Cold Sequence 200 & 320 amp
Specifications• 200 amp – 4, 5 or 7 terminal.
• 320 amp continuous – 4, 5 or 7 terminal 600 volt, 10K AIC.
• Ringless heavy duty lever bypass meter socket as required by utility.
• UL Listed system includes meter socket, disconnect and neutral – installed into one enclosure.
• Suitable for use as service equipment only.
• Circuit breaker connected ahead of meter for added safety while servicing equipment.
• Circuit breaker type rated: 200 amp @ 600V @ 22K, 480V @ 35K, 240V @ 65K AIC.
• Disconnects have lockable/sealable safety covers for ON / OFF operation.
• Overhead/underground units have upper and lower covers with lock and sealing provisions for utility security.
• Overhead/underground units have large hub opening for 3” or 4” hub. Order hubs separately.
• Underground units have side-by-side covers with lock and sealing provisions for utility security.
• Type 3R enclosure constructed with heavily galvanized G90 steel with light gray polyester powder coat finish.
• Convenient concentric knockouts and ample mounting embosses for ease of installation.
• Wire terminations accept copper or aluminum conductors. See ordering information for line and load wire sizes.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary
by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician
and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in
specifications and features shown without notice or obligation.
OH/UG SERVICEU5767-X-200-CB200 AMP
UG SERVICEU5797-O-400-CB320 AMP
COLDSEQUENCE 3/17Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
Catalog Number Amp Term System Service Line Load Disconnect AIC Drawing Wt (lbs.)
U5764-X-200-CB 200 4 1Ø3W OH/UG* 1/0-350 kcmil #6-350 200a CB *** Fig A 47
U5764-X-200-5T-CB 200 5 1Ø3W OH/UG* 1/0-350 kcmil #6-350 200a CB *** Fig A 47
U5765-X-200-CB 200 5 3Ø3W OH/UG* 1/0-350 kcmil #6-350 200a CB *** Fig A 52
U5767-X-200-CB 200 7 3Ø4W OH/UG* 1/0-350 kcmil #6-350 200a CB *** Fig A 53
U5784-O-200-CB 200 4 1Ø3W UG 1/0-350 kcmil #6-350 200a CB *** Fig B 64
U5784-O-200-5T-CB 200 5 1Ø3W UG 1/0-350 kcmil #6-350 200a CB *** Fig B 64
U5785-O-200-CB 200 5 3Ø3W UG 1/0-350 kcmil #6-350 200a CB *** Fig B 70
U5787-O-200-CB 200 7 3Ø4W UG 1/0-350 kcmil #6-350 200a CB *** Fig B 71
Catalog Number Amp Term System Service Line Load Disconnect AIC Drawing Wt (lbs.)
U5764-X-200-TF 200 4 1Ø3W OH/UG* 1/0-350 kcmil #6-350 200a TF 200K Fig A 43
U5764-X-200-5T-TF 200 5 1Ø3W OH/UG* 1/0-350 kcmil #6-350 200a TF 200K Fig A 43
U5765-X-200-TF 200 5 3Ø3W OH/UG* 1/0-350 kcmil #6-350 200a TF 200K Fig A 47
U5767-X-200-TF 200 7 3Ø4W OH/UG* 1/0-350 kcmil #6-350 200a TF 200K Fig A 48
U5784-O-200-TF 200 4 1Ø3W UG 1/0-350 kcmil #6-350 200a TF 200K Fig B 61
U5784-O-200-5T-TF 200 5 1Ø3W UG 1/0-350 kcmil #6-350 200a TF 200K Fig B 61
U5785-O-200-TF 200 5 3Ø3W UG 1/0-350 kcmil #6-350 200a TF 200K Fig B 65
U5787-O-200-TF 200 7 3Ø4W UG 1/0-350 kcmil #6-350 200a TF 200K Fig B 66
Catalog Number Amp Term System Service Line Load Disconnect AIC Drawing Wt (lbs.)
U5794-X-400-CB 320 4 1Ø3W OH (2) 3/0-500 kcmil (2) 3/0-500 kcmil 400a CB 10K Fig C 79
U5794-X-400-5T-CB 320 5 1Ø3W OH (2) 3/0-500 kcmil (2) 3/0-500 kcmil 400a CB 10K Fig C 79
U5795-X-400-CB 320 5 3Ø3W OH (2) 3/0-500 kcmil (2) 3/0-500 kcmil 400a CB 10K Fig C 83
U5796-X-400-CB 320 7 3Ø4W OH (2) 3/0-500 kcmil (2) 3/0-500 kcmil 400a CB 10K Fig C 86
U5797-O-400-CB 320 4 1Ø3W UG (2) 3/0-500 kcmil (2) 3/0-500 kcmil 400a CB 10K Fig D 101
U5797-O-400-5T-CB 320 5 1Ø3W UG (2) 3/0-500 kcmil (2) 3/0-500 kcmil 400a CB 10K Fig D 101
U5798-O-400-CB 320 5 3Ø3W UG (2) 3/0-500 kcmil (2) 3/0-500 kcmil 400a CB 10K Fig D 108
U5799-O-400-CB 320 7 3Ø4W UG (2) 3/0-500 kcmil (2) 3/0-500 kcmil 400a CB 10K Fig D 110
200 Amp Circuit Breaker Disconnect Ahead Of Meter Socket
200 Amp T-Fuse Pullout Disconnect Ahead Of Meter Socket
400 Amp (320 Amp Continuous) Circuit Breaker Disconnect Ahead Of Meter Socket
Cold Sequence 200 & 320 amp
Barrel lock provision on meter panel available. Add -BL suffix to end of catalog number.* UL Listed for overhead and underground use. Consult utility for underground use acceptance.** Outline drawings and knockout information are located on back page.*** Circuit breaker type rated: 600V @ 22K, 480V @ 35K, 240V @ 65K AIC.
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary
by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician
and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in
specifications and features shown without notice or obligation.
COLDSEQUENCE 3/17Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
1.13
1.13
56.00
35.50
00.100.1
13.00 O.D.6.50
C (4)
A (5)
6.01 I.D.
3.75
2.74
.69
1.942.77
2.25 2.44
4.50 4.50
B (1)BB (1)
D (2)
1.13
2.78
13.00 O.D.
1.00 1.006.50
1.13
43.00
33.00
C (6)A (5)
4.06 4.06
2.00 2.03.76
2.19
B (1)BB (1)
2.06
4.84 I.D.
2.78
1.13
11.13
28.00
1.13
1.00
6.41
19.59
26.00 O.D.
1.00
A (4)2.06
4.84 I.D.
BB (2)
2.88
2.44
2.25 2.44
.69
2.19
6.59 6.59
2.25
4.50 4.50 4.50 4.50
1.94B (2)
BB (2)C (6)D (4)
NOT
KO CONFIGURATIONSAU L MTG. EMBOSSB0 .25” 0.5” CONC.C1 .25” 1.5” 2” 2.5” 3” CONC.D1 .25” 1.5” 2” 2.5” CONC.BB 0 .25” SOLID
KO CONFIGURATIONSAU L MTG. EMBOSSB0 .25” 0.5” CONC.C1 .25” 1.5” 2” 2.5” 3” CONC.BB 0 .25” SOLID
KO CONFIGURATIONSAU L MTG. EMBOSSB0 .25” 0.5” CONC.C1 .25” 1.5” 2” 2.5” 3” CONC.BB 0 .25” SOLID
1.13
36.00
1.13
00.100.1
26.00 O.D.
15.50
6.4119.59
A (4)
6.00 I.D.
2.74
.687 2.444.50
2.254.50
4.50
2.25 2.444.50
1.942.77
C (6)
B (2)
BB (2)
D (4)
3.750
KO CONFIGURATIONSAU L MTG. EMBOSSB0 .25” 0.5” CONC.C1 .25” 1.5” 2” 2.5” 3” CONC.D1 .25” 1.5” 2” 2.5” CONC.BB 0 .25” SOLID
FIG. A – 200 AMP OH/UG (U5764)F IG. B – 200 AMP UG (U5784)
FIG. C – 320 AMP OH (U5794)F IG. D – 320 AMP UG (U5797)
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary
by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician
and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in
specifications and features shown without notice or obligation.