Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 1
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Electrical Transient Analyzer Program
Load Flow Analysis
Number of Buses:
Swing V-Control Load Total
Number of Branches:
XFMR2 Reactor Line/Cable Impedance Tie PDXFMR3 Total
1 0 3 4
2 0 0 2 0 0 4
Loading Category (1): Design
Generation Category (1): Design
Load Diversity Factor: None
Maximum No. of Iteration: 99
System Frequency: 50 Hz
Unit System: English
Project Filename: 1-03121004071
Output Filename: E:\Kuliah\Prak. DSTL\Prkt. Load Flow\1-03121004071\Loadflow1.lfr
Precision of Solution: 0.0001000
Method of Solution: Newton-Raphson Method
7/23/2019 Complete Report Fl 1
2/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 2
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Adjustments
Transformer Impedance:
Reactor Impedance:
Adjustments
Apply
/Global
Individual
PercentTolerance
Overload Heater Resistance:
Transmission Line Length:
Cable Length:
Temperature Correction
Transmission Line Resistance:
Cable Resistance:
Apply
Adjustments
Individual
/Global Degree C
Individual
Individual
Individual
Individual
Yes
Yes
No
No
No
Yes
Yes
7/23/2019 Complete Report Fl 1
3/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 3
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Bus Input Data
Sub-sys
GenericConstant IConstant ZConstant kVAInitial VoltageBus
MvarMWMvarMWMvarMWMvarMWAng.% Mag.kVID
Load
20.000Bus1 1 100.0 150.0
70.000Bus2 1 100.0 0.0
70.000Bus3 1 100.0 0.0
33.000 62.00020.000Bus4 1 100.0 0.0
62.0000.000 33.000Total Number of Buses: 4 0.000 0.000 0.000 0.000 0.000
ID kV
Generation Bus
Sub-sysType
Voltage
% Mag. Angle MW Mvar Max Min
Generation Mvar Limits
% PF
Bus1 120.000 Swing 100.0 150.0
0.000 0.000
7/23/2019 Complete Report Fl 1
4/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 4
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Line/Cable Input Data
ID Library Size T (C)
Line/Cable
Ohms or Siemens/1000 ft per Conductor (Cable) or per Phase (Line)
Adj. (ft) #/Phase% Tol.
Length
YR X
Line1 98425.2 1 0.060960 0.030480750.0
Line2 98425.2 1 0.060960 0.030480750.0
Line / Cable resistances are listed at the specified temperatures.
7/23/2019 Complete Report Fl 1
5/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 5
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
2-Winding Transformer Input Data
ID MVA Prim. kV Sec. kV % Z X/R Prim. Sec.
Transformer % Tap Setting
% Tol.
Rating Z Variation
+ 5% - 5%
Phase Shift
Type Angle% Z
Adjusted
T1 100.000 20.000 70.000 12.50 34.10 0 000 0 Std Pos. Seq. 0.00012.5000
T2 100.000 70.000 20.000 12.50 34.10 0 000 0 Std Pos. Seq. 0.00012.5000
2-Winding Transformer Load Tap Changer (LTC) Settings
ID Secondary Bus IDPrimary Bus ID Tap % Step Regulated Bus ID
Transformer Connected Buses ("*" LTC Side)
Tap % V kV
Transformer Load Tap Changer Setting
% Min. % Max.
7/23/2019 Complete Report Fl 1
6/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 6
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Branch Connections
ID From Bus To Bus R X ZType
CKT/Branch % Impedance, Pos. Seq., 100 MVA BaseConnected Bus ID
Y
T1 Bus1 0.37 12.49 12.50Bus22W XFMR
T2 Bus3 0.37 12.49 12.50Bus42W XFMR
Line1 Bus2 12.24 6.12 13.69Bus3Line
Line2 Bus2 12.24 6.12 13.69Bus3Line
7/23/2019 Complete Report Fl 1
7/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 7
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
LOAD FLOW REPORT
Bus
ID kV
Voltage
Ang.% Mag.
Generation
MW Mvar
Load
MW Mvar
Load Flow
MW Mvar AmpID % PF
XFMR
% Tap
Bus1* 20.000 150.0100.000 52.87825.367 Bus2 25.367 52.878 1693.0 43.30 0
Bus2 70.000 148.293.348 Bus3 12.621 24.290 241.9 46.10 0 0 0
Bus3 12.621 24.290 241.9 46.1
Bus1 -25.241 -48.580 483.7 46.1
Bus3 70.000 149.790.130 Bus2 -11.568 -23.764 241.9 43.80 0 0 0
Bus2 -11.568 -23.764 241.9 43.8
Bus4 23.135 47.527 483.7 43.8
Bus4 20.000 147.683.502 43.23023.009 Bus3 -23.009 -43.230 1693.0 47.00 0
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
7/23/2019 Complete Report Fl 1
8/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 8
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Bus Loading Summary Report
ID
Bus
kV
Directly Connected Load
MW Mvar MVA % PF AmpRated Amp LoadingMW Mvar MW Mvar
Constant kVA Constant Z Constant IPercent
Generic
MW Mvar
Total Bus Load
Bus1 20.000 58.648 1693.043.30 0 0 0 0 0 0 0
Bus2 70.000 54.746 483.746.10 0 0 0 0 0 0 0
Bus3 70.000 52.859 483.743.80 0 0 0 0 0 0 0
Bus4 20.000 48.972 1693.047.00 0 23.009 43.230 0 0 0 0
*Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
#Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
7/23/2019 Complete Report Fl 1
9/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 9
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Branch Loading Summary Report
ID Type
Loading
Amp %
Capability
(MVA) MVA %
Loading (output)
CKT / Branch Cable & Reactor
Transformer
Loading (input)
%MVA
Ampacity
(Amp)
T1 Transformer 100.000 58.648 58.6 54.746 54.7
T2 Transformer 100.000 52.859 52.9 48.972 49.0
* Indicates a branch with operating load exceeding the branch capability.
7/23/2019 Complete Report Fl 1
10/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 10
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Branch Losses Summary Report
ID MW Mvar MW Mvar kW kvar From To
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage% Drop
Vd
in Vmag
25.367 52.878 -25.241 -48.580 126.0 4297.6 100.0 93.3 6.65T1
12.621 24.290 -11.568 -23.764 1052.9 526.5 93.3 90.1 3.22Line1
12.621 24.290 -11.568 -23.764 1052.9 526.5 93.3 90.1 3.22Line2
23.135 47.527 -23.009 -43.230 126.0 4297.6 90.1 83.5 6.63T2
2357.9 9648.0
7/23/2019 Complete Report Fl 1
11/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 11
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
Alert Summary Report
Cable 95.0100.0
Bus
MarginalCritical
95.0100.0
Loading
% Alert Settings
95.0100.095.0100.0
95.0100.0
LineTransformer
Reactor
Panel
95.0100.0
95.0 98.0
102.0105.0
95.0100.0
95.0100.0
95.0100.0
100.0
Generator Excitation
Bus Voltage
UnderExcited (Q Min.)
OverExcited (Q Max.)
UnderVoltage
OverVoltage
Protective Device
Generator
Critical Report
Device ID Type Rating/LimitCondition Unit Operating % Operating Phase Type
70.000 kV 65.343 93.3 3-PhaseUnder VoltageBus2 Bus
Bus3 70.000 kV 63.091 90.1 3-PhaseUnder VoltageBus
Bus4 20.000 kV 16.700 83.5 3-PhaseUnder VoltageBus
Gen1 41.964 Mvar 52.878 126.0 3-PhaseOver ExcitedGenerator
7/23/2019 Complete Report Fl 1
12/12
Location: Lab. DSTL
Engineer: Ahmad Okky SaputraStudy Case: LF
7.0.0
Page: 12
SN: 12345678
Filename: 1-03121004071
Project: Load Flow 1ETAP
Contract: 03121004071
Date: 09-17-2015
Revision: Base
Config.: Normal
0.0000.0000.000
0.0000.0000.000
Lagging46.9848.972
Total Generic Load:
Total Constant I Load:
0.0000.000
9.6482.358
Number of Iterations: 3
System Mismatch:
Apparent Losses:
SUMMARY OF TOTAL GENERATION , LOADING & DEMAND
0.000
Lagging
Lagging
43.23023.009
0.0000.000
43.2558.64852.87825.367
0.0000.0000.000
43.2558.64852.87825.367
% PFMVAMvarMW
Total Static Load:
Total Motor Load:
Total Demand:
Source (Non-Swing Buses):
Source (Swing Buses):