Contactor A95-30-11

Embed Size (px)

Citation preview

  • 8/2/2019 Contactor A95-30-11

    1/4

    A95 A110 3-pole contactors

    45 to 55 kWAC operated

    Description

    A95 .. . A110 contactors are mainly used for control ling 3-phase motors and power circuits up to690 / 1000 V AC or 220 V DC.

    These contactors are of the block type design with:

    3 main poles

    control circuit: AC operated

    add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.

    Ordering details

    IEC UL/CSA Rated control circuit

    voltage

    Uc

    (1)

    Auxiliary

    contacts

    fitted

    Type Order code Weight

    Pkg

    (1 pce)

    Rated operational 3-phasemotorrating

    Generaluserating

    power current

    40 C400 V 690 V 480 V 600 V AC

    AC-3 AC-1kW A hp A V 50 Hz V 60 Hz kg

    45 145 60 125 24 24 0 0 A95-30-00 1SFL431001R8100 2.000

    48 48 0 0 A95-30-00 1SFL431001R8300 2.000

    110 110120 0 0 A95-30-00 1SFL431001R8400 2.000

    22 023 0 23 024 0 0 0 A9 5-30 -0 0 1SFL431 001 R80 00 2.000

    23 02 40 24 026 0 0 0 A9 5-30 -0 0 1 SFL431 001 R88 00 2.000

    38 04 00 40 041 5 0 0 A9 5-30 -0 0 1 SFL431 001 R85 00 2.000

    40 04 15 4 15 44 0 0 0 A9 5-30 -0 0 1 SFL431 001 R86 00 2.000

    55 160 75 140 24 24 0 0 A110-30-00 1SFL451001R8100 2.000

    48 48 0 0 A110-30-00 1SFL451001R8300 2.000

    110 110120 0 0 A110-30-00 1SFL451001R8400 2.000

    22 023 0 2 30 24 0 0 0 A11 0-30 -0 0 1 SFL4 510 01R800 0 2.000

    2 30 24 0 2 40 2 60 0 0 A11 0-30 -0 0 1 SFL4 510 01R880 0 2.000

    3 80 40 0 4 00 4 15 0 0 A11 0-30 -0 0 1 SFL4 510 01R850 0 2.000

    4 00 41 5 4 15 4 40 0 0 A11 0-30 -0 0 1 SFL45 10 01R860 0 2.000

    (1) Other control voltages see voltage code table.

    1SBC573242F0301

    A95-30-00

    Main dimensions mm, inches

    123.5 4.86"

    6 0.24"

    E0784D1

    20

    0.7

    9"

    10 0.39"

    6.5 0.26"

    90 3.54"

    148

    5.8

    3"

    E0783D

    A95, A110

    5/18 | ABB

    5

    1SFC101007C0201

  • 8/2/2019 Contactor A95-30-11

    2/4

  • 8/2/2019 Contactor A95-30-11

    3/4

    A95, A110 and

    AF95, AF110 3-pole contactorsMain accessories

    Main accessory fitting details

    Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted.

    Contactor

    types

    Main

    poles

    Availa ble

    auxiliary

    contacts

    Front-mounted accessories Side-mounted accessories

    Auxiliary contact blocks Auxiliary contact blocks Interlock unit

    1-pole CA5- .. 4-pole CA5- .. 2-pole CAL.. VE5-2

    A95, A110 3 0 0 0 1 to 6 x CA5-.. or 1 x CA5-.. (4-pole) + 1 to 2 x CAL18-11 or 1 x VE5-2+ 2 x 1-pole CA5-.. +1 x CAL18-11

    AF95, AF110 3 0 0 0 1 to 6 x CA5-.. or 1 x CA5-.. (4-pole) + 1 to 2 x CAL18-11 or 1 x VE5-2+ 2 x 1-pole CA5-.. +1 x CAL18-11

    Overload relays fitting details (1)Contactor types Thermal overload relays Electronic overload relays

    A95, A110 TA80DU (29...80 A) or TA110DU (65...110 A) E140DU (50...140 A)

    AF95, AF110

    The addition of an overload relay on the contactor does not prevent fitting of many other accessories as shown above.

    (1) Direct mounting - No kit required.

    Contactor and main accessories (other accessories available)

    RV5/..

    VE5-2

    CAL18-11

    TA

    overload relay

    A.. contactor

    CA5-10

    CA5-22E

    5/20 | ABB

    5

    1SFC101026C020

    1

  • 8/2/2019 Contactor A95-30-11

    4/4

    A95, A110 and

    AF95, AF110 3-pole contactorsMain accessories

    Ordering details (1)

    For contactors Auxiliarycontacts

    Type Order code Pkgqty

    Weight(1 pce)

    kg

    Front-mounted instantaneous auxiliary contact blocksA95, A1 10 and AF95, AF110 1 CA5-10 1SBN0100 10R1010 10 0.014

    1 CA5-01 1SBN010010R1001 10 0.014

    A95, A1 10 and AF95, AF110 2 2 CA5-22E 1SBN0100 40R1022 2 0.060

    Side-mounted instantaneous auxiliary contact blocksA95, A1 10 and AF95, AF110 1 1 CAL18-11 1SFN010720R1011 2 0.050

    Mechanical and electrical interlock unitA95, A1 10 and AF95, AF110 2 VE5-2 1SBN030210R1000 1 0.146

    Surge suppressorsFor contactors Rated control circuit Type Order code Pkg Weight

    voltage qty (1 pce)

    Uc

    V AC DC kg

    A95 ... A110 24...50 RV5/50 1SBN050010R1000 2 0 .015

    50...133 RV5/133 1SBN050010R1001 2 0.015

    110...250 RV5/250 1SBN050010R1002 2 0.015

    250...440 RV5/440 1SBN050010R1003 2 0.015

    A95 ... A110 24...50 RC5-2/50 1SBN050200R1000 2 0.015

    50...133 RC5-2/133 1SBN050200R1001 2 0.015

    110...250 RC5-2/250 1SBN050200R1002 2 0.015

    250...440 RC5-2/440 1SBN050200R1003 2 0.015

    Connecting links with manual motor startersA95, A1 10 and AF95, AF110 For MS495 BEA110/495 1SBN0845 06R1000 1 0.124

    Connection set for reversing contactorsA95, A1 10 and AF95, AF110 BEM110-30 1SFN0843 01R1000 1 0.450

    Mounting plate for mechanical interlocked contactorsA95, A1 10 and AF95, AF110 PN110-2 1 1SFN0943 01R1000 1 0.600

    (1) See "Main accessory fitting details" table.

    1SBC580992F0301

    CA5-10

    1SFC101033F0201

    CAL18-11

    1SBC574001F0301

    RV5/50

    01

    02

    NC

    E0085D1

    01

    02

    NC

    VE5-1, VE5-2

    Terminal marking and positioning

    A1

    A2

    A1

    A2

    31 5 31 5

    42 6 42 6

    BEM... connection set

    ABB | 5/21

    5

    1SFC101076C0201