SECTION 26.11 2009-09

CONSTaNT CurrENT SpECIfICaTIONS:

TESTINg paramETErS fOr 100% INITIal

baTTEry CapaCITy

CONSTaNT CurrENT SpECIfICaTIONS:

TESTINg paramETErS fOr 100% INITIal

baTTEry CapaCITy

Page 2: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 1

High capacity in a small footprint. Frees upvaluable floor space for other equipment.

Jar to cover heat seal. Jar and cover are heatsealed and bead smoothed for a more reliable seal.

Safety vent. 3-10 psi opening pressure,self-resealing.

Color-coded terminal polarity. Provides easyterminal identification.

Heat sealed post seal. Non-corrosivepolypropylene-to-polypropylene bond is asstrong as the original material.

Interface between lead post and plastic sleeve.Coated with a viscous agent which ensures avirtually leak-free bond.

Modular steel tray. Easy to install.

Container and Cover. Polypropylene is standard.Flame retardant, UL94 V-0/28% L.O.I. is optional.

Environmentally friendly Lead-Calcium-Tin-Silverpositive plate grid alloy. Ideal for both float andcycling applications.

Space for positive plate growth. Space is providedso growth can occur away from post and cover sealsto increase battery life.

High separator compression. Reduces possibilityof loss of capacity and degradation of theplate-to-separator contact.

QUALIFICATIONS• 20 Year design life in float applications and 1200

cycles in cycle applications @ 25ºC when operated per the I&O Manual.

• Absolyte GP is qualified to stack horizontally up toeight high for use in 1997 UBC/2001 CBC SeismicZone IV (at or below grade).

• UL Recognized, ISO 9001:2000, designed to meetTelcordia SR4228.

• NEBS Level 3 Certified in certain configurations.

8

9

10

1

2

3

4

5

6

7

11

Post Access optimized for ease of maintenanceand assessment of battery health

12

8

9

7

11

3

10

1

Designed for High Performance and Sustainability

6

2

12

5

4

4

4

5

6

Page 3: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 2

6-50G056-50G076-50G096-50G13

6-90G076-90G096-90G116-90G136-90G15

3-100G133-100G153-100G173-100G193-100G213-100G233-100G253-100G273-100G293-100G313-100G331-100G391-100G451-100G511-100G571-100G631-100G691-100G751-100G811-100G871-100G931-100G99

Absolyte GP Module Weights and Dimensions

* Includes 77 mm (3") additional for Module Cover Assembly

NOTE: Design and/or specifications subject to change without notice. If questions arise, contact your local Exide sales representative for clarification. Rates shown assume connectors that are properly sized.

50G

90G

100G

MODULETYPE

VOLTS

NOMAH CAP

(8 HR)

STACKING DIMENSIONS

LENGTH HEIGHT DEPTHUNPACKED

WEIGHT

DOMESTICPACKEDWEIGHT

EXPORTPACKEDWEIGHT

IN MM IN MM IN MM LBS KG LBS KG LBS KG

12 104 17.19 437 8.53 217 16.22 412 157 71 176 80 228 104 12 152 21.69 551 8.53 217 16.22 412 209 95 228 104 280 127 12 208 26.19 665 8.53 217 16.22 412 252 114 271 123 323 147 12 312 35.19 894 8.53 217 16.22 412 356 162 381 173 433 197

12 256 21.69 551 8.53 217 23.56 599 316 143 335 152 413 187 12 344 26.19 665 8.53 217 23.56 599 396 180 415 188 493 224 12 432 30.69 780 8.53 217 23.56 599 477 216 502 228 581 264 12 520 35.19 894 8.53 217 23.56 599 557 253 582 264 661 300 12 608 39.69 1008 8.59 218 23.56 599 637 289 668 303 747 339

6 600 19.93 506 8.53 217 26.38 670 328 149 356 162 436 198 6 696 22.18 563 8.59 218 26.38 670 374 170 408 185 489 222 6 800 24.50 622 8.59 218 26.38 670 424 192 446 202 528 240 6 896 26.75 679 8.59 218 26.38 670 470 213 491 223 574 260 6 1000 29.00 737 8.59 218 26.38 670 515 234 539 245 623 283 6 1096 31.25 794 8.59 218 26.38 670 561 255 589 267 674 306 6 1200 33.50 851 8.59 218 26.38 670 608 276 637 289 723 328 6 1296 35.75 908 8.59 218 26.38 670 653 296 684 310 772 350 6 1400 38.00 965 8.59 218 26.38 670 704 319 736 334 824 374 6 1496 40.25 1022 8.59 218 26.38 670 750 340 783 355 873 396 6 1600 42.50 1080 8.59 218 26.38 670 795 361 829 376 920 417 2 1800 19.93 506 8.53 217 26.38 670 328 149 356 162 436 198 2 2088 22.18 563 8.59 218 26.38 670 374 170 408 185 489 222 2 2400 24.50 622 8.59 218 26.38 670 424 192 446 202 528 240 2 2688 26.75 679 8.59 218 26.38 670 470 213 491 223 574 260 2 3000 29.00 737 8.59 218 26.38 670 515 234 539 245 623 283 2 3288 31.25 794 8.59 218 26.38 670 561 255 589 267 674 306 2 3600 33.50 851 8.59 218 26.38 670 608 276 637 289 723 328 2 3888 35.75 908 8.59 218 26.38 670 653 296 684 310 772 350 2 4200 38.00 965 8.59 218 26.38 670 704 319 736 334 824 374 2 4488 40.25 1022 8.59 218 26.38 670 750 340 783 355 873 369 2 4800 42.50 1080 8.59 218 26.38 670 795 361 829 376 920 417

Page 4: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 3

50G05

50G09

90G07

90G11

90G15

100G13

100G17

100G21

100G25

100G29

100G33

100G45

100G57

100G69

100G81

100G93

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity Amperes to 1.75 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

CELL HOURS MINUTES

TYPE 24 12 10 8 7 6 5 4 3 2 1 30 15 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

50G

90G

100G

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

4.6 8.4 9.7 12 13 15 17 20 25 34 52 87 121 166

6.9 12.6 14.6 17 19 22 25 30 37 50 79 130 182 248

9.3 16.7 19 23 26 29 34 40 50 67 105 173 242 331

13.9 25 29 35 39 44 51 60 74 101 157 260 363 497

10.8 21.1 24.5 29 33 37 42 50 62 84 136 195 241 295

15.3 28.1 32.7 39 44 49 56 67 83 112 181 259 321 393

18.9 35.2 40.9 49 54 61 71 84 103 140 226 324 401 492

22.5 42.2 49 59 65 74 85 100 124 168 271 389 481 590

27.0 49.2 57 69 76 86 99 117 145 196 317 454 561 688

26 49 56 67 75 84 97 115 142 192 281 406 508 635

30 57 66 79 87 98 113 134 166 223 327 473 593 741

34 65 75 90 100 112 129 153 190 255 374 541 678 847

39 73 85 101 112 126 145 172 213 287 421 608 762 953

43 81 94 112 125 140 161 191 237 319 468 676 847 1059

48 89 103 123 137 154 177 210 261 351 515 744 932 1165 52 97 113 135 149 168 194 229 285 383 561 811 1016 1271

56 105 122 146 162 182 210 248 308 415 608 879 1101 1377

60 113 131 157 174 196 226 267 332 447 655 946 1186 1483

65 121 141 168 187 211 242 287 356 479 702 1014 1270 1588

69 130 150 179 199 225 258 306 379 511 749 1082 1355 1694

78 146 169 202 224 253 290 344 427 575 842 1217 1525 1906

89 170 197 236 262 295 339 401 498 670 982 1420 1779 2224

103 194 225 269 299 337 387 458 569 766 1123 1622 2033 2542

116 219 254 303 336 379 436 516 640 862 1263 1825 2287 2859

130 243 282 337 374 421 484 573 711 958 1403 2028 2541 3177

143 267 310 370 411 463 532 630 782 1053 1544 2231 2795 3495

157 291 338 404 448 505 581 688 854 1149 1684 2434 3049 3812

167 316 366 438 486 547 629 745 925 1245 1825 2636 3303 4130

181 340 394 471 523 589 678 802 996 1341 1965 2839 3557 4448

194 364 423 505 561 632 726 860 1067 1436 2105 3042 3811 4765

208 389 451 538 598 674 774 917 1138 1532 2246 3245 4065 5083

Page 5: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 4

CELL HOURS MINUTES

TYPE 24 12 10 8 7 6 5 4 3 2 1 30 15 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.78 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

4.6 8.1 9.5 11 13 14 17 20 24 33 51 83 115 156

6.9 12.2 14.2 17 19 22 25 30 37 49 77 124 172 234

9.2 16.2 19 23 25 29 33 39 49 66 102 165 230 313

13.8 24 28 34 38 43 50 59 73 99 154 248 345 469

10.8 21.1 24.4 29 32 36 42 49 61 81 130 182 222 270

15.3 28.1 32.6 39 43 49 56 66 81 109 174 243 296 360

18.9 35.1 40.7 49 54 61 70 82 101 136 217 304 371 450

22.5 42.1 49 58 65 73 84 98 121 163 261 364 445 540

27.0 49.2 57 68 76 85 97 115 142 190 304 425 519 630

25 48 56 67 74 83 96 113 140 188 276 383 475 590

30 56 65 78 86 97 111 132 163 219 321 447 554 688

34 64 75 89 99 111 127 151 186 250 367 511 633 786

39 72 84 100 111 125 143 169 210 282 413 575 712 885

43 80 93 111 123 139 159 188 233 313 459 639 791 983

47 88 102 122 136 153 175 207 256 344 505 702 870 1081

51 96 112 133 148 166 191 226 280 376 551 766 950 1180

56 104 121 144 160 180 207 245 303 407 597 830 1029 1278

60 113 130 156 173 194 223 264 326 438 643 894 1108 1376

65 121 140 167 185 208 239 282 350 470 689 958 1187 1474

68 129 149 178 197 222 255 301 373 501 735 1022 1266 1573

76 145 168 200 222 250 287 339 420 563 827 1150 1424 1769

89 169 196 233 259 291 334 395 489 657 964 1341 1662 2064

103 193 224 267 296 333 382 452 559 751 1102 1533 1899 2359

116 217 251 300 333 375 430 508 629 845 1240 1724 2137 2654

130 241 279 333 370 416 478 565 699 939 1378 1916 2374 2949

140 265 307 367 407 458 526 621 769 1033 1516 2107 2611 3244

154 289 335 400 444 499 573 678 839 1127 1653 2299 2849 3539

167 313 363 433 481 541 621 734 909 1221 1791 2491 3086 3834

181 338 391 467 518 583 669 791 979 1315 1929 2682 3324 4129

194 362 419 500 555 624 717 847 1049 1409 2067 2874 3561 4423

205 386 447 533 592 666 764 904 1119 1502 2205 3065 3798 4718

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 6: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 5

CELL HOURS MINUTES

TYPE 24 12 10 8 7 6 5 4 3 2 1 30 15 1

50G05 5.1 9.2 10 12 14 16 18 21 27 36 55 88 120 170

50G07 7.7 13 16 19 21 24 27 32 40 54 83 132 181 253

50G09 10 18 21 25 28 32 36 43 53 72 111 176 241 338

50G13 15 27 32 38 42 48 54 65 80 108 167 264 362 486

90G07 12 23 27 32 35 40 45 53 66 88 141 192 230 293

90G09 17 31 36 43 47 53 61 71 88 118 189 256 307 383

90G11 21 39 45 53 59 67 76 88 110 147 236 321 384 466

90G13 25 46 54 64 71 80 91 106 132 177 283 385 461 548

90G15 29 54 63 75 83 93 107 124 154 206 331 449 538 613

100G13 28 53 62 73 82 91 105 124 156 201 301 406 492 575

100G15 33 62 72 85 95 107 123 145 182 235 351 474 574 640

100G17 38 71 82 97 109 122 140 165 208 269 401 542 656 838

100G19 42 80 93 110 123 137 158 186 234 302 451 610 738 919

100G21 47 89 103 122 136 153 175 207 260 336 502 678 820 1004

100G23 52 98 113 134 150 168 193 228 286 369 552 745 902 1075

100G25 57 107 124 146 164 183 211 248 312 403 602 813 984 1151

100G27 61 116 134 159 177 199 228 269 338 437 652 881 1066 1212

100G29 66 125 144 171 191 214 246 290 364 470 702 949 1148 1418

100G31 71 134 155 183 205 229 263 311 390 504 753 1017 1230 1506

100G33 76 143 165 195 218 245 281 331 416 538 803 1084 1312 1577

100G39 84 159 186 219 246 273 315 372 468 603 903 1218 1476 1725

100G45 99 186 216 255 285 321 369 435 546 705 1053 1422 1722 1920

100G51 114 213 246 291 327 366 420 495 624 807 1203 1626 1968 2514

100G57 126 240 279 330 369 411 474 558 702 906 1353 1830 2214 2757

100G63 141 267 309 366 408 459 525 621 780 1008 1506 2034 2460 3012

100G69 156 294 339 402 450 504 579 684 858 1107 1656 2235 2706 3225

100G75 171 321 372 438 492 549 633 744 936 1209 1806 2439 2952 3453

100G81 183 348 402 477 531 597 684 807 1014 1311 1956 2643 3198 3636

100G87 198 375 432 513 573 642 738 870 1092 1410 2106 2847 3444 4254

100G93 213 402 465 549 615 687 789 933 1170 1512 2259 3051 3690 4518

100G99 228 429 495 585 654 735 843 993 1248 1614 2409 3252 3936 4731

Amperes to 1.80 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Page 7: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 6

CELL HOURS MINUTES

TYPE 24 12 10 8 7 6 5 4 3 2 1 30 15 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.81 Final Volts Per Cell @ 25ºC (77 ºF)

90G

50G

100G

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

4.6 8.1 9.4 11 12 14 16 19 24 32 49 78 108 143

6.9 12.1 14.0 17 19 21 24 29 36 48 74 118 161 214

9.1 16.1 19 22 25 28 32 38 47 64 98 157 215 286

13.7 24 28 34 37 42 48 57 71 96 147 235 323 429

10.8 20.8 24.1 29 32 36 41 48 59 79 124 170 204 238

14.4 27.7 32.1 38 42 48 54 64 79 105 166 227 271 317

18.9 34.6 40.1 48 53 59 68 80 98 131 207 284 339 397

22.5 41.5 48 57 64 71 82 96 118 157 248 341 407 476

26.1 48.5 56 67 74 83 95 112 138 183 290 397 475 556

25 48 55 66 73 82 94 111 136 181 268 361 434 514

30 56 65 77 85 96 110 129 159 211 313 421 507 600

33 64 74 88 97 110 126 148 182 241 357 481 579 685

38 72 83 99 110 123 141 166 204 271 402 541 652 771

42 80 92 110 122 137 157 185 227 301 447 601 724 857

47 87 101 121 134 151 173 203 250 331 491 662 797 942

50 95 111 132 146 164 188 222 272 361 536 722 869 1028

55 103 120 143 158 178 204 240 295 391 581 782 941 1113

59 111 129 154 171 192 220 259 318 421 626 842 1014 1199

64 119 138 165 183 205 235 277 341 451 670 902 1086 1285

68 127 147 176 195 219 251 296 363 481 715 962 1159 1370

76 143 166 198 219 247 282 333 409 542 804 1083 1303 1542

89 167 194 231 256 288 330 388 477 632 938 1263 1521 1799

100 191 221 264 292 329 377 443 545 722 1072 1444 1738 2056

113 215 249 297 329 370 424 499 613 812 1206 1624 1955 2313

127 239 276 330 366 411 471 554 681 903 1340 1804 2172 2570

140 262 304 363 402 452 518 610 749 993 1474 1985 2390 2827

151 286 332 396 439 493 565 665 817 1083 1609 2165 2607 3084

165 310 359 429 475 534 612 721 886 1174 1743 2346 2824 3340

178 334 387 462 512 575 659 776 954 1264 1877 2526 3041 3597

192 358 415 495 548 616 706 831 1022 1354 2011 2707 3258 3854

203 382 442 528 585 658 753 887 1090 1444 2145 2887 3476 4111

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 8: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 7

CELL HOURS

TYPE 24 12 10 8 7 6 5 4 3 2 1

50G05 .

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.83 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

4.5 7.9 9.2 11 12 14 16 19 23 31 48

6.8 11.9 13.8 17 18 21 24 28 35 47 72

9.0 15.9 18 22 24 28 32 37 46 62 96

13.6 24 28 33 37 41 47 56 69 94 143

10.8 20.5 23.7 28 31 35 40 47 58 77 118

14.4 27.3 31.6 38 42 47 54 63 77 102 158

18.0 34.1 39.5 47 52 59 67 79 96 128 197

22.5 41.0 47 56 63 70 80 94 116 154 237

26.1 47.8 55 66 73 82 94 110 135 179 276

25 47 55 65 72 81 92 109 134 177 258

29 55 64 76 84 94 108 127 156 207 301

33 63 73 87 96 108 123 145 178 237 344

38 71 82 98 108 121 139 163 201 266 386

42 79 91 108 120 135 154 181 223 296 429

46 87 100 119 132 148 170 199 245 325 472

50 95 110 130 144 162 185 218 267 355 515

55 103 119 141 156 175 200 236 290 384 558

59 111 128 152 168 189 216 254 312 414 601

63 118 137 163 180 202 231 272 334 444 644

68 126 146 174 192 216 247 290 357 473 687

76 142 164 195 216 243 277 326 401 532 773

86 166 192 228 252 283 324 381 468 621 902

100 190 219 260 288 323 370 435 535 710 1031

113 213 246 293 324 364 416 489 602 798 1159

127 237 274 325 360 404 462 544 668 887 1288

138 261 301 358 396 445 509 598 735 976 1417

151 284 329 391 432 485 555 653 802 1064 1546

165 308 356 423 468 526 601 707 869 1153 1675

176 332 383 456 504 566 647 761 936 1242 1803

189 355 411 488 540 606 694 816 1003 1331 1932

203 379 438 521 576 647 740 870 1070 1419 2061

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 9: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 8

CELL HOURS

TYPE 24 12 10 8 7 6 5 4 3 2 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.84 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

4.5 7.9 9.1 11 12 14 16 18 23 31 47

6.7 11.8 13.7 16 18 20 23 28 34 46 70

9.0 15.8 18 22 24 27 31 37 46 62 94

13.4 24 27 33 36 41 47 55 68 92 140

10.8 20.4 23.6 28 31 35 40 46 57 75 116

14.4 27.2 31.4 37 41 46 53 62 76 100 155

18.0 34.0 39.3 47 52 58 66 77 95 125 193

22.5 40.8 47 56 62 69 79 93 114 151 232

26.1 47.6 55 65 72 81 92 108 132 176 271

25 47 54 65 71 80 92 107 132 173 251

29 55 64 75 83 94 107 125 153 202 293

33 63 73 86 95 107 122 143 175 231 335

38 71 82 97 107 120 137 161 197 260 376

41 79 91 108 119 134 153 179 219 289 418

46 86 100 119 131 147 168 197 241 318 460

50 94 109 129 143 160 183 215 263 347 502

54 102 118 140 155 174 198 233 285 376 544

59 110 127 151 167 187 214 251 307 405 585

63 118 136 162 179 200 229 269 329 434 627

67 126 145 172 191 214 244 286 351 462 669

76 141 163 194 214 240 275 322 395 520 753

86 165 191 226 250 281 320 376 460 607 878

100 189 218 259 286 321 366 430 526 694 1004

113 212 245 291 322 361 412 483 592 780 1129

124 236 272 323 357 401 458 537 658 867 1254

138 259 299 356 393 441 503 591 724 954 1380

151 283 327 388 429 481 549 645 789 1041 1505

162 306 354 420 465 521 595 698 855 1127 1631

176 330 381 453 500 561 641 752 921 1214 1756

189 354 408 485 536 601 687 806 987 1301 1882

200 377 436 517 572 641 732 859 1052 1387 2007

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 10: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 9

CELL HOURS

TYPE 24 12 10 8 7 6 5 4 3 2 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.86 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

4.4 7.8 9.0 11 12 13 15 18 22 30 45

6.6 11.7 13.6 16 18 20 23 27 33 44 67

8.8 15.6 18 22 24 27 31 36 44 59 90

13.1 23 27 32 36 40 46 54 66 89 135

10.8 20.1 23.3 28 31 34 39 46 56 73 111

14.4 26.8 31.0 37 41 46 52 61 74 97 148

18.0 33.5 38.8 46 51 57 65 76 93 121 185

21.6 40.2 47 55 61 69 78 91 111 145 222

25.2 47.0 54 65 71 80 91 107 130 170 258

24 46 53 63 70 78 89 104 126 164 238

28 54 62 74 81 91 104 121 147 192 278

32 61 71 84 93 104 118 138 168 219 318

37 69 80 95 104 117 133 156 189 246 358

41 77 89 105 116 130 148 173 210 274 397

45 84 97 116 128 143 163 190 231 301 437

49 92 106 126 139 156 177 207 252 329 477

53 100 115 137 151 169 192 225 273 356 516

57 107 124 147 162 182 207 242 294 383 556

61 115 133 158 174 195 222 259 315 411 596

66 123 142 168 186 208 237 277 336 438 636

73 138 159 189 209 234 266 311 378 493 715

84 161 186 221 244 273 311 363 441 575 834

97 184 213 252 278 312 355 415 504 657 953

111 207 239 284 313 351 399 467 567 739 1073

122 230 266 315 348 389 444 519 631 821 1192

135 253 292 347 383 428 488 570 694 904 1311

146 276 319 378 418 467 532 622 757 986 1430

159 299 345 410 452 506 577 674 820 1068 1549

170 322 372 441 487 545 621 726 883 1150 1668

184 345 399 473 522 584 666 778 946 1232 1788

197 368 425 504 557 623 710 830 1009 1314 1907

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 11: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 10

CELL HOURS

TYPE 24 12 10 8 7 6 5 4 3 2 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.88 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

4.2 7.5 8.7 10 11 13 15 17 21 28 42

6.4 11.3 13.0 15 17 19 22 26 32 42 63

8.5 15.1 17 21 23 26 29 34 42 57 84

12.7 23 26 31 34 38 44 52 63 85 127

10.8 19.7 22.6 27 29 33 37 44 53 69 103

14.4 26.2 30.2 36 39 44 50 58 70 92 138

18.0 32.8 37.7 45 49 55 62 73 88 115 172

21.6 39.3 45 53 59 66 75 87 106 138 207

25.2 45.9 53 62 69 77 87 102 123 161 241

23 44 51 60 66 74 84 98 119 156 221

27 52 60 70 77 86 98 114 139 182 258

32 59 68 80 88 98 112 130 159 208 295

35 67 77 90 99 111 126 147 178 234 332

40 74 85 100 110 123 140 163 198 260 369

43 82 94 110 121 135 154 179 218 285 406

48 89 102 120 132 148 168 196 238 311 443

51 96 111 130 143 160 182 212 258 337 479

55 104 119 140 154 172 196 228 278 363 516

59 111 128 150 166 185 210 244 297 389 553

63 119 136 160 177 197 224 261 317 415 590

70 133 153 180 199 222 252 293 357 467 664

81 156 179 210 232 258 294 342 416 545 775

95 178 204 241 265 295 336 391 476 623 885

105 200 230 271 298 332 377 440 535 701 996

119 222 255 301 331 369 419 489 595 779 1107

130 245 281 331 364 406 461 538 654 856 1217

143 267 306 361 397 443 503 587 714 934 1328

154 289 332 391 430 480 545 636 773 1012 1438

165 311 357 421 463 517 587 685 833 1090 1549

178 333 383 451 497 554 629 733 892 1168 1660

189 356 408 481 530 591 671 782 952 1246 1770

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 12: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 11

CELL HOURS

TYPE 24 12 10 8 7 6 5 4 3 2 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.90 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

4.1 7.3 8.4 10 11 12 14 17 20 27 40

6.1 10.9 12.6 15 17 19 21 25 30 40 60

8.1 14.5 17 20 22 25 28 33 41 54 80

12.2 22 25 30 33 37 42 50 61 81 120

9.9 18.9 21.7 26 28 32 36 42 51 66 95

13.5 25.2 29.0 34 38 42 48 56 68 88 126

17.1 31.5 36.2 43 47 53 60 70 85 111 158

20.7 37.8 43 51 56 63 72 84 102 133 189

24.3 44.1 51 60 66 74 84 97 119 155 221

23 42 49 57 63 70 80 93 112 146 205

26 50 57 67 74 82 93 108 131 170 239

30 57 65 76 84 94 106 124 150 195 273

34 64 73 86 95 105 119 139 169 219 308

38 71 81 96 105 117 133 155 187 243 342

41 78 89 105 116 129 146 170 206 268 376

45 85 97 115 126 140 159 185 225 292 410

50 92 106 124 137 152 173 201 243 317 444

53 99 114 134 147 164 186 216 262 341 478

57 106 122 143 158 176 199 232 281 365 513

60 113 130 153 168 187 212 247 300 390 547

68 127 146 172 189 211 239 278 337 438 615

78 149 170 201 221 246 279 324 393 511 718

89 170 195 229 252 281 319 371 450 584 820

103 191 219 258 284 316 358 417 506 657 923

113 212 243 287 315 351 398 464 562 730 1025

124 234 268 315 347 386 438 510 618 803 1128

135 255 292 344 378 421 478 556 674 877 1230

149 276 317 373 410 457 518 603 730 950 1333

159 297 341 401 441 492 558 649 787 1023 1435

170 319 365 430 473 527 597 695 843 1096 1538

181 340 390 458 504 562 637 742 899 1169 1641

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 13: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 12

CELL HOURS

TYPE 24 12 10 8 7 6 5 4 3 2 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.92 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

3.9 6.7 7.8 9 10 12 13 16 19 25 37

5.8 10.1 11.7 14 16 17 20 23 29 38 56

7.7 13.5 16 19 21 23 27 31 38 51 75

11.6 20 23 28 31 35 40 47 58 76 112

9.9 18.1 20.8 25 27 30 34 40 48 62 89

12.6 24.2 27.8 33 36 40 45 53 64 82 119

16.2 30.2 34.7 41 45 50 57 66 80 103 149

19.8 36.3 42 49 54 60 68 79 95 123 178

22.5 42.3 49 57 63 70 80 92 111 144 208

22 40 46 54 59 65 74 86 104 134 185

25 47 53 63 69 76 86 100 121 157 216

29 53 61 72 79 87 99 114 138 179 247

32 60 69 81 88 98 111 129 156 201 278

36 67 76 89 98 109 123 143 173 224 309

40 74 84 98 108 120 136 157 190 246 340

43 80 92 107 118 131 148 172 207 268 371

47 87 99 116 128 142 160 186 225 291 402

50 94 107 125 137 153 173 200 242 313 433

54 100 115 134 147 164 185 215 259 336 463

58 107 122 143 157 175 197 229 276 358 494

65 120 137 161 177 196 222 257 311 403 556

76 140 160 188 206 229 259 300 363 470 649

86 160 183 215 236 262 296 343 415 537 742

97 181 206 242 265 295 333 386 467 604 834

108 201 229 268 295 327 370 429 518 671 927

119 221 252 295 324 360 407 472 570 738 102

130 241 275 322 353 393 444 515 622 805 111

140 261 298 349 383 425 481 558 674 872 1205

151 281 321 376 412 458 518 601 726 940 1298

162 301 344 403 442 491 555 644 778 1007 1390

173 321 367 430 471 524 592 687 829 1074 1483

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 14: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 13

CELL HOURS

TYPE 24 12 10 8 7 6 5 4 3 2 1

50G05

50G07

50G09

50G13

90G07

90G09

90G11

90G13

90G15

100G13

100G15

100G17

100G19

100G21

100G23

100G25

100G27

100G29

100G31

100G33

100G39

100G45

100G51

100G57

100G63

100G69

100G75

100G81

100G87

100G93

100G99

Amperes to 1.94 Final Volts Per Cell @ 25ºC (77 ºF)

50G

90G

100G

3.6 6.4 7.4 9 10 11 12 15 18 23 34

5.5 9.6 11.1 13 15 16 19 22 26 34 50

7.3 12.7 15 18 19 22 25 29 35 46 67

10.9 19 22 26 29 33 37 44 53 68 101

9.0 17.1 20 23 25 28 32 37 44 57 82

12.6 22.8 26 31 34 37 42 49 59 76 109

15.3 28.5 33 38 42 47 53 61 74 95 136

18.9 34.2 39 46 51 56 64 74 88 114 164

21.6 40 46 54 59 66 74 86 103 133 191

20 38 43 50 55 61 69 80 96 123 164

23 44 50 58 64 71 80 93 112 143 191

27 50 57 67 73 81 92 106 128 164 219

30 56 64 75 82 91 103 119 144 184 246

33 63 71 84 91 101 115 133 160 204 273

37 69 79 92 101 112 126 146 176 225 301

41 75 86 100 110 122 137 159 192 245 328

43 81 93 109 119 132 149 172 207 266 355

47 88 100 117 128 142 160 186 223 286 383

50 94 107 125 137 152 172 199 239 307 410

54 100 114 134 146 162 183 212 255 327 438

59 113 129 150 165 183 206 239 287 368 492

70 132 150 175 192 213 241 278 335 429 574

81 150 171 200 220 244 275 318 383 491 656

89 169 193 225 247 274 309 358 431 552 738

100 188 214 251 274 304 344 398 479 613 820

111 207 236 276 302 335 378 437 527 675 902

122 226 257 301 329 365 412 477 575 736 984

130 244 279 326 357 396 447 517 622 797 1066

140 263 300 351 384 426 481 557 670 859 1149

151 282 322 376 412 457 515 597 718 920 1231

162 301 343 401 439 487 550 636 766 981 1313

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Ratings represent 100% initial battery system capacity

Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity

Page 15: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 14

Absolyte GP Performance Curves @25°C (77°F)

Am

p-H

ours

/Pos

itive

Am

p-H

ours

/Pos

itive

Amps/Positive

Amps/Positive

50G Series 1 to 60 Minutes

50G Series 1 to 10 Hours

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34

60

50

40

30

20

10

0

35

30

25

20

15

10

5

020 30 40 50 60 70 80 90 100 110 120 130 140 150 160

10 89 7 6 5.5 5 4.5 4 3 2

1.5

1

1.75

1.751.50VPC

1.78

1.78

1.80

1.80

1.941.92

1.861.84

1.831.81

1.81

1.901.88

60 MIN 45 30 25 20 15

1 MIN

5

10

Page 16: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 15

Am

p-H

ours

/Pos

itive

Absolyte GP Performance Curves @25ºC (77ºF)

Am

p-H

ours

/Pos

itive

Amps/Positive

Amps/Positive

90G Series 1 to 60 Minutes

90G Series 1 to 10 Hours

30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200

1.81

60 MIN 45 30 25

1.75 1.50VPC

1.78

1.80

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60

3

1

1.5

4.5 4610 9 8 7 5.5 5 3.5 22.5

1.941.92 1.901.881.86

1.841.83

1.811.80

1.781.75

100

90

80

70

60

50

40

30

20

10

0

70656055504540353025201510

50

15

10

5

1 MIN

Page 17: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 16

Absolyte GP Performance Curves @25ºC (77ºF)

Am

p-H

ours

/Pos

itive

Am

ps-H

ours

/Pos

itive

Amps/Positive

Amps/Positive

100G Series 1 to 60 Minutes

100G Series 1 to 10 Hours0G Series 1 to 10 Hours

70

65

60

55

50

45

40

35

30

25

20

15

10

5

0

110

100

90

80

70

60

50

40

30

20

10

0

40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64

60 MIN 45 30 25 20

15

10

5

1 MIN

23

1

1.5

2.5

1.941.92

1.901.88

1.861.841.831.81

1.801.78

1.75

3.510 9 8 7 6 5.5 5 4.5 4

Page 18: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 17

% R

echa

rge

Absolyte GP Recharge Characteristics @25ºC (77ºF)

50G/90G/100G Series 2.25 Volts Per Cell Float

Time, Hours

Cha

rge

Cur

rent

, Am

ps (p

er 1

00A

H)

Vol

tage

, VPC

11010510095908580757065605550454035302520151050

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30

2.3

2.2

2.1

2

1.9

1.8

1.7

18

16

14

12

10

8

6

4

2

0

Recharge Current

% Recharge

Recharge Voltage

100% DOD

80% DOD

Page 19: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Page 18

NOTES

Page 20: CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr … GP Section 26 … · SECTION 26.11 2009-09 CONSTaNT CurrENT SpECIfICaTIONS: TESTINg paramETErS fOr 100% INITIal baTTEry

®

Exide Technologies – The Industry Leader.

Exide Technologies is a global leader in stored electrical energy solutions for all major critical reserve power applications and needs. Network power applications include communication/data networks, UPS systems for computers and control systems, electrical power generation and distribution systems, as well as a wide range of other industrial standby power applications. With a strong manufacturing base in both North America and Europe and a truly global reach (operations in more than 80 countries) in sales and service, is best positioned to satisfy your back up power needs locally as well as all over the world.

Based on over 100 years of technological innovation the leads the industry with the most recognized global brands such as ABSOLYTE®, SONNENSCHEIN®, MARATHON®, SPRINTER®, RELAY GEL®, ONYX™ and GNB FLOODED CLASSIC™. They have come to symbolize quality, reliability, performance and excellence in all the markets served.

Exide Technologies takes pride in its commitment to a bet-ter environment. Its Total Battery Management program, an integrated approach to manufacturing, distributing and recycling of lead acid batteries, has been developed toensure a safe and responsible life cycle for all of its products.

®

Powered by

Exide Technologies Industrial EnergyIllinoisUSA800.872.0471

www.exide.com

Section 26.11 2009-09

matsonmd
Callout
to ensure