Construction Building Mat 2009 2

Embed Size (px)

Citation preview

  • 8/3/2019 Construction Building Mat 2009 2

    1/9

    Rehabilitation of reinforced concrete axially loaded elements

    with polymer-modified cementicious mortar

    Carlo Pellegrino *, Francesca da Porto, Claudio Modena

    Department of Structural and Transportation Engineering, University of Padova, Via Marzolo 9, 35131 Padova, Italy

    a r t i c l e i n f o

    Article history:

    Received 21 November 2008Received in revised form 16 May 2009

    Accepted 18 June 2009

    Keywords:

    Reinforced concrete

    Repair mortars

    Interface

    Cracking

    Columns

    a b s t r a c t

    The aim of the paper is to investigate the compatibility and the efficiency of the rehabilitation interven-

    tion on reinforced concrete columns with polymer-modified cementicious mortar. This paper presents

    the results of experimental tests on axial behaviour of reinforced concrete columns, with square cross-

    section, repaired by polymer-modified cementicious mortar. Tests were repeated varying repair thick-

    ness, which included or did not include the steel reinforcement on one face of the square column. Despite

    this type of intervention is quite common in practice, the effect of repair thickness on the intervention

    efficiency, in relation to the existing steel reinforcement configuration, had not been previously studied

    in detail for axially loaded elements.

    Results were discussed and compared with those from control columns, which were tested in non-

    damaged, non-repaired conditions. The main findings of this work can be summarized as follows. The

    repair cannot restore the load-bearing capacity of non-damaged control columns, although they give

    acceptable results. Repairs that include the longitudinal reinforcement show good properties, with stable

    behaviour, sharing of loads, and plasticization of the material before failure, whereas thin repairs that do

    not include the reinforcement do not have adequate performance due to premature debonding. Non-lin-

    ear numerical models also confirmed the different behaviour of the two types of repair.

    2009 Elsevier Ltd. All rights reserved.

    1. Introduction

    The field of rehabilitation and strengthening of reinforced con-

    crete structural elements shows an increasing interest for existing

    constructions and various projects have been carried out around

    the world over the past two decades. Structural strengthening

    and repairing is aimed at increasing or restoring the load-bearing

    capacity of the element, due to changes in conditions of use (e.g.

    increased loading) or deterioration and damage of the concrete

    structure (for example due to environmental conditions or seismic

    events). Historically, steel has been the primary material used to

    strengthen concrete structures. Bonded steel plates or stirrups

    have been applied externally to successfully repair reinforced con-

    crete elements. However, using steel as a strengthening element

    adds additional dead load to the structure and normally requires

    corrosion protection. Externally bonded fiber-reinforced polymers

    (FRP) sheets/plates exhibit several attractive properties, such as

    low weight-to-strength ratios, non-corrosiveness, and ease of

    application. A number of experimental programs and analytical

    studies have been developed in the last few years at the University

    of Padova on flexural [19,28], shear [16,17,18] and bond behaviour

    [21,20] of FRP strengthened elements. In this context, adding or

    applying mortar, spraying concrete or mortar with the aim of reha-

    bilitating and/or strengthening of existing reinforced concrete

    structures is also a possible way of intervention with a more tradi-

    tional and common material [5].

    Emberson and Mays [1] carried out one of the first extensive

    experimental studies on the influence of mechanical and physical

    properties of repair mortars, applied on axially loaded (in tension)

    reinforced concrete elements. They numerically modelled the axial

    load transfer through repair and substrate in the linear elastic

    range. They also worked on flexural elements, and studied the ef-

    fect of repairs applied either in the compression or tension regions

    of reinforced concrete beams [2]. Following, most research focused

    on flexural elements. For example, Hassan et al. [9] tested the com-

    patibility of cementicious, polymer, and polymer-modified mortar

    repairs to concrete. Ro et al. [24] tested beams designed to fail in

    flexure, after localized artificial corrosion at midspan and localized

    patch-repair with three types of mortar (cement based, epoxy resin

    binder, and polymer-modified mortar). Park and Yang [15] tested

    eight beams repaired in the tension region with ordinary Portland

    and polymer-modified cement mortar. They varied reinforcement

    ratio and repair length. Shannag and Al-Ateek [26] tested 30

    under-reinforced concrete beams, repaired in the tension region

    with five materials: ordinary Portland cement and four types of

    fiber-reinforced cementicious materials. Once repaired, the beams

    were tested as they were or after accelerated corrosion. Nounu and

    0950-0618/$ - see front matter 2009 Elsevier Ltd. All rights reserved.doi:10.1016/j.conbuildmat.2009.06.025

    * Corresponding author. Tel./fax: +39 049 8275618.

    E-mail address: [email protected] (C. Pellegrino).

    Construction and Building Materials 23 (2009) 31293137

    Contents lists available at ScienceDirect

    Construction and Building Materials

    j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / c o n b u i l d m a t

    http://dx.doi.org/10.1016/j.conbuildmat.2009.06.025mailto:[email protected]://www.sciencedirect.com/science/journal/09500618http://www.elsevier.com/locate/conbuildmathttp://www.elsevier.com/locate/conbuildmathttp://www.sciencedirect.com/science/journal/09500618mailto:[email protected]://dx.doi.org/10.1016/j.conbuildmat.2009.06.025
  • 8/3/2019 Construction Building Mat 2009 2

    2/9

    Chaudhary [14] compared ordinary Portland cement with free

    flowing micro-concretes, obtaining better results with the latter.

    Kim et al. [12] applied fiber-reinforced cementicious materials at

    the intrados of reinforced concrete beams with and without stir-

    rups. Recently, Jumaat et al. [11] made a review of various repair

    materials and techniques for reinforced concrete beams.

    Experimental review of ten different repair methods for axially

    loaded columns, which took into account not only the structuralperformance and failure modes, but also the applicability and

    cost-efficiency of the repairs, was carried out by Ramirez [23],

    who found good results for methods based on application of

    cementicious materials. Among the wide literature on repair of

    reinforced concrete columns oriented to the seismic field (a com-

    prehensive literature review can be found in [6], few authors con-

    sidered the case of jacketing with mortar or concrete without

    adding additional reinforcement. Fukuyama et al. [7] tested eight

    damaged columns, repaired with different techniques, and found

    that replacement of cover with concrete can restore the original

    column shear strength and deflection capacity, without any in-

    crease of cross-section or steel percentage. The use of shrinkage

    compensating mortar can even improve strength, although faster

    strength degradation may occur. In general, the main aim of

    cementicious repair of concrete columns is to assist the repaired

    columns to carry the axial load, particularly when a significant

    amount of material in compression is lost due to the action of cor-

    rosion. Rahman et al. [22] numerically studied the problem of dry-

    ing shrinkage and creep in cementicious repair of reinforced

    concrete columns. Shambira and Nounu [25] experimentally

    studied the long-term behaviour of this type of intervention. They

    applied two types of localized repairs, polymer and polymer-mod-

    ified mortars, on one side of axially loaded columns. Despite the

    short-term behaviour was acceptable, the long-term behaviour

    worsened due to high shrinkage, and shrinkage forces induced par-

    asite bending in the columns. Mangat and OFlaherty [13] applied

    seven different ordinary and polymer-modified cementicious

    materials, on the unpropped compression members of two existing

    bridges. The case studies showed that repairs displayed structuralinteraction with the structure, and those made with stiff materials

    were more efficient than others, which is in disagreement with

    other results. For example, Sharif et al. [27] assessed the effective-

    ness of localized repairs on two sides of axially loaded columns.

    They applied two cementicious materials with low and high elastic

    modulus, under loaded and unloaded conditions. They demon-

    strated that repairs are structurally effective only if applied on un-

    loaded columns, or become effective only if further loads are added

    to the columns. The load distribution between the repair layer and

    the concrete is even, only if the elastic modules of the two materi-

    als are similar.

    Some issues related to the rehabilitation of reinforced concrete

    columns, such as the choice of the repair material properties and

    its geometric configuration with the aim of improving the compat-ibility of the intervention, are thus still objects of research. In this

    framework, the effect of thickness of repair material on the effi-

    ciency of rehabilitation interventions, in relation to the existing

    steel reinforcement configuration, was not studied in detail for axi-

    ally loaded elements.

    The objective of this study is to give some new insights on val-

    idating the effectiveness of repair intervention with polymer-mod-

    ified cementicious mortar repairs applied to square columns, under

    axial loads, to recover the original properties of columns. In partic-

    ular the aim is to verify the effect of repair thickness (including

    steel reinforcement or not), on cracking pattern and, in general,

    structural behaviour of axially loaded element. For this reason,

    experimental and numerical study on square columns, subjected

    to axial loads, repaired with polymer-modified cementicious mor-tar is carried out. The repair material had similar mechanical prop-

    erties, slightly higher tensile strength than the concrete substrate

    and two different thicknesses (including steel reinforcement or

    not) and was applied over the entire length of one face of the col-

    umns. Experimental results were compared in terms of cracking

    pattern, ultimate capacity, axial and transversal strains with those

    from control columns, which were tested in non-damaged, non-re-

    paired conditions.

    Simplified three-dimensional numerical models, implementingnon-linear constitutive laws for materials, were developed to sim-

    ulate the behaviour of control and repaired columns.

    2. Experimental program

    The main objective of the experimental program was to assess the static behav-

    iour under axial loading of six reinforced concrete columns repaired with polymer-

    modified cementicious material. The following subsections describe the specimens

    used for experimental testing, the materials adopted for their construction and re-

    pair, and the testing procedure.

    2.1. Design and preparation of specimens

    Six columns were made with square section of 300 300 mm area, 20 mm con-

    crete cover, 0.8 m total height. Longitudinal reinforcement was constituted by four

    12 mm diameter reinforcing bars. Stirrups having 8 mm diameter were placed at

    140 mm spacing. The six columns were divided into three test series. Two speci-

    mens were used as control columns (P00_a;b) and were tested in non-damaged/

    non-repaired conditions. Other four columns were repaired on one face. They were

    cast leaving the reinforcement non-covered with a curing process of 28 days. After

    this period, the non-covered surface was prepared. The preparation of the surface

    included roughening, cleaning of dust, powders and any impurities to improve

    the adhesion between concrete core and mortar, and wetting. The polymer-modi-

    fied cementicious mortar for repair was applied after eventual evaporation of water

    in excess.

    Repair mortar was 50 mm thick and included the longitudinal reinforcement on

    two columns (P50_a;b). 15 mm of repair mortar were sufficient to obtain the origi-

    nal 300 300 mm section on other two columns (P15_a;b). In the latter case, repair

    was intended to restore only the concrete cover. Fig. 1 shows the details and Table 1

    lists the data of the tested columns.

    2.2. Materials

    The main mechanical properties of concrete were experimentally evaluatedafter 28 days curing. Average compressive strength on 150 150 150 mm cubic

    specimens, determined from results of four samples casted during the column

    800 800

    P0_a;b

    P

    300

    800

    2 12

    300

    2 12

    300

    P15_a;b

    P

    300

    2 12

    300

    2 12

    300

    P50_a;b

    P

    300

    2 12

    300

    2 12

    300

    15 50

    Stirrup spacing 140mm

    Fig. 1. Dimensions, rebars and repairs arrangement of columns.

    3130 C. Pellegrino et al. / Construction and Building Materials 23 (2009) 31293137

  • 8/3/2019 Construction Building Mat 2009 2

    3/9

    construction was 34.8 N/mm2. Mean tensile strength, measured by splitting tests on

    three cylindrical samples having diameter 150 mm and height 300 mm, was 3.19 N/

    mm2. Elastic modulus was not measured, but according to the measured cubic com-

    pressive strength and Eurocode 2 formulations [3], it was assumed to be around

    32,500 N/mm2.

    Ribbed bars used for longitudinal reinforcement and for transversal reinforce-

    ment were both tested in tension. Mechanical properties were similar for the two

    types of bars; mean yield stress was 532 N/mm2 and mean tensile strength was

    628 N/mm2. Strain at failure was 25%.

    Finally, the cementicious material, used for repairing all columns, was pre-

    mixed, tixotropic, polymer-modified mortar with high-strength hydraulic binders

    and aggregates having maximum thickness of 4 mm. This product has high bond

    properties, low CO2 and vapour permeability, limited shrinkage. It is generally used

    for cover repair in reinforced concrete structures. Mechanical properties of the re-

    pair mortar were measured on samples having dimensions of 40 40 160 mm,

    cast during the repair interventions on columns. These samples were tested after

    28 days curing. Density of hardened mortar was 2170 kg/m3. Mean tensile strength

    deducted from six flexural tests was equal to 3.48 N/mm2. Mean cubic compressive

    strength (six samples) was 39.6 N/mm2, mean elastic modulus (three samples) was

    26,200 N/mm2. Table 2 compares the mechanical properties of the concrete support

    and the repair material. It can be seen that the measured compressive strengths dif-

    fer for 4.8 MPa, the measured tensile strengths differ for about 0.3 MPa and con-

    crete and mortar elastic modules differ for less than 10 kN/mm 2.

    2.3. Testing procedures

    Axial tests on columns were carried out monotonically, under a 10,000 kN load-

    ing machine, with loads increased between 0.5 and 2.5 kN/s. Pressure transducer

    mounted on theloadingmachine wasusedto measurethe applied loads.The control

    columns were instrumented with six strain transducers (DD1; 100 mm measuring

    base), placed at mid-height along the columns. Four DD1 were placed on two adja-

    cent orthogonal faces, two in the horizontal and two in the vertical direction, to

    measure transverse and axial strains. On the other two faces, two horizontal DD1

    were placed close to the column corners, in order to gather information on possible

    instability of the reinforcement. Two linear variable differential transducers (LVDT)

    with 600 mm measuring base were also placed vertically on two faces, to measure

    overall axial strains of the columns. For the repaired columns, other two strain

    transducers (DD1) were placed across the repair layer-concrete column interface,

    to gather information on the behaviour of the interface. The other instruments were

    placed on two adjacent orthogonal faces, one of which was repaired and the other

    left in the original conditions, in order to gather information on the behaviour of

    the repair material. Fig. 2 shows thetest setupand instrumentationon thefour sides

    of a repaired columnand some details of displacement andstrain transducers on the

    repair layer and across the interface between concrete support and mortar layer.

    3. Test results

    In thefollowing themain resultsof theexperimental programare

    shown in terms of failure modes, cracking patterns, stress vs. (axial

    and transversal) strain curves of undamaged and repaired columns.

    3.1. Failure modes and ultimate loads

    All columns showed compressive failure with crushing of con-

    crete. Vertical and sub-vertical cracks generally developed close

    to one column end, where damage was concentrated. Cracks also

    connected each other close to the column corners, with spalling

    of the reinforcement cover at corners. Differences in failure modes

    were determined by presence and thickness of the repair. Fig. 3

    shows the crack patterns of the tested columns.

    For the control columns P00_a and P00_b, failure occurred by

    crushing of concrete, respectively, at the lower and at the upper

    end of the column. Cracks had vertical or sub-vertical patterns

    and were distributed on the four column sides. Larger cracks were

    located close to the column corners and were connected to those

    on the adjacent column face. Ultimate loads reached by the control

    columns, 2929 and 2869 kN, corresponded to average stresses on

    the cross-sections of 31.0 and 31.9 N/mm2 (see Table 3).

    Columns P15_a and P15_b were repaired on one side only, with

    15 mm thick mortar layer. At failure, cracks had vertical or sub-

    vertical patterns and were distributed on the three non-repaired

    column sides. They were localized at the upper end of column

    (P15_a) and on the overall specimen height (P15_b). Larger cracks

    were located close to the column corners and were connected to

    those on the adjacent column faces. However, in both specimens,

    the repair did not crack, but clearly debonded from the concrete

    substrate (Fig. 4) at 1901 and 1575 kN, corresponding to average

    stresses on the cross-sections of 21.1 and 17.5 N/mm 2 (76% and

    58% of ultimate load). Ultimate loads were 2507 and 2709 kN,

    respectively, corresponding to average stresses on the cross-sec-

    tions of 27.9 and 30.1 N/mm2, on average 92% of the ultimate

    capacity reached by the control columns (see Table 3).

    Columns P50_a and P50_b were repaired on one side only with50 mm thick mortar layer, and showed different behaviour. Cracks

    had vertical or sub-vertical patterns at failure and were distributed

    on the four column sides, including the repaired one. The repair

    only partially debonded from the concrete substrate at the column

    corners (Fig. 5), at 2430 and 2160 kN, corresponding to average

    stresses on the cross-sections of 27.0 and 24.0 N/mm2 (93% and

    86% of ultimate load). Ultimate loads were 2606 and 2501 kN,

    respectively, and corresponded to average stresses on the cross-

    sections of 29.0 and 27.8 N/mm2, on average 90% of the ultimate

    capacity reached by the control columns (see Table 3).

    3.2. Stresses and strains

    Fig. 6 shows the stressstrain curves of three columns: withoutrepair (P00_a), with 15 mm thick repair (P15_a) and with 50 mm

    thick repair (P50_a). In these diagrams, axial strains (compression)

    are plotted positive and transversal strains (tension) negative.

    Fig. 7 compares all stressaxial strain curves, with axial strains

    measured on the non-repaired sides of the columns (above) and

    on the repairs (below; in this diagram, axial strains of control col-

    umns are left as reference values). Fig. 8 compares all stresstrans-

    versal strain curves, with transversal strains measured on the

    non-repaired sides of columns (above) and on repairs (below; in

    this diagram, transversal strains of control columns are left as

    reference values). In the diagrams of Fig. 7 and 8, axial and trans-

    versal strains are both plotted positive.

    In control columns, the strains measured on orthogonal faces

    had the same trend and the stressaxial strain relationship was al-most parabolic (see P00_a in Fig. 6). The ratio of transversal to axial

    Table 1

    Details of specimens.

    Type of element/test Section (mm2) Longitudinal reinforcement ql (%) Transversal reinforcement qw (%) Condition Designation

    Tension Compression

    Column 300 300 4U12 0.50 1U8/140 mm 0.24 Control column P00_a; P00_b

    Axial Repair 15 mm P15_a; P15_b

    Repair 50 mm P50_a; P50_b

    Table 2

    Mechanical properties of concrete and repair mortar.

    Property Concrete Mortar

    Density of hardened material (kg/m3) 2380 2168

    Mean cubic compressive strength (N/mm2) 34.8 39.6

    Mean elastic modulus (kN/mm2) 32.5a 26.2

    Mean tensile strength (N/mm2) 3.19 3.48

    a Evaluated on the basis of EN 1992-1-1.

    C. Pellegrino et al. / Construction and Building Materials 23 (2009) 31293137 3131

  • 8/3/2019 Construction Building Mat 2009 2

    4/9

    strains in the elastic phase, on average, was about 0.2. Axial

    strains at ultimate load, on average, were 2.45 103, i.e. failure

    occurred after concrete plasticization (see Table 4).

    The columns repaired with thick mortar layer (see P50_a in

    Fig. 6) showed similar behaviour. The strains measured on orthog-

    onal faces had the same trend but, in this case, they were gauged

    on the repaired and the non-repaired sides of the column, which

    were thus working together, although the repair always gave high-

    er values of strain. The ratio of transversal to axial strains mea-sured on the non-repaired sides of the columns in the elastic

    phase, on average, was around 0.22. Despite the higher strains

    measured, also the ratio of transversal to axial strains measured

    on the repairs was, on average, 0.20 (see Table 4). The repairs par-

    tially debonded at the column corners at average stress level of 90%

    of the ultimate capacity. When this circumstance occurred, repair

    mortar had already started plasticizing on both columns (average

    axial strains on repair of 2.33 103; Table 4). At that point,

    the stiffness of the repaired columns, which initially was higher

    than that of the control columns, decreased and became lower(Fig. 7). Debonding, however, was not complete since the non-re-

    STRAIN TRASDUCER

    LVDT TRASDUCER

    STRAIN

    TRASDUCERS

    LVDT TRASDUCER

    Fig. 2. Test setup and instrumentation for axial tests on columns.

    3132 C. Pellegrino et al. / Construction and Building Materials 23 (2009) 31293137

  • 8/3/2019 Construction Building Mat 2009 2

    5/9

    paired and repaired sides of the columns kept working together

    (see P50_a in Fig. 6) until reaching the ultimate load. Average axial

    strains on the non-repaired and repaired sides of P50_a and P50_b

    at ultimate load were 2.25 103 and 3.01 103, i.e. failure

    occurred with plasticization of both concrete on the non-repaired

    column sides, and mortar repairs (see Table 4).

    The columns repaired with thin mortar layer (see P15_a in

    Fig. 6) presented different behaviour. The strains measured on

    orthogonal faces, i.e. on the repaired and the non-repaired sides

    of the columns, had the same trend only during the first elastic

    phase. During this phase, the ratio of transversal to axial strains

    measured on the non-repaired sides of the columns, on average,was again around 0.21, and it was slightly lower on the repaired

    sides, where the axial strains were higher (in average 0.17; Table

    4). At stress level of 76% and 58% of the ultimate capacity (in P15_a

    and P15_b, respectively), the repairs debonded from the concrete.

    When this circumstance occurred, the repairs could not carry load

    any more, as demonstrated by the strain release (see P15_a in

    Fig. 6; axial strains of repair for P15_a and P15_b in Fig. 7 and

    transversal strain across the interface between concrete support

    and mortar layer for P15_a and P15_b in Fig. 8). In this case, plas-

    ticization had not yet started (average axial strain on repaired and

    non-repaired sides: 0.76 103 and 1.19 103; Table 4). At

    that point, the stiffness of the repaired columns, which was ini-

    tially higher than that of the control columns, decreased and be-

    came lower (Fig. 7). At ultimate load, average axial strains on thenon-repaired sides of P15_a and P15_b were 2.18 103, while

    the values on the repairs were not significant (Table 4). Failure thus

    occurred immediately after plasticization of concrete on the origi-

    nal, non-repaired portion of the columns, without any contribution

    of the mortar repairs.

    The stressstrain curves of undamaged (P00_b), and repaired

    (P15_b, P50_b) columns were not shown in Fig. 6 as they are sim-

    ilar to the corresponding (P00_a), and (P15_a, P50_a) columns.

    Stressstrain curves for P00_b, P15_b and P50_b columns are com-

    pared with the others in Figs. 7 and 8.

    4. Finite element modeling of tested columns

    Three-dimensional non-linear finite element models were usedto simulate the experimentally observed behaviour. The Straus7

    code (G+D Computing [8]) was used for the numerical analyses.

    Eight-node solid elements were used to model concrete substrate,

    while beam elements were used for the steel reinforcement. In re-

    paired columns type P15 and P50, the mortar repair was also mod-

    elled with eight-node solid elements, having properties different

    from those adopted for concrete. The interface between concrete

    substrate and mortar repair was modelled by means of link ele-

    ments with tension cut-off. Translation of nodes at the upper and

    lower bases was restrained in the two orthogonal horizontal direc-

    tions to reproduce friction between upper and lower faces of the

    columns and the loading machine plate. Simplified parabolic

    stressstrain relationships derived from Hognestad [10] wereadopted for the concrete substrate and the mortar repair, while

    elasto-plastic bilinear relationship with hardening was used for

    steel. The properties of materials were derived from the experi-

    mental tests and are listed in Table 5. The Poisson ratio of the con-

    crete and steel were assumed according to Eurocode 2 [3] and

    Eurocode 3 [4], respectively. The Poisson ratio of the mortar was

    assumed equal to that of the concrete. The described models were

    used to carry out non-linear static analyses, under constantly

    increasing loads.

    Fig. 9 compares experimental and numerical stressstrain

    curves. For the non-damaged, non-repaired columns (type P00),

    the model reproduces very well the mean stressstrain curves

    of the two tested specimens until peak value. Initial elastic stiff-

    ness and value of ultimate load are well reproduced, as can beseen by the stresstransversal strain curve and stressaxial

    strain curve. Only the latter is slightly stiffer in the model. In

    the case of columns type P15, repaired with 15 mm thick mortar

    layer the model reproduces quite well the values of initial elastic

    stiffness and ultimate load, as can be seen by the stresstrans-

    versal strain curve and stressaxial strain curve obtained on

    the non-repaired side of the column. The axial strains on the re-

    pair had trend similar to that measured on the non-repaired side

    of the column only during the first elastic phase, and the model

    still gives good results. During experimental tests, at stress level

    between 76% and 58% of the ultimate capacity, the repairs deb-

    onded from the concrete. Although the model cannot reproduce

    the subsequent strain release, the numerical curve presents a

    sudden discontinuity at the upper bound of this range of stres-ses. The model is thus able to show the debonding of repair. This

    Fig. 3. Crack pattern of columns at failure.

    C. Pellegrino et al. / Construction and Building Materials 23 (2009) 31293137 3133

  • 8/3/2019 Construction Building Mat 2009 2

    6/9

    phenomenon is also described by the model displacement in

    horizontal direction (see Fig. 10). In the case of columns type

    P50, repaired with 50 mm thick mortar layer, the model is not

    able to get the difference in the initial elastic stiffness of the ori-

    ginal column and the repair, but can average the two trends and

    does not present any discontinuity (Fig. 9), nor evidence marked

    debonding, according to experimental evidence.

    5. Discussion

    The experimental results obtained on axially loaded columns

    showed that repairs on one side of the columns could not re-estab-

    lish completely the load-bearing capacity of the non-damaged con-

    trol columns. Ultimate load of the repaired columns was on

    Table 3

    Results of axial tests.

    Column D ebonding loa d ( kN ) ( a) U ltima te loa d (k N) (b) (a )/ (b)

    P00_a 2929

    P00_b 2869

    P15_a 1901 2507 0.76

    P15_b 1575 2709 0.58

    P50_a 2430 (partial) 2606 0.93

    P50_b 2160 (partial) 2501 0.86

    Fig. 4. Failure with debonding of mortar layer (P15_b).

    Fig. 5. Cracking of mortar and along the interface (P50_a).

    3134 C. Pellegrino et al. / Construction and Building Materials 23 (2009) 31293137

  • 8/3/2019 Construction Building Mat 2009 2

    7/9

    average 91% that of the control columns. Thin repairs (15 mm),

    substituting only the reinforcement cover, showed premature deb-

    onding from the concrete substrate, on average at 67% of the ulti-

    mate load. After debonding, the repairs were not effective, as

    revealed by strain analysis, and the entire load was transferred to

    the original, non-repaired portion of the columns. When the repair

    layer included the reinforcement (50 mm thick), the global behav-

    iour of the repaired columns was improved. Debonding of repair

    from the concrete substrate was limited and occurred only at the

    column corners, on average at 90% of ultimate load. After partial

    debonding, the repairs kept on collaborating with the concrete

    support, as revealed by strain analysis. Plasticization of both con-

    crete on the non-repaired column sides and mortar repairs re-vealed that both portions of the repaired columns were

    contributing to the column capacity, even in the non-linear phaseuntil failure.

    Simplified three-dimensional numerical models, implementing

    non-linear constitutive laws for materials, could simulate fairly

    well not only the behaviour of control columns, but also that of re-

    paired columns. In the case of thin repairs, the models evidenced

    the premature debonding of the repairs. Similar models can be

    thus effectively used for assessment and design of interventions.

    6. Conclusions

    In this work an experimental investigation to control the effec-

    tiveness of polymer-modified cementicious mortar repairs applied

    to square columns under axial loads is carried out. The repair

    material had similar mechanical properties and slightly higher ten-sile strength than the concrete substrate and was applied over the

    entire length of one face of columns. The aim is to give some new

    insights on validating the effectiveness of such materials in recov-

    ering the properties of non-damaged, non-repaired columns, veri-

    fying the effect of repair thickness (including the steel

    reinforcement or not), on cracking pattern, strength and deforma-

    bility of axially loaded element.

    The main conclusions arising from the experimental tests show

    that polymer-modified cementicious mortars, with limited shrink-

    age and mechanical properties similar to those of the concrete sub-

    strate, can be effective for the repair of reinforced concrete

    columns. The effectiveness of the intervention depends also on po-

    sition and thickness of the repair layer.

    For columns repaired on one side only, the repairs cannot re-store the load-bearing capacity of non-damaged control columns,

    Average stress-strain on P00_a

    0

    5

    10

    15

    20

    25

    30

    35

    -2 0 -1.5 -1.0 -0.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    -2 0 -1.5 -1.0 -0.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    -2 0 -1.5 -1.0 -0.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    Strain [10-3]

    Stres

    s[N/mm

    2]

    transv. strain column

    transv. strain column

    axial strain column

    axial strain column

    Average stress-strain on P15_a

    0

    5

    10

    15

    20

    25

    30

    35

    Strain [10-3

    ]

    Stress[N/m

    m2]

    transv. strain column

    transv. strain interface

    transv. strain repair

    axial strain column

    axial strain repair

    Average stress-strain on P50_a

    0

    5

    10

    15

    20

    25

    30

    35

    Strain [10-3

    ]

    Stress[N/mm

    2]

    transv. s train column

    transv. strain interface

    transv. strain repair

    axial strain column

    axial strain repair

    Fig. 6. Stressstrain curves of undamaged (P00_a), and repaired (P15_a, P50_a)

    columns.

    Average stress-axial strain on column

    0

    5

    10

    15

    20

    25

    30

    35

    0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    Strain [10-3

    ]

    Stress

    [N/mm

    2]

    P00_a (column)P00_b (column)P15_a (column)P15_b (column)P50_a (column)P50_b (column)

    Average stress-axial strain on repair

    0

    5

    10

    15

    20

    25

    30

    35

    Strain [10-3

    ]

    Stress[N/mm

    2]

    P00_a (column)P00_b (column)P15_a (repair)P15_b (repair)P50_a (repair)P50_b (repair)

    Fig. 7. Stressaxial strain curves, on original column and on repair (all specimens).

    C. Pellegrino et al. / Construction and Building Materials 23 (2009) 31293137 3135

  • 8/3/2019 Construction Building Mat 2009 2

    8/9

    although they give acceptable results (91% of the ultimate capacity

    of the control columns). In any case, repairs that include the longi-

    tudinal reinforcement show good properties, with stable behav-

    iour, sharing of loads, and plasticization of the material before

    failure, whereas thin repairs that do not include the reinforcement

    do not have adequate performance due to premature debonding.

    Hence, from the practical point of view, a rehabilitation interven-tion on axially loaded elements that include the longitudinal steel

    reinforcement may be generally recommended since it is more

    effective than that involving only the concrete cover without

    including steel bars. In fact, the action of the transverse steel al-

    lows sharing of loads between the mortar and the concrete core

    until failure, avoiding premature debonding of the mortar layer,

    when the steel bars are included in the repair layer.

    Average stress-transv. strain on column

    0

    5

    10

    15

    20

    25

    30

    35

    Strain [10-3

    ]

    Stress[N/mm

    2]

    P00_a (column)P00_b (column)P15_a (column)P15_b (column)P50_a (column)P50_b (column)

    Average stress-transv. strain on repair

    0

    5

    10

    15

    20

    25

    30

    35

    Strain [10-3

    ]

    Stress[N/mm

    2]

    P00_a (column)P00_b (column)P15_a (repair)P15_b (repair)P50_a (repair)P50_b (repair)

    0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    Fig. 8. Stresstransversal strain curves, on original column and on repair (allspecimens).

    Average stress-strain on P00

    0

    5

    10

    15

    20

    25

    30

    35

    Strain [10-3

    ]

    Stress[N/m

    m2]

    P00_a transv. columnP00_b transv. column

    P00 transv. col. model

    P00_a axial columnP00_b axial column

    P00 axial col. model

    Average stress-strain on P15

    0

    5

    10

    15

    20

    25

    30

    35

    Strain [10-3

    ]

    Stress[N/mm

    2]

    P15_a transv. columnP15_b transv. columnP15 transv. col. modelP15_a axial columnP15_b axial columnP15 axial col. modelP15_a axial repairP15_b axial repairP15 axial rep. model

    Average stress-strain on P50

    0

    5

    10

    15

    20

    25

    30

    35

    Strain [10-3

    ]

    Stress[N/mm

    2]

    P50_a transv. columnP50_b transv. columnP50 transv. col. modelP50_a axial columnP50_b axial columnP50 axial col. modelP50_a axial repairP50_b axial repairP50 axial rep. model

    -2 0 -1.5 -1.0 -0.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    -2 0 -1.5 -1.0 -0.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    -2 0 -1.5 -1.0 -0.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

    Fig. 9. Experimental and numerical stressstrain curves of undamaged (P00), andrepaired (P15; P50) columns.

    Table 4

    Stresses and strains of axial tests.

    Column Stress (N/mm2) 1/3 Ultimate load (a)/(b) Stress (N/mm2) Debonding Ultimate Load

    Transv. strain (a)

    (103)

    Axial strain (b)

    (103)

    Transv. strain

    (103)

    Axial strain Stress (N/mm2) Axial Strain

    (103)

    P00_a 10.3 0.08 0.41 0.19 31.0 2.41

    P00_b 10.6 0.08 0.39 0.20 31.9 2.52

    P15_a Column 9.3 0.06 0.31 0.21 21.1 0.20 0.97 27.9 2.25

    Repair 0.09 0.51 0.18 0.23 1.30 0.79

    P15_b Column 10.0 0.06 0.30 0.21 17.5 0.13 0.55 30.1 2.11

    Repair 0.06 0.38 0.15 0.06 1.08 0.54

    P50_a Column 9.7 0.05 0.23 0.20 27.0 0.25 1.48 29.0 2.28

    Repair 0.12 0.74 0.16 0.43 2.25 3.30

    P50_b Column 9.3 0.05 0.24 0.23 24.0 0.29 1.06 27.8 2.21

    Repair 0.24 1.00 0.24 0.54 2.40 2.71

    3136 C. Pellegrino et al. / Construction and Building Materials 23 (2009) 31293137

  • 8/3/2019 Construction Building Mat 2009 2

    9/9

    The behaviour of axially loaded columns repaired with thin or

    thick repairs can be also reproduced by simplified three-dimen-

    sional non-linear finite element models.

    Acknowledgements

    The authors gratefully acknowledge Tassullo S.p.A. that pro-vided materials and specimens for experimental testing, and Eng.

    Diego Testolin for his contribution to the experimental investiga-

    tion developed during his MSc thesis. The experimental tests were

    carried out at the Laboratory of Structural Materials Testing of the

    University of Padova, Italy.

    References

    [1] Emberson NK, Mays GC. Significance of property mismatch in the patch repairof structural concrete. Part 2: Axially loaded reinforced concrete members.Mag Concrete Res 1990;42(152):16170.

    [2] Emberson NK, Mays GC. Significance of property mismatch in the patch repairof structural concrete. Part 3: Reinforced concrete members in flexure. MagConcrete Res 1996;48(174):4557.

    [3] European Committee for Standardization. Eurocode 2 Design of concretestructures. Part 1-1: General rules and rules for buildings. EN 1992-1-1,Brussels, Belgium; 2004.

    [4] European Committee for Standardization. Eurocode 3 Design of steelstructures. Part 1-1: General rules and rules for buildings. EN 1993-1-1,Brussels, Belgium; 2005.

    [5] European Committee for Standardization. Products and systems for theprotection and repair of concrete structures Definitions, requirements,quality control and evaluation of conformity. Part 3: Structural and non-structural repair. EN 1504-3, Brussels, Belgium; 2005.

    [6] Fib. Seismic assessment and retrofit of reinforced concrete buildings. State ofArt Report, Bulletin 24. Federation International du Beton: Lausanne(Switzerland); 2003.

    [7] Fukuyama K, Higashibata Y, Miyauchi Y. Studies on repair and strengtheningmethods of damaged reinforced concrete columns. Cement Concrete Compos2000;22:818.

    [8] G+D Computing. Straus7 users manual. Sydney; 2005.[9] Hassan KE, Brooks JJ, Al-Alawi L. Compatibility of repair mortars with concrete

    in a hot-dry environment. Cement Concrete Compos 2001;23:93101.[10] Hognestad E. A study of combined bending and axial load in reinforced

    concrete members, Bulletin No. 399. University of Illinois, Urbana ILUSA: Engineering Experimental Station; 1951.

    [11] Jumaat MZ, Kabir MH, Obaydullah M. A review of the repair of reinforcedconcrete beams. J Appl Sci Res 2006;2(6):31726.

    [12] Kim JHJ, Lim YM, Won JP, Park HG, Lee KM. Shear capacity and failurebehaviour of DFRCC repaired RC beams at tensile region. Eng Struct2007;29:12131. doi:10.1016/j.engstruct.2006.04.023.

    [13] Mangat PS, OFlaherty FJ. Influence of elastic modulus on stress redistributionand cracking in repair patches. Cement Concrete Res 2000;30:12536.

    [14] Nounu G, Chaudhary Z-UL-H. Reinforced concrete repair in beams. ConstrBuild Mater 1999;13:195212.

    [15] Park SK, Yang DS. Flexural behaviour of reinforced concrete beams withcementitious repair materials. Mater Struct 2005;38:32934. doi:10.1617/14051.

    [16] Pellegrino C, Modena C. FRP shear strengthening of RC beams with transversesteel reinforcement. J Compos Constr 2002;6(2):10411.

    [17] Pellegrino C, Modena C. FRP shear strengthening of RC beams: experimentalstudy and analytical modelling. ACI Struct J 2006;103(5):7208.

    [18] Pellegrino C, Modena C. An experimentally based analytical model for shearcapacity of FRP strengthened reinforced concrete beams. Mech Compos Mater2008;44(3):23144.

    [19] Pellegrino C, Modena C. Flexural strengthening of real-scale RC and PRC beams

    with end-anchored pre-tensioned FRP laminates. ACI Struct J2009;106(3):31928.[20] Pellegrino C, Modena C. Influence of FRP axial rigidity on FRP-concrete bond

    behaviour: an analytical study. Adv Struct Eng, in press.[21] Pellegrino C, Tinazzi D, Modena C. An experimental study on bond behavior

    between concrete and FRP reinforcement. J Compos Constr 2008;12(2):1809.[22] Rahman K, Baluch MH, Al-Gadhib A. Modeling of shrinkage and creep stresses

    in concrete repair. ACI Mater J 1999;96(5):54250.[23] Ramirez JL. Ten concrete column repair methods. Constr Build Mater

    1996;10:195202.[24] Ro O, Andrade C, Izquierdo D, Alonso C. Behaviour of patch-repaired concrete

    structural elements under increasing static loads to flexural failure. J Matercivil Eng 2005;17(2):16877. doi:10.1061/(ASCE)0899-1561(2005)17:2. 168.

    [25] Shambira MV, Nounu G. On the effect of time-dependent deformations on thebehaviour of patch-repaired reinforced concrete short columns. Constr BuildMater 2000;14:42532.

    [26] Shannag MJ, Al-Ateek SA. Flexural behaviour of strengthened concrete beamswith corroding reinforcement. Constr Build Mater 2006;20:83440.

    [27] Sharif A, Rahman MK, Al-Gahtani AS, Hameeduddin M. Behaviour of patch

    repair of axially loaded reinforced concrete beams. Cement Concrete Compos2006;28:73441. doi:10.1016/j.cemconcomp.2006.05.013.

    [28] Valluzzi MR, Grinzato E, Pellegrino C, Modena C. IR thermography for interfaceanalysis of FRP laminates externally bonded to RC beams. Mater Struct2009;42(1):2534.

    Table 5

    Model material properties.

    Material fc (N/mm2) ecu (%) fct (N/mm

    2) ectu (%) fy (N/mm2) ey (%) ft (N/mm

    2) et (%) E (N/mm2) m ()

    Concrete 28.90 0.18 3.19 0.01 32,500 0.20

    Mortar 32.87 0.25 3.48 0.01 26,200 0.20

    Steel 532 0.27 628 25 200,000 0.30

    Fig. 10. Model displacement in horizontal direction for P15 at debonding (left) and

    P50 at same vertical load level (right).

    C. Pellegrino et al. / Construction and Building Materials 23 (2009) 31293137 3137

    http://dx.doi.org/10.1016/j.engstruct.2006.04.023http://dx.doi.org/10.1016/j.engstruct.2006.04.023http://dx.doi.org/10.1617/14051http://dx.doi.org/10.1617/14051http://dx.doi.org/10.1061/(ASCE)0899-1561(2005)17:2http://dx.doi.org/10.1061/(ASCE)0899-1561(2005)17:2http://dx.doi.org/10.1016/j.cemconcomp.2006.05.013http://dx.doi.org/10.1016/j.cemconcomp.2006.05.013http://dx.doi.org/10.1061/(ASCE)0899-1561(2005)17:2http://dx.doi.org/10.1617/14051http://dx.doi.org/10.1617/14051http://dx.doi.org/10.1016/j.engstruct.2006.04.023