SECTION 26.11 2009-09
CONSTaNT CurrENT SpECIfICaTIONS:
TESTINg paramETErS fOr 100% INITIal
baTTEry CapaCITy
CONSTaNT CurrENT SpECIfICaTIONS:
TESTINg paramETErS fOr 100% INITIal
baTTEry CapaCITy
®
Page 1
High capacity in a small footprint. Frees upvaluable floor space for other equipment.
Jar to cover heat seal. Jar and cover are heatsealed and bead smoothed for a more reliable seal.
Safety vent. 3-10 psi opening pressure,self-resealing.
Color-coded terminal polarity. Provides easyterminal identification.
Heat sealed post seal. Non-corrosivepolypropylene-to-polypropylene bond is asstrong as the original material.
Interface between lead post and plastic sleeve.Coated with a viscous agent which ensures avirtually leak-free bond.
Modular steel tray. Easy to install.
Container and Cover. Polypropylene is standard.Flame retardant, UL94 V-0/28% L.O.I. is optional.
Environmentally friendly Lead-Calcium-Tin-Silverpositive plate grid alloy. Ideal for both float andcycling applications.
Space for positive plate growth. Space is providedso growth can occur away from post and cover sealsto increase battery life.
High separator compression. Reduces possibilityof loss of capacity and degradation of theplate-to-separator contact.
QUALIFICATIONS• 20 Year design life in float applications and 1200
cycles in cycle applications @ 25ºC when operated per the I&O Manual.
• Absolyte GP is qualified to stack horizontally up toeight high for use in 1997 UBC/2001 CBC SeismicZone IV (at or below grade).
• UL Recognized, ISO 9001:2000, designed to meetTelcordia SR4228.
• NEBS Level 3 Certified in certain configurations.
8
9
10
1
2
3
4
5
6
7
11
Post Access optimized for ease of maintenanceand assessment of battery health
12
8
9
7
11
3
10
1
Designed for High Performance and Sustainability
6
2
12
5
4
4
4
5
6
®
Page 2
6-50G056-50G076-50G096-50G13
6-90G076-90G096-90G116-90G136-90G15
3-100G133-100G153-100G173-100G193-100G213-100G233-100G253-100G273-100G293-100G313-100G331-100G391-100G451-100G511-100G571-100G631-100G691-100G751-100G811-100G871-100G931-100G99
Absolyte GP Module Weights and Dimensions
* Includes 77 mm (3") additional for Module Cover Assembly
NOTE: Design and/or specifications subject to change without notice. If questions arise, contact your local Exide sales representative for clarification. Rates shown assume connectors that are properly sized.
50G
90G
100G
MODULETYPE
VOLTS
NOMAH CAP
(8 HR)
STACKING DIMENSIONS
LENGTH HEIGHT DEPTHUNPACKED
WEIGHT
DOMESTICPACKEDWEIGHT
EXPORTPACKEDWEIGHT
IN MM IN MM IN MM LBS KG LBS KG LBS KG
12 104 17.19 437 8.53 217 16.22 412 157 71 176 80 228 104 12 152 21.69 551 8.53 217 16.22 412 209 95 228 104 280 127 12 208 26.19 665 8.53 217 16.22 412 252 114 271 123 323 147 12 312 35.19 894 8.53 217 16.22 412 356 162 381 173 433 197
12 256 21.69 551 8.53 217 23.56 599 316 143 335 152 413 187 12 344 26.19 665 8.53 217 23.56 599 396 180 415 188 493 224 12 432 30.69 780 8.53 217 23.56 599 477 216 502 228 581 264 12 520 35.19 894 8.53 217 23.56 599 557 253 582 264 661 300 12 608 39.69 1008 8.59 218 23.56 599 637 289 668 303 747 339
6 600 19.93 506 8.53 217 26.38 670 328 149 356 162 436 198 6 696 22.18 563 8.59 218 26.38 670 374 170 408 185 489 222 6 800 24.50 622 8.59 218 26.38 670 424 192 446 202 528 240 6 896 26.75 679 8.59 218 26.38 670 470 213 491 223 574 260 6 1000 29.00 737 8.59 218 26.38 670 515 234 539 245 623 283 6 1096 31.25 794 8.59 218 26.38 670 561 255 589 267 674 306 6 1200 33.50 851 8.59 218 26.38 670 608 276 637 289 723 328 6 1296 35.75 908 8.59 218 26.38 670 653 296 684 310 772 350 6 1400 38.00 965 8.59 218 26.38 670 704 319 736 334 824 374 6 1496 40.25 1022 8.59 218 26.38 670 750 340 783 355 873 396 6 1600 42.50 1080 8.59 218 26.38 670 795 361 829 376 920 417 2 1800 19.93 506 8.53 217 26.38 670 328 149 356 162 436 198 2 2088 22.18 563 8.59 218 26.38 670 374 170 408 185 489 222 2 2400 24.50 622 8.59 218 26.38 670 424 192 446 202 528 240 2 2688 26.75 679 8.59 218 26.38 670 470 213 491 223 574 260 2 3000 29.00 737 8.59 218 26.38 670 515 234 539 245 623 283 2 3288 31.25 794 8.59 218 26.38 670 561 255 589 267 674 306 2 3600 33.50 851 8.59 218 26.38 670 608 276 637 289 723 328 2 3888 35.75 908 8.59 218 26.38 670 653 296 684 310 772 350 2 4200 38.00 965 8.59 218 26.38 670 704 319 736 334 824 374 2 4488 40.25 1022 8.59 218 26.38 670 750 340 783 355 873 369 2 4800 42.50 1080 8.59 218 26.38 670 795 361 829 376 920 417
®
Page 3
50G05
50G09
90G07
90G11
90G15
100G13
100G17
100G21
100G25
100G29
100G33
100G45
100G57
100G69
100G81
100G93
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity Amperes to 1.75 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
CELL HOURS MINUTES
TYPE 24 12 10 8 7 6 5 4 3 2 1 30 15 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
50G
90G
100G
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
4.6 8.4 9.7 12 13 15 17 20 25 34 52 87 121 166
6.9 12.6 14.6 17 19 22 25 30 37 50 79 130 182 248
9.3 16.7 19 23 26 29 34 40 50 67 105 173 242 331
13.9 25 29 35 39 44 51 60 74 101 157 260 363 497
10.8 21.1 24.5 29 33 37 42 50 62 84 136 195 241 295
15.3 28.1 32.7 39 44 49 56 67 83 112 181 259 321 393
18.9 35.2 40.9 49 54 61 71 84 103 140 226 324 401 492
22.5 42.2 49 59 65 74 85 100 124 168 271 389 481 590
27.0 49.2 57 69 76 86 99 117 145 196 317 454 561 688
26 49 56 67 75 84 97 115 142 192 281 406 508 635
30 57 66 79 87 98 113 134 166 223 327 473 593 741
34 65 75 90 100 112 129 153 190 255 374 541 678 847
39 73 85 101 112 126 145 172 213 287 421 608 762 953
43 81 94 112 125 140 161 191 237 319 468 676 847 1059
48 89 103 123 137 154 177 210 261 351 515 744 932 1165 52 97 113 135 149 168 194 229 285 383 561 811 1016 1271
56 105 122 146 162 182 210 248 308 415 608 879 1101 1377
60 113 131 157 174 196 226 267 332 447 655 946 1186 1483
65 121 141 168 187 211 242 287 356 479 702 1014 1270 1588
69 130 150 179 199 225 258 306 379 511 749 1082 1355 1694
78 146 169 202 224 253 290 344 427 575 842 1217 1525 1906
89 170 197 236 262 295 339 401 498 670 982 1420 1779 2224
103 194 225 269 299 337 387 458 569 766 1123 1622 2033 2542
116 219 254 303 336 379 436 516 640 862 1263 1825 2287 2859
130 243 282 337 374 421 484 573 711 958 1403 2028 2541 3177
143 267 310 370 411 463 532 630 782 1053 1544 2231 2795 3495
157 291 338 404 448 505 581 688 854 1149 1684 2434 3049 3812
167 316 366 438 486 547 629 745 925 1245 1825 2636 3303 4130
181 340 394 471 523 589 678 802 996 1341 1965 2839 3557 4448
194 364 423 505 561 632 726 860 1067 1436 2105 3042 3811 4765
208 389 451 538 598 674 774 917 1138 1532 2246 3245 4065 5083
®
Page 4
CELL HOURS MINUTES
TYPE 24 12 10 8 7 6 5 4 3 2 1 30 15 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.78 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
4.6 8.1 9.5 11 13 14 17 20 24 33 51 83 115 156
6.9 12.2 14.2 17 19 22 25 30 37 49 77 124 172 234
9.2 16.2 19 23 25 29 33 39 49 66 102 165 230 313
13.8 24 28 34 38 43 50 59 73 99 154 248 345 469
10.8 21.1 24.4 29 32 36 42 49 61 81 130 182 222 270
15.3 28.1 32.6 39 43 49 56 66 81 109 174 243 296 360
18.9 35.1 40.7 49 54 61 70 82 101 136 217 304 371 450
22.5 42.1 49 58 65 73 84 98 121 163 261 364 445 540
27.0 49.2 57 68 76 85 97 115 142 190 304 425 519 630
25 48 56 67 74 83 96 113 140 188 276 383 475 590
30 56 65 78 86 97 111 132 163 219 321 447 554 688
34 64 75 89 99 111 127 151 186 250 367 511 633 786
39 72 84 100 111 125 143 169 210 282 413 575 712 885
43 80 93 111 123 139 159 188 233 313 459 639 791 983
47 88 102 122 136 153 175 207 256 344 505 702 870 1081
51 96 112 133 148 166 191 226 280 376 551 766 950 1180
56 104 121 144 160 180 207 245 303 407 597 830 1029 1278
60 113 130 156 173 194 223 264 326 438 643 894 1108 1376
65 121 140 167 185 208 239 282 350 470 689 958 1187 1474
68 129 149 178 197 222 255 301 373 501 735 1022 1266 1573
76 145 168 200 222 250 287 339 420 563 827 1150 1424 1769
89 169 196 233 259 291 334 395 489 657 964 1341 1662 2064
103 193 224 267 296 333 382 452 559 751 1102 1533 1899 2359
116 217 251 300 333 375 430 508 629 845 1240 1724 2137 2654
130 241 279 333 370 416 478 565 699 939 1378 1916 2374 2949
140 265 307 367 407 458 526 621 769 1033 1516 2107 2611 3244
154 289 335 400 444 499 573 678 839 1127 1653 2299 2849 3539
167 313 363 433 481 541 621 734 909 1221 1791 2491 3086 3834
181 338 391 467 518 583 669 791 979 1315 1929 2682 3324 4129
194 362 419 500 555 624 717 847 1049 1409 2067 2874 3561 4423
205 386 447 533 592 666 764 904 1119 1502 2205 3065 3798 4718
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 5
CELL HOURS MINUTES
TYPE 24 12 10 8 7 6 5 4 3 2 1 30 15 1
50G05 5.1 9.2 10 12 14 16 18 21 27 36 55 88 120 170
50G07 7.7 13 16 19 21 24 27 32 40 54 83 132 181 253
50G09 10 18 21 25 28 32 36 43 53 72 111 176 241 338
50G13 15 27 32 38 42 48 54 65 80 108 167 264 362 486
90G07 12 23 27 32 35 40 45 53 66 88 141 192 230 293
90G09 17 31 36 43 47 53 61 71 88 118 189 256 307 383
90G11 21 39 45 53 59 67 76 88 110 147 236 321 384 466
90G13 25 46 54 64 71 80 91 106 132 177 283 385 461 548
90G15 29 54 63 75 83 93 107 124 154 206 331 449 538 613
100G13 28 53 62 73 82 91 105 124 156 201 301 406 492 575
100G15 33 62 72 85 95 107 123 145 182 235 351 474 574 640
100G17 38 71 82 97 109 122 140 165 208 269 401 542 656 838
100G19 42 80 93 110 123 137 158 186 234 302 451 610 738 919
100G21 47 89 103 122 136 153 175 207 260 336 502 678 820 1004
100G23 52 98 113 134 150 168 193 228 286 369 552 745 902 1075
100G25 57 107 124 146 164 183 211 248 312 403 602 813 984 1151
100G27 61 116 134 159 177 199 228 269 338 437 652 881 1066 1212
100G29 66 125 144 171 191 214 246 290 364 470 702 949 1148 1418
100G31 71 134 155 183 205 229 263 311 390 504 753 1017 1230 1506
100G33 76 143 165 195 218 245 281 331 416 538 803 1084 1312 1577
100G39 84 159 186 219 246 273 315 372 468 603 903 1218 1476 1725
100G45 99 186 216 255 285 321 369 435 546 705 1053 1422 1722 1920
100G51 114 213 246 291 327 366 420 495 624 807 1203 1626 1968 2514
100G57 126 240 279 330 369 411 474 558 702 906 1353 1830 2214 2757
100G63 141 267 309 366 408 459 525 621 780 1008 1506 2034 2460 3012
100G69 156 294 339 402 450 504 579 684 858 1107 1656 2235 2706 3225
100G75 171 321 372 438 492 549 633 744 936 1209 1806 2439 2952 3453
100G81 183 348 402 477 531 597 684 807 1014 1311 1956 2643 3198 3636
100G87 198 375 432 513 573 642 738 870 1092 1410 2106 2847 3444 4254
100G93 213 402 465 549 615 687 789 933 1170 1512 2259 3051 3690 4518
100G99 228 429 495 585 654 735 843 993 1248 1614 2409 3252 3936 4731
Amperes to 1.80 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
®
Page 6
CELL HOURS MINUTES
TYPE 24 12 10 8 7 6 5 4 3 2 1 30 15 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.81 Final Volts Per Cell @ 25ºC (77 ºF)
90G
50G
100G
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
4.6 8.1 9.4 11 12 14 16 19 24 32 49 78 108 143
6.9 12.1 14.0 17 19 21 24 29 36 48 74 118 161 214
9.1 16.1 19 22 25 28 32 38 47 64 98 157 215 286
13.7 24 28 34 37 42 48 57 71 96 147 235 323 429
10.8 20.8 24.1 29 32 36 41 48 59 79 124 170 204 238
14.4 27.7 32.1 38 42 48 54 64 79 105 166 227 271 317
18.9 34.6 40.1 48 53 59 68 80 98 131 207 284 339 397
22.5 41.5 48 57 64 71 82 96 118 157 248 341 407 476
26.1 48.5 56 67 74 83 95 112 138 183 290 397 475 556
25 48 55 66 73 82 94 111 136 181 268 361 434 514
30 56 65 77 85 96 110 129 159 211 313 421 507 600
33 64 74 88 97 110 126 148 182 241 357 481 579 685
38 72 83 99 110 123 141 166 204 271 402 541 652 771
42 80 92 110 122 137 157 185 227 301 447 601 724 857
47 87 101 121 134 151 173 203 250 331 491 662 797 942
50 95 111 132 146 164 188 222 272 361 536 722 869 1028
55 103 120 143 158 178 204 240 295 391 581 782 941 1113
59 111 129 154 171 192 220 259 318 421 626 842 1014 1199
64 119 138 165 183 205 235 277 341 451 670 902 1086 1285
68 127 147 176 195 219 251 296 363 481 715 962 1159 1370
76 143 166 198 219 247 282 333 409 542 804 1083 1303 1542
89 167 194 231 256 288 330 388 477 632 938 1263 1521 1799
100 191 221 264 292 329 377 443 545 722 1072 1444 1738 2056
113 215 249 297 329 370 424 499 613 812 1206 1624 1955 2313
127 239 276 330 366 411 471 554 681 903 1340 1804 2172 2570
140 262 304 363 402 452 518 610 749 993 1474 1985 2390 2827
151 286 332 396 439 493 565 665 817 1083 1609 2165 2607 3084
165 310 359 429 475 534 612 721 886 1174 1743 2346 2824 3340
178 334 387 462 512 575 659 776 954 1264 1877 2526 3041 3597
192 358 415 495 548 616 706 831 1022 1354 2011 2707 3258 3854
203 382 442 528 585 658 753 887 1090 1444 2145 2887 3476 4111
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 7
CELL HOURS
TYPE 24 12 10 8 7 6 5 4 3 2 1
50G05 .
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.83 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
4.5 7.9 9.2 11 12 14 16 19 23 31 48
6.8 11.9 13.8 17 18 21 24 28 35 47 72
9.0 15.9 18 22 24 28 32 37 46 62 96
13.6 24 28 33 37 41 47 56 69 94 143
10.8 20.5 23.7 28 31 35 40 47 58 77 118
14.4 27.3 31.6 38 42 47 54 63 77 102 158
18.0 34.1 39.5 47 52 59 67 79 96 128 197
22.5 41.0 47 56 63 70 80 94 116 154 237
26.1 47.8 55 66 73 82 94 110 135 179 276
25 47 55 65 72 81 92 109 134 177 258
29 55 64 76 84 94 108 127 156 207 301
33 63 73 87 96 108 123 145 178 237 344
38 71 82 98 108 121 139 163 201 266 386
42 79 91 108 120 135 154 181 223 296 429
46 87 100 119 132 148 170 199 245 325 472
50 95 110 130 144 162 185 218 267 355 515
55 103 119 141 156 175 200 236 290 384 558
59 111 128 152 168 189 216 254 312 414 601
63 118 137 163 180 202 231 272 334 444 644
68 126 146 174 192 216 247 290 357 473 687
76 142 164 195 216 243 277 326 401 532 773
86 166 192 228 252 283 324 381 468 621 902
100 190 219 260 288 323 370 435 535 710 1031
113 213 246 293 324 364 416 489 602 798 1159
127 237 274 325 360 404 462 544 668 887 1288
138 261 301 358 396 445 509 598 735 976 1417
151 284 329 391 432 485 555 653 802 1064 1546
165 308 356 423 468 526 601 707 869 1153 1675
176 332 383 456 504 566 647 761 936 1242 1803
189 355 411 488 540 606 694 816 1003 1331 1932
203 379 438 521 576 647 740 870 1070 1419 2061
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 8
CELL HOURS
TYPE 24 12 10 8 7 6 5 4 3 2 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.84 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
4.5 7.9 9.1 11 12 14 16 18 23 31 47
6.7 11.8 13.7 16 18 20 23 28 34 46 70
9.0 15.8 18 22 24 27 31 37 46 62 94
13.4 24 27 33 36 41 47 55 68 92 140
10.8 20.4 23.6 28 31 35 40 46 57 75 116
14.4 27.2 31.4 37 41 46 53 62 76 100 155
18.0 34.0 39.3 47 52 58 66 77 95 125 193
22.5 40.8 47 56 62 69 79 93 114 151 232
26.1 47.6 55 65 72 81 92 108 132 176 271
25 47 54 65 71 80 92 107 132 173 251
29 55 64 75 83 94 107 125 153 202 293
33 63 73 86 95 107 122 143 175 231 335
38 71 82 97 107 120 137 161 197 260 376
41 79 91 108 119 134 153 179 219 289 418
46 86 100 119 131 147 168 197 241 318 460
50 94 109 129 143 160 183 215 263 347 502
54 102 118 140 155 174 198 233 285 376 544
59 110 127 151 167 187 214 251 307 405 585
63 118 136 162 179 200 229 269 329 434 627
67 126 145 172 191 214 244 286 351 462 669
76 141 163 194 214 240 275 322 395 520 753
86 165 191 226 250 281 320 376 460 607 878
100 189 218 259 286 321 366 430 526 694 1004
113 212 245 291 322 361 412 483 592 780 1129
124 236 272 323 357 401 458 537 658 867 1254
138 259 299 356 393 441 503 591 724 954 1380
151 283 327 388 429 481 549 645 789 1041 1505
162 306 354 420 465 521 595 698 855 1127 1631
176 330 381 453 500 561 641 752 921 1214 1756
189 354 408 485 536 601 687 806 987 1301 1882
200 377 436 517 572 641 732 859 1052 1387 2007
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 9
CELL HOURS
TYPE 24 12 10 8 7 6 5 4 3 2 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.86 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
4.4 7.8 9.0 11 12 13 15 18 22 30 45
6.6 11.7 13.6 16 18 20 23 27 33 44 67
8.8 15.6 18 22 24 27 31 36 44 59 90
13.1 23 27 32 36 40 46 54 66 89 135
10.8 20.1 23.3 28 31 34 39 46 56 73 111
14.4 26.8 31.0 37 41 46 52 61 74 97 148
18.0 33.5 38.8 46 51 57 65 76 93 121 185
21.6 40.2 47 55 61 69 78 91 111 145 222
25.2 47.0 54 65 71 80 91 107 130 170 258
24 46 53 63 70 78 89 104 126 164 238
28 54 62 74 81 91 104 121 147 192 278
32 61 71 84 93 104 118 138 168 219 318
37 69 80 95 104 117 133 156 189 246 358
41 77 89 105 116 130 148 173 210 274 397
45 84 97 116 128 143 163 190 231 301 437
49 92 106 126 139 156 177 207 252 329 477
53 100 115 137 151 169 192 225 273 356 516
57 107 124 147 162 182 207 242 294 383 556
61 115 133 158 174 195 222 259 315 411 596
66 123 142 168 186 208 237 277 336 438 636
73 138 159 189 209 234 266 311 378 493 715
84 161 186 221 244 273 311 363 441 575 834
97 184 213 252 278 312 355 415 504 657 953
111 207 239 284 313 351 399 467 567 739 1073
122 230 266 315 348 389 444 519 631 821 1192
135 253 292 347 383 428 488 570 694 904 1311
146 276 319 378 418 467 532 622 757 986 1430
159 299 345 410 452 506 577 674 820 1068 1549
170 322 372 441 487 545 621 726 883 1150 1668
184 345 399 473 522 584 666 778 946 1232 1788
197 368 425 504 557 623 710 830 1009 1314 1907
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 10
CELL HOURS
TYPE 24 12 10 8 7 6 5 4 3 2 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.88 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
4.2 7.5 8.7 10 11 13 15 17 21 28 42
6.4 11.3 13.0 15 17 19 22 26 32 42 63
8.5 15.1 17 21 23 26 29 34 42 57 84
12.7 23 26 31 34 38 44 52 63 85 127
10.8 19.7 22.6 27 29 33 37 44 53 69 103
14.4 26.2 30.2 36 39 44 50 58 70 92 138
18.0 32.8 37.7 45 49 55 62 73 88 115 172
21.6 39.3 45 53 59 66 75 87 106 138 207
25.2 45.9 53 62 69 77 87 102 123 161 241
23 44 51 60 66 74 84 98 119 156 221
27 52 60 70 77 86 98 114 139 182 258
32 59 68 80 88 98 112 130 159 208 295
35 67 77 90 99 111 126 147 178 234 332
40 74 85 100 110 123 140 163 198 260 369
43 82 94 110 121 135 154 179 218 285 406
48 89 102 120 132 148 168 196 238 311 443
51 96 111 130 143 160 182 212 258 337 479
55 104 119 140 154 172 196 228 278 363 516
59 111 128 150 166 185 210 244 297 389 553
63 119 136 160 177 197 224 261 317 415 590
70 133 153 180 199 222 252 293 357 467 664
81 156 179 210 232 258 294 342 416 545 775
95 178 204 241 265 295 336 391 476 623 885
105 200 230 271 298 332 377 440 535 701 996
119 222 255 301 331 369 419 489 595 779 1107
130 245 281 331 364 406 461 538 654 856 1217
143 267 306 361 397 443 503 587 714 934 1328
154 289 332 391 430 480 545 636 773 1012 1438
165 311 357 421 463 517 587 685 833 1090 1549
178 333 383 451 497 554 629 733 892 1168 1660
189 356 408 481 530 591 671 782 952 1246 1770
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 11
CELL HOURS
TYPE 24 12 10 8 7 6 5 4 3 2 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.90 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
4.1 7.3 8.4 10 11 12 14 17 20 27 40
6.1 10.9 12.6 15 17 19 21 25 30 40 60
8.1 14.5 17 20 22 25 28 33 41 54 80
12.2 22 25 30 33 37 42 50 61 81 120
9.9 18.9 21.7 26 28 32 36 42 51 66 95
13.5 25.2 29.0 34 38 42 48 56 68 88 126
17.1 31.5 36.2 43 47 53 60 70 85 111 158
20.7 37.8 43 51 56 63 72 84 102 133 189
24.3 44.1 51 60 66 74 84 97 119 155 221
23 42 49 57 63 70 80 93 112 146 205
26 50 57 67 74 82 93 108 131 170 239
30 57 65 76 84 94 106 124 150 195 273
34 64 73 86 95 105 119 139 169 219 308
38 71 81 96 105 117 133 155 187 243 342
41 78 89 105 116 129 146 170 206 268 376
45 85 97 115 126 140 159 185 225 292 410
50 92 106 124 137 152 173 201 243 317 444
53 99 114 134 147 164 186 216 262 341 478
57 106 122 143 158 176 199 232 281 365 513
60 113 130 153 168 187 212 247 300 390 547
68 127 146 172 189 211 239 278 337 438 615
78 149 170 201 221 246 279 324 393 511 718
89 170 195 229 252 281 319 371 450 584 820
103 191 219 258 284 316 358 417 506 657 923
113 212 243 287 315 351 398 464 562 730 1025
124 234 268 315 347 386 438 510 618 803 1128
135 255 292 344 378 421 478 556 674 877 1230
149 276 317 373 410 457 518 603 730 950 1333
159 297 341 401 441 492 558 649 787 1023 1435
170 319 365 430 473 527 597 695 843 1096 1538
181 340 390 458 504 562 637 742 899 1169 1641
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 12
CELL HOURS
TYPE 24 12 10 8 7 6 5 4 3 2 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.92 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
3.9 6.7 7.8 9 10 12 13 16 19 25 37
5.8 10.1 11.7 14 16 17 20 23 29 38 56
7.7 13.5 16 19 21 23 27 31 38 51 75
11.6 20 23 28 31 35 40 47 58 76 112
9.9 18.1 20.8 25 27 30 34 40 48 62 89
12.6 24.2 27.8 33 36 40 45 53 64 82 119
16.2 30.2 34.7 41 45 50 57 66 80 103 149
19.8 36.3 42 49 54 60 68 79 95 123 178
22.5 42.3 49 57 63 70 80 92 111 144 208
22 40 46 54 59 65 74 86 104 134 185
25 47 53 63 69 76 86 100 121 157 216
29 53 61 72 79 87 99 114 138 179 247
32 60 69 81 88 98 111 129 156 201 278
36 67 76 89 98 109 123 143 173 224 309
40 74 84 98 108 120 136 157 190 246 340
43 80 92 107 118 131 148 172 207 268 371
47 87 99 116 128 142 160 186 225 291 402
50 94 107 125 137 153 173 200 242 313 433
54 100 115 134 147 164 185 215 259 336 463
58 107 122 143 157 175 197 229 276 358 494
65 120 137 161 177 196 222 257 311 403 556
76 140 160 188 206 229 259 300 363 470 649
86 160 183 215 236 262 296 343 415 537 742
97 181 206 242 265 295 333 386 467 604 834
108 201 229 268 295 327 370 429 518 671 927
119 221 252 295 324 360 407 472 570 738 102
130 241 275 322 353 393 444 515 622 805 111
140 261 298 349 383 425 481 558 674 872 1205
151 281 321 376 412 458 518 601 726 940 1298
162 301 344 403 442 491 555 644 778 1007 1390
173 321 367 430 471 524 592 687 829 1074 1483
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 13
CELL HOURS
TYPE 24 12 10 8 7 6 5 4 3 2 1
50G05
50G07
50G09
50G13
90G07
90G09
90G11
90G13
90G15
100G13
100G15
100G17
100G19
100G21
100G23
100G25
100G27
100G29
100G31
100G33
100G39
100G45
100G51
100G57
100G63
100G69
100G75
100G81
100G87
100G93
100G99
Amperes to 1.94 Final Volts Per Cell @ 25ºC (77 ºF)
50G
90G
100G
3.6 6.4 7.4 9 10 11 12 15 18 23 34
5.5 9.6 11.1 13 15 16 19 22 26 34 50
7.3 12.7 15 18 19 22 25 29 35 46 67
10.9 19 22 26 29 33 37 44 53 68 101
9.0 17.1 20 23 25 28 32 37 44 57 82
12.6 22.8 26 31 34 37 42 49 59 76 109
15.3 28.5 33 38 42 47 53 61 74 95 136
18.9 34.2 39 46 51 56 64 74 88 114 164
21.6 40 46 54 59 66 74 86 103 133 191
20 38 43 50 55 61 69 80 96 123 164
23 44 50 58 64 71 80 93 112 143 191
27 50 57 67 73 81 92 106 128 164 219
30 56 64 75 82 91 103 119 144 184 246
33 63 71 84 91 101 115 133 160 204 273
37 69 79 92 101 112 126 146 176 225 301
41 75 86 100 110 122 137 159 192 245 328
43 81 93 109 119 132 149 172 207 266 355
47 88 100 117 128 142 160 186 223 286 383
50 94 107 125 137 152 172 199 239 307 410
54 100 114 134 146 162 183 212 255 327 438
59 113 129 150 165 183 206 239 287 368 492
70 132 150 175 192 213 241 278 335 429 574
81 150 171 200 220 244 275 318 383 491 656
89 169 193 225 247 274 309 358 431 552 738
100 188 214 251 274 304 344 398 479 613 820
111 207 236 276 302 335 378 437 527 675 902
122 226 257 301 329 365 412 477 575 736 984
130 244 279 326 357 396 447 517 622 797 1066
140 263 300 351 384 426 481 557 670 859 1149
151 282 322 376 412 457 515 597 718 920 1231
162 301 343 401 439 487 550 636 766 981 1313
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Ratings represent 100% initial battery system capacity
Absolyte GP Performance Specifications - Constant Current Testing Parameters for 100% Initial Battery Capacity
®
Page 14
Absolyte GP Performance Curves @25°C (77°F)
Am
p-H
ours
/Pos
itive
Am
p-H
ours
/Pos
itive
Amps/Positive
Amps/Positive
50G Series 1 to 60 Minutes
50G Series 1 to 10 Hours
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34
60
50
40
30
20
10
0
35
30
25
20
15
10
5
020 30 40 50 60 70 80 90 100 110 120 130 140 150 160
10 89 7 6 5.5 5 4.5 4 3 2
1.5
1
1.75
1.751.50VPC
1.78
1.78
1.80
1.80
1.941.92
1.861.84
1.831.81
1.81
1.901.88
60 MIN 45 30 25 20 15
1 MIN
5
10
®
Page 15
Am
p-H
ours
/Pos
itive
Absolyte GP Performance Curves @25ºC (77ºF)
Am
p-H
ours
/Pos
itive
Amps/Positive
Amps/Positive
90G Series 1 to 60 Minutes
90G Series 1 to 10 Hours
30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
1.81
60 MIN 45 30 25
1.75 1.50VPC
1.78
1.80
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
3
1
1.5
4.5 4610 9 8 7 5.5 5 3.5 22.5
1.941.92 1.901.881.86
1.841.83
1.811.80
1.781.75
100
90
80
70
60
50
40
30
20
10
0
70656055504540353025201510
50
15
10
5
1 MIN
®
Page 16
Absolyte GP Performance Curves @25ºC (77ºF)
Am
p-H
ours
/Pos
itive
Am
ps-H
ours
/Pos
itive
Amps/Positive
Amps/Positive
100G Series 1 to 60 Minutes
100G Series 1 to 10 Hours0G Series 1 to 10 Hours
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
110
100
90
80
70
60
50
40
30
20
10
0
40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64
60 MIN 45 30 25 20
15
10
5
1 MIN
23
1
1.5
2.5
1.941.92
1.901.88
1.861.841.831.81
1.801.78
1.75
3.510 9 8 7 6 5.5 5 4.5 4
®
Page 17
% R
echa
rge
Absolyte GP Recharge Characteristics @25ºC (77ºF)
50G/90G/100G Series 2.25 Volts Per Cell Float
Time, Hours
Cha
rge
Cur
rent
, Am
ps (p
er 1
00A
H)
Vol
tage
, VPC
11010510095908580757065605550454035302520151050
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
2.3
2.2
2.1
2
1.9
1.8
1.7
18
16
14
12
10
8
6
4
2
0
Recharge Current
% Recharge
Recharge Voltage
100% DOD
80% DOD
®
Page 18
NOTES
®
Exide Technologies – The Industry Leader.
Exide Technologies is a global leader in stored electrical energy solutions for all major critical reserve power applications and needs. Network power applications include communication/data networks, UPS systems for computers and control systems, electrical power generation and distribution systems, as well as a wide range of other industrial standby power applications. With a strong manufacturing base in both North America and Europe and a truly global reach (operations in more than 80 countries) in sales and service, is best positioned to satisfy your back up power needs locally as well as all over the world.
Based on over 100 years of technological innovation the leads the industry with the most recognized global brands such as ABSOLYTE®, SONNENSCHEIN®, MARATHON®, SPRINTER®, RELAY GEL®, ONYX™ and GNB FLOODED CLASSIC™. They have come to symbolize quality, reliability, performance and excellence in all the markets served.
Exide Technologies takes pride in its commitment to a bet-ter environment. Its Total Battery Management program, an integrated approach to manufacturing, distributing and recycling of lead acid batteries, has been developed toensure a safe and responsible life cycle for all of its products.
®
Powered by
Exide Technologies Industrial EnergyIllinoisUSA800.872.0471
www.exide.com
Section 26.11 2009-09