14
COMPACT Fluorescent Ballast Index Page Click on Model Number for Detailed Specification Sheet Model Number Number of Lamps Input Voltage Lamp Wattage Starting Other info SCO213RS 2 120 13 Rapid series SCO213RS 2 277 13 Rapid series SCC213RS 2 347 13 Rapid series SCO113RS 1 120 13 Rapid series SCT113RS 1 277 13 Rapid series SCC113RS 1 347 13 Rapid series SCE218RS 2 230 18 Rapid series SCE118RS 1 230 18 Rapid series SCO218RS 2 120 18 Rapid series SCT218RS 2 277 18 Rapid series SCC218RS 2 347 18 Rapid series SCO118RS 2 120 18 Rapid series SCT118RS 2 277 18 Rapid series SCC118RS 2 347 18 Rapid series SCO232CL 2 or 1 120 32/26 Rapid series SCO232CL 1 120 42 Rapid series SCT232CL 2 or 1 277 32/26 Rapid series SCT232CL 1 277 42 Rapid series SCC232CL 2 or 1 347 32/26 Rapid series SCC232CL 1 347 42 Rapid series SCU218 2 or 1 120 to 277 18/13 Program series SCU232 2 or 1 120 to 277 32/26 Program series SCU232 1 120 to 277 42 Program series SCU242 2 or 1 120 to 277 42/32/26 Program series SCC242 2 or 1 347 42/32/26 Program series SXU240RS 2 or 1 120 to 277 42/32 Program series SAO340RS 3 120 42/32/26 Rapid series SAT340RS 3 277 32/32/26 Rapid series SAC340RS 3 347 32/32/26 Rapid series SAO440IS 4 120 32/26 Instant parallel SAT440IS 4 277 32/26 Instant parallel SAC440IS 4 347 32/26 Instant parallel NCU257 2 or 1 120 to 277 57 Program series NCJ257 2 or 1 90 TO 240 57 Program series SCU257 2 or 1 120 to 277 57 Program parallel SCJ257 2 or 1 90 TO 240 57 Program parallel SCU270 2 or 1 120 to 277 70 Program series SCJ270 2 or 1 90 TO 240 70 Program series Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634

Compact Ballast and Lamps

Embed Size (px)

Citation preview

Page 1: Compact Ballast and Lamps

COMPACT Fluorescent Ballast Index Page Click on Model Number for Detailed Specification Sheet

Model Number Number of Lamps

Input Voltage Lamp Wattage Starting Other info

SCO213RS 2 120 13 Rapid series SCO213RS 2 277 13 Rapid series SCC213RS 2 347 13 Rapid series SCO113RS 1 120 13 Rapid series SCT113RS 1 277 13 Rapid series SCC113RS 1 347 13 Rapid series SCE218RS 2 230 18 Rapid series SCE118RS 1 230 18 Rapid series SCO218RS 2 120 18 Rapid series SCT218RS 2 277 18 Rapid series SCC218RS 2 347 18 Rapid series SCO118RS 2 120 18 Rapid series SCT118RS 2 277 18 Rapid series SCC118RS 2 347 18 Rapid series SCO232CL 2 or 1 120 32/26 Rapid series SCO232CL 1 120 42 Rapid series SCT232CL 2 or 1 277 32/26 Rapid series SCT232CL 1 277 42 Rapid series SCC232CL 2 or 1 347 32/26 Rapid series SCC232CL 1 347 42 Rapid series SCU218 2 or 1 120 to 277 18/13 Program series SCU232 2 or 1 120 to 277 32/26 Program series SCU232 1 120 to 277 42 Program series

SCU242 2 or 1 120 to 277 42/32/26 Program series SCC242 2 or 1 347 42/32/26 Program series SXU240RS 2 or 1 120 to 277 42/32 Program series

SAO340RS 3 120 42/32/26 Rapid series SAT340RS 3 277 32/32/26 Rapid series SAC340RS 3 347 32/32/26 Rapid series SAO440IS 4 120 32/26 Instant parallel SAT440IS 4 277 32/26 Instant parallel SAC440IS 4 347 32/26 Instant parallel NCU257 2 or 1 120 to 277 57 Program series

NCJ257 2 or 1 90 TO 240 57 Program series

SCU257 2 or 1 120 to 277 57 Program parallel SCJ257 2 or 1 90 TO 240 57 Program parallel SCU270 2 or 1 120 to 277 70 Program series SCJ270 2 or 1 90 TO 240 70 Program series

Due to continuing efforts to offer improved products all specifications are subject to change without prior notice

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634

Page 2: Compact Ballast and Lamps

COMPACT 2 x 13W COMPACT 1 x 13W Rapid Start Rapid Start (Series) High Frequency Electronic ballast for Compact Fluorescent 13W Philips, Osram or GE (Double or Triple) lamps.

Technical Specification: CSA, UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 15% For Bottom leads Specify “B” at the end of Model # Case Size: Series C1S Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 1/10/02

NO. OF LAMPS

INPUT VOLTAGE LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

2 120V 13 29 0.24 > 0.90 SCO213RS

2 277V 13 29 0.10 > 0.90 SCT213RS

2 347V 13 29 0.08 > 0.90 SCC213RS

NO. OF LAMPS

INPUT VOLTAGE LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

1 120V 13 17 0.14 > 0.90 SCO113RS

1 277V 13 17 0.06 > 0.90 SCT113RS

1 347V 13 17 0.05 > 0.90 SCC113RS

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 3: Compact Ballast and Lamps

COMPACT 1, 2 x 18W CIRCLINE T5 2X22W, 1X40W 2D 2x16W, 1x38W Rapid Start European Voltage Rapid Start (Series) High Frequency Electronic ballast for Compact Fluorescent 18W Philips, GE or Osram lamps.

Technical Specification: UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 15% For Bottom leads Specify “B” at the end of Model # Case Size: Series C1S Due to continuing efforts to offer improved products all specifications are subject to change without prior notice

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

2 230V 18 40 0.18 0.90 SCE218RS

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

1 230V 18 22 0.1 0.90 SCE118RS

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 4: Compact Ballast and Lamps

COMPACT 1, 2 x 18W CIRCLINE T5 2X22W, 1X40W 2D 2x16W, 1x38W Rapid Start Rapid Start (Series) High Frequency Electronic ballast for Compact Fluorescent 18W Philips, GE or Osram lamps.

Technical Specification: CSA, UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 15% For Bottom leads Specify “B” at the end of Model # Case Size: Series C1S Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 1/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

2 120V 18 40 0.34 0.90 SCO218RS

2 277V 18 40 0.14 0.90 SCT218RS

2 347V 18 40 0.20 0.90 SCC218RS

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

1 120V 18 22 0.19 0.90 SCO118RS

1 277V 18 22 0.08 0.90 SCT118RS

1 347V 18 22 0.06 0.90 SCC118RS

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 5: Compact Ballast and Lamps

COMPACT 1 or 2x18W, 13W 2D 1x28W Programmed Start

Programmed Start (Series) Universal Voltage 120V-277V High Frequency Electronic ballast for one or two (1 or 2) 18W, 13W PL-C or one (1) 2D 28W Fluorescent lamps.

Technical Specification: CSA, UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor , HL Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 10% For Bottom leads Specify “B” at the end of Model #

Case Size: Series C1U Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 2/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS AVERAGE

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

2 120V 18/13 39/31 0.32/0.25 0.90/0.96 SCU218

2 277V 18/13 39/31 0.14/0.10 0.90/0.96 “

1 120V 18/13/28 20/17/30 0.16/0.14/0.25 0.96/1.06/0.95 “

1 277V 18/13/28 20/17/30 0.05/0.04/0.11 0.96/1.06/0.95 “

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 6: Compact Ballast and Lamps

COMPACT 1 or 2x32W, 26W, 1x42W 2D 1 or 2x28W, 1x55W Rapid Start Rapid Start (Series) High Frequency Electronic ballast for one or two (1 or 2) Compact 32W, 26W or one (1) 42W, one or two (1 or 2) 2D 28W or one (1) 2D 55W 4-pin Fluorescent lamps.

Technical Specification: CSA, UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 15% For Bottom leads Specify “B” at the end of Model # Case Size: Series C2S Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 2/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS AVERAGE MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

2/1 120V 32/26/42 63/36 & 52/30/45 0.52/0.30 & 0.43/0.25/0.38 >0.88 SCO232CL

2/1 277V 32/26/42 63/36 & 52/30/45 0.23/0.13 & 0.19/0.10/0.16 >0.88 SCT232CL

2/1 347V 32/26/42 63/36 & 52/30/45 0.18/0.10 & 0.15/0.08/0.13 >0.88 SCC232CL

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 7: Compact Ballast and Lamps

COMPACT 1 or 2x32W, 26W COMPACT 1x42W Programmed Start

Programmed Start (Series) Universal Voltage 120V-277V High Frequency Electronic ballast for one or two (1 or 2) 32W, 26W or one (1) 42W Compact Fluorescent lamps.

Technical Specification: CSA, UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor , HL Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 10% For Bottom leads Specify “B” at the end of Model # Case Size: Series C1U Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 2/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS AVERAGE

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

2/1 120V 32/26 64/33 & 52/28 0.53/0.27 & 0.43/0.23 >0.90 SCU232

2/1 277V 32/26 64/33 & 52/28 0.23/0.11 & 0.18/0.10 >0.90 “

1 120V 42 44 0.36 >0.90 SCU232

1 277V 42 44 0.15 >0.90 “

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 8: Compact Ballast and Lamps

COMPACT 1 or 2 x 42W, 32W, 26W BIAX 1 or 2 x 40W, 39W, 36W Programmed Start

Programmed Start (Series) Universal Voltage 120V-277V or 347V, High Frequency Electronic ballast for one or two (1 or 2) Compact 42W, 32W, 26W or Biax 40W, 39W, 36W, or one (1) 55W, 50W GE, Philips or Osram Fluorescent lamps.

Technical Specification: CSA, UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor, HL Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 15% For Bottom leads Specify “B” at the end of Model #

Case Size: Series C4U

Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 2/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS INPUT WATTS MAX INPUT

CURRENT (A) BALLAST FACTOR

MODEL

2 120V 42/32 & 40/36 87/67 & 79/62 0.73/0.57 & 0.68/0.52 0.90 SCU242

2 277V 42/32 & 40/36 87/67 & 79/62 0.31/0.24 & 0.28/0.22 0.90 “ 2 347V 42/32 & 40/36 87/67 & 79/62 0.25/0.19 & 0.22/0.17 0.90 SCC242

1 120V 42/32 & 40/36 46/34 & 43/34 0.38/0.28 & 0.35/0.28 0.90 SCU242 1 277V 42/32 & 40/36 46/34 & 43/34 0.16/0.12 & 0.15/0.12 0.90 “ 1 347V 42/32 & 40/36 46/34 & 43/34 0.13/0.09 & 0.12/0.09 0.90 SCC242

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 9: Compact Ballast and Lamps

BIAX (TT5) 1 or 2x40W, 39W, 36W COMPACT 1 or 2x42W, 32W

Programmed Start Programmed Start (series) Universal Voltage 120V-277V, High Frequency Electronic ballast for one or two Biax 40W, 36W or two 39W or one or two Compact 42W, 32W GE, Philips, or Osram Fluorescent lamps.

Technical Specification: UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor , HL Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 10%

Case Size: Series MU Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 5/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

2 & 1 120V 40/42 84/46 90/47 0.70/0.38 0.84/0.90 0.88/0.95 SXU240RS

2 & 1 277V 40/42 84/46 90/47 0.30/0.16 0.86/0.92 0.88/0.95 “

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 10: Compact Ballast and Lamps

COMPACT 3x42W, 32W, 26W BIAX (TT5) 3x40W, 39W, 36W LINEAR T5 3x21W Rapid Start

Rapid Start (series) Electronic High Frequency ballast for three (3) Biax (TT5) 40W, 39W, 36W or Linear T5 21W, or Compact 42W, 32W, 26W GE, Philips or Osram Fluorescent lamps.

Technical Specification: CSA, UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 10o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 15% For Bottom leads Specify “B” at the end of Model # Case Size: Series FS Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 1/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS AVERAGE

INPUT WATTS MAX INPUT

CURRENT (A) BALLAST FACTOR

MODEL

3 120V 40/21/42 110/70/126 0.91/0.58/1.05 >0.90 SAO340RS

3 277V 40/21/42 110/70/126 0.39/0.25/0.45 >0.90 SAT340RS

3 347V 40/21/42 110/70/126 0.31/0.20/0.36 >0.90 SAC340RS

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 11: Compact Ballast and Lamps

BIAX (TT5) 4x40W, 39W, 36W, 27W, 24W LINEAR T5 4x28W, 21W, 14W COMPACT 4x32W, 26W Instant Start

Instant Start (parallel) High Frequency Electronic ballast for Four (4) Linear T5 28W, 21W, 14W, or Biax (TT5) 40W, 39W, 36W, 27W, 24W, or Compact 32W, 26W GE, Philips, or Osram Fluorescent lamps.

Technical Specification: CSA, UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 10o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 15% For Bottom leads Specify “B” at the end of Model #

Case Size: Series FS Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 1/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

AVERAGE INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

4 277V 40/28/32 125/108/120 1.04/0.90/1.0 >0.85 SAO440IS

4 277V 40/28/32 125/108/120 0.45/0.38/0.43 >0.85 SAT440IS

4 347V 40/28/32 125/108/120 0.36/0.31/0.34 >0.85 SAC440IS

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 12: Compact Ballast and Lamps

COMPACT 1 or 2 x 57W Programmed Start

Programmed Start (Series) Universal Voltage 120-277V, High Frequency Electronic ballast for Compact Fluorescent one or two (1 or 2) 57W GE or Osram lamps with Auto Reset feature.

Technical Specification: UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 EMI FCC Parts 18, Subparts C, Class A Thermal Protection: CLASS P Rating: Type 1 Outdoor , HL Lamp Current Crest Factor: < 1.6 Sound Rating: Class A Remote Mounting Distance: 21 ft Min. Starting Temp : - 18o C Power Factor: 0.99 Max. Case Temp: 90o C Input Frequency: 50/60HZ End of Lamp Life Protection Circuit THD: < 10% For Bottom leads Specify “B” at the end of Model #

Case Size: Series C4U Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 5/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

BALLAST FACTOR

MODEL

2 120V 57 113 0.95 0.85 NCU257

2 277V 57 111 0.4 0.85 “

2 90-240V 57 112 1.02 0.85 NCJ257

1 120V 57 58 0.48 0.90 NCU257

1 277V 57 58 0.22 0.90 “

1 90-240V 57 57 0.32 0.90 NCJ257

3 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 13: Compact Ballast and Lamps

COMPACT 1 or 2x57W Programmed Start

Programmed Start (Series) Universal Voltage 120V-277V, High Frequency Electronic ballast for Compact Fluorescent one or two (1 or 2) 57W GE or Osram lamps with Auto Reset feature.

Technical Specification: UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 Factory ISO-9002 Certified Thermal Protection: CLASS P Rating: Type 1 Outdoor , HL Lamp Current Crest Factor: < 1.7 Sound Rating: Class A Remote Wiring Distance: 21 ft Min. Starting Temp : - 20o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ IR Interference: None End of Lamp Life Protection Circuit For Bottom leads Specify “B” at the end of Model # Case Size: Series C4U Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 4/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

THD (%)

BALLAST FACTOR

MODEL

2/1 120V 57 113/58 0.95/0.48 <10 0.85/0.90 SCU257

2/1 220/240V 57 112/57 0.49/0.25 <10 0.85/0.90 “

2/1 277V 57 111/58 0.40/0.22 <10 0.85/0.90 “

2/1 90-240V 57 112/57 1.02/0.32 <10 0.85/0.90 SCJ257

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com

Page 14: Compact Ballast and Lamps

COMPACT 1 or 2 x70W Programmed Start Programmed Start (Series) High Frequency Electronic ballast for Compact Fluorescent one or two 70W GE lamps.

Technical Specification: UL Listed, CUL Certified Surge Protection: Meets ANSI C62.41 Factory ISO-9002 Certified Thermal Protection: CLASS P Rating: Type 1 Outdoor , HL Lamp Current Crest Factor: < 1.7 Sound Rating: Class A Remote Wiring Distance: 21 ft Min. Starting Temp : - 15o C Power Factor: 0.99 Max. Case Temp: 75o C Input Frequency: 50/60HZ IR Interference: None End of Lamp Life Protection Circuit For Bottom leads Specify “B” at the end of Model #

Case Size: Series C7U Due to continuing efforts to offer improved products all specifications are subject to change without prior notice 2/10/02

NO. OF LAMPS

INPUT VOLTAGE

LAMP WATTS

INPUT WATTS

MAX INPUT CURRENT (A)

THD (%)

BALLAST FACTOR

MODEL

2/1 120V 70 147/74 1.2 /0.62 <10 0.92/0.99 SCU270

2/1 277V 70 143/74 0.52/ 0.27 <10 0.92/0.99 “

2/1 90-240V 70 147/74 1.6/0.82 <10 0.91/0.94 SCJ270

5 YEAR LIMITED WARRANTY Manufacturer warrants to the purchaser: Electronic Ballast will be free from defects in material or workmanship from the date of manufacture conditioned upon proper storage, installation, use, and maintenance and conformance with any recommendations of Manufacturer.

1500 Marine Drive, #200 North Vancouver, BC V7P 1T7 TEL: 604-904-9533 FAX: 604-904-9634 www.sagelighting.com