Compressor carrier

Embed Size (px)

Citation preview

  • 8/20/2019 Compressor carrier

    1/115

    Container Refrigeration

    T-318 Rev A

    OPERATION AND SERVICE

    for

    69NT40-541-300 TO 399Container Refrigeration Units

    r

  • 8/20/2019 Compressor carrier

    2/115

    OPERATION AND SERVICE MANUALCONTAINER REFRIGERATION UNIT

    Models

    69NT40-541-300 to 399

  • 8/20/2019 Compressor carrier

    3/115

  • 8/20/2019 Compressor carrier

    4/115

    iiT-318

    TABLE OF CONTENTS -- Continued

    PARAGRAPH NUMBER Page

    DESCRIPTION 2--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1 GENERAL DESCRIPTION 2--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.1 Refrigeration Unit -- Front Section 2--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.2 Fresh Air Makeup Vent 2--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.3 Evaporator Section 2--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1.4 Compressor Section 2--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.5 Air-cooled Condenser Section 2--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.6 Water-Cooled Condenser Section 2--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.7 Control Box Section 2--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.8 Communications Interface Module 2--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2 REFRIGERATION SYSTEM DATA 2--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3 ELECTRICAL DATA 2--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.4 SAFETY AND PROTECTIVE DEVICES 2--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.5 REFRIGERATION CIRCUIT 2--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    MICROPROCESSOR 3--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1 TEMPERATURE CONTROL MICROPROCESSOR SYSTEM 3--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.1 Keypad 3--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.2 Display Module 3--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.3 Controller 3--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2 CONTROLLER SOFTWARE 3--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2.1 Configuration Software (Configuration Variables) 3--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2.2 Operational Software (Function Codes) 3--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3 MODES OF OPERATION 3--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.1 Temperature Control -- Perishable Mode 3--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.2 Evaporator Fan Operation 3--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.3 Defrost Interval 3--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.4 Failure Action 3--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.5 Generator Protection 3--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.6 Condenser Pressure Control 3--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.7 Arctic Mode 3--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.8 Perishable Mode -- Conventional 3--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.9 Perishable Mode -- Economy 3--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.10 Perishable Mode -- Dehumidification 3--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.11 Perishable, Dehumidification -- Bulb Mode 3--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.12 Temperature Control -- Frozen Mode 3--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.13 Frozen Mode -- Conventional 3--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.14 Frozen Mode -- Economy 3--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4 CONTROLLER ALARMS 3--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.5 UNIT PRE-TRIP DIAGNOSTICS 3--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6 DataCORDER 3--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.1 Description 3--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.2 DataCORDER Software 3--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.3 Sensor Configuration (dCF02) 3--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.4 Logging Interval (dCF03) 3--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 8/20/2019 Compressor carrier

    5/115

    iii   T-318

    TABLE OF CONTENTS -- Continued

    PARAGRAPH NUMBER Page

    3.6.5 Thermistor Format (dCF04) 3--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.6 Sampling Type (dCF05 & dCF06) 3--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.7 Alarm Configuration (dCF07 -- dCF10) 3--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.8 DataCORDER Power-Up 3--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.9 Pre-Trip Data Recording 3--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.10 DataCORDER Communications 3--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.11 USDA Cold Treatment 3--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.12 USDA Cold Treatment Procedure 3--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.13 DataCORDER Alarms 3--12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    OPERATION 4--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.1 INSPECTION (Before Starting) 4--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.2 CONNECT POWER 4--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.2.1 Connection To 380/460 VAC Power 4--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.2.2 Connection to190/230 VAC Power 4--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.3 ADJUST FRESH AIR MAKEUP VENT 4--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.3.1 Upper Fresh Air Makeup Vent 4--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.3.2 Lower Fresh Air Makeup Vent 4--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.3.3 Fresh Air Position Sensor 4--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.4 CONNECT WATER-COOLED CONDENSER 4--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.4.1 Water-Cooled Condenser with Water Pressure Switch 4--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.4.2 Water-Cooled Condenser with Condenser Fan Switch 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.5 CONNECT REMOTE MONITORING RECEPTACLE 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6 STARTING AND STOPPING INSTRUCTIONS 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6.1 Starting the Unit 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6.2 Stopping the Unit 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.7 START-UP INSPECTION 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.7.1 Physical Inspection 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.7.2 Check Controller Function Codes 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.7.3 Start Temperature Recorder 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.7.4 Complete Inspection 4--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.8 PRE-TRIP DIAGNOSIS 4--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.9 OBSERVE UNIT OPERATION 4--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.9.1 Crankcase Heater 4--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.9.2 Probe Check 4--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.10 SEQUENCE OF OPERATION 4--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.10.1 Sequence of Operation -- Perishable Mode Cooling 4--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.10.2 Sequence of Operation -- Perishable Mode Heating 4--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.10.3 Sequence of Operation -- Frozen Mode Cooling 4--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.10.4 Sequence of Operation -- Defrost 4--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.11 EMERGENCY OPERATION 4--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.11.1 Emergency Bypass Operation 4--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.11.2 Emergency Defrost Operation 4--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.12 ARCTIC MODE 4--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    TROUBLESHOOTING 5--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.1 UNIT WILL NOT START OR STARTS THEN STOPS 5--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 8/20/2019 Compressor carrier

    6/115

    ivT-318

    TABLE OF CONTENTS -- Continued

    PARAGRAPH NUMBER Page

    5.2 UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING 5--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING 5--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING 5--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.5 UNIT WILL NOT TERMINATE HEATING 5--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.6 UNIT WILL NOT DEFROST PROPERLY 5--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.7 ABNORMAL PRESSURES (COOLING) 5--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.8 ABNORMAL NOISE OR VIBRATIONS 5--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.9 CONTROLLER MALFUNCTION 5--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.10 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW 5--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.11 THERMOSTATIC EXPANSION VALVE MALFUNCTION 5--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.12 AUTOTRANSFORMER MALFUNCTION 5--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.13 WATER-COOLED CONDENSER OR WATER PRESSURE SWITCH 5--4. . . . . . . . . . . . . . . . . . . . . . . .

    SERVICE 6--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.1 SECTION LAYOUT 6--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.2 SERVICE VALVES 6--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.3 MANIFOLD GAUGE SET 6--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.4 PUMPING THE UNIT DOWN 6--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.5 REFRIGERANT LEAK CHECKING 6--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.6 EVACUATION AND DEHYDRATION 6--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.6.1 General 6--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.6.2 Preparation 6--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.6.3 Procedure - Complete System 6--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.6.4 Procedure - Partial System 6--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.7 REFRIGERANT CHARGE 6--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.7.1 Checking the Refrigerant Charge 6--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.7.2 Adding Refrigerant to System (Full Charge) 6--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.7.3 Adding Refrigerant to System (Partial Charge) 6--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.8 COMPRESSOR 6--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.8.1 Removal and Replacement of Compressor 6--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.8.2 Compressor Disassembly 6--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.8.3 Compressor Reassembly 6--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.8.4 Preparation 6--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.8.5 Installing the Components 6--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.8.6 Compressor Oil Level 6--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.9 HIGH PRESSURE SWITCH 6--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.9.1 Replacing High Pressure Switch 6--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.9.2 Checking High Pressure Switch 6--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.10 CONDENSER COIL 6--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.11 CONDENSER FAN AND MOTOR ASSEMBLY 6--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.12 WATER-COOLED CONDENSER CLEANING 6--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.13 FILTER-DRIER 6--12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.14 THERMOSTATIC EXPANSION VALVE 6--12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.14.1 Checking Superheat 6--13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.14.2 Expansion Valve Replacement 6--13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 8/20/2019 Compressor carrier

    7/115

    v   T-318

    TABLE OF CONTENTS -- Continued

    PARAGRAPH NUMBER Page

    6.15 EVAPORATOR COIL AND HEATER ASSEMBLY 6--14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.15.1 Evaporator Coil Replacement 6--14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.15.2 Evaporator Heater Replacement 6--14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.16 EVAPORATOR FAN AND MOTOR ASSEMBLY 6--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.16.1 Replacing the Evaporator Fan Assembly 6--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.16.2 Disassemble the Evaporator Fan Assembly 6--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.16.3 Assemble the Evaporator Fan Assembly 6--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.17 EVAPORATOR FAN MOTOR CAPACITOR 6--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.17.1 When To Check For A Defective Capacitor 6--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.17.2 Removing the Capacitor 6--16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.17.3 Checking the Capacitor 6--16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.18 SUCTION MODULATION VALVE 6--16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.18.1 Pre-check Procedure 6--16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.18.2 Checking the Stepper Valve 6--17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.18.3 Checking the Controller 6--17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.18.4 Emergency Repair Procedures 6--17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.19 DPRV CHECK PROCEDURE 6--17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.20 AUTOTRANSFORMER 6--18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.21 CONTROLLER 6--18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.21.1 Handling Controller 6--18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.21.2 Controller Troubleshooting 6--19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.21.3 Controller Programming Procedure 6--19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.21.4 Removing and Installing the Controller 6--20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.21.5 Battery Replacement 6--20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.22 TEMPERATURE SENSOR SERVICE 6--20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.22.1 Sensor Checkout Procedure 6--20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.22.2 Sensor Replacement 6--20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.22.3 Sensor Re-Installation 6--21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.23 VENT POSITION SENSOR (VPS) 6--22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.24 ELECTRONIC PARTLOW TEMPERATURE RECORDER 6--23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.24.1 Replacing the Recorder 6--23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.24.2 Changing the Chart 6--23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.24.3 Adjusting the Recorder Stylus 6--24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.24.4 Rezeroing the Recording Thermometer 6--24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.24.5 Rezeroing the Recording Thermometer 6--25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.25 MAINTENANCE OF PAINTED SURFACES 6--25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.26 COMPOSITE CONTROL BOX REPAIRS 6--25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.27 COMMUNICATIONS INTERFACE MODULE INSTALLATION 6--28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.28 POWER FACTOR CORRECTOR CAPACITORS (PFC) 6--28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    ELECTRICAL WIRING SCHEMATIC 7--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7.1 INTRODUCTION 7--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 8/20/2019 Compressor carrier

    8/115

    viT-318

    LIST OF ILLUSTRATIONS

    FIGURE NUMBER Page

    Figure 2-1 Refrigeration Unit -- Front Section 2--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 2-2 Evaporator Section -- Units With Center Access Panel 2--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 2-3 Compressor Section 2--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 2-4 Condenser Section 2--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 2-5 Water-Cooled Condenser Section 2--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 2-6 Control Box Section 2--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Figure 2-7 Refrigeration Circuit Schematic 2--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 3-1 Temperature Control System 3--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 3-2 Keypad 3--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 3-3 Display Module 3--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 3-4 Micro-Link 3 Controller 3--3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 3-5 Standard Configuration Report 3--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 3-6 Data Reader 3--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 4-1 Autotransformer 4--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 4-2 Make Up Air Flow Chart 4--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 4-3 Controller Operation -- Perishable Mode 4--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Figure 4-4 Controller Operation -- Frozen Mode 4--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 4-5 Perishable Mode Cooling 4--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 4-6 Perishable Mode Heating 4--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 4-7 Frozen Mode 4--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 4-8 Defrost 4--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-1 Service Valve 6--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-2 Manifold Gauge Set 6--1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-3 R-134a Manifold Gauge/Hose Set 6--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-4 Refrigeration System Service Connections 6--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-5 Compressor Service Connections 6--4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-6 Compressor 6--5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-7 Exploded View of Valve Plate 6--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-8 Bottom Plate Removed 6--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-9 Oil Pump and Bearing Head 6--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-10 Low Profile Oil Pump 6--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-11 Motor End Cover 6--7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-12 Equalizing Tube and Lock Screw Assembly 6--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-13 Crankshaft Assembly 6--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-14 Suction Valve & Positioning Springs 6--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-15 Piston Ring 6--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-16 High Pressure Switch Testing 6--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-17 Water-Cooled Condenser Cleaning -- Forced Circulation 6--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-18 Water Cooled Condenser Cleaning - Gravity Circulation 6--12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-19 Thermostatic Expansion Valve Bulb 6--13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-20 Thermostatic Expansion Valve 6--13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-21 Hermetic Thermostatic Expansion Valve Brazing Procedure 6--13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-22 Hermetic Thermostatic Expansion Valve Bulb Location 6--14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-23 Evaporator Fan Assembly 6--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-24 Suction Modulation Valve (SMV) 6--16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 8/20/2019 Compressor carrier

    9/115

    vii   T-318

    LIST OF ILLUSTRATIONS -- Continued

    FIGURE NUMBER Page

    Figure 6-25 DPRV Replacement Value Chart 6--18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-26 Controller Section of the Control Box 6--18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-27 Sensor Types 6--21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-28 Sensor and Cable Splice 6--21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-29 Supply Sensor Positioning 6--22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-30 Return Sensor Positioning 6--22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-31 Electronic Partlow Temperature Recorder 6--24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-32 Door Hinge Repair 6--26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-33 Insert Location 6--27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-34 Communications Interface Installation 6--28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 6-35 R-134a Compressor Pressure and Motor Current Curves Versus Ambient Temperature 6--32. . . . .

    Figure 6-35 R-134a Compressor Pressure and Motor Current Curves Versus Ambient Temperature 6--33. . . . .

    Figure 7-1 Legend 7--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 7-2 SCHEMATIC DIAGRAM -- Units with Normal Evaporator Fan Capability 7--3. . . . . . . . . . . . . . . . . . . .

    Figure 7-3 SCHEMATIC DIAGRAM -- Units with Single Evaporator Fan Capability 7--4. . . . . . . . . . . . . . . . . . . .

    Figure 7-4 SCHEMATIC DIAGRAM -- TransFRESH and Vent Position Sensors (VPS) 7--5. . . . . . . . . . . . . . . . .

    Figure 7-5 SCHEMATIC DIAGRAM -- Emergency Bypass 7--6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Figure 7-6 SCHEMATIC DIAGRAM, WIRING DIAGRAM -- Electronic Partlow Recorder 7--7. . . . . . . . . . . . . . .

    Figure 7-7 UNIT WIRING DIAGRAM -- Units with Normal Evaporator Fan Capability 7--8. . . . . . . . . . . . . . . . . .

    Figure 7-8 UNIT WIRING DIAGRAM -- Units with Single Evaporator Fan Capability 7--10. . . . . . . . . . . . . . . . . . .

    LIST OF TABLES

    TABLE NUMBER Page

    Table 2-1 Safety and Protective Devices 2--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-1 Keypad Function 3--2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-2 DataCORDER Configuration Variables 3--8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-3 DataCORDER Standard Configurations 3--9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-4 Controller Configuration Variables 3--13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-5 Controller Function Codes 3--14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-6 Controller Alarm Indications 3--18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-7 Controller Pre-Trip Test Codes 3--21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-8 DataCORDER Function Code Assignments 3--25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-9 DataCORDER Pre-Trip Result Records 3--26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 3-10 DataCORDER Alarm Indications 3--27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Table 6-1 Sensor Temperature/Resistance Chart 6--20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 6-2 Crack, Chip & Hole Repair Kit 6--26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 6-3 Insert Repair Kit 6--26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 6-4 Drill Information 6--26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 6-5 Recommended Bolt Torque Values 6--29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 6-6 Wear Limits For Compressors 6--29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 6-7 Compressor Torque Values 6--30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Table 6-8 R-134a Temperature - Pressure Chart 6--31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 8/20/2019 Compressor carrier

    10/115

    T-318Safety--1

    SAFETY SUMMARY 

    GENERAL SAFETY NOTICES

    The following general safety notices supplement the specific warnings and cautions appearing elsewhere in thismanual. They are recommended precautions that must be understood and applied during operation andmaintenanceof the equipment covered herein. The general safety notices are presented in the following three sections labeled:First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warnings and cautionsappearing elsewhere in the manual follows the general safety notices.

    FIRST AID

     An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately.

    OPERATING PRECAUTIONS

     Always wear safety glasses.

    Keep hands, clothing and tools clear of the evaporator and condenser fans.

    No work should be performed on the unit until all circuit breakers, start-stop switches areturned off, and power supplyis disconnected.

     Always work in pairs. Never work on the equipment alone.

    In case of severe vibration or unusual noise, stop the unit and investigate.

    MAINTENANCE PRECAUTIONS

    Beware of unannounced starting of the evaporator and condenser fans. Do not open the condenser fan grille orevaporator access panels before turning power off, and disconnecting and securing the power plug.

    Be sure power is turned off before working on motors, controllers, solenoid valves, and electrical control switches. Tagcircuit breaker and power supply to prevent accidental energizing of circuit.

    Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems withthe system should be diagnosed and any necessary repairs performed by qualified service personnel.

    When performing any arc welding on the unit or container, disconnect all wire harness connectors from the modules inboth control boxes. Do not remove wire harness from the modules unless you are grounded to the unit frame with astatic safe wrist strap.

    In case of electrical fire, open circuit switch and extinguish with CO2 (never use water).

    UNIT LABEL IDENTIFICATION

    To help identify the label hazards on the unit and explain the level of awareness each one carries, an explanation isgiven with the appropriate consequences:

    DANGER -- Indicates an immediate hazard that WILL result in severe personal injury or death.

    WARNING -- Warns against hazards or unsafe conditions which COULD result in severe personal injury or death.

    CAUTION -- Warns against potentially hazardous or unsafe practices that could result in minor personal injury, productor property damage.

  • 8/20/2019 Compressor carrier

    11/115

  • 8/20/2019 Compressor carrier

    12/115

    T-318Safety--3

    WARNING

    With power OFF discharge the capacitorbefore disconnecting the circuit wiring.

    WARNING

    The unit power plug must be disconnectedto remove power from circuit breaker CB1

    WARNING

    Make sure power to the unit is OFF and

    power plug disconnected before removing

    capacitor(s).

    WARNING

    Before removing the capacitors, the

    terminals must be checked for voltage with

    a multimeter. The discharge resistors

    installed on the unit (capacitors) should

    bring the voltage to a safe level in a minute.

    However, there may be a broken resistor

    that retains voltage for a longer period.

    Therefore, it is highly recommended to wait

    15 minutes and to check for voltage.

    CAUTION

    Do not remove wire harnesses from con-

    troller unless you are grounded to the unitframe with a static safe wrist strap.

    CAUTION

    Unplug all controller wire harness connec-tors before performing arc welding on anypart of the container.

    CAUTION

    Pre-trip inspection should not be per-formed with critical temperature cargoes in

    the container.

    CAUTION

    When Pre-Trip key is pressed, dehumidifi-cation and bulb mode will be deactivated.At the completion of Pre-Trip activity, dehu-midification and bulb mode must be reacti-

    vated.

    CAUTION

    When condenser water flow is below 11 lpm

    (3 gpm) or when water-cooler is not in use,the CFS switch MUST be set to position “I”or the unit will not operate properly.

    CAUTION

    Pre-trip inspection should not be per-

    formed with critical temperature cargoes inthe container.

    CAUTIONWhen Pre-Trip key is pressed, dehumidifi-cation and bulb mode will be deactivated.At the completion of Pre-Trip activity, dehu-

    midification and bulb mode must be reacti-vated.

    CAUTION

    When a failure occurs during automatic

    testing, the unit will suspend operationawaiting operator intervention.

    CAUTION

    When Pre-Trip test Auto 2 runs to comple-tion without being interrupted, the unit willterminate pre-trip and display “Auto 2”“end.” The unit willsuspend operation untilthe user depresses the ENTER key!

  • 8/20/2019 Compressor carrier

    13/115

    Safety--4T-318

    CAUTION

    The unit will remain in thefull cooling mode

    as long as the emergency bypass switch is

    in the BYPASS position and the MODE

    SWITCH is in the FULL COOL position. If

    the cargo may be damaged by low tempera-

    tures, the operator must monitor container

    temperature and manually cycle operationas required to maintain temperature within

    required limits.

    CAUTION

    The unit will remain in the DEFROST mode

    as long as the emergency defrost switch isin the DEFROST position. To prevent cargo

    damage, the operator must monitor con-tainer temperature and manually cycle op-

    eration as required to maintain temperaturewithin required limits.

    CAUTION

    To prevent trapping liquid refrigerant in themanifold gauge set, be sure set is broughtto suction pressure before disconnecting.

    WARNING

    Before disassembly of any external com-pressor component, make sure to relievepossible internal pressure by loosening thebolts and tapping the component with a

    soft hammer to break the seal.

    CAUTION

    Removing the compressor motor press-fitstator in the field is not recommended. The

    rotor and stator are a matched pair andshould not be separated.

    CAUTION

    The copper tube that connects to the oilsuction strainer extends out the bottomwith the bottom plate removed. Take pre-cautions to avoid bending or breaking itwhile changing crankcase positions.

    CAUTION

    Ensure that the thrust washer does not falloff dowel pins while installing oil pump.

    CAUTION

    The set screw on the crankshaft must be

    removed for this type of oil pump.   (SeeFigure 6-9.)

    CAUTION

    Use only Carrier Transicold approvedPolyol Ester Oil (POE) -- Castrol-IcematicSW20 compressor oil with R-134a. Buy inquantities of one quart or smaller. When

    using this hygroscopic oil, immediatelyreseal. Do not leave container of oil open orcontamination will occur.

    CAUTION

    Take necessary steps (place plywood overcoil or use sling on motor)to prevent motorfrom falling into condenser coil.

    CAUTION

    DO NOT disassemble piston from NEW suc-

    tion modulating valve powerhead assem-bly. Doing so may result in damage to pis-ton.

    CAUTION

    Do not remove wire harnesses from con-troller unless you are grounded to the unitframe with a static safe wrist strap.

    CAUTION

    Unplug all controller connectors beforeperforming arc welding on any part of the

    container.

    CAUTION

    The unit must be OFF whenever a program-ming card is inserted or removed from thecontroller programming port.

  • 8/20/2019 Compressor carrier

    14/115

    T-318Safety--5

    CAUTION

    Do not allow moisture to enter wire splicearea as this may affect the sensor resis-

    tance.

    CAUTION

    Do not allow the recorder stylus to snapback down. The stylus arm base is

    spring-loaded, and damage may occur tothe chart or the stylus force may be altered.

    CAUTION

    DO NOT move the stylus arm up and down

    on the chart face. This will result in damageto the stylus motor gear.

  • 8/20/2019 Compressor carrier

    15/115

    1--1 T-318

    SECTION 1

    INTRODUCTION

    1.1 INTRODUCTION

    The Carrier Transicold model 69NT40-541-300/399series units are of lightweight aluminum frameconstruction, designed to fit in the front of a containerand serve as the container’s front wall.

    They are one piece, self-contained, all-electric units,which includes cooling and heating systems to provideprecise temperature control.

    The units are suppled with a complete charge of refrigerant R-134a and compressor lubricating oil, andare ready for operation upon installation. Forkliftpockets are provided for unit installation and removal.

    The base unit operates on nominal 380/460 volt, 3phase, 50/60 hertz power. An optional autotransformermay be fitted to allow operation on nominal 190/230 , 3phase, 50/60 hertz power. Power for the control systemis provided by a transformer, which steps the supplypower down to 18 and 24 volts, single phase.

    The controller is a Carrier Transicold Micro-Link 3

    microprocessor. The controller will operateautomatically to select cooling, holding or heating asrequired to maintain the desired set point temperaturewithin very close limits. The unit may also be equippedwith a mechanical or electronic temperature recorder.

    The controller has a keypad and display for viewing orchanging operating parameters. The display is alsoequipped with lights to indicate various modes of operation.

    1.2 CONFIGURATION IDENTIFICATION

    Unit identification information is provided on a platelocated near the compressor. The plate provides theunit model number, the unit serial number and the unitparts identification number (PID). The model numberidentifies the overall unit configuration while the PIDprovides information on specific optional equipment,factory provision to allow for field installation of optionalequipment and differences in detailed parts.

    Configuration identification for the models coveredherein may be obtained on the Container ProductsGroup Information Center by authorized CarrierTransicold Service Centers.

    1.3 OPTION DESCRIPTION

    Various options may be factory or field equipped to thebase unit. These options are listed in the tables anddescribed in the following subparagraphs.

    1.3.1 Battery

    The refrigeration controller may be fitted with standardreplaceable batteries or a rechargeable battery pack.

    1.3.2 Dehumidification

    The unit may be fitted with a humidity sensor. Thissensor allows setting of a humidity set point in thecontroller. In the dehumidification mode the controllerwill operate to reduce internal container moisture level.

    1.3.3 Control Box 

    Units are equipped with a composite material box andmay be fitted with a lockable door.

    1.3.4 Display Module

    The unit may be fitted with a backlit Liquid CrystaDisplay (LCD) or a Light Emitting Diode (LED) Display

    1.3.5 Temperature Readout

    The unit may be fitted with suction and discharge

    temperature sensors. The sensor readings may beviewed on the controller display.

    1.3.6 Pressure Readout

    The unit may be fitted with suction and dischargepressure gauges, or suction and discharge transducersor no pressure readout. The transducer readings maybe viewed on the controller display.

    1.3.7 USDA

    The unit may be supplied with fittings for additionatemperature probes, which allow recording of USDACold Treatment data by the integral DataCORDERfunction of the Micro-Link refrigeration controller.

    1.3.8 InterrogatorUnits that use the DataCORDER function are fitted withinterrogator receptacles for connection of equipment todownload the recorded data. Two receptacles may befitted; one accessible from thefront of the container andthe other mounted inside the container (with the USDAreceptacles).

    1.3.9 Remote Monitoring

    The unit may be fitted with a remote monitoringreceptacle. This item allows connection of remoteindicators for COOL, DEFROST and IN RANGEUnless otherwise indicated, the receptacle is mountedat the control box location

    1.3.10 Communications.The unit may be fitted with a communications interfacemodule. The communications interface module is aslave module, which allows communication with amaster central monitoring station. The module wirespond to communication and return information overthe main power line. Refer to the ship master systemtechnical manual for further information.

    1.3.11 Compressor

    The unit is fitted with a single speed reciprocatingcompressor.

    1.3.12 Condenser Coil

    The unit is fitted with a 3--row coil using 7mm tubing.

    1.3.13 Autotransformer

     An autotransformer may be provided to allow operationon 190/230, 3 phase, 50/60 hertz power. Theautotransformer raises the supply voltage to thenominal 380/460 volt power required by the base unitThe autotransformer may also be fitted with anindividual circuit breaker for the 230 volt power.

    If the unit is equipped with an autotransformer andcommunications module, the autotransformer will befitted with a transformer bridge unit (TBU) to assist incommunications.

  • 8/20/2019 Compressor carrier

    16/115

    1--2T-318

    1.3.14 Temperature Recorder

    The units may be fitted with an electronic temperaturerecording device.

    1.3.15 Gutters

    Rain gutters may be fitted over the control box andrecorder section to divert rain away form the controls.The different gutters include standard length boltedgutters, extended length gutters, and riveted gutters.

    1.3.16 Handles

    The unit may be equipped with handles to facilitateaccess to stacked containers. These handles mayinclude fixed handles (located at the sides of the unit)and/or a hinged handle at the center (attached to thecondenser coil cover).

    1.3.17 Thermometer Port

    The unit may be fitted with ports in the front of the framefor insertion of a thermometer to measure supply and/orreturn air temperature. If fitted, the port(s) will require acap and chain.

    1.3.18 Water Cooling

    The refrigeration system may be fitted with awater-cooled condenser. The condenser is constructedusing copper-nickel tube for seawater applications. Thewater-cooled condenser is in series with the air-cooledcondenser and replaces the standard unit receiver.When operating on the water-cooled condenser, thecondenser fan can be deactivated by either a waterpressure switch or condenser fan switch. Depending onthe unit’s configuration and the compressor dischargetemperature, the condenser fan may also be activatedduring water-cooled condenser operation.

    1.3.19 Back Panels

    Back panel designs that may be fitted include panels of aluminum and stainless steel. Panels may have accessdoors and/or hinge mounting.

    1.3.20 460 Volt CableVarious power cable and plug designs are available forthe main 460 volt supply. The plug options tailor thecables to each customers requirements.

    1.3.21 230 Volt Cable

    Units equipped with an autotransformer require anadditional power cable for connection to the 230 voltsource. Various power cable and plug designs areavailable. The plug options tailor the cables to eachcustomers requirements.

    1.3.22 Cable Restraint

    Various designs are available for storage of the powercables. These options are variations of the compressor

    section front cover.1.3.23 Upper Air (Fresh Air Make Up)

    The unit may be fitted with an upper fresh air makeupassembly. The fresh air makeup assembly is availablewith a vent positioning sensor (VPS) and may also befitted with screens.

    1.3.24 Lower Air (Fresh Air Make Up)

    The unit may be fitted with a lower fresh air makeupassembly. The fresh air makeup assembly is availablewith a vent positioning sensor (VPS) and may also befitted with screens.

    1.3.25 Arctic Mode

    To improve operation in cold ambients, the unit may befitted with a crankcase heater. The crankcase heater isoperated any time the unit is under power and thecompressor is not running. The purpose of the heater isto warm the compressor oil and boil off any liquidrefrigerant that may be present in the crankcase.

    1.3.26 Power Correction

    The unit may be fitted with a set of power factor

    correction capacitors to assist in correction of imbalance in current draw by the compressor.

    1.3.27 Evaporator

    The evaporator section is equipped with a hermeticthermalexpansion valve anda heat exchanger. The unitmay have six heaters.

    1.3.28 Evaporator Fan Operation

    Two evaporator fan motor operation systems areavailable. On units with Normal Evaporator FanOperation, opening of an evaporator fan internalprotector will shut down the unit. On units equipped withSingle Evaporator Fan Capability, additional relays areinstalled to allow the unit to continue to operate on a

    single fan.1.3.29 Labels

    Operating instructionand function code listing labels willdiffer depending on the options installed. For example,additional operating instructions are required todescribe start-up of a unit equipped with anautotransformer. Where the labels are available withadditional languages, they are listed in the parts list.

    1.3.30 Plate Set

    Each unit is equipped with a tethered set of wiringschematic and wiring diagram plates. The plate sets areordered using a seven-digit base part number and atwo-digit dash number.

    1.3.31 Controller

    Two different controllers are available:1. Remanufactured -- Controller is the equivalent of anew OEM controller and is supplied with a 12 monthwarranty.2. Repaired -- Controller has had previous faultsrepaired and upgraded with the latest software.Note: Repaired controllers are NOT to be used forwarranty repairs. Only full OEM remanufacturedcontrollers are to be used.Controllers will be factory equipped with the latestversion of operational software, but will NOT beconfigured for a specific model number and will need tobe configured at the time of installation or sale.

    1.3.32 Condenser Grille

    Two styles of condenser grilles are available -- directbolted grilles and hinged grilles.

    1.3.33 Emergency Bypass

    The unit may be equipped with switches to allowemergency bypass of the controller. The EMERGENCYBYPASS switch functions to bypass thecontroller in theevent of controller failure. The EMERGENCYDEFROST switch functions to bypass all controls andplace the unit in the defrost mode.

  • 8/20/2019 Compressor carrier

    17/115

    T-3182--1

    SECTION 2

    DESCRIPTION

    2.1 GENERAL DESCRIPTION

    2.1.1 Refrigeration Unit -- Front Section

    The unit is designed so that the majority of thecomponents are accessible from the front (see

    Figure 2-1). The unit model number, serial number, and

    parts identification number can be found on the seriaplate to the left of the compressor.

    2.1.2 Fresh Air Makeup Vent

    The function of the upper or lower makeup air vent is toprovide ventilation for commodities that require fresh ai

    circulation.

    1

    2

    5

    3

    4

    9

    12

    6

    13

    11

    7

    10

    8

    1. Access Panel (Evaporator Fan #1)/ThermostaticExpansion Valve / HTT)

    2. Fork Lift Pockets3. Control Box4. Compressor5. Unit Serial Number, Model Number, and

    Parts Identification Number (PID) Plate6. Condenser Fan7. TransFRESH Communications Connector

    8. Interrogator Connector (Front Left)9. Temperature Recorder10. Lower Fresh Air Makeup Vent Location

    (Blank Cover Shown)11. TIR (Transports Internationaux Routiers)

    Sealing Provisions - Typical All Panels12. Upper Fresh Air Makeup Vent13. Access Panel (Evaporator Fan #2)/ Humidity

    Sensor / Return Temperature Sensor

    Figure 2-1 Refrigeration Unit -- Front Section

  • 8/20/2019 Compressor carrier

    18/115

    T-318   2--2

    2.1.3 Evaporator Section

    The evaporator section (Figure 2-2) contains the returntemperature sensor, humidity sensor, thermostaticexpansion valve, dual-speed evaporator fans (EM1 andEM2), evaporator coil and heaters, defrost temperaturesensor, heat termination thermostat, and heatexchanger.

    The evaporator fans circulate air through the containerby pulling it in the top of the unit, directing it through theevaporator coil where it is heated or cooled, anddischarging it at the bottom.

    The evaporator components are accessible byremoving the upper rear panel (as shown in Figure 2-2).

    1312

    1011

    1

    2

    3

    4

    5

    7

    9

    14

    15

    6

    8

    TXV Bulb(under Insulation)

    16

    1. Evaporator Fan Motor #12. Return Recorder Sensor (RRS) / Return

    Temperature Sensor (RTS)3. Humidity Sensor4. Evaporator Fan Motor #25. Defrost Temperature Sensor6. Heater Termination Thermostat7. Evaporator Coil8. Hermetic Thermostatic Expansion Valve

    9. Heat Exchanger10. Interrogator Connector (Rear)

    11. USDA Probe Receptacle PR212. USDA Probe Receptacle PR113. USDA Probe Receptacle PR314. Cargo Probe Receptacle PR415. Evaporator Coil Heaters16. TXV Bulb Routing

    Figure 2-2 Evaporator Section -- Units With Center Access Panel

  • 8/20/2019 Compressor carrier

    19/115

    T-3182--3

    2.1.4 Compressor Section

    The compressor section includes the compressor (withhigh pressure switch), power cable storagecompartment, and autotransformer.

    This section also contains the suction modulating valve,

    discharge pressure regulating valve, dischargetemperature sensor, and discharge/suction pressuretransducers.

    The supply temperature sensor, supply recordesensor, and ambient sensor are located at the right sideof the compressor.

    11

    12

    1

    2

    3

    4

    56

    7

    9

    10

    1516

    17

    1819

    22

    20

    21

    13

    14

    8

    1. Autotransformer2. Power Cables and Plug3. Compressor Sight Glass View Port4. Compressor Guard5. Supply Temperature Sensor6. Supply Recorder Sensor7. Ambient Sensor8 Supply Air Thermometer Port9. Discharge Service Valve

    10. Discharge Temperature Sensor

    11. Discharge Pressure Regulating Valve

    12. Suction Temperature Sensor13. Quench Valve Temperature Bulb14. Quench Valve15. Access Valve16. Suction Modulating Valve17. Suction Service Valve18. Compressor Crankcase Heater19. Compressor Motor20. Suction Pressure Transducer21. High Pressure Switch

    22. Discharge Pressure TransducerFigure 2-3 Compressor Section

  • 8/20/2019 Compressor carrier

    20/115

    T-318   2--4

    2.1.5 Air-cooled Condenser Section

    The air-cooled condenser section (Figure 2-4) consistsof the condenser fan, condenser coil, receiver with sightglass/moisture indicator, quench valve, manual liquid

    line valve, filter-drier, condenser pressure transducer,and fusible plug.

    The condenser fan pulls air in through the bottom of thecoil and discharges it horizontally out through thecondenser fan grille.

    5

    6

    7

    15

    1

    2  43

    8

    10

    9

    11

    13

    12

    14

    1. Grille and Venturi Assembly2. Condenser Fan3. Key4. Condenser Fan Motor5. Condenser Coil Cover6. Condenser Coil7. Condenser Motor Mounting Bracket8. Receiver

    9. Sight Glass10. Fusible Plug (Rupture Disc -- Alternate)11. Condenser Pressure Transducer12. Sight Glass/Moisture Indicator13. Filter-Drier14. Liquid Line Service Valve15. Quench Valve

    Figure 2-4 Condenser Section

  • 8/20/2019 Compressor carrier

    21/115

    T-3182--5

    2.1.6 Water-Cooled Condenser Section

    The water-cooled condenser section (Figure 2-5)consists of a water-cooled condenser, sight glass,

    quench expansion valve, rupture disc, condensepressure transducer, filter-drier, water couplings, andwater pressure switch. The water-cooled condensereplaces the standard unit receiver.

    1

    2

    3 4 5 6

    7

    8

    9

    1011

    1. Sight Glass2. Water-Cooled Condenser3. Rupture Disc4. Condenser Pressure Transducer5. Quench Valve6. Filter-Drier

    7. Liquid Line Service Valve8. Moisture/Liquid Indicator9. Coupling (Water In)

    10. Self Draining Coupling (Water Out)11. Water Pressure Switch

    Figure 2-5 Water-Cooled Condenser Section

  • 8/20/2019 Compressor carrier

    22/115

    T-318   2--6

    2.1.7 Control Box Section

    The control box (Figure 2-6) includes the manualoperation switches, circuit breaker (CB-1), compressor,fan and heater contactors, control power transformer,fuses, keypad, display module, current sensor module,controller module and the communications interfacemodule.

    2.1.8 Communications Interface Module

    The communications interface module is a slavemodule, which allows communication with a mastercentral monitoring station. The module will respond tocommunication, and return information over the mainpower line. Refer to the master system technical manualfor further information.

    161718 121415

    1 2   3   4   5   6

    710 919 11 8132021

    1. Compressor Contactor2. Heater Contactor3. Display Module4. Communications Interface Module5. Controller/DataCORDER Module (Controller)

    6. Key Pad7. Emergency Defrost Light8. Start-Stop Switch9. Remote Monitoring Receptacle

    10. Manual Defrost Switch11. Condenser Fan Switch

    12. Controller Battery Pack13. Interrogator Connector (Box Location)14. Control Transformer15. Evaporator Fan Contactor - E116. Evaporator Fan Contactor - S1

    17. Evaporator Fan Contactor - S2 or EF18. Evaporator Fan Contactor - E2 or ES19. Condenser Fan Contactor20. Circuit Breaker -- 460V21. Current Sensor Module

    Figure 2-6 Control Box Section

  • 8/20/2019 Compressor carrier

    23/115

    T-3182--7

    2.2 REFRIGERATION SYSTEM DATA

    a. Compressor/MotorAssembly

    Number of Cylinders 6

    Model 06DR

    CFM 41

    Weight (Dry) 118 kg (260 lb)

     Approved Oil Castrol Icematic

    Oil Charge degrees 3.6 liters (7.6 U.S. pints)

    Oil Sight Glass The oil level range, with the compressor off,should be between the bottom and one-eighthlevel of the sight glass.

    b. Expansion Valve Superheat

    Verify at -18 degreesC(0 degrees F) contain-er box temperature

    4.5 to 6.7 C (8 to 12 F)

    c. Heater Termination ThermostatOpens 54 (+/-) C = 130 (+/-) F

    Closes 38 (+/- 4) C = 100 (+/- 7) F

    d. High Pressure SwitchCutout 25 (+/- 1.0) kg/cm@ = 350 (+/- 10) psig

    Cut-In 18 (+/- 0.7) kg/cm@ = 250 (+/- 10) psig

    e. Refrigerant Charge

    Unit ConfigurationCharge Requirements -- R-134a

    3 row condenserWater-CooledCondenser   5.2 kg (11.5 lbs)

    Receiver 4.9 kg (10.8 lbs)

    NOTEWhen replacing the following components (f.), (g.) and (h.), refer to the installation instructions included with the

    replacement part for additional information.

    f. Fusible Plug* Melting point 99 C = (210 F)

    Torque* 6.2 to 6.9 mkg (45 to 50 ft-lbs)

    g. Sight Glass/Moisture Indicator   Torque 8.9 to 9.7 mkg (65 to 70 ft-lbs)

    h. Rupture Disc

    Bursts at 35 +/- 5% kg/cm@ = (500 +/- 5% psig)

    Torque

    (P/N 14-00215-03)   1.4 to 2 mkg (10 to 15 ft-lbs)

    i. Condenser PressureTransducer

    Condenser Fan Starts

    The condenser fan will start if the condenserpressure is greater than 14.06 kg/cm@ (200psig) OR the condenser fan is OFF for morethan 60 seconds.

    Condenser Fan Stops

    The condenser fan will stop if the condenserpressure is less than 9.14 kg/cm@ (130 psig) AND the condenser fan remains ON for at least30 seconds.

    j. Unit Weight   Refer to unit model number plate.

    k. Water Pressure SwitchCut-In

      0.5 +/- 0.2 kg/cm@

    3-row condenser (7 +/- 3 psig)

    Cutout 1.6 +/- 0.4 kg/cm@ (22 +/- 5 psig)l. Discharge Pressure

    Regulating Valve   Factory Setting 32.7 +/- 2.5 kg/cm@ (72+/- 5.5 psig)

     * Rupture Disc, part number 14 -00215 -04 may be installed as an alternate for the receiver mounted fusible plug.

  • 8/20/2019 Compressor carrier

    24/115

    T-318   2--8

    2.3 ELECTRICAL DATA

    a. Circuit Breaker

    CB-1 Trips at 29 amps

    CB-2 (50 amp) Trips at 62.5 amps

    CB-2 (70 amp) Trips at 87.5 amps

    b. CompressorMotor   Full Load Amps (FLA)

      17.6 amps @ 460 VAC(with current limiting set at 21 amps)

    c. Condenser FanMotor

    380 VAC, Single Phase,50 Hz

    460 VAC, Single Phase,60 hz

    Full Load Amps 1.3 amps 1.6 ampsHorsepower 0.43 hp 0.75 hp

    Rotations Per Minute 1425 rpm 1725 rpm

    Voltage and Frequency 360 -- 460 VAC +/- 2.5 hz 400 -- 500 VAC +/- 2.5 hz

    Bearing Lubrication Factory lubricated, additional grease not required.

    Rotation Counter-clockwise when viewed from shaft end.

    d. Evaporator CoilHeaters

    Number of Heaters 6

    Rating 750 watts +5/ -10% each @ 230 VAC

    Resistance (cold) 66.8 to 77.2 ohms @ 20 C (68 F)

    Type Sheath

    e. Evaporator FanMotor(s)

    380 VAC/50 hz 460 VAC/60 hz

    Full Load AmpsHigh Speed

      1.6 2.0

    Full Load AmpsLow Speed

      0.8 1.0

    Nominal HorsepowerHigh Speed

      0.70 0.84

    Nominal HorsepowerLow Speed

      0.09 0.11

    Rotations Per MinuteHigh Speed

      2850 rpm 3450 rpm

    Rotations Per MinuteLow Speed

      1425 rpm 1750 rpm

    Voltage and Frequency 360 -- 460 VAC +/- 1.25 hz 400 -- 500 VAC +/- 1.5 hz

    Voltage & Frequency us-ing power autotransformer

      180 -- 230 VAC +/- 1.25hz 200 -- 250 VAC +/- 1.5 hz

    Bearing Lubrication Factory lubricated, additional grease not required

    Rotation CW when viewed from shaft end

    f. Fuses

    Control Circuit 7.5 amps (F3A, F3B)

    Controller/DataCORDER 5 amps (F1 & F2)

    Emergency Defrost 5 amps (FED)

    Drain Line Heater 5 amps (FDH)

    Humidity PowerTransformer

      5 amps (FH)

    g. Compressor Crankcase Heater   180 watts @ 460 VAC

  • 8/20/2019 Compressor carrier

    25/115

    T-3182--9

    2.3 ELECTRICAL DATA (Continued)

    h. Humidity Sensor

    Orange wire Power

    Red wire Output

    Brown wire Ground

    Input voltage 5 vdc

    Output voltage 0 to 3.3 vdc

    Output voltage readings verses relative humidity (RH) percentage:

    30% 0.99 V

    50% 1.65 V70% 2.31 V

    90% 2.97 V

    i. Controller   Setpoint Range -30 to +30 C ( -22 to +86 F)

    2.4 SAFETY AND PROTECTIVE DEVICES

    Unit components are protected from damage by safety and protective devices listed in the following table. Thesedevices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition occurs

    Table 2-1 Safety and Protective Devices

    UNSAFE CONDITION SAFETY DEVICE DEVICE SETTING

    Circuit Breaker (CB-1) -- Manual Reset Trips at 29 amps (460 VAC)

    Excessive current draw Circuit Breaker (CB-2, 50 amp) --Manual Reset  Trips at 62.5 amps (230

    VAC)

    Circuit Breaker (CB-2, 70 amp) --Manual Reset  Trips at 87.5 amps (230

    VAC)

    Excessive current draw in thecontrol circuit   Fuse (F3A & F3B) 7.5 amp rating

    Excessive current draw by thecontroller   Fuse (F1 & F2) 5 amp rating

    Excessive current draw by theemergency defrost circuit   Fuse (FED) 5 amp rating

    Excessive condenser fan mo-tor winding temperature   Internal Protector (IP-CM) -- Automatic Reset N/A

    Excessive compressor motorwinding temperature   Internal Protector (IP-CP) -- Automatic Reset N/A

    Excessive evaporator fan mo-tor(s) winding temperature   Internal Protector(s) (IP-EM) -- Automatic Reset N/A

     Abnormal pressures/tempera-tures in the high refrigerantside

    Fusible Plug -- Used on the Receiver

    Rupture Disc -- Used on the Water-CooledCondenser

    99 C = (210 F)

    35 kg/cm@ = (500 psig)

     Abnormally high discharge

    pressure   High Pressure Switch (HPS)

      Opens at 25 kg/cm@

    (350 psig)

  • 8/20/2019 Compressor carrier

    26/115

    T-318   2--10

    2.5 REFRIGERATION CIRCUIT

    Starting at the compressor (see Figure 2-7, upperschematic), the suction gas is compressed to a higherpressure and temperature.

    The gas flows through the discharge service valve intothe pressure regulating valve. During periods of lowambient operation, the discharge pressure regulatingvalve modulates the flow of refrigerant to maintain a pre-set minimum discharge pressure. Refrigerant gas then

    moves into the air-cooled condenser. When operatingwith the air-cooled condenser active, air flowing acrossthe coil fins and tubes cools the gas to saturationtemperature. By removing latent heat, the gascondenses to a high pressure/high temperature liquidand flows to the receiver, which stores the additionalcharge necessary for low temperature operation.

    When operating with the water-cooled condenser active(see Figure 2-7, lower schematic), the refrigerant gaspasses throughthe air-cooledcondenser and enters thewater-cooled condenser shell. The water flowing insidethe tubing cools the gas to saturation temperature in thesame manner as the air passing over the air-cooledcondenser. The refrigerant condenses on the outside of the tubes and exits as a high temperature liquid. The

    water-cooled condenser also acts as a receiver, storingexcess refrigerant.

    The liquid refrigerant continues through the liquid lineservice valve, the filter-drier (which keeps refrigerantclean and dry), and a heat exchanger (that increasessubcooling of the liquid) to the thermostatic expansionvalve. As the liquid refrigerant passes through thevariable orifice of the expansion valve, some of itvaporizes into a gas (flash gas). Heat is absorbed fromthe return air by the balance of the liquid, causing it tovaporize in the evaporator coil. The vapor then flowsthrough the suction modulatingvalve to thecompressor.

    The thermostatic expansion valve is activated by thebulb strapped to the suction line near the evaporator

    outlet. The valve maintains a constant superheat at thecoil outlet regardless of load conditions.

    During periods of low load, the suction modulating valvedecreases flow of refrigerant to the compressor. Thisaction balances the compressor capacity with the loadand prevents operation with low coil temperatures. Inthis mode of operation, the quench valve will open asrequired to provide sufficient liquid refrigerant flow intothesuction line for cooling of the compressor motor. Thequench valve senses refrigerant condition entering thecompressor and modulates the flowto prevent entranceof liquid into the compressor.

    The refrigeration system is also fitted with a condenserpressure transducer, which feeds information to thecontroller. When operating on the air-cooled condenser,the controller programming will operate the condenserfan so as to attempt to maintain discharge pressuresabove 130 psig in low ambients. At ambients below 27degrees C (80 degrees F), the condenser fan will cycleon and off depending on condenser pressure andoperating times.

    1 The condenser fan will start if the condenser pres-sure is greater than 200 psig OR the condenser fanhas been OFF for more than 60 seconds.

    2 The condenser fan will stop if the condenser pres-sure is less than 130 psig AND the condenser fanhas been running for at least 30 seconds.

     At ambients above 27 C (80 F), condenser pressurecontrol is disabled and the condenser fan runscontinuously.

    On systems fitted with a water pressure switch, thecondenser fan will be off when there is sufficientpressure to open the switch. If water pressure dropsbelow the switch cut out setting, the condenser fan willbe automatically started. When operating a systemfittedwitha condenser fanswitch, thecondenser fanwillbe off when the switch is placed in the “O” position. Thecondenser fan will be onwhen the switch is placed in the“I” position.

  • 8/20/2019 Compressor carrier

    27/115

    T-3182--11

    FILTER DRIER

    TXV

    TXV BULB

    MODULATING VALVE

    PRESSURE

    TRANSDUCER

    HEAT EXCHANGER

    SIGHT GLASS

    FILTER DRIER

    HEAT EXCHANGER

    MODULATING VALVE

    PRESSURE

    TRANSDUCER

    SIGHT GLASS

    FUSIBLE PLUG

    RECEIVER

    SERVICE VALVE

    WATER-COOLED

    CONDENSER

    TXV

    TXV BULB

    EVAPORATOR

    CONDENSER

    PRESSURE TRANSDUCER

    SERVICE VALVE

    DISCHARGE PRESSURE

    REGULATING VALVE

    EVAPORATOR

    CONDENSER

    SERVICE VALVE

    SERVICE VALVE

    Circuit with Receiver

    QUENCH VALVE

    QUENCH VALVE

    Circuit with Water-Cooled Condenser

    FUSIBLE PLUG

    SuctionLiquid

    Discharge

    Suction

    Liquid

    Discharge

    DISCHARGE PRESSURE

    REGULATING VALVE

    Figure 2-7 Refrigeration Circuit Schematic

  • 8/20/2019 Compressor carrier

    28/115

    T-3183--1

    SECTION 3

    MICROPROCESSOR

    3.1 TEMPERATURE CONTROL MICROPRO-CESSOR SYSTEM

    The temperature control Micro-Link 3 microprocessorsystem (see Figure 3-1) consists of a keypad, displaymodule, control module (controller), andinterconnecting wiring. The controller houses thetemperature control software and the DataCORDER

    Software. The temperaturecontrolsoftware functions tooperate the unit components as required to provide thedesired cargo temperature and humidity. TheDataCORDER software functions to record unit

    operating parameters and cargo temperatureparameters for future retrieval. Coverage of thetemperature control software begins with paragraph3.2. Coverage of the DataCORDER software isprovided in paragraph 3.6.

    The keypad and display module serve to provide useraccess and readouts for both of the controller functions

    temperature control, and DataCORDER. The functionsare accessed by keypad selections and viewed on thedisplay module. The components are designed topermit ease of installation and removal.

    TODISPLAY 

    CONTROL MODULEDISPLAY MODULE

    KEYPAD

    CONFIGURATIONSOFTWARE

    CONFIGURATION VARIABLE

    (CnF##)

    TEMPERATURE CONTROL SOFTWARE

    ALARMS(AL68)

    DATASTORAGEMEMORY 

    OPERATIONALSOFTWARE

    FUNCTION

    CODE (dC)

    TODISPLAY 

    (Scrollback)

    DATABANK CARD

    Figure 3-1 Temperature Control System

  • 8/20/2019 Compressor carrier

    29/115

    T-318   3--2

    3.1.1 Keypad

    The keypad (Figure 3-2) is mounted on the right-handside of the control box. The keypad consists of 11 pushbutton switches that act as the user’s interface with thecontroller. Descriptions of the switch functions areprovided in Table 3-1.

    ENTER

    BATTERY

    POWER

    MANUAL

    DEFROST/ 

    INTERVAL

    CODE

    SELECT

    PRE

    TRIP

     ALARM

    LIST

     ALT.

    MODE

    RETURN

    SUPPLY

    _C

    _F

    Figure 3-2 Keypad

    COOL HEAT DEFROST IN RANGEALARM SUPPLY RETURN

    SETPOINT/Code AIR TEMPERATURE/Data

    Figure 3-3 Display Module

    3.1.2 Display Module

    The display module (Figure 3-3) consists of five digital

    displays and seven indicator lights. The indicator lightsinclude:

    1. Cool -- White LED: Energized when the refrigerantcompressor is energized.

    2. Heat -- Orange LED: Energized to indicate heaterop-eration in the heat or defrost mode.

    3. Defrost -- Orange LED: Energized when the unit is inthe defrost mode.

    4. In-Range -- Green LED: Energized when the con-trolled temperatureprobe is within specified toleranceof set point.

    Table 3-1 Keypad Function

    KEY FUNCTION

    Code Select Accesses function codes.

    Pre-Trip  Displays the pre-trip selection menu.

    Discontinues pre-trip in progress.

     Alarm List  Displays alarm list and clears the

    alarm queue.

    Manual

    Defrost/ Interval

    Displays selected defrost mode. De-

    pressing and holding the Defrost in-terval key for five seconds will initiatedefrost using the same logic as if theoptional manual defrost switch wastoggled on.

    Enter  Confirms a selection or saves a

    selection to the controller

     Arrow Up  Change or scroll a selection upward

    Pre-trip advance or test interruption.

     Arrow Down  Change or scroll a selection down-

    ward. Pre-trip repeat backward

    Return/ Supply

    Displays non-controlling probe tem-perature (momentary display).

    DegreesC/-Degrees F

    Displays alternate English/Metricscale (momentary display). When setto degrees Fahrenheit, pressure isdisplayed in psig and vacuum in “/hg.“P” appears after the value to indi-cate psig and “i” appears for inchesof mercury.

    When set to degrees Celsius, pres-sure readings are in bars. “b” ap-pears after the value to indicate bars.

    BatteryPower

    Initiate battery backup mode to allowset point and function code selectionif AC power is not connected.

     ALT. Mode

    This key is pressed to switch thefunctions from the temperature soft-ware to the DataCORDER Software.The remaining keys function thesame as described above except thereadings or changes are made to theDataCORDER programming.

    NOTE

    The controlling probe in the perishable rangewill be theSUPPLY air probe and thecontrollingprobe in the frozen range will be the RETURNair probe.

    5. Supply -- Yellow LED: Energized when the supply air

    probe is used for control. When this LEDis illuminated,the temperature displayed in the AIR TEMPERATUREdisplay is the reading at the supply air probe. ThisLEDwill flash if dehumidification or humidification is en-abled.

    6. Return -- Yellow LED: Energized when the return airprobe is used for control. When this LEDis illuminated,the temperature displayed in the AIR TEMPERATUREdisplay is the reading at the return air probe. This LEDwill flash if dehumidification or humidification is en-abled.

    7. Alarm -- Red LED: Energized when there is an activeor an inactive shutdown alarm in the alarm queue.

  • 8/20/2019 Compressor carrier

    30/115

    T-3183--3

    81 2 3 3 3 3 34 5 6 7

    1. Mounting Screw2. Micro-Link 3

    Controller3. Connectors4. Test Points

    5. Fuses6. Control Circuit Power Connection

    (Location: In back of controller)7. Software Programming Port8. Battery Pack

    Figure 3-4 Micro-Link 3 Controller

    3.1.3 Controller

    CAUTIONDo not remove wire harnesses from con-troller unless you are grounded to the unitframe with a static safe wrist strap.

    CAUTION

    Unplug all controller wire harness connec-tors before performing arc welding on anypart of the container.

    NOTE

    Do not attempt to service the controller. Break-ing the seal will void the warranty.

    NOTE

    Do not attempt to use an ML2i PC card in anML3equippedunit. The PC cards arephysicallydifferent and will result in damageto the control-ler.

    The Micro-Link 3 controller is a single modulemicroprocessor as shown in Figure 3-4. It is fitted withtest points, harness connectors and a software cardprogramming port.

    3.2 CONTROLLER SOFTWAREThe controller software is a custom designed programthat is subdivided intothe configuration software andtheoperational software. The controller software performsthe following functions:

    a. Control supply or return air temperature to requiredlimits, provide modulated refrigeration control, elec-tric heat control and defrost. Defrost is performed toclear buildup of frost and ice from the coil to ensurecontinuous conditioned air delivery to the load.

    b. Provide default independent readouts of set point andsupply or return air temperatures.

    c. Provide ability to read, and if applicable, modify theconfiguration software variables, operating softwarefunction codes, and alarm code indications.

    d. Provide a pre-trip step-by-step checkout of refrigeration unit performance, including proper componentoperation, electronic and refrigeration control operation, heater operation, probe calibration, pressurelimiting, and current limiting settings.

    e. Provide battery-powered ability to access or changeselected codes and set points without AC power connected

    f. Provide the ability to reprogram the software throughthe use of a memory card.

    3.2.1 Configuration Software (Configuration Vari-ables)

    The configuration software is a variable listing of thecomponents available for use by the operationasoftware. This software is factory-installed inaccordance with the equipment fitted and options listedon the original purchase order. Changes to theconfiguration software are required only when theoriginal softwarehas been lost or a physical change hasbeen made to theunit, such as theaddition or removal oan option. A configuration variable list is provided inTable 3-4 (page 3--13). A change to the factory-installedconfiguration software is achieved via a configurationcard.

    3.2.2 Operational Software (Function Codes)

    The operational software is the actual operationprogramming of the controller, which activates odeactivatescomponents in accordance with current unioperation conditions and operator selected modes ooperation.

    The programming is divided into function codes. Someof the codes are read only while the remaining codesmay be user configured. The value of the useconfigurable codes can be assigned in accordance withuser desired mode of operation. A list of the functioncodes is provided in Table 3-5 (page 3--14)

  • 8/20/2019 Compressor carrier

    31/115

    T-318   3--4

    To access the function codes, perform the following:

    a. Press the CODE SELECT key, then press an arrowkey until the left window displays the desired codenumber.

    b. The right window will display the value of this item forfive seconds before returning to the normal displaymode.

    c. If a longer time is desired, press the ENTER key to ex-tend the time to 30 seconds.

    3.3 MODES OF OPERATION

    The operational software responds to various inputs.These inputs come from the temperature and pressuresensors, the temperature set point, the settings of