technology frees up space previously needed for infrastructure support.2. Adapt to ever-changing power requirements

No need to abandon previous investment when power density needs increase or if physically moving your data centre. Adapt to changing wattage requirements in your racks with single- or multi- branch rack-mount power distribution units.3. Accelerate speed of deployment

Electrical and physical modularity allows for rapid installation with minimal engineering.4. Lower the cost of service contracts

Simplicity of system design and intelligent modular parts lessen the dependency on expensive service contracts.5. Increase availability

Specifically engineered to deliver higher availability through proactively designed, building block architecture and reduced MTTR

10 reasons for choosing a Newave modular UPS

Conclusion

Page 29: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 29

6. Decrease mean-time-to-recovery (MTTR) Compartmentalize potential failures with system components consisting of intelligent,

maintainable modules for quick fault recovery.7. Plan for a power density that is increasing and unpredictable

Eliminate hot spots in your data centre caused by higher power densities by targeting availability where you need it most.

8. Minimize points of failure between the UPS and the critical load Move redundancy closer to the load and prevent the majority of failures that cause critical load downtime.

9. Minimize human error Simplicity of design and intelligent modules increase system availability by mitigating human error: the number one cause of critical load downtime.

10. Decrease the operating costs With efficiency up to 96% (double conversion mode), the operating costs for a Conceptpower DPA modular UPS can be >40% less compared to those for a previous generation.

10 reasons for choosing a Newave modular UPS

Conclusion

Page 30: Continuos power protection availability 28 March 20111 Newave unique MODULAR power protection concept for mission critical applications CONCEPTPOWER DPA

28 March 2011 Conceptpower DPA 30

With the modular, safe swap UPS systems, you can build your own IT-Facility to meet simultaneously and most accurately:

1) Higher Availability

2) Unmatched flexibility to changes

3) Reduced footprint

4) Lowest TCO

5) Product standardization

AND ALL THIS AT BEST POSSIBLE COST

Conclusion