Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Dr. H. V. Saikumar, Sharanki. R 37
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
Comparative Study of Performance of Electric
Spring and STATCOM
Dr. H. V. Saikumar Sharanki. R Professor Mtech. Power Systems
Department of Electrical and Electronics Department of Electrical and Electronics National Institute of Engineering, Mysore National Institute of Engineering, Mysore
[email protected] [email protected] Abstract- The Electric Spring is an emerging technology and
has been proposed recently as an effective means of distributed
voltage control. An Electric Spring (ES) a power electronics
device adaptive to fluctuating mains voltage. It can therefore be
distributed over the power grid (e.g. households, industrial sites
etc) to stabilize the main voltage. The idea is to regulate the
voltage across the critical (C) loads while allowing the non-
critical (NC) impedance type loads (e.g. water heaters) to vary
their power consumption and thus contribute to demand side
response. In this paper, a comparison is made between the
performance of an Electric Spring and a STATCOM to control
the main voltage and hence the reactive power. For a given
range of supply voltage variation, the total reactive power
capacity required for each option to produce the desired
voltage regulation at the point of connection is compared. A
simple case study with an ES and STATCOM is presented first
to show that the ES and STATCOM require comparable
reactive power to achieve similar voltage regulation. The
performance of Electric Spring (ES) is further extended
through a case study on IEEE-14 bus test feeder system. In both
cases, it turns out that reactive power capacity required by ES
is less than that required by STATCOM.
I. INTRODUCTION
The control of voltage and reactive power is a major issue
in power system operation. This is because of the topological
differences between distribution and transmission systems.
Since the power system supplies power to a vast number of
loads and is feeding from many generating units, there is a
problem of maintaining voltages within required limits. As
load varies, the reactive power requirements of the
transmission system vary. Since the reactive power cannot
be transferred or transported over long distances, voltage
control has to be effected by using special devices installed
at various location of the system which possess difficulties
in keeping sufficient levels of voltage in the power system
network.
The proper selection and coordination of equipment for
controlling reactive power and voltage stability are among
the major challenges of power system engineering. These
challenges gave birth to some selected devices to
compensate reactive power. Voltage control in medium
voltage (MV) or low voltage (LV) distribution networks is
typically exercised through transformer tap-changers and/or
switched capacitors/reactors. Sometimes a Static
Compensator (STATCOM) is used for fast and precise
voltage regulation, especially for the sensitive/critical loads
[1].
The novel concept of Electric Spring (ES) has been
proposed for reactive power control and voltage regulation.
In electrical engineering terms, this electric spring is a
special form of reactive power controller. Here, the load is
divided into two type’s viz., a non-critical load and a critical
load. By connecting an electric spring in series with the non-
critical load, we can ensure that the voltage and power at the
critical load remain constant when the line voltage feeding
the load fluctuates [2]. Such an arrangement of load is
termed as “Smart load.”
At times of generation shortfall or network constraint, the
voltage of the Non-Critical (NC) loads is reduced while
regulating the voltages across the Critical (C) loads by
controlling the reactive power. One way to exercise this
control is to use the so called Electric Spring (ES) [1-2]. A
simple case study with an ES and STATCOM is presented
in this paper using MATLAB/SIMULINK to show that the
ES and STATCOM require comparable reactive power to
achieve similar voltage regulation. Further, the performance
of an Electric Spring (ES) is further substantiated through a
case study on the IEEE 14 bus test feeder system to show
that ES requires less reactive power capacity than
STATCOM.
II. PRINCIPLES OF ELECTRIC SPRING
The principle of ES is explained based on the principle of
mechanical spring described by Robert Hook in 1678. The
Hook’s law states that force of mechanical spring,
Dr. H. V. Saikumar, Sharanki. R 38
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
𝑭 = −𝑘𝑥 (1)
Where, F is the force vector, k is the spring constant and x is
the displacement vector.
The potential energy stored in the mechanical spring is:
𝑃𝐸 =1
2𝑘𝑥2 (2)
Electric Spring is an electric device that can be used to
provide electric voltage support, store electric energy and
damp electric oscillation [3].
The basic relationship of ES is,
𝑞 = {𝐶𝑣𝑎 𝑖𝑛𝑑𝑢𝑐𝑡𝑖𝑣𝑒 𝑚𝑜𝑑𝑒−𝐶𝑣𝑎 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑖𝑣𝑒 𝑚𝑜𝑑𝑒
(3)
𝑞 = ∫ 𝑖𝑐 𝑑𝑡 (4)
where, q is the electric charge stored in a capacitor with
capacitance C, va is the electric potential difference across
the capacitor, and ic is the current flowing into the capacitor.
From equation (3) and (4) electric spring can be represented
as a current controlled voltage source.
A. Analogy of Electric Spring
Analogies of mechanical spring and ES under 3
conditions are represented in Fig.1. The neutral position of
ES represents a reference voltage at which the spring is
designed to maintain.
Fig.1: Analogy of Mechanical Spring and Electric Spring
Here, ES and 𝑍1 across main voltage are connected in series
to maintain 𝑉𝑠 to its nominal reference value 𝑉𝑆𝑟𝑒𝑓 in case of
neutral position. Similar to mechanical spring, ES can
provide voltage boosting and reduction functions.
The voltage boosting function is explained by compressing
the spring. In this case, to maintain 𝑉𝑆 = 𝑉𝑆𝑟𝑒𝑓 , ES voltage
increases in positive direction and output voltage of NC load
will be less than reference voltage. Similarly, voltage
reduction is explained by expanding the mechanical spring
as shown in Fig.1. In this case, to maintain 𝑉𝑆 = 𝑉𝑆𝑟𝑒𝑓, ES
voltage increases but in negative direction and the output
voltage of NC load will be greater than reference voltage.
The generation of ES voltage and the practical
implementation of ES and its characteristics are explained
in [3]. The operating limits of Electric Spring discussed in
[3-4]. The phasor diagram for both voltage boosting and
voltage reduction function is shown in Fig.2 [5]. The energy
storage capability of the electric spring can be seen from the
potential electric energy stored in the capacitor:
𝑃𝐸 =1
2𝐶𝑣𝑎
2 (5)
So the capacitor C serves as the energy storage element for
the electric spring.
Fig.2:
Phasor diagram for voltage boosting and voltage reduction
Since ES is connected in series with 𝑍1, it provides to
dissipate electric energy for damping purpose. The NC load
voltage 𝑉𝑜 and ES voltage 𝑉𝑎 can change in a special manner
such that the load power consumption of 𝑍1 will follow the
variation of renewable power generation. This unique
feature of ES offers a new solution in future power systems
with intermittent renewable energy source.
III. ELECTRIC SPRING AS REACTIVE POWER
CONTROLLERS
Electric springs are reactive power controllers with input
voltage control instead of the traditional output voltage
control used in series reactive power compensators [6]. The
inverter structure and functions of the ES are similar to the
reactive power compensators (RPC), but the concept and
operating principle are totally different.
Dr. H. V. Saikumar, Sharanki. R 39
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
The series RPC is used to regulate the (output) load
voltage/power; therefore the power generation has to follow
the load demand.
Conversely, an ES uses generation-side parameters such as
mains voltage as the control variable. Thus the non-critical
load voltage fluctuates and the ES would provide voltage
regulation and automatically shape the load power to follow
the power generated [7]. The requirement of installing an
electric spring with a non-critical load, as shown in Fig. 3, is
also different from that of conventional reactive power
compensators.
Fig. 3: Arrangement of an ES connected in series with a NC load
The electric spring comprises a power inverter with a dc bulk
capacitor on the dc side and an inductive-capacitive (LC)
filter on the ac side of the power inverter A full bridge
inverter is designed as shown in Fig.4. Voltage Source
Converter is implemented using MOSFETS. The four
freewheeling diodes of the power inverter behave like a
diode rectifier which rectifies the ac voltage into a dc one
𝑉𝑑𝑐 across the bulk capacitor. The pulse width-modulation
switching method is adopted in the power inverter to
generate a controllable ac voltage across the filter capacitor.
This controllable ac voltage is the output voltage of the
electric spring.
Fig.4: Power inverter used as a reactive power controller
The vector equation for the electric spring is,
𝑣𝑜 = 𝑣𝑠 − 𝑣𝑎 (6)
the power balance equation can be expressed as,
𝑃𝑖𝑛 =𝑣𝑠
2−𝑣𝑎2
𝑅1+
𝑣𝑠2
𝑅2 (7)
𝑃𝑖𝑛 = 𝑃1 + 𝑃2 (8)
Where, 𝐑𝟏 and 𝐏𝟏 are the resistance and power consumption
of the NC load respectively; and 𝐑𝟐 and 𝐏𝟐 are the
resistance and power consumption of the C load
respectively; 𝐯𝐬 and 𝐯𝐚 are the root-mean-square values of
the ac mains and electric spring voltage respectively.
Examples for NC loads include electric heaters,
refrigerators and lighting systems. Critical loads refer to
electric loads that require a well-regulated mains voltage,
such as life-supporting medical equipment and computer
controlled equipment. Equation (8) indicates that, if the
electric spring can regulate 𝑣𝑠 , 𝑃2 should be constant and
𝑃1 should follow the time-varying profile of the intermittent
power generation as shown in Fig. 5.
Fig. 5: Power profiles of NC load P1 and C load P2 when the mains voltage
vs is regulated by the reactive power controller. Let the rated power of the non-critical load when the electric
spring is not activated (i.e.,𝑣𝑎 = 0 ) be:
𝑃1𝑚𝑎𝑥 =
𝑣𝑠2
𝑅1 (9)
Let the actual power of the non-critical load power under
the control of electric spring (i.e., 𝑣𝑎 ≥ 0𝑉) be:
𝑃1𝑒𝑠 =
𝑣𝑠2−𝑣𝑎
2
𝑅1 (10)
From Equation (9) and (10), the relationship between the
rated power of NC load for without and with ES is given by,
𝑃1𝑚𝑎𝑥 ≥ 𝑃1
𝑒𝑠 (11)
Where 𝑃1
𝑚𝑎𝑥 and 𝑃1𝑒𝑠 are the rated power of NC load when
ES is not activated and ES activated respectively.
III. ELECTRIC SPRINGS FOR REDUCTION OF
ENERGY STORAGE
Now consider a general power grid consisting of an AC
generator, a renewable power source, energy storage
(battery banks), a set of non-critical loads and a set of
Dr. H. V. Saikumar, Sharanki. R 40
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
critical loads as shown in Fig. 6. The power flow diagram is
shown in Fig. 7 in which the power from the energy storage
can be positive or negative depending on whether the storage
device is discharging or charging [6-7].
Fig. 6: Schematic of a power grid.
The power balance equation of the power grid in Fig. 7 can
be expressed as:
𝑃𝐺 + 𝑃𝑅 + 𝑃𝑆 = 𝑃1 + 𝑃2 (12)
Fig. 7: Power flow diagram.
PS is positive when the battery is discharging and negative
when it is charging. Re-arranging Equation (12) with the
storage power as the subject of the equation,
𝑃𝑆 = −𝑃𝐺 − 𝑃𝑅 + 𝑃1 + 𝑃2 (13)
Where, PG is the power generated by the ac generator, PR is
the renewable power, and PS is the power from the energy
storage.
Without the electric spring, the energy storage requirement
for duration of T is:
𝐸𝑆 = ∫ 𝑃𝑆𝑇
0 𝑑𝑡 = − ∫ 𝑃𝐺
𝑇
0 𝑑𝑡 − ∫ 𝑃𝑅
𝑇
0 𝑑𝑡 +
∫ 𝑃1𝑚𝑎𝑥𝑇
0 𝑑𝑡 + ∫ 𝑃2
𝑇
0 𝑑𝑡 (14)
With the electric spring, the energy storage requirement for
the same duration is:
𝐸𝑆𝑒𝑠 = ∫ 𝑃𝑆
𝑇
0 𝑑𝑡 = − ∫ 𝑃𝐺
𝑇
0 𝑑𝑡 − ∫ 𝑃𝑅
𝑇
0 𝑑𝑡 +
∫ 𝑃1𝑒𝑠𝑇
0 𝑑𝑡 + ∫ 𝑃2
𝑇
0 𝑑𝑡 (15)
The difference of the energy storage requirements with and
without the electric spring can be obtained by subtracting
Equation (14) from (15), resulting in:
𝐸𝑆 − 𝐸𝑆𝑒𝑠 = ∫ 𝑃1
𝑚𝑎𝑥𝑇
0 𝑑𝑡 − ∫ 𝑃1
𝑒𝑠𝑇
0 𝑑𝑡 (16)
In view of Equation (9),
∫ 𝑃1𝑚𝑎𝑥𝑇
0 𝑑𝑡 ≥ ∫ 𝑃1
𝑒𝑠𝑇
0 𝑑𝑡 (17)
Therefore,
𝐸𝑆 ≥ 𝐸𝑆𝑒𝑠 (18)
Equation (18) shows that the use of the electric spring can
theoretically reduce the energy storage requirements in the
power grid.
V. PRACTICAL EVALUATION OF TEST SYSTEM
WITH ELECTRIC SPRING AND STATCOM
A. Test system
In order to compare the voltage regulation performance
of a single ES against that of a STATCOM, a simple test
system as shown in Fig. 8 has been considered [5-7]. The
experimental setup for evaluating the response of the ES
under a weakly regulated power grid is shown in Fig.8. The
details of system and Electric Spring specifications are
explained in [5-7].
Fig. 8: Simulation set-up with an intermittent source and an equivalent
power grid
B. Simulink model and results
The base system is modeled in MATLAB/SIMULINK
without controller, with ES and STATCOM. Fig. 9 shows
the Simulink model with Electric spring.
Two sets of experiments are carried out with different levels
of active or reactive power fluctuation generated by the
renewable energy source simulator.
Dr. H. V. Saikumar, Sharanki. R 41
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
Fig. 9: Simulink model of the test system using Electric Spring
(i) Voltage Suppression mode
The voltage across the critical load is increased above the
nominal value (216 V) by reducing the reactive power
absorption of the renewable energy source. At t=1 s, the
reactive power absorption by the intermittent renewable
source is reduced from 1.7 KVAr down to 1.2 KVAr.
Without any voltage control, the load voltage increases from
the nominal value of 216 V up to 235 V as shown by Fig.
10(a). Both ES and STATCOM are able to restore the
voltage across the critical load back to the nominal value as
shown in Figs. 10(b) and 10(c). The ES achieves this by
injecting about 166 V in series with the non-critical load
voltage across which drops to about 50 V as shown in Fig.
11 and Fig. 12 respectively. In order to suppress the voltage,
both ES and STATCOM absorb reactive power (indicated
by positive sign of Q) from the system. As shown in Fig.
13(a), Electric spring absorbs reactive power of about 165
Var more than the STATCOM. It is observed that the
reactive power consumed by ES to restore the critical load
voltage to normal value is higher than the reactive power
consumed by STATCOM to achieve the same voltage. This
is because the improper proportion of critical and non-
critical loads, as explained in [1-5].
(a) (b) (c)
Fig. 10: Critical load voltage (a) Without controller, (b) with ES and (c) with STATCOM
Fig. 11: Electric Spring Voltage Fig.12: Non-critical load voltage
(a) (b)
Fig 13: Reactive Power exchange (a) with Electric Spring and (b) with
STATCOM
(ii) Voltage Support mode
At t=1.0 s, the reactive power absorption by the
intermittent renewable energy source increased from
500VAr to 700VAr. Without any voltage control, the load
voltage is seen to drop from the nominal value of 216 V to
slightly below 120 V as shown in Fig. 14(a).
As before, both STATCOM and ES are able to
restore the voltage across the critical load back to the
nominal value as shown in Figs. 14(b) and 14(c). The ES
achieves this by injecting about 119 V in series with the
non-critical load the voltage across which drops to about 97
V as shown in Fig. 15 and Fig. 16 respectively. In order to
suppress the voltage, both ES and STATCOM inject
reactive power (as indicated by negative sign of Q) into the
system.
Dr. H. V. Saikumar, Sharanki. R 42
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
(a) (b) (c)
Fig. 14: Critical load voltage (a) Without controller, (b) with ES and (c)
with STATCOM
Comparing Fig. 17(a) and Fig. 17(b), it is observed that ES
inject about 150 VAr less than the STATCOM. It is observed
that the reactive power consumed by ES to restore the critical
load voltage to normal value is lesser than the reactive power
consumed by STATCOM to achieve the same voltage. This
is due to the fact that an increase in ES voltage will result in
a reduction of non-critical load voltage which causes a
decrease in reactive power than an equivalent STATCOM to
restore the system voltage.
Fig.
15: Electric Spring Voltage Fig. 16: Non-critical load voltage
(a) (b)
Fig 17: Reactive Power exchange (a) with Electric Spring and (b) with STATCOM
VI. CASE STUDY: IEEE 14-BUS TEST FEEDER SYSTEM
A. Test System
After comparing the performance of a single ES against a
STATCOM, the focus is to compare the performance of
electric spring against that of STATCOM in IEEE test feeder
system.
To investigate this, the IEEE 14-bus test feeder system
shown in Fig.18 is considered [10].
Fig 18: Standard IEEE 14-bus system
It consists of five Generator buses, three of which are
synchronous compensators used only for reactive power
support. There are 11 loads in the system totaling 259 MW
and 81.3 Mvar. The modeling is done in
MATLAB/SIMULINK software tool. Usually bus no.1 is
considered as slack bus. Synchronous generators are
connected at bus 1 and 2 whereas synchronous
compensators are connected at bus 3, 6 and 8 as shown in
Fig. 18. Since synchronous compensators are used for
reactive power support, consider the synchronous
compensator at bus 6. This bus 6 is directly connected to the
loads at bus 5, 11, 12 and 13 respectively. Modify the IEEE
14-bus system by connecting Electric Spring (ES) and a
STATCOM to sensitive loads at bus 12 and 13 respectively.
A distribution transformer is connected between bus 6 and
bus 12, 13 as shown in Fig. 19 to step down the source
voltage. Each load assumed to have an equal proportion
between critical and non-critical load. All other circuit
parameters are exactly the same as feeder is set up to study
unbalanced operation.
B. Simulation Results and discussion
(i) Voltage Suppression Mode
The performance of Electric Spring connected at bus 12
has been compared with that of a STATCOM, which is
connected at bus 13. A 5% step increase in the source
voltage at bus 6 is simulated. Without Electric Springs and
STATCOM it is observed that the load voltage at bus 12 and
13 (voltage across the critical load) increases from 400 V to
415V as shown in the fig 20(a). Both ES and STATCOM
are able to restore the voltage across the critical load back
to the nominal value as shown in Figs. 20(b) and 20(c)
respectively.
Dr. H. V. Saikumar, Sharanki. R 43
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
The ES achieve this by injecting about 170 V in series with
the non-critical load voltage across which drops to about 225
V as shown in Fig. 21 and Fig.22 respectively. In order to
suppress the voltage, both ES and STATCOM absorb
reactive power (as indicated by positive sign of Q) from the
system. Comparing Fig. 23(a) and Fig. 23(b), it is found that
𝑄𝑉𝐴𝑟 of Electric Spring (ES) is 530 KVAr and 𝑄𝑉𝐴𝑟 of
STATCOM is about 2100KVAr. Thus it is observed that the
reactive power capacity required for the ES is 3 to 4 times
less than that required for STATCOM.
Fig 19: Modeling of IEEE 14-bus system with ES and STATCOM at bus
12 and 13 respectively
(a) (b) (c)
Fig. 20: Critical load voltage (a) Without controller, (b) with ES and (c)
with STATCOM
Fig. 21: Electric Spring Voltage Fig. 22: Non-critical load voltage
(a) (b)
Fig 23: Reactive Power exchange (a) with Electric Spring and (b) with STATCOM
(ii) Voltage support mode
A 5% step reduction in the source voltage at bus 6 is
simulated. Without Electric Springs and STATCOM it is
observed that the load voltage at bus 12 and 13 (voltage
across critical load) decreases from 400 V to 380V as shown
in the fig 24(a). Both STATCOM and ESs are able to restore
the voltage across the critical load back to the nominal value
as shown in Figs. 24(b) and 24(c). The ES achieve this by
injecting about 190 V in series with the non-critical load
voltage across which drops to about 220 V as shown in Fig.
25 and Fig. 26 respectively. In order to support the voltage,
both ES and STATCOM inject reactive power (as indicated
by negative sign of Q) from the system.
(a) (b) (c)
Fig. 24: Critical load voltage (a) Without controller, (b) with ES and (c)
with STATCOM
Dr. H. V. Saikumar, Sharanki. R 44
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
Comparing Fig. 27(a) and Fig. 27(b), 𝑄𝑉𝐴𝑟 of Electric Spring
(ES) is about 8 MVAr and 𝑄𝑉𝐴𝑟 of STATCOM is about 32
MVAr. Thus it is observed that the reactive power capacity
required for the ES is about 3 to 4 times less than that
required by the STATCOM.
Fig. 25: Electric Spring Voltage Fig. 26: Non-critical load voltage
(a) (b)
Fig 27: Reactive Power exchange (a) with Electric Spring and (b) with STATCOM
For both voltage suppression and voltage support modes of
operation, an ES connected to the critical load at bus 12 is
shown to achieve better voltage control than a STATCOM
connected to critical load at bus 13 because both loads at bus
12 and 13 are sensitive loads.
The study on the modified IEEE 14-node test feeder
network confirms the following.
Reactive power capacity required by ES is less than
that of required by STATCOM. This helps in better
total voltage control using Electric Spring (ES)
compared to STATCOM.
Modes
Critical Voltage
Electric
spring
Voltage
Non-
Critical
Voltage
Reactive Power
Without
controller
With ESs
& STAT-
COM
With
ES
With
STAT-
COM
Voltage
suppression
mode
Increases
from
400 V up
to 415 V
Suppress
back to
400 V
𝑉𝐸𝑆 =
170V
𝑉𝑁𝐶 =
225V
𝑄𝑉𝐴𝑟=
530 KVAr
𝑄𝑉𝐴𝑟=
2100
KVArr
Voltage
support mode
Decreases
from
400 V to
380V
Brings
back to
400 V
𝑉𝐸𝑆 =
190V
𝑉𝑁𝐶 =
210V
𝑄𝑉𝐴𝑟=
8 MVAr
𝑄𝑉𝐴𝑟=
32 MVAr
Table 1: Overall Results for both voltage supress mode and support
mode and its Reactive power exchange
VII. CONCLUSION
In this paper, a comparison is made between Electric Spring
and STATCOM with respect to reactive power control. For
a given range of supply voltage variation, reactive power
capacity required by both Electric spring and STATCOM is
compared by connecting to sensitive loads. A simple case
study with a single ES and STATCOM is presented first to
show that the ES and STATCOM require comparable
reactive power to achieve similar voltage regulation.
Further, an IEEE 14-bus test feeder system is modified by
connecting transformer between bus 6 and buses 12, 13.
Also, Electric Spring and STACOM connected to the
critical loads at bus 12 and 13 respectively. Two modes of
operation Viz., voltage suppression mode and voltage
support mode are studied. In both modes, it turns out that
Electric Spring requires less reactive power capacity than
STATCOM. The ESs have the potential to solve the
stability problems arising from intermittent nature of
renewable energy sources and ensure that load demand will
follow power generation which is a new control method for
smart grid.
REFERENCES
[1] X. Luo, C.K. Lee, Z. Akhtar, B. Chaudhuri, S.C. Tan,
S.Y.R. Hui, “ Distributed voltage control with Electric
spring : Cpmparision with STATCOM,” IEEE
TRANSACTIONS ON SMART GRID, VOL. 6, NO. 1,
JANUARY 2015.
[2] D. Westermann and A. John, “Demand matching wind
power generation with wide-area measurement and DSM,”
IEEE Trans. Energy Convers., vol. 22, no. 1, pp. 145–149,
Mar. 2007
Dr. H. V. Saikumar, Sharanki. R 45
Conference Proceeding of
6th International Conference on Innovative Research in Engineering Science and Management (ICIRESM-16) at The Institutions of Electroanic and Telecommunication Engineers (IETE), Lodhi Road, New Delhi, Delhi, India
on 9th October 2016 ISBN: 978-81-932712-8-5
[3] S. Y. Hui, C. K. Lee, and F. F. Wu, “Electric springs: A
new smart grid technology,” IEEE Trans. Smart Grid, vol.
3, no. 3, pp. 1552–1561, Sep. 2012.
[4] C. K. Lee, N. R. Chaudhuri, B. Chaudhuri, and S. Y. R.
Hui, “Droop control of distributed electric springs for
stabilizing future power grid,” IEEE Trans. Smart Grid, vol.
4, no. 3, pp. 1558–1566, Sep. 2013.
[5] N. R. Chaudhuri, C. K. Lee, B. Chaudhuri, and S. Y. R.
Hui,“Dynamic modeling of electric springs,” IEEE Trans.
Smart Grid, to be published [Online].
[6] T. J. E. Miller, Reactive Power Control in Electric
Systems. Hoboken, NJ, USA: Wiley, 1982.
[7] C. K. Lee and S. Y. Hui, “Reduction of energy storage
requirements in future smart grid using electric springs,”
IEEE Trans. Smart Grid, vol. 4, no. 3, pp. 1–7, Sep. 2013.
[8] IEEE 14-Node Test Feeder [Online]. Available:
http://ewh.ieee.org/soc/pes/dsacom/testfeeders/
[9] J. Dixon, L. Moran, J. Rodriguez, and R. Domke,
“Reactive power compensation technologies: State-of-the-
art review,” Proc. IEEE, vol. 93, no. 12, pp. 2144–2164,
Dec. 2005.
[10] S. C. Tan, C. K. Lee, and C. K. R. Hui, “General steady-
state analysis and control principle of electric springs with
active and reactive power compensations,” IEEE Trans.
Power Electron., vol. 28, no. 8, pp. 3958–3969, Aug. 2013.
[11] N. G. Hingorani and L. Gyugyi, Understanding FACTS:
Concepts and Technology of Flexible AC Transmission
Systems. Piscataway, NJ, USA IEEE Press, 2000.