© ABB Distribution Automation 07/03/22 Station Automation Series COM 600 OVERVIEW Mike Kerkhof Senior Application Engineer Distribution Automation Integration

COM 600 - Overview

Embed Size (px)

DESCRIPTION

COM 600 - Overviewabb.

Citation preview

Page 1: COM 600 - Overview

© A

BB

Dis

trib

utio

n A

utom

atio

n04

/20/

23

Station Automation Series COM 600

OVERVIEW

Mike Kerkhof

Senior Application Engineer

Distribution Automation Integration

Page 2: COM 600 - Overview

- 2

-

COM600 Station Computer

Page 3: COM 600 - Overview

- 3

-

Content

Basic Introduction

COM 600 Product Overview

Applications

Technical data

Configuration Procedure

Page 4: COM 600 - Overview

- 4

-

Basic introduction

COM 600 Station Computer Provides substation data to any personnel

through local HMI in substation or/and to any user through WAN/LAN networks

Easy to use web-browser user interface

SW bundled with ruggedized industrial HW

Fully complaint to IEC 61850 standard

Efficient and easy engineering with ABB IED’s

Compatible with any IED using open protocols

Suitable for any indoor installation

Page 5: COM 600 - Overview

- 5

-

Basic introduction

Control and Monitoring

Parameter settings & DR

Local HMI

StationCommunication

NCC Communication

External OPC client

Remote parameter

setting

COM 600 Industrial Embedded Computer

L

AN

/WA

N/

Intr

anet

/In

tern

et

Page 6: COM 600 - Overview

- 6

-

Content

Basic Introduction

COM 600 Product Overview

Applications

Technical data

Configuration Procedure

Page 7: COM 600 - Overview

- 7

-

Product overview – COM 600

HMI functionality - true web based HMI for substations Single line diagram

Dynamic busbar coloring

Controls, secured

Alarms & Events

Measurements

Disturbance record upload

Parameter setting for the IEDs

System diagnostics

Multi language support

User management

Page 8: COM 600 - Overview

- 8

-

Product overview – COM 600

OPC/IEC 61850 based architecture IEC 61850 Data Modelling

Cross referencing between protocols base on IEC 61850 data models

Drag and Drop signal mapping

Supports all utility required protocols

for communication to NCC

Supports OPC client/server principal

Page 9: COM 600 - Overview

- 9

-

Single line diagram

SLD uses one screen only Zoom in/out, Pan, Freeze

Two different voltage levels One voltage level in one row Automatic setting of default

scale Symbols for MV process

Local/Remote switch / bay / station

“All” MV apparatuses, ANSI and IEC style

Measurements Free text tags

Configurable colors, fonts, line styles

Page 10: COM 600 - Overview

- 10

-

SLD Editor Tool

Configuration of IED is retrieved by means of a Connectivity Package, which can include also the Single-Line-Diagram Still it’s freely configurable Predefined set of IEC and

ANSI symbols

Simple and easy to use Guides You to do logically

relevant configuration

IEC 61850-6 (SCL) import/export of SLD information

Page 11: COM 600 - Overview

- 11

-

Alarms

Alarm list with following columns: Date & Time Bay (from substation structure) Device (from substation structure) Object text (from d attribute of data) Status (from the event handling

definition for the data) Alarms are divided to two groups,

persisting and fleeting alarms based on current status of an alarm. Alarms can be acknowledged one by one as all of at once.

Filtering per bay, voltage level Filtering can be done automatically

from the substation structure tree Audio alarm supported for web

browsers

Page 12: COM 600 - Overview

- 12

-

Events

Event list page with columns: Date & Time Bay (from substation structure) Device (from substation

structure) Object text (from d attribute of

data) Event (from the event handling

definition for the data

Filtering can be applied per bay, voltage level

Filtering can be done automatically from the substation structure tree

Page 13: COM 600 - Overview

- 13

-

Control dialogs

Controllable switches SBO and direct controls

Support for IEC 61850 interlocking, synchro-check and reservation information

Forced cancel operation Station/remote/local authority

handling Freely definable web-links

Page 14: COM 600 - Overview

- 14

-

Measurements

All measurements available in IED can be displayed

Measurement display is configurable Scaling factor Texts Units Configuration can be

retrieved also from ConPkg or SCL files

Page 15: COM 600 - Overview

- 15

-

Disturbance record upload

The protection and control device generates disturbance records that can be uploaded from the HMI for further analysis.

Supported format is COMTRADE via IEC 61850-8-1

Page 16: COM 600 - Overview

- 16

-

Busbar coloring

Busbar coloring needs no additional configuration!

4 different modes: Powered/Unpowered based

Different voltage level

Powered/Unpowered parts

Earthed part

Voltage level based Voltage source based

Incoming/Outgoing

No busbar coloring

Freely configurable colors

Page 17: COM 600 - Overview

- 17

-

Parameters setting

Simple, but visual parameter setting tool Parameters coming from Conn.

Pkgs Visible parameters are to be

filtered on configuration phase

Changed parameters are indicated as bold

Configurable descriptions Features to ease the use and

avoid mistakes: Changed parameters bolded

after modifications Ranges, units are shown and

checked run-time

Page 18: COM 600 - Overview

- 18

-

Multilanguage support

Page 19: COM 600 - Overview

- 19

-

System diagnostics

Communication structure tree view shows quickly the health of secondary systems

Each object has mode detailed diagnostic information available

Page 20: COM 600 - Overview

- 20

-

User Management

Four different type of users Viewer Operator Engineer Administrator

User management is done from Web HMI Add user Change Password Administration of existing users

For security reasons Default password has to be

changed Certain Password length is

required

Page 21: COM 600 - Overview

- 21

-

… and more

Zoom in/out Ctrl +/-

Pan screen Alt + mouse

Several browser windows can used run in large/multi-monitor setups

Use browser features like Favorites to navigate to Your stations

And of course… Application can be accessed from anywhere

Fully web-based – real thin client

Page 22: COM 600 - Overview

- 22

-

On-line diagnostics

Web server for diagnostic information

Page 23: COM 600 - Overview

- 23

-

Other Features

Value manipulation facilities Linear and step-wise linear scales Inverting of signals

High performance on the gateway function – protocol mapping is done on the start-up phase, not on run-time

Proven protocol quality and interoperability SNTP time synchronization support (client and server)

Page 24: COM 600 - Overview

- 24

-

Content

Basic Introduction

COM 600 Product Overview

Applications

Technical data

Configuration Procedure

Page 25: COM 600 - Overview

- 25

-

Applications – COM 600

NCC and / or DCSconnection

Suitable both for Utility and Industry Applications

Providing Communication Gateway and HMI function typically for one MV substation up to 40 bays

Transferring all needed substation data to Network Control Center or Distributed Control System

HMI can be displayed Monitor/Touch Screen connected to unit locally PC directly connected to unit Through LAN/WAN networks (Intranet/Internet)

Remote/Local safety operations with Switchgear and IEDs

Flexible installation Thanks to size unit can be installed in low-

voltage compartment of Medium Voltage Switchgear

Page 26: COM 600 - Overview

- 26

-

Network Control Centers

COM 600

Touch Screen for Local HMI Functions

Local access

LAN/WAN

LAN/WAN

Remote communication

Process Communication

Remote access

Utility Applications

Page 27: COM 600 - Overview

- 27

-

Industrial ApplicationsProcess Control System

COM 600

Touch Screen for Local HMI Functions

Local Access

LAN/WAN

LAN/WAN

OPC Client/Server (DA, AE)

LV Devices & Energy Meters

Modbus RTU

Process Communication

Page 28: COM 600 - Overview

- 28

-

COM600 Supported communication protocols

Master protocol Slave protocol

DNP3 LAN/WAN DNP3 LAN/WAN

DNP3 Serial DNP3 Serial

Modbus Serial Modbus Serial

Modbus TCP Modbus TCP

IEC 61850-8-1 External OPC

IEC 60870-5-101 IEC 60870-5-101

IEC 60870-5-103 IEC 60870-5-104

IEC 60870-5-104 SPA router

LON - LAG

MNS iS Connectivity

SPA

Page 29: COM 600 - Overview

- 29

-

Single Channel - Tree Topology

Page 30: COM 600 - Overview

- 30

-

Single Channel - Ring Topology at Station Level

Page 31: COM 600 - Overview

- 31

-

Content

Basic Introduction

COM 600 Product Overview

Applications

Technical data

Configuration Procedure

Page 32: COM 600 - Overview

- 32

-

Technical data - HW

Industrial Computer (no moving parts) Intel Pentium M (1.6 GHz) 1 GB SDRAM, 8 GB SSD Industrial Flash Memory Power supply option (High voltage: 76 – 240VDC) 2 x Ethernet 100BaseTX 4 x COM (1 x RS485/232, 3 x RS 232) 4 x USB and SVGA, Audio 1 slot for extension (LON, RS232/485, 2xLAN) Hardware watchdog Dimensions 214(W) x 122,5(H) x 313(D) IP 4x enclosure Operating Ambient Temperature -25°C… +70°C Storage Temperature -40°C… +70°C Operating Humidity – 95% EMC CE/FCC class B RoHS compliant

Page 33: COM 600 - Overview

- 33

-

Interfaces

Indication LEDs

ON/OFF

PCMCIA(not used at the moment)

Compact Flash

PowerInput

LAN’sAudio

USB

PCI

Serial portsRS 232

Serial portsRS 232/485

VGA

All Interfaces are accessible from the front

Page 34: COM 600 - Overview

- 34

-

PCI card extensions

RS 232/485 4 or 8 additional - 9 pin inputs

Operating temp. 0°C-65°C

OR

Extension of Ethernet 2 additional RJ 45

Operating temp. 0°C-60°C

All PCI cards are RoHS certified

Page 35: COM 600 - Overview

- 35

-

Content

Basic Introduction

COM 600 Product Overview

Applications

Technical data

Configuration Procedure

Page 36: COM 600 - Overview

- 36

-

OPC Client

Configuration tool on a PC Web Server

OPC Server

IEC 61850

SCL

Connectivity Package’s for IEDs and/or device profiles

Conf

IEC 61850-8-1

Standard web-browser

Con

figur

atio

n P

hase

- O

fflin

e

DNP 3.0 Slave

OPC Client

Onl

ine

Ope

ratio

n

COM 600 – software environment

Remote control

Har

den

ed X

P e

mb

ed

ded

HMI application

Page 37: COM 600 - Overview

- 37

-

Configuration data flows

ABB IEDConnectivityPackages

SABdatabase

COM 600

ABB IEDconfiguration

data

IEC 61850 interface

descriptions =ICD/CID

SCD files

Stationlayout

Local namingconventions

Interface requirements and specs

HMI and gateway configuration

Com

munication P

aram

eter

s,co

lors

IED productinformation

IED instance information

Info

rmat

ion fr

om 3r

d par

ty

IEDs

SABuser

SL

D

NCCresponsible

Manually collected information

Automatically collected information

Information modeling, cross-referencing

Other requirements

Page 38: COM 600 - Overview

- 38

-

Configuration Work Flow

Define project and it’s basic

settings

Create communication structure for

the station

Own IP addressUser management

Add protocols, communication lines, sub networks …Add IEDs, using ConPkg tools or Generic IEDs. Copy/paste “type” solution

Finalize substation structure

Add/modify substations, voltage levels, bays, if not retrieved from ConPkgs/SCL files. Finalize “type” solutions

Finalize single-line diagram

Fine-tune layout, connect bays to busbars, add descriptive texts, choose coloring, add extra objects, define power source.

Customize Alarm & Event

handling

Customize IED parameter

settings

Project specific event and alarm handling can be defined for any signal. Default handling can be modified/removed /new handling added

To keep HMI simple, a subset of available parameters can be selected to be shown

Configure NCC links

Add slave protocol lines, assign addresses. Review / finalize with NCC.

Upload configuration

Upload the configuration to the device. Ready!

Page 39: COM 600 - Overview