7/21/2019 Construct Not as Per AFC Drwg http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 1/9 S/N LOCATION FINDING / COMMENTS PICTURE DRAWING REFERENCE STQ REMARK SOLUTION (PDPC) 1.0 Fire water pipe Fire Hydrant construct not as per AFC drwg SSGP-05-BU-C-4302  nil To construct pipe support 2.0 Auxiliary Building 9 Door inside and outside Auxiliary Bldg shall “Air tight”, door type not as per AFC drwg. SSGP-05-BU-S-1305 (page 5/7) nil Done Refer STQ… PDPC will communicate with vendor to provide rubber seal.

Construct Not as Per AFC Drwg

Embed Size (px)

DESCRIPTION

ok

Citation preview

Page 1: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 1/9

S/N LOCATION FINDING /

COMMENTS

PICTURE DRAWING REFERENCE STQ REMARK SOLUTION

(PDPC)

1.0 Fire water

pipe

Fire Hydrant

construct not as

per AFC drwg

SSGP-05-BU-C-4302

 

nil To construct pipe

support

2.0 Auxiliary

Building

9 Door inside and

outside Auxiliary

Bldg shall “Air

tight”, door type

not as per AFC

drwg.

SSGP-05-BU-S-1305 (page 5/7) nil Done

Refer

STQ… 

PDPC will communicate

with vendor to provide

rubber seal.

Page 2: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 2/9

3.0 Fire water

Tank

Fire Water Tank

handrail using

angle steel and

not steel pipe

N/A, only shown in shop drawing. STQ-389

(TSG-

4046)

Ok/

closed

4.0 Auxiliary

Building

Additional

Inergent tank

storage

SSGP-05-BU-S-1305(page 1/7) nil

5.0 All Building

(sample

from

Auxiliary

bldg.)

Bottom of door

not as per AFC

typical Threshold

detail, all door

missing

threshold.

SSGP-05-BU-S-1305 nil

Page 3: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 3/9

 6.0 Auxiliary

Building

Level of bottom

hoop for Cage

ladder is too

height more than

max

requirement.

SSGP-00-GN-S-0004 nil Info

7.0 Utility Air

Compressor

Cage ladder

location not as

per AFC drawing

SSGP-05-BU-S-3313 nil To check

TQ

Page 4: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 4/9

8.0 Utility Air

Compressor

Toe wall not as

per AFC drawing

SSGP-05-BU-S-3313 nil Construct no TQ

9.0 Compressor

Building

A,B,C and D

Non shrink grout

shall be applied

under all majorsteel structure.

SSGP-00-GN-S-0002 nil

10.0 ADMIN

BUILDING.

Missing

10mmx10mm

drip mould at top

of all window

SSGP-05-BU-S-1306 Nil

Page 5: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 5/9

11.0 ADMIN

BUILDING.

Door install not

as per AFC

drawing.

If refer AFC drwg

this door shall

have vision

panel.

SSGP-05-BU-S-1306-A1 SHEET 1, 5 AND 6 OF 9

nil STQ for

changing

the size

and

material

of door

refer

STQ/430

Page 6: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 6/9

12.0 ADMIN

BUILDING

If refer to the

picture at the

right, we can see

opening with

louvered, but if

check AFC

drawing this

opening not exist

only 400 x 200

cutout in above

false ceiling

(actual on site

this cutout

located on left

side of door)

nil

13.0 VENT STACK

BLOW

DOWN

AREA

Steel plate not as

per spec. (see

picture PDPC

using chequered

plate) and no

blasting before

install

10mm thick plate STQ

change

the

shape

and high

available

nil

Sample from

others

platform.

Page 7: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 7/9

14.0 Auxiliary

building

1.Door D17 is

excluded panic

bar but on site

PDPC install

panic bar.

2. No skirting

SSGP-00-GN-S-0004 nil nil

Page 8: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 8/9

Page 9: Construct Not as Per AFC Drwg

7/21/2019 Construct Not as Per AFC Drwg

http://slidepdf.com/reader/full/construct-not-as-per-afc-drwg 9/9

17.0 Ditto Not as per AFC

drawing refer

door detail and

schedule

Drawing number same above