WESTERN REGIONAL LOAD DESPATCH CENTER
MUMBAI
SCADA - Communication
Abhimanyu Gartia
DY GENERAL Manager
7/28/2019 Communication 12082011
2/36
COMMUNICATIONCOMMUNICATION
REQUIREMENTS FOR SCADAREQUIREMENTS FOR SCADA
Communication media should have:Communication media should have:* High Reliability* High Reliability
* High Availability* High Availability
* Rapid Response* Rapid Response
* Transparency* Transparency
* Economy* Economy* Flexibility* Flexibility
* Maintainability* Maintainability
7/28/2019 Communication 12082011
3/36
Load Despatching Facilities in India
SLDC AP
WRLDC
NLDC Main
NRLDC
Sub LDC C Sub LDC W
VSAT Commn
PG FO Comn
Sub LDC V
NLDC Backup
SRLDC ERLDC NERLDC
SLDC KAR SLDC AS SLDC TR
10 Sec
2 Sec
2Sec
10 Sec
New DelhiKatwariasarai
KalcuttaGolf Course Road
ULDC Commn
RTU C RTU X
RTU ARTU X
KPTCL ABB
RTU A
31 SLDCs, 5 RLDCs, 1+1 NLDC
Wideband speech and data communication
Common database in SLDC/RLDC
7/28/2019 Communication 12082011
4/36
Complete SolutionComplete Solution
WS
Historian
InternetInternet
Firewall
Corporate LAN
DMS/SCADAOther
Systems
Router/Firewall
IndustrialDefender Guard
PERIMETERPROTECTION
IndustrialDefenderConsole
MONITORING,REPORTING, DATAGATHERING AND DATAARCHIVING FROM EVERYSECURITY SYSTEMCOMPONENT
IndustrialDefenderNIDS
IndustrialDefenderHIDS/RHIDSRemote
HMI
Test/QA
HOST SECURITY ANDPERFORMANCEMONITORING
Security AuditSystem DesignInstallationCommissioningLife Cycle Support
NETWORKSECURITY ANDPERFORMANCE
MONITORING
(Industrial IDSRules)
7/28/2019 Communication 12082011
5/36
Secure Access to ElectricalSecure Access to Electrical
SubstationsSubstations
7/28/2019 Communication 12082011
6/36
POSSIBLE COMMUNICATIONPOSSIBLE COMMUNICATION
Data on different ProtocolData on different Protocol IEC 60870IEC 60870--55--101101 IEC 60870IEC 60870--55--104104
IEC 61850IEC 61850
ModbusModbus
OPC serverOPC server IT interfaceIT interface
SchedulingScheduling
Data wear housingData wear housing
Web interfaceWeb interface
PMU interfacePMU interface
7/28/2019 Communication 12082011
7/36
Complete SolutionComplete Solution
WS
Historian
InternetInternet
Firewall
Corporate LAN
DMS/SCADAOther
Systems
Router/Firewall
IndustrialDefender Guard
PERIMETERPROTECTION
IndustrialDefenderConsole
MONITORING,REPORTING, DATAGATHERING AND DATAARCHIVING FROM EVERYSECURITY SYSTEMCOMPONENT
IndustrialDefenderNIDS
IndustrialDefenderHIDS/RHIDSRemote
HMI
Test/QA
HOST SECURITY ANDPERFORMANCEMONITORING
Security AuditSystem DesignInstallationCommissioningLife Cycle Support
NETWORKSECURITY ANDPERFORMANCE
MONITORING
(Industrial IDSRules)
7/28/2019 Communication 12082011
8/36
Secure Access to ElectricalSecure Access to Electrical
SubstationsSubstations
7/28/2019 Communication 12082011
9/36
Scan CyclesScan Cycles
All the analog data are scanned every 10/12All the analog data are scanned every 10/12
secondsseconds
Status information are reported by exceptionStatus information are reported by exceptionAll status information are scanned for integrityAll status information are scanned for integrity
check every 10 minutescheck every 10 minutes
The SOE datas are time stamped at 1 msThe SOE datas are time stamped at 1 ms
resolutionresolution
Time synchronisation is done every 10Time synchronisation is done every 10minutesminutes
7/28/2019 Communication 12082011
10/36
Modes of CommunicationModes of Communication
PLCCPLCC Leased Telephone circuitsLeased Telephone circuits
Microwave CommunicationMicrowave Communication Fibre Optics CommunicationFibre Optics Communication
Satellite CommunicationSatellite Communication
7/28/2019 Communication 12082011
11/36
PLCCPLCC High voltage lines themselves are used as communicationHigh voltage lines themselves are used as communication
links.links.
Carrier Frequency: 50Carrier Frequency: 50--300 KHz.300 KHz.
3 channels are used generally:3 channels are used generally:MainMain--ChannelChannel -->>
speech channelspeech channel 300 Hz to 2000 Hz300 Hz to 2000 Hz
TelemetringTelemetring-- 2000 Hz to 3400 Hz2000 Hz to 3400 Hz
ProtectionProtection
--ChannelChannel
--II
-->>
speech channelspeech channel 300 Hz to 2000 Hz300 Hz to 2000 Hz
TeleprotectionTeleprotection-- 2000 Hz to 3400 Hz2000 Hz to 3400 Hz
ProtectionProtection--ChannelChannel--II (BackupII (Backup--Protection)Protection)-->>speech channelspeech channel 300 Hz to 2000 Hz300 Hz to 2000 Hz
TeleprotectionTeleprotection-- 2000 Hz to 3400 Hz2000 Hz to 3400 Hz
7/28/2019 Communication 12082011
12/36
PLCCPLCCAdvantages:Advantages:
1.1. High reliabilityHigh reliability
2.2. All channels are available for dedicated use byAll channels are available for dedicated use by
powerpower--utility aloneutility alone
Disadvantages:Disadvantages:
1.1. Cost of insulating communication equipment is highCost of insulating communication equipment is high2.2. High noise level due to CoronaHigh noise level due to Corona
3.3. High speed dataHigh speed data--transfer not possible because oftransfer not possible because of
Bandwidth limitations.Bandwidth limitations.
7/28/2019 Communication 12082011
13/36
Applications of PLCCApplications of PLCCVoice CommunicationVoice Communication
Fascimile TransmissionFascimile Transmission TeleTele--ProtectionProtection
TeleTele--MeteringMetering
7/28/2019 Communication 12082011
14/36
Types of CouplingsTypes of Couplings
3 coupling schemes to couple voice, fax,3 coupling schemes to couple voice, fax,teletele--protection and teleprotection and tele--metering to themetering to the
highhigh--voltage transmission line:voltage transmission line:
PhasePhase--toto--Ground CouplingGround Coupling
PhasePhase--toto--Phase CouplingPhase Coupling
InterInter--Line CouplingLine Coupling
7/28/2019 Communication 12082011
15/36
STATION-B
PLCC PANELS
STATION-A
LMU
ESLADC
CC
WT
PLCC PANELS
ESLADC
CC
WT
PHASE-TO-GROUND COUPLING
ES=Earth Switch DC=Drainage Coil WT=Wave TrapLA=Lightening Arrester LMU=Line Matching Unit CC=Coupling capacitor
7/28/2019 Communication 12082011
16/36
STATION-B
PLCC PANELS
STATION-A
LMU
ESLADC
CC
WT
PLCC PANELS
ESLADC
CC
WT
PHASE-TO-PHASE COUPLING
ES=Earth Switch DC=Drainage Coil WT=Wave Trap
LA=Lightening Arrester LMU=Line Matching Unit CC=Couplingcapacitor
BT=Balancing Transformer
WT
LMU
BT BT
LMU LMU
CC
WT
CC
7/28/2019 Communication 12082011
17/36
STATION-B
PLCC PANELS
STATION-A
LMU
ESLADC
CC
WT
PLCC PANELS
ESLADC
CC
WT
INTER-LINE COUPLING
ES=Earth Switch DC=Drainage Coil WT=Wave Trap
LA=Lightening Arrester LMU=Line Matching Unit CC=Coupling capacitor BT=Balancing
LMU
BT BT
LMU LMU
CCCC
7/28/2019 Communication 12082011
18/36
Microwave CommunicationMicrowave Communication
LineLine--ofof--sight communicationsight communication Requires repeaters at 50Requires repeaters at 50--60 kms. Intervals60 kms. Intervals
Provides sufficient bandwidth to meet the needs ofProvides sufficient bandwidth to meet the needs ofpower utilitypower utility
Higher availability than PLCC, availablity not affected byHigher availability than PLCC, availablity not affected bymaintenance or faults on the power linesmaintenance or faults on the power lines
Suffers from multipathSuffers from multipath--fading effectfading effect
In India, WPC (wireless planning & coIn India, WPC (wireless planning & co--ordination) wingordination) winghas assigned 2.3has assigned 2.3--2.5 GHz and 2.82.5 GHz and 2.8--5 GHz bands to power5 GHz bands to powersector usage.sector usage.
7/28/2019 Communication 12082011
19/36
Digital Microwave Systems
7/28/2019 Communication 12082011
20/36
Leased Telephone CircuitsLeased Telephone CircuitsSimple solution, no need to develop own
dedicated communication facility bypower utility
Availability of this mode ofcommunication at remotely locatedsubstations is the deciding factor
7/28/2019 Communication 12082011
21/36
FiberFiber
--Optic CommunicationOptic Communication
FiberFiber--optic communication is a method of transmitting information fromoptic communication is a method of transmitting information from
one place to another by sending light through an optical fiber.one place to another by sending light through an optical fiber. The lightThe light
forms an electromagnetic carrier wave that is modulated to carryforms an electromagnetic carrier wave that is modulated to carry
informationinformation
The process of communicating using fiber-optics involves the following basicsteps:
Creating the optical signal using a transmitter
Relaying the signal along the fiber, ensuring that the signal does not
become too distorted or weakReceiving the optical signal and converting it into an electrical signal
Analog/DigitalInterface
Voltage toCurrentconverter
LightSource
Source toFiber
Interface
Fiber toLight
Detector
Interface
LightDetector
Current toVoltage
converter
Analog/DigitalInterface
OUTPUT
INPUT
Optical Fiber
7/28/2019 Communication 12082011
22/36
Fiber Optic CommunicationFiber Optic Communication Advantages:Advantages:
The ability to carry much more information and deliver it wiThe ability to carry much more information and deliver it with greater fidelityth greater fidelitythan either copper wire or coaxial cable.than either copper wire or coaxial cable.
Fiber optic cable can support much higher data rates, and aFiber optic cable can support much higher data rates, and at greater distancest greater distances
The fiber is totally immune to virtually all kinds of interferenThe fiber is totally immune to virtually all kinds of interference, includingce, includinglightning, and will not conduct electricity. It can therefore colightning, and will not conduct electricity. It can therefore come in directme in direct
contact with high voltage electrical equipment and power lines.contact with high voltage electrical equipment and power lines.
POWERGRIDPOWERGRID uses overhead fiber optic communication:uses overhead fiber optic communication:
OPGWOPGW (optical ground wire cable)(optical ground wire cable)ADSSADSS (all dielectric self supporting cable)(all dielectric self supporting cable)
WRAP AROUNDWRAP AROUND
7/28/2019 Communication 12082011
23/36
Fibre Optic Systems
7/28/2019 Communication 12082011
24/36
OPGW
FODP OLTE
ADD DROP MUX2 MB/S
MICROWAVE RADIO
TERMINAL
2 MB/S
INTEGRATION OF DIGITAL & ANALOG
NETWORKS
PLCC
VOICE
CARD
DATA
CARD
7/28/2019 Communication 12082011
25/36
OPGWOPGW OPGW (optical ground wire) replacesOPGW (optical ground wire) replaces
shield wiresshield wires Provides lightning protectionProvides lightning protection
Provides communicationProvides communication
Lightning short circuit damageLightning short circuit damage
Installation requires long term outageInstallation requires long term outage
ExpensiveExpensive Superior performanceSuperior performance
7/28/2019 Communication 12082011
26/36
ADSS F.OADSS F.O
ADSS (all dielectric self supporting) whichADSS (all dielectric self supporting) whichis mounted at various locations, typically 3is mounted at various locations, typically 3
to 10 meters below the phase conductorsto 10 meters below the phase conductors..
ADSS costs less than OPGWADSS costs less than OPGW
Higher fiber count than Wrap type.Higher fiber count than Wrap type.
Can be installed on towers not designedCan be installed on towers not designed
for shield wires.for shield wires.
Suitable for hot line installationSuitable for hot line installation
7/28/2019 Communication 12082011
27/36
WRAP AROUND F.OWRAP AROUND F.O
WrapWrap--type which is wound aroundtype which is wound aroundshield wires and, in some instances,shield wires and, in some instances,around energized conductorsaround energized conductors
HotHot--line installation is difficultline installation is difficult Cost more than ADSS, but less thanCost more than ADSS, but less than
OPGWOPGW
Need a shield wireNeed a shield wire
No operation problem is observedNo operation problem is observed
7/28/2019 Communication 12082011
28/36
OPGW
WRAP
ADSS
OVERHEAD CABLES FOROVERHEAD CABLES FOR
POWER UTILITIESPOWER UTILITIES
7/28/2019 Communication 12082011
29/36
OPGW ADSS WRAP AROUND
AL STRAND
AL COATED STEEL STRAND
AL TUBE
XLPE SHEATH
POLYESTER TAPE
MOISTURE BLOCKING COMPOUND
AERIAL OPTICAL FIBRE CABLES
FIBRE
STRENGTH MEMBERS
LOOSE TUBE
AD\AS\RKG\JP\FIBCROSS
7/28/2019 Communication 12082011
30/36
FIBRE OPTIC CABLE INSTALLATION
OPGW
WRAP AROUND
ADSS
AD\AS\RKG\JP\FIBINST
7/28/2019 Communication 12082011
31/36
SATELLITE COMMUNICATIONSATELLITE COMMUNICATION
A geostationary satellite isA geostationary satellite is
used as an active repeater.used as an active repeater.
Modulated signals are sendModulated signals are send
from earth VSATs in 6 GHzfrom earth VSATs in 6 GHz
band to the satellite.band to the satellite.
Signals are beamed back toSignals are beamed back toearth in 4 GHz band.earth in 4 GHz band.
Roundtime propagation delayRoundtime propagation delay
of 540ms existsof 540ms exists
Communication is interruptedCommunication is interrupted
during eclipses.during eclipses.
7/28/2019 Communication 12082011
32/36
VIJAYAWADATALLAPALLI
GAJUWAKA
VIDYUTH SOUDHA
GOOTY
SALEM400
UDUMALPETTRICHUR NORTH
MADURAI
TRICHY
SRIPERUMBUDUR
NEYVELI
CHINAKAMPALLYDAVANAGERE
RAMAGUNDAM
PONDY
SOMANAHALLI
P
N
PALLOM
KAYANKULAM
RSCC (1)
CPCC (1)
SLDC (4)
SUB-LDC / SCC (14)
FIBRE OPTIC LINK 110/132kv
FIBRE OPTIC LINK (220kv)
FIBRE OPTIC LINK (400kv)
FIBRE OPTIC LINK (SEB)
MICROWAVE LINK (35 links)
SATELLITE LINK (KEB)
RTU LOCATIONS 201
WARANGAL
PEDAPALLIDURSHED
JAMMIKUNTA
VTPS
VIZAG SWS
KAKINADA
BOMMUR
BHIMADOLE
NSAGAR PH
SRISAILAM PH
SRISAILAM LBPHKURNOOL
SOMAYAJULAPALLI
MUDDANOOR RTPP
ANANTHAPUR
SHAPURNAGAR
GHANAPUR
CH.GUTTA
HYDERABAD 400
LEGENDLEGEND
CHALAKUDI
KALAMASSERY
VIAKKAM
KUNDRAPARIPALLI
TRIVANDRUM NORTH
VYDYUTHI BHAVANAM
KOZHIKODE
KANNUR-B
MADURAI400
CHENNAI
CHIDAMBARAM
MYLADUTURAI
SALEM230
ERODE
SIVAGANGA
KARAIKUDI
THIRUMAYAMPUDUKOTTAI
THIRUVARURORTHANADU
KOVILVENNI
ADANIKOTTAI
INGUR
PONGALORE
PANRUTI
VILLIANUR
SP.KOVIL
BANGALORE
KUMBALGODI
HUBLI
APSEB
RTUS
82
TNEB
RTUS
40
KSEB
RTUS
30
KEB
RTUS
22
PONDY
RTUS
05
CENTRAL
SECTOR RTUS
22
Lingasugur
7/28/2019 Communication 12082011
33/36
i C i f i S C
7/28/2019 Communication 12082011
34/36
Sembatti
Madurai 400
Trichy 400
Paramakudi SamayapuramMadurai North
Kodayar PH2
Madurai
Sub LDC
Karaikudi
Tanjore 230
S R PudurPariyar PH
Theni Kayathar
E
Sathur
TTPS
Podukotta
C
Echengodu
Adanakottai
Peramballur
Kovilvenni
Pugalur
Thiruvarur
Tuticorin Auto
Trichy 230
Chennai
Sub-LDC
(NLC TS-I)
Erode Sub-LDC
(Erode)
Wideband Channel Routing for Madurai Sub-LDC
OrthonaduSivagangai
Existing RTU 9 nos.
Existing RTU integrated
New RTUs 13 nos.
PLCC Link
MW Link
WRTCC
WR-SC&C Communication systemSLDCGOA
7/28/2019 Communication 12082011
35/36
WRLDC Borivalli VavHaldarwa Jambuva
Gotri
SLDC Asoj
Itarsi
Indore
Sub-LDC
ItarsiVchalKorba
STPPRaipurBhilai-400
(SLDC)
Jabalpur-400
Asoj
WRTCC
Indore
Dhule
VindhyanchalChandrapurPhadge
Kalwa
Tarapur 1&2
Itarsi-220
Bina-400 Bhopal-400
Sub-LDC
Satna-220
Katni-220
Ja
balpur-220
SLDC-
JabalpurKorba-West
Korba-East
Kalwa
Kawas
Rajgarh
Khandwa
Sipat
Raigarh
Bhatapara
Seoni
Bhilai-220
Vadodara
POP
Gandhar
Kakrapar
Dehgam
Tarapur 3&4
Phadge
Bhadrawati
Satna
Bina
Gwalior
VapiBoiser
LEGENDSGreen - ULDC Wideband Link
BLUE - PDT Link
Black - PLCC Link
Main Data PLCC Channel
St. By Data PLCC Channel
Both Main and Std. By Data PLCC Channel
Haldarwa Jambuva Asoj
62 Nos. PLCC Equipment
109 Nos. Wideband ULDC Eqpt
MPSEB Sector
CSEB Sector
CSEB Sector
GEB Sector
WR SC&C Communication system
ILA-387
ILA-174
ILA-311
ILA-194ILA-362 ILA-702ILA-368
KR-13RaipurBVati
SEBs Wideband Equipment and OFC
OPGW
U/G OFC
GOA
Leased Link
PondaMapusa
7/28/2019 Communication 12082011
36/36
ChalakudyT. NorthKozhikode -BKannur-B
Kalamassery
PallomKayamkulamKundraParipallyTrivendrum
North
Vidyuthi
Bhavanam
RSCC,Bangalore
(Udumalpet)
Wideband Routing from Sub-LDC to SLDC,(Kalamassery)
COMMUNICATION NETWORK FOR KERALA
MW Link
FO Link