16
Installation Instructions Original Instructions Compact 5000 I/O Digital 16-point Sinking Input Modules Catalog Numbers 5069-IB16, 5069-IB16F, 5069-IB16K The 5069-IB16, 5069-IB16F, and 5069-IB16K digital 16-point sinking input modules detect input transitions on field devices. That is, the modules detect when an input changes state from OFF to ON or from ON to OFF. The input modules convert input state transition signals to the appropriate logic level used in the controller. Compact 5000 I/O™ modules use the Producer/Consumer communication model. The Producer/Consumer communication model is an intelligent data exchange between module and other system devices in which each module produces data without first being polled. The modules are used as local I/O modules in CompactLogix™ 5380 and Compact GuardLogix™ 5380 controller systems. They can also be used as remote I/O modules with CompactLogix 5380, Compact GuardLogix 5380 controllers, and some other Logix 5000™ controllers. For more information on how to use Compact 5000 I/O modules, see the publications that are listed in Additional Resources on page 13 . Summary of Changes Topic Page About the Module 5 Install a System 5 Install the Removable Terminal Block 7 Install the Module 7 Install the End Cap 8 Wire the Removable Terminal Block 9 Disconnect Wires from the Removable Terminal Block 9 Wiring Diagram 10 Use a Cable Tie 11 Power the System 11 Remove the Module 11 Specifications 12 Additional Resources 13 Topic Pages Added catalog number for conformally coated module Throughout

Compact 5000 I/O Digital 16-point Sinking Input Modules · Compact 5000 I/O Digital 16-point Sinking Input Modules Catalog Numbers 5069-IB16, 5069-IB16F, 5069-IB16K The 5069-IB16,

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

  • Installation Instructions

    Original Instructions

    Compact 5000 I/O Digital 16-point Sinking Input ModulesCatalog Numbers 5069-IB16, 5069-IB16F, 5069-IB16K

    The 5069-IB16, 5069-IB16F, and 5069-IB16K digital 16-point sinking input modules detect input transitions on field devices. That is, the modules detect when an input changes state from OFF to ON or from ON to OFF. The input modules convert input state transition signals to the appropriate logic level used in the controller.

    Compact 5000 I/O™ modules use the Producer/Consumer communication model. The Producer/Consumer communication model is an intelligent data exchange between module and other system devices in which each module produces data without first being polled.

    The modules are used as local I/O modules in CompactLogix™ 5380 and Compact GuardLogix™ 5380 controller systems. They can also be used as remote I/O modules with CompactLogix 5380, Compact GuardLogix 5380 controllers, and some other Logix 5000™ controllers.

    For more information on how to use Compact 5000 I/O modules, see the publications that are listed in Additional Resources on page 13.

    Summary of Changes

    Topic Page

    About the Module 5

    Install a System 5

    Install the Removable Terminal Block 7

    Install the Module 7

    Install the End Cap 8

    Wire the Removable Terminal Block 9

    Disconnect Wires from the Removable Terminal Block 9

    Wiring Diagram 10

    Use a Cable Tie 11

    Power the System 11

    Remove the Module 11

    Specifications 12

    Additional Resources 13

    Topic Pages

    Added catalog number for conformally coated module Throughout

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.注意:在安装、配置、操作和维护本产品前,请阅读本文档以及“其他资源”部分列出的有关设备安装、配置和操作的相应文档。除了所有适用规范、法律和标准的相关要求之外,用户还必须熟悉安装和接线说明。

    安装、调整、投运、使用、组装、拆卸和维护等各项操作必须由经过适当训练的专业人员按照适用的操作规范实施。

    如果未按照制造商指定的方式使用该设备,则可能会损害设备提供的保护。

    ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes.El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de práctica aplicable.Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada.ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis.É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o código de prática aplicável. Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы, перечисленные в разделе «Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования. Пользователи обязаны ознакомиться с инструкциями по установке и прокладке соединений, а также с требованиями всех применимых норм, законов и стандартов.Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться обученным персоналом в соответствии с применимыми нормами и правилами.Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.注意 : 本製品を設置、構成、稼動または保守する前に、本書および本機器の設置、設定、操作についての参考資料の該当箇所に記載されている文書に目を通してください。ユーザは、すべての該当する条例、法律、規格の要件に加えて、設置および配線の手順に習熟している必要があります。

    設置調整、運転の開始、使用、組立て、解体、保守を含む諸作業は、該当する実施規則に従って訓練を受けた適切な作業員が実行する必要があります。

    本機器が製造メーカにより指定されていない方法で使用されている場合、機器により提供されている保護が損なわれる恐れがあります。

    ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten, bevor Sie dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den Installations- und Verdrahtungsanweisungen vertraut machen.Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit den anwendbaren Ausführungsvorschriften vorgenommen werden.Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein.ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer, configurer, utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur.Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.주의 : 본 제품 설치 , 설정 , 작동 또는 유지 보수하기 전에 본 문서를 포함하여 설치 , 설정 및 작동에 관한 참고 자료 섹션의 문서들을 반드시 읽고 숙지하십시오 . 사용자는 모든 관련 규정 , 법규 및 표준에서 요구하는 사항에 대해 반드시 설치 및 배선 지침을 숙지해야 합니다 .

    설치 , 조정 , 가동 , 사용 , 조립 , 분해 , 유지보수 등 모든 작업은 관련 규정에 따라 적절한 교육을 받은 사용자를 통해서만 수행해야 합니다 .

    본 장비를 제조사가 명시하지 않은 방법으로 사용하면 장비의 보호 기능이 손상될 수 있습니다 .

    ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”, riguardanti l’installazione, la configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici e standard applicabili.Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır.Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun şekilde yapılabilir.Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir.注意事項:在安裝、設定、操作或維護本產品前,請先閱讀此文件以及列於「其他資源」章節中有關安裝、設定與操作此設備的文件。使用者必須熟悉安裝和配線指示,並符合所有法規、法律和標準要求。

    包括安裝、調整、交付使用、使用、組裝、拆卸和維護等動作都必須交由已經過適當訓練的人員進行,以符合適用的實作法規。

    如果將設備用於非製造商指定的用途時,可能會造成設備所提供的保護功能受損。

    POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigurace a provozu tohoto zařízení. Uživatelé se musejí vedle požadavků všech relevantních vyhlášek, zákonů a norem nutně seznámit také s pokyny pro instalaci a elektrické zapojení.Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy.Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje.UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi kodeksami, prawem i normami.Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z obowiązującym kodeksem postępowania.Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone.OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller utföra underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert, configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in overeenstemming met de geldende praktijkregels.Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.

    2 Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    Waste Electrical and Electronic Equipment (WEEE)

    At the end of its life, this equipment should be collected separately from any unsorted municipal waste.

    Environment and Enclosure

    ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

    This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.

    This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

    In addition to this publication, see the following:• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements.• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

    Electrical Safety Considerations

    ATTENTION: • Do not wire more than 1 conductor on any single RTB terminal.• In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle

    the module. • This equipment is certified for use only within the surrounding air temperature range of 0…60 °C (32…140 °F) The equipment must not be used outside of

    this range.• Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.

    North American Hazardous Location Approval

    The following information applies when operating this equipment in hazardous locations.

    Informations sur l’utilisation de cet équipement en environnements dangereux.

    Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

    Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

    WARNING:Explosion Hazard –• Do not disconnect equipment unless power has been removed

    or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power

    has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

    • Substitution of components may impair suitability for Class I, Division 2.

    • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

    AVERTISSEMENT:Risque d’Explosion – • Couper le courant ou s'assurer que l'environnement est classé non

    dangereux avant de débrancher l'équipement.• Couper le courant ou s'assurer que l'environnement est classé non

    dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

    • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

    • S'assurer que l'environnement est classé non dangereux avant de changer les piles.

    Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018 3

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    European Hazardous Location Approval

    The following applies to products marked , II 3 G. Such modules:• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive

    94/9/EC. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details.• The type of protection is "Ex nA IIC T4 Gc" according to EN 60079-15.• The 5069-IB16, 5069-IB16F, and 5069-IB16K modules comply to standards: EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO 15 ATEX 1484X.• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations

    correspond to Zone 2 classification according to ATEX directive 1999/92/EC.

    IEC Hazardous Location Approval

    The following applies to products with IECEx certification: Such modules:• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations

    correspond to Zone 2 classification to IEC 60079-0.• The type of protection is "Ex nA IIC T4 Gc" according to IEC 60079-15.• The 55069-IB16, 5069-IB16F, and 5069-IB16K modules comply to standards IEC 60079-0:6th Edition, IEC-60079-15:4th Edition, reference IECEx certificate number IECEx UL 15.0055X.• May have catalog numbers followed by a “K” to indicate a conformal coating option.

    Special Conditions for Safe Use

    WARNING: • This equipment is not resistant to sunlight or other sources of UV radiation.• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in

    EN/IEC 60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool.

    • This equipment shall be used within its specified ratings defined by Rockwell Automation.• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in

    Zone 2 environments.• The instructions in the user manual shall be observed.• This equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes.• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this

    product.• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.• Earthing is accomplished through mounting of modules on rail.• Devices shall be used in an environment of not more than Pollution Degree 2.

    Prevent Electrostatic Discharge

    ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:• Touch a grounded object to discharge potential static.• Wear an approved grounding wriststrap.• Do not touch connectors or pins on component boards.• Do not touch circuit components inside the equipment.• Use a static-safe workstation, if available.• Store the equipment in appropriate static-safe packaging when not in use.

    IMPORTANT Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for the purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability for actual use based upon the examples shown in this publication.

    4 Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018

    http://www.rockwellautomation.com/products/certification

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    About the Module Install a SystemBased on your application design, you must install a CompactLogix 5380 controller, CompactLogix 5480 controller, Compact GuardLogix 5380 controller or a Compact 5000 I/O EtherNet/IP™ adapter before you can install the module.

    For more information on how to install these components, see Additional Resources on page 13.

    Required ComponentsTo install the module, you need these components.

    DC INPUT

    5069-IB16

    Module Status indicator

    I/O Status Indicator

    Top Interlocking Piece

    Bottom Interlocking Piece

    DIN Rail Latch

    RTB Handle

    RTB

    MOD Power Bus and SA Power Bus Connectors (isolated from each other internally)

    RTB Lower Tab

    Lower hook for use with cable tie.

    Component Description

    Removable terminal blocks

    One of the following RTB types.• 5069-RTB18-SPRING RTB• 5069-RTB18-SCREW RTBIMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that you order only the RTB type that your system requires.

    End capAn end cap ships with the CompactLogix 5380 controllers, CompactLogix 5480 controller, and Compact GuardLogix 5380 controllers and the Compact 5000 I/O EtherNet/IP adapters.

    Tools

    The following tools are needed:• Screwdriver• Wire stripper• WiresFor more information on available wire sizes and wire insulation stripping length, see Specifications on page 12.

    Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018 5

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    Dimensions Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

    Use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail with Compact 5000 I/O modules.

    System Power ConsiderationsA CompactLogix 5380 controller, CompactLogix 5480 controller, or Compact 5000 I/O EtherNet/IP adapter provides power to the module.

    The following power types are available:

    • Module (MOD) power - System-side power that is required to operate the Compact 5000 I/O modules. MOD power is provided through the MOD power RTB and passed across the MOD power bus.

    • Sensor/Actuator (SA) power - Field-side power that is used to power field-side devices. SA power is provided through the SA power RTB and passed across the SA power bus.

    The first component in the system, that is, the controller or the adapter, establishes an SA power bus.

    A system can have multiple SA power buses. You use 5069-FPD field potential distributors to establish a new SA power bus. SA power buses are isolated from each other.

    If a system includes Compact 5000 I/O modules that use AC SA power and modules that use DC SA power, you must install them on separate SA power buses.

    To keep the modules on separate SA power buses, complete the following steps.

    a. Install the modules that use one type of SA power, for example DC, to the right of the adapter or controller, that is, the first SA power bus.

    b. Install the 5069-FPD field potential distributor to establish a second SA power bus.

    DC INPUT

    5069-IB16

    109.09 mm (4.29 in.)

    25.56 mm (1.01 in.)

    144.57 mm (5.69 in.)

    105.42 mm (4.15 in.)

    22 mm (0.87 in.)ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation® publication 1770-4.1 for more information.

    6 Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    c. Install the modules that use the other type of SA power, for example AC, on the second SA power bus.

    Install the Removable Terminal Block

    1. Hook the bottom of the RTB on the module.

    2. Push the RTB against the module until the RTB clicks into place.

    3. Push the RTB handle against the RTB until you hear another click.

    Install the Module

    Install the I/O module next to the right-most device in the system. To install the module, complete these steps.

    1. Confirm that MOD power and all sources of SA power are off.

    If you remove the module with power applied, the system MOD power bus and SA power bus are affected. For example, you can interrupt MOD power to the other modules in the system. Unintended consequences can occur as a result.

    2. If an end cap is installed on the right-most module that is installed in the system, remove it and keep for later use.

    3. Confirm that the DIN rail latch is closed.

    4. If the DIN rail latches are open, gently push the rear latch back until the front latch pops up and clicks.

    IMPORTANT We recommend that you use separate external power supplies for MOD power and SA power respectively. This practice helps to prevent unintended consequences that can result if you use one supply.

    If you use separate external power supplies, the loss of power from one external power supply does not affect the availability of power from the other supply. For example, if separate external power supplies are used and SA power is lost, MOD power remains available for the Compact 5000 I/O modules.

    WARNING: If you connect or disconnect the removable terminal block (RTB) with power applied, an electric arc can occur. This could cause an explosion in hazardous location installations.

    The removable terminal block (RTB) does not support "removal and insertion under power" (RIUP) capability. Do not connect or disconnect the removable terminal block (RTB) while power is applied. Be sure that power is removed before proceeding.

    WARNING: If you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations.

    The module does not support "removal and insertion under power" (RIUP) capability. Do not connect or disconnect the module while power is applied. Be sure that power is removed before proceeding.

    ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last module on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.

    Open PositionClosed Position

    Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018 7

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    5. Align the interlocking pieces of the module with the device on the left.

    The top interlocking pieces engage first.

    6. Push the module toward the DIN rail until a click indicates that the module is locked in place.

    7. Verify that the module is installed in one of the following ways:• If the module is installed next to a controller or adapter, the

    front of the module is set back slightly from the front of the controller or adapter.

    • If the module is installed next to another I/O module, the fronts of both modules are flush with each other.

    Install the End CapYou must install an end cap on the last module in your system.

    1. Align the end cap with the interlocking pieces on the module.

    2. Push the end cap toward the DIN rail until it locks in place.

    ADAPTER

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    Top Interlocking Pieces

    Bottom Interlocking Piece

    IMPORTANT You install the end cap after the last module is installed on the DIN rail. This design helps to prevent the end cap from going beyond the locked position.

    If you push the end cap beyond the locked position or insert it from the backwards direction, you can damage the MOD power bus and SA power bus connector.

    ADAPTER

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    ADAPTER

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    Interlocking Pieces

    End Cap

    End Cap

    8 Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    Wire the Removable Terminal Block

    1. Confirm that MOD power and all sources of SA power are turned off.

    2. Strip insulation from the wires that you connect to the RTB.

    3. Connect the wire to the terminal.

    Disconnect Wires from the Removable Terminal Block

    Disconnect wires from the RTB.

    WARNING: If you connect or disconnect wiring while power is applied, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

    RTB Type Action

    Screw Strip12 mm (0.47 in.) of insulation from the wires.

    Spring Strip 10 mm (0.39 in.) of insulation from the wires.

    RTB Type Action

    Screw1. Insert the wire into the terminal.2. Turn the screwdriver to close the terminal on the wire. Torque the

    screw to 0.4 N•m (3.5 lb•in).

    Spring Push the wire into the terminal. If the wire is too thin, crimp a wire ferrule on the wire and insert it.

    5069-RTB18-SPRING RTB5069-RTB18-SCREW RTB

    WARNING: If you connect or disconnect wiring while power is applied, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

    RTB Type Action

    Screw 1. Turn the screwdriver counter-clockwise to open the terminal.2. Remove the wire.

    Spring1. Insert and hold a screwdriver in the right-side terminal.2. Remove the wire.3. Pull out the screwdriver.

    5069-RTB18-SCREW RTB

    5069-RTB18-SPRING RTB

    Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018 9

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    Wiring DiagramThe following example wiring diagram applies to the 5069-IB16, 5069-IB16F, and 5069-IB16K digital input modules.

    DC INPUT

    5069-IB16

    Input Channel 0 (I00)Input Channel 1 (I01)Input Channel 2 (I02)Input Channel 3 (I03)Input Channel 4 (I04)Input Channel 5 (I05)Input Channel 6 (I06)

    Input Channel 7 (I07)Input Channel 8 (I08)Input Channel 9 (I09)

    Input Channel 10 (I10)Input Channel 11 (I11)Input Channel 12 (I12)Input Channel 13 (I13)Input Channel 14 (I14)Input Channel 15 (I15)

    No ConnectNo Connect

    DC (+)

    2-wire Sensor

    3-wire Sensor

    DC (–)

    Channel ConnectionsThe diagram shows devices that are connected to channels 0, 3, and 6. You are not restricted to use only those channels.

    You can connect devices to any channel or combination of channels as needed.

    SA PowerConnections to an external power supply that provides SA power via the SA Power RTB on one of the following:

    • CompactLogix 5380 controller

    • 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter

    • 5069-FPD field potential distributor

    IMPORTANT: Remember the following:• The 5069-IB16 and 5069-IB16F module inputs use a shared

    common. The inputs have a return through internal module circuitry to the SA (–) terminal on the SA Power RTB. For more information, see page 6.

    • If you install modules in a Compact 5000 I/O system that use AC SA power and DC SA power, you must install them on separate SA power buses.

    You use the 5069-FPD field potential distributor to establish a new SA power bus in a Compact 5000 I/O system. SA power buses are isolated from each other. To keep the modules on separate SA power buses, complete the following steps.

    1. Install the modules that use one type of SA power, for example AC, to the right of the adapter or controller, that is, the first SA power bus.

    2. Install the 5069-FPD field potential distributor to establish a second SA power bus.

    3. Install the modules that use the other type of SA power, for example DC, on the second SA power bus.

    10 Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    Use a Cable TieAfter you connect the required wires to the RTB, you can use a cable tie to bundle the wires. There is a lower hook at the bottom of the module that you use to secure the tied bundle to the module.

    1. Make sure that you have a cable tie long enough to contain the wires that are connected to the module.

    The maximum width of the cable tie is 4.5 mm (0.18 in).

    2. Gather the wires at the bottom of the module.

    3. Thread the cable tie through the lower hook at the bottom of the RTB.

    4. Wrap the cable tie around the wires and secure it.

    Power the SystemAfter you install all Compact 5000 I/O modules, you can turn on MOD power and, if used, SA power to the system.

    For more information on MOD power and SA power, see System Power Considerations on page 6.

    Remove the Module

    1. Confirm that MOD power and all sources of SA power are turned off.

    2. If necessary, remove the end cap from the module.

    3. If desired, disconnect wires from the RTB as described on page 9.

    4. Press the DIN rail latch down until it clicks and let go.

    5. Pull the module off the DIN rail.

    6. To replace the module, follow the steps that are described beginning at Install the Module on page 7.

    ATTENTION: Do not remove or replace the module while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.

    IMPORTANT Before you remove MOD power and, if used, SA power, consider the effect on your system.

    When you remove MOD power from the controller or adapter, you shut down power to all modules in the system. That is, all system-side is removed. When you remove SA power from the controller, adapter or a field potential distributor, all field-side power that is provided by that component is removed.

    We strongly recommend that you take the appropriate actions to help prevent unintended consequences that can result from a system power shutdown before removing MOD power or SA power.

    ADAPTER

    AENTR

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    ADAPTER

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018 11

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    SpecificationsThis table lists a subset of the module specifications. For a list of all specifications, see the Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data, publication 5069-TD001.

    Attribute 5069-IB16, 5069-IB16F, 5069-IB16K

    Temperature, operating• IEC 60068-2-1 (Test Ad, Operating Cold),• IEC 60068-2-2 (Test Bd, Operating Dry Heat),• IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

    0…60 °C (32…140 °F)

    Temperature, surrounding air, max 60 °C (140 °F)

    Enclosure type rating None (open-style)

    Voltage and current ratings

    Input ratings 4…7.4 mA per channel @ 10…32V DC

    MOD Power 75 mA @ 18…32V DC

    MOD Power Passthrough(1) 9.55 A @ 18…32V DC

    SA Power 200 mA @ 10…32V DC

    SA Power Passthrough(2) 9.95 A @ 10…32V DC

    Do not exceed 10 A MOD or SA Power (Passthrough) current draw.

    Isolation voltage250V (continuous), Basic Insulation TypeNo isolation between SA power and input portsNo isolation between individual input ports

    Wire size

    5069-RTB18-SCREW connections 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater,

    3.5 mm (0.14 in.) max diameter including insulation, single wire connection only.

    5069-RTB18-SPRING connections 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater,

    2.9 mm (0.11 in.) max diameter including insulation, single wire connection only.

    Insulation stripping length

    5069-RTB18-SCREW connections 12 mm (0.47 in.)

    5069-RTB18-SPRING connections 10 mm (0.39 in.)

    RTB torque specifications (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)

    DIN railCompatible zinc-plated, yellow-chromate steel DIN rail. You can use the following DIN rail sizes:• EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)• EN50022 - 35 x 15 mm (1.38 x 0.59 in.)

    North American Temp Code T4

    ATEX Temp Code T4

    IECEx Temp Code T4

    (1) Maximum level of MOD Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.

    (2) Maximum level of SA Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.

    12 Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018

    http://literature.rockwellautomation.com/idc/groups/literature/documents/td/5069-td001_-en-p.pdf

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    Additional Resources

    You can view or download publications at http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

    Resource Description

    Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data, publication 5069-TD001 Provides specifications for Compact 5000 I/O modules and EtherNet/IP adapters.

    Compact 5000 I/O Digital Modules User Manual, publication 5069-UM004 Describes how to use the Compact 5000 I/O standard and safety digital modules.

    Compact 5000 EtherNet/IP Adapters User Manual, publication 5069-UM007 Describes how to use Compact 5000 EtherNet/IP adapters.

    CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, publication 5069-UM001 Describes how to use CompactLogix 5380 and Compact GuardLogix 5380 controllers.

    Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation® industrial system.

    Product Certifications website, http://www.rockwellautomation.com/global/certification/overview.page Provides declarations of conformity, certificates, and other certification details.

    Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018 13

    http://literature.rockwellautomation.com/idc/groups/literature/documents/td/5069-td001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/5069-um004_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/5069-um001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.rockwellautomation.com/global/certification/overview.pagehttp://www.rockwellautomation.com/global/certification/overview.pagehttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/5069-um007_-en-p.pdfhttp://www.rockwellautomation.com/global/literature-library/overview.page

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    Notes:

    14 Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018

  • Compact 5000 I/O Digital 16-point Sinking Input Modules

    Rockwell Automation SupportUse the following resources to access support information.

    Documentation FeedbackYour comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.

    Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates. https://rockwellautomation.custhelp.com/

    Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page

    Direct Dial Codes Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page

    Literature Library Installation Instructions, Manuals, Brochures, and Technical Data. http://www.rockwellautomation.com/global/literature-library/overview.page

    Product Compatibility and Download Center (PCDC)

    Get help determining how products interact, check features and capabilities, and find associated firmware. http://www.rockwellautomation.com/global/support/pcdc.page

    Preliminary Rockwell Automation Publication 5069-IN004C-EN-P - October 2018 15

  • Allen-Bradley, Compact 5000, CompactLogix, GuardLogix, Logix 5000, Rockwell Automation, Rockwell Software, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.

    EtherNet/IP is a trademark of ODVA, Inc.

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

    Rockwell Automation maintains current product environmental information on its website athttp://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

    Preliminary Publication 5069-IN004C-EN-P - October 2018 PN-510737Supersedes Publication 5069-IN004A-EN-P -October 2015 Copyright © 2018 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page

    Compact 5000 I/O Digital 16-point Sinking Input ModulesSummary of ChangesAbout the ModuleInstall a SystemRequired ComponentsDimensionsGround ConsiderationsSystem Power Considerations

    Install the Removable Terminal BlockInstall the ModuleInstall the End CapWire the Removable Terminal BlockDisconnect Wires from the Removable Terminal BlockWiring DiagramUse a Cable TiePower the SystemRemove the ModuleSpecificationsAdditional ResourcesBack Cover

    Introduction_Category Types

    This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

    Publication Type and Print Category

    Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder Min **Order Max **Life Cycle Usage / Release Option

    ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

    APA3D2Application Solution or Customer Success Story5100Presale / External

    ARNANAArticle/Editorial/BylineNANAPresale / Internal

    (press releases should not be checked into DocMan or printed)

    ATB3, B4D5Application techniques5100Presale / External

    BRA2 Primary, A1NABrochures5100Presale / External

    CAC2 Primary, C1NACatalogue150Presale / External

    CGNANACatalogue Guide150Presale / External

    CLNANACollection550Presale / External

    COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

    CPE-onlyE-only, D5Competitive Information550NA / Confidential

    DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

    DIA1, A3NADirect Mail5100Presale / Internal

    DMNANAProduct Demo550Presale / Internal

    DSB3D5Dimensions Sheet15Post / External

    DUB3D5Document Update15Post / External

    GRB2D6Getting Results15Post / External

    INB3 Primary, B2D5, D6Installation instructions15Post / External

    LMNANALaunch Materials550Presale / Internal

    PCB3D5Packaging Contents

    PLE-only primary, B3E-onlyPrice List550Presale / Internal

    PMB2D6Programming Manual15Post / External

    PPA3D1Profile (Single Product or Service). NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

    QRB2 primary, B3, B5D5, D6Quick Reference15Post / External

    QSB2 primary, B3, B5D5, D6Quick Start15Post / External

    RMB2D5, D6Reference Manual15Post / External

    RNB3D5Release Notes15Post / External

    SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External

    SGB2D5, D6Selection Guide B/W550Presale / External

    SPA1, A2, A3, A4NASales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

    SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

    TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External

    TGB2, B3D6Troubleshooting Guide15Post / External

    UMB2 Primary, B4D6User Manual B/W15Post / External

    WDB3D5Wiring Diagrams / Dwgs15Post / Internal

    WPB3 Primary, B5D5White Paper550Presale / External

    ** Minimum order quantities on all JIT items are based on the publication length. **

    Publication lengthMinimum Order Quantity

    77 or more pages1 (no shrink wrap required)

    33 to 76 pages25

    3 to 32 pages50

    1 or 2 pages100

    Pre-sale / MarketingAll paper in this category is White Brightness, 90% or better. Opacity 90% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    A14 color170 gsm 2pp100# gloss cover, 100# gloss text

    A24 color170 gsm , folded, 4pp100# gloss cover, 80# gloss text

    A34 colorCover 170 gsm with Body 120 gsm, > 4pp80# gloss cover, 80# gloss text

    A42 color170gsm Silk – 120gsm Silk80# gloss cover, 80# gloss text

    A52 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A61 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A74 color cover2 color textSelection GuideCategory being deleted10 Point Cover C2S50# matte sheet text

    A84 color coverCategory being deleted50# matte sheet text, self cover

    2 color text

    Selection Guide

    A92 color100gsm bond50# matte sheet text, self cover

    Selection Guide

    Gray shading indicates Obsolete Print Catagories

    Post Sale / Technical Communication

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

    2 color text50# matte sheet text

    B21 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B31 color100gsm bond50# matte sheet text, self cover

    B42 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B52 color100gsm bond50# matte sheet text, self cover

    Catalogs

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

    4 color text45# Coated Sheet

    C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

    2 color text32#-33# Coated Sheet

    JIT / PODAll paper in this category is White Brightness, 82% or better. Opacity 88% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    D14 color170gsm white silk80# gloss cover, coated 2 sides

    D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

    D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

    D41 color160gsm tab90# index

    D51 color80gsm bond20# bond, self cover

    D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D72 color160gsm tab90# index

    D82 color80gsm bond20# bond, self cover

    D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

    Gray shading indicates Obsolete Print Catagories

    Just In Time (JIT) or Off Set (OS)?

    Use these guidelines to determine if your publication should be JIT (just in time/print on demand) or if it would be more economical to print OS (offset/on a press). OS print jobs require an RFQ (Request For Quote) in US. If your job fits into the “Either” category, an RFQ is recommended, but not required. In the US, RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the JIT category. Guidelines differ for black & white and color printing, so be sure to check the correct tables.

    Black & White Printing

    Color Printing

    Color Printing

    Print Spec Sheet

    JIT Printing SpecificationsRA-QR005J-EN-P - 6/14/2013

    Printing SpecificationYOUR DATA HEREInstructionsNO

    (required) Publication Number:5069-IN004C-EN-PSample: 2030-SP001B-EN-P11” x 17”LOOSE -Loose LeafYESPre-sale / MarketingTOP

    Use Legacy Number:YES or NO8.5” x 11”PERFECT - Perfect BoundA1LEFT

    Legacy Number if applicable:Sample Legacy Number: 0160-5.338.375” x 10.875SADDLE - Saddle StitchA2RIGHTCORNER

    Publication Title:Compact 5000 I/O Digital 16-point Sinking Input Modules Installation InstructionsSample: ElectroGuard Selling Brief80 character limit - must match DocMan Title8.25” x 11” (RA product profile std)PLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

    Used in Manufacturing:YESYES or NO - If Yes, must have Part No. listed below8.25” x 10.875”STAPLED1 -1 positionA3

    Part Number:PN-510737If SAP Part Number, be sure to enter PN- before the number7.385” x 9” (RSI Std)STAPLED1B - bottom 1 positionA5

    (required) CategoryD5Select Print Category A,B,C or D from category list, on "Introduction_Category Types" tab6” x 4”STAPLED2 - 2 positionsA6

    Paper Stock Color:White is assumed. For color options contact your vendor5.5” x 8.5” (half-size)THERMAL - Thermal bound (Tape bound)A7

    Ink Color:One color assumes BLACK / 4 color assume CMYK / Indicate PMS number here4.75” x 7.75”THERMALO - Thermal Bound (Tape bound - offline)A8

    (required) Page Count ofPublication:16Total page count including cover. Enter PAGE count, not SHEET count4.75” x 7” (slightly smaller half-size)A9

    (required) Finished Trim Size Width:8.5” x 11”This is sheet size, before folding4.25" x 5.50"Post Sale / Technical Communication

    Fold:SampleReview key below. Leave blank if folded for saddle stitching4” x 6”B1

    Finished Fold Size:4.25" x 5.5"This is size after folding is completed3” x 5”B2

    Binding/Stitching:SADDLE - Saddle StitchReview key below9” x 12” (Folder)B3None

    Stitching Location:SIDEBlank, Corner or SideA4 (8 ¼” x 11 ¾”) (210 x 297 mm)B4Half or V or Single Fold

    Drill Hole (Yes/No):NOAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of ¼ inch from the inner page border.A5 (5.83” x 8.26”) (148 x 210 mm)B5C or Tri-Fold

    Number of Tabs Needed:5 tab in stock at RR Donnelley36” x 24” PosterCatalogsDbleParll

    Number of Pages per Pad:Average sheets of paper. 25, 50 75,100 Max24” x 36” PosterC1Sample

    Glue Location on Pad:Glue location on pads18” x 24” PosterC2Short (must specify dimensions between folds in Comments)

    (required) Business Group:Marketing CommercialAs entered in DocManJIT/PODZ or Accordian Fold

    (required) Cost Center:19134 - IAIf your Business Unit is Marketing Commercial, add the appropriate division name after 19134 using the chart on the right. All other Business Units: Enter only the number as in DocMan, no description. Example - 1902119134 - Commerc 19134 - OEM 19134 - Compone 19134 - Power C19134 - Global 19134 - Process 19134 - IA 19134 - Service 19134 - IMC 19134 - Safety 19134 - Industr 19134 - Softwar19134 - Mkt Dig 19134 - US MarkeD1Microfold or French Fold - designate no. of folds in Comments - intended for single sheet only to be put in box for manufacturing

    Comments:After the publication is printed, two folds are needed. First, fold the top to the bottom and then fold from the left to the right. After folding, the PN should show on the lower right corner.D2Double Gate

    FoldsHalf, V, Single C or Tri

    Dble Parll

    Z or Accordian Microfold or French

    Double Gate

    Short FoldSaddle-Stitch Items All page quantities must be divisible by 4.Note: Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location.80 pgs max. on 20# (text and cover)76 pgs max. on 20# (text) and 24# (cover)72 pgs max. on 24# (text and cover)

    Perfect Bound Items940 pgs max. w/cover (90# index unless indicated otherwise)70 pgs. min. for spine without words200 pgs min. for spine with words

    Plastcoil Bound Items530 pgs max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise)

    Tape Bound Items250 pgs max. on 20# no cover240 pgs max. w/cover (90# index unless indicated otherwise)D3

    D4

    D5

    D6

    D7

    D8

    D9

    MBD000B020A.bin

    MBD000B020C.bin

    MBD000B020B.bin

    MBD000B0206.bin

    MBD000B0208.bin

    MBD000B0209.bin

    MBD000B0207.bin

    MBD000B0204.bin

    MBD000B0205.bin

    MBD000B0203.bin

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles false /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice