Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
14 D+D SEPTEMBER 2014
Coatings Technology
Calculated ImpactCan WUFI calculate the impact of coatings permeance on wall systems?By Kevin Brown, Harold DeCelle and Kenneth Trimber, KTA-Tator Inc.
he permeance of coating systems
applied to the interior and exterior
walls of single-wythe CMU (con-
crete masonry unit) buildings, and
the number of maintenance re-
paints, can directly impact wall-sys-
tem performance.
The question is — by how much. Get-
ting that answer in advance on projects
could likely prevent many coating and
wall-system failures.
This article discusses the permeance of
coatings and presents the results of pre-
liminary thermodynamic modeling using
WUFI-ORNL/IBP (Oak Ridge National Lab-
In the “wet cup method,” Procedure B of ASTM E 96 Standard Test Methods for Water Vapor Transmission of Materials, dry paint films sealedon dishes of deionized water are measured for vapor permeability. Photo courtesy of KTA-Tator.
T
Coatings Technology15
oratory/Fraunhofer Institute for Building
Physics) to track the effects of a few inte-
rior/exterior coating-permeance scenarios
on the performance of wall systems.
As you may know, WUFI comes from the
German “Wärme und Feuchte instationär,”
which roughly translated, means “heat and
humidity transient.” WUFI is a software
family that helps design professionals cal-
culate real-world one- and two-dimensional
heat and moisture transport in multi-layer
building wall assemblies exposed to
weather.
The model examined in this article uses
two hypothetical but identical CMU build-
ings. Variables include building locations —
Providence, R.I. and Miami; the permeance
of interior wall coatings — no coating and 5
English perms; and exterior coating system
permeance — 40, 25, 15 and 5 English
perms applied to 8-inch (20-cm) concrete
block.
Vapor DriveFor background, let’s review the signifi-
cance of vapor drive. The following discus-
sion of vapor drive is from the
November/December 2012 Durability + De-
sign article, “Coating System Concerns for
Single-Wythe CMU Construction1.”
A “vapor drive” is caused by the difference in rel-ative humidity (RH) between the building interior(typically higher RH) and the exterior environment(typically lower RH), causing water molecules inthe interior air to pass through molecules of thewall components. If the wall is not insulated, andgiven certain exterior ambient climatic conditions,temperature will cycle within the block and fallbelow the dew point, causing the vapor to con-dense, wetting the interior of the block and po-tentially leading to coatings problems. The degreeof vapor drive is controlled by the porosity of the
denses to liquid. The most obvious signs thatthis is occurring is the presence of surface con-densation or efflorescence, but the most dam-aging effect of the moisture is when it becomestrapped behind the paint or within the fabric ofthe wall. Cures include good ventilation, a con-sistent heating level, a contiguous air/vaporbarrier and good wall insulation.
In the example of a building in a northern cli-mate, if moisture vapor cannot pass through theexterior coating at a sufficiently rapid rate, itwill build up and condense to liquid, potentiallyincreasing the vapor pressure behind the coat-ing at the wall interface, resulting in coatingblistering. The cyclic temperature conditionswill result in accumulation of more moisture inthe form of liquid, and expansion of blisters withincreasing periods of vapor pressure. Eventu-ally the coating system adhesion will fail.
While permeance is a key factor in se-
lecting coating systems for walls, other
factors affect wall performance including
air infiltration/exfiltration, stack effect,
wind load, insulation and mechanical pres-
surization, as well as defects in the cop-
ing, roof membrane, gutters, flashing,
mortar and sealants.
Determining Water-Vapor Permeance of CoatingsSelection of interior and exterior coating
systems should be based on the expected
vapor drive, and the vapor permeance of
the coatings. Laboratory water-vapor per-
meance testing measures the rate at
which a solid material lets moisture pass
from one side of a membrane to the other.
ASTM E 96 Standard Test Methods for
Water Vapor Transmission of Materials is
commonly used to test the properties of
coating films — both individual coats and
entire systems. Test conditions should be
chosen based on the material design pa-
wall, together with environmental factors, espe-cially:
Moisture gradients. Moisture vapor will natu-rally move from a higher concentration to alower concentration until in balance. With highvapor pressure to the interior of the wall, and lowvapor pressure to the exterior of the wall, vapordrive will be directed outward (and vice versawhen the relative vapor pressures are reversed).The greater the difference of this vapor pressureor “concentration gradient,” the greater is thevapor drive.
Temperature gradients. Moisture vapor willnaturally move from the warm side of a wall tothe cooler side. With higher temperatures to theinterior of the wall and lower temperatures to theexterior of the wall, vapor drive will be directedoutward (and vice-versa when the differences intemperature are reversed). The greater the“temperature gradient” (difference), the greaterthe vapor drive.In other words, the movement of moisture via
diffusion is a result of differences in vapor pres-sure that are related to the temperature andmoisture content of the air on both sides of thewall. The mixed climates found across the coun-try, both in the interior space and external to thebuilding, must be taken into consideration whendetermining the direction of vapor diffusion andwhen designing the painting system.
The practical problems that can occur if
vapor drive is ignored during building de-
sign and construction were described by
Cindy O’Malley, Chuck Duffin and Steve
Revnew in their paper “Use of Atlas Test
Cells to Assess the Performance of Coat-
ings with Varied Permeance over Concrete
Masonry Units,” which they presented at
The Society for Protective Coating’s Green-
COAT conference in 2012.
If the exterior coating material blocks or re-stricts this natural flow of warmer air to coolerair it will lead to a buildup of vapor. When cool-ing of the air (vapor) occurs, the vapor con-
16 D+D SEPTEMBER 2014
rameters for use, but Procedure B, wet cup
method, is frequently used for coatings.
Procedure B involves the application of a
coat, or the entire system of coatings, to
polyester sheets so that after drying, films
of consistent thickness can be removed
from the sheets to produce free-standing
films. The researchers cut the films into
discs and seal them to open-faced glass
dishes of a specific diameter — 4 inches (10
cm), for example — filled with deionized
water to three-quarters of their volumes.
They weigh the dishes and expose them in
a controlled temperature/humidity cham-
ber at approximately 23 C (73 F) and 50
percent RH for 17 days.
The researchers weigh the dishes at pre-
scribed intervals during the exposure pe-
riod and plot the results on a graph. When
the testing is done, they calculate perme-
ance, commonly reported in English perm
units. It is critical to know which method
generated the data, in order to compare re-
sults. Different test methods, even under
the same ASTM standard, can yield differ-
ent results.
The sophisticated computer program
WUFI-ORNL/IBP assesses the combined
heat and moisture transfer in building com-
ponents based on building type and local
interior and exterior environments. Build-
ing envelope components such as wall ma-
terials, windows and insulation are entered
into the program, and it calculates the im-
pact of the components on heating loss
and the direction of vapor diffusion and liq-
uid transport through the walls. WUFI-
ORNL/IBP has been used to determine the
effect that the interior/exterior placement
of air and weather barrier coatings can
have on the performance of building walls.
WUFI doesn’t house specific coating sys-
tem data by manufacturer or product type
but the advanced versions allow the user
to enter a permeance value. The perme-
ance value includes the entire coating sys-
Fig. 1: Providence – This graph of the exterior block face shows high moisture in winter. The graph isbased on 5-perm coatings on the exterior and interior surfaces. The extension of the graph above the redline indicates moisture build-up.
Efflorescence exuding from a pinhole in an exterior coating indicates the presence of moisture withinthe wall. WUFI may hold answers about the effects of coating permeance on wall-system ability tohandle moisture vapor. Photo courtesy of KTA-Tator.
3/1/2015 9/1/2015 3/1/2016 9/1/2016 3/1/2017 9/1/2017
2.49
2.35
2.21
2.08
1.94
1.8
3.6
3.4
3.2
3
2.8
2.6
Concrete Brick
Water Con
tent [M
.- %]
Water Con
tent [lb/ft3]
Click our Reader e-Card at www.durabilityanddesign.com/ric
H
18 D+D SEPTEMBER 2014
tem (primer and topcoat) including re-
paints, if applicable. A few manufacturers
have permeance values for coating sys-
tems but many haven’t published this in-
formation.
If the permeance values aren’t known,
laboratory testing must determine them,
or else users must determine the values
based on experience.
The authors ran a few building scenar-
ios by inserting values for the permeance
of exterior coatings based on data deter-
mined in the laboratory2, together with
the anticipated reduction in permeance
after repainting. The authors used values
40, 25, 15 and 5 English perms for the ex-
terior coatings applied to 8-inch concrete
block.
Interior treatments included bare CMU
and low-permeance (5 English perms)
coatings. The authors entered the values
into WUFI to determine the predicted ef-
fect that changes in interior and exterior
coating permeance might have on the
performance of walls in identical, 8-inch
single-wythe CMU buildings in Provi-
dence and Miami. The interior building
environment stayed consistent with air
conditioning, heating set point 69.98 F
(21.1 C) and cooling set point 75.02 F
(23.9 C), no dehumidification, and low
density sprayed-polyurethane foam insu-
lation in the wall cavity.
WUFI Modeling ResultsThe authors drew the following conclu-
sions from the specific variables ana-
lyzed, but readers should not rely on the
results that follow for making building-
specific coating decisions since variables
such as the wall-system assembly, dehu-
midification, interior conditioning, insula-
tion and other factors will affect the
results.
The authors judged performance in
each scenario by the amount of moisture
Fig. 2: Providence – This biological graph shows the interior surface. The graph is based on 5-perm coatingson exterior and interior surfaces. The graph indicates potential for mold growth within the first season.
Moisture trapped in wall systems causes all sorts of damage, from biological growth to coatingdelamination. Here, moisture trying to escape from the wall has created blisters in exterior paint. Photo courtesy of KTA-Tator.
45 60 75
100
80
60
40
20
0
7.63 in (Interior Surface)– – LIM B I ––– LIM B II
Relativ
e Hu
midity
[%]
Temperature [°F]
Coatings Technology19
WUFI predicted would develop in the
walls, and the potential for mold growth.
The model included cycling for three years,
Oct. 1, 2014 through Oct. 1, 2017 using
“cold year” cycles.
MiamiThe wall system performed best with the
interior bare and a low-permeance (5 Eng-
lish perms) coating on the exterior.
When the interior side was bare, the
wall system performance, while still good,
decreased as the permeance of the exterior
coating system increased (from 15 to 40
English perms).
With a low-permeance system (5 perms)
on the interior, the performance of the wall
system was best with a low-permeance ex-
terior coating system (5 perms).
When the interior was coated with a
low-permeance system (5 perms), in-
creaing the permeance of the exterior coat-
ing system (from 15-40 perms) decreased
wall-system performance, creating poten-
tial for biological growth on the interior.
See Figure 3 on page 20.
The permeance of the interior coating
system influenced performance more (bare
CMU was better), than the permeance of
the exterior coating system (although
lower permeance was better).
ProvidenceThe wall system performed best with the
interior side bare and a high-permeance
coating (40 perms) on the exterior, the op-
posite of Miami.
Performance worsened when the interior
and exterior sides were both coated with
low permeance systems (5 perms). The
low permeance on the exterior caused poor
performance, the opposite of Miami. See
Figure 1 on page 16.
The preceding scenario (5 perms interior
and 5 perms exterior) created biological
growth potential. See Figure 2 on page 18.
Exterior coating permeance influenced
wall-system performance (the higher the
permeance the better) more than the inte-
rior. A 5-perm interior coating system
showed a slight performance decrease
compared to bare block.
OverallIn these scenarios, the Miami wall system
outperformed the Providence wall system.
The authors have seen this in existing
buildings. Southern buildings generally
sustain less peeling, blistering and sub-
Click our Reader e-Card at durabilityanddesign.com/ric
20 D+D SEPTEMBER 2014
strate damage such as spalling and mortar
deterioration than buildings in the North.
Much additional modeling needs to be
undertaken before relying on WUFI to se-
lect coating systems, but the preliminary
analysis conducted for this article indi-
cates that WUFI has a great deal of prom-
ise for use in the coatings industry.
Questions and answers regarding the
potential use of WUFI based on the initial
analysis include:
Q: Will interior/exterior painting strate-
gies that are successful in one geographi-
cal location perform the same in another
location?
A: Based on preliminary modeling of a few
scenarios using identical insulated build-
ing designs in Florida and Rhode Island,
the answer is no. The same coating sys-
tem can result in differences in the per-
formance of walls depending on the local
environment. In the models run by the au-
thors, an exterior coating with low perme-
ance provided the best performance in
Miami, but the same system provided the
worst performance in Providence.
Q: Does WUFI appear to be of value in
making judgments on the number of re-
paints that are feasible before problems
occur with the wall’s performance?
A: Based on laboratory-generated perme-
ance data of a few coating systems after re-
painting, it appears that WUFI could have
great utility in determining the number of
building-specific repaints that are feasible
before problems occur. However, more
analysis is required, and brand-specific per-
meance data is needed to better determine
the utility of the program for this purpose.
Potential for CoatingsThe modeling using the WUFI program
demonstrates WUFI’s value as a tool to as-
sist in selecting coatings for the interior and
exterior walls of single-wythe CMU build-
ings based on the permeance of the coat-
ings and the building-specific
interior/exterior climate.
The modeling also suggests that once
the permeance of given systems, by brand,
is established analytically for both the new
installation and each repaint, WUFI will be
able to predict the number of mainte-
nance-painting operations that are feasible
before problems with the building walls
can be expected.
The modeling also shows that the selec-
tion of coating systems depends on the
permeance of the systems and the unique
service environment for both interiors and
exteriors. That is, using the same interior
and exterior coating systems and mainte-
nance painting schedule on the walls of a
building located in one climate, such as
Miami, may not be the best approach for a
building in another climate, such as Provi-
dence.
Based on the success of the preliminary
modeling, the authors plan additional
modeling to include more building-specific
variables and environments to better ex-
amine the capability of WUFI for use in
coating system selection.
Assuming the more in-depth analysis is
promising, the WUFI database will need to
be populated with permeance data for a
variety of interior and exterior building-
wall paint systems, including the reduc-
tion of permeance after multiple repaints.
The authors are willing to coordinate the
collection of coating permeance data, and
independently review the data for submis-
sion if coating manufacturers are inter-
ested in participating.
References(1) “Coating System Concerns for Single
Wythe Concrete Masonry Unit (CMU)
Construction,” K. Trimber, Durability +
Design: the Journal of Architectural
Coatings, November/December 2012,
Vol. 2, No. 6. pp. 32-39.
(2) “Use of Atlas Test Cells to Assess the
Performance of Coatings with Varied
Fig. 3: Miami – This biological graph shows the interior surface. The graph is based on a 5-perm coatingsystem on the interior and a 40-perm coating system on the exterior. The graph indicates potential formold growth within the first season.
45 60 75
100
90
80
70
60
50
7.63 in (Interior Surface)– – LIM B I ––– LIM B II
Relativ
e Hu
midity
[%]
Temperature [°F]
Coatings Technology21
Permeance over Concrete Masonry Units
(CMU)”, Cindy O’Malley – KTA-Tator,
Inc. Chuck Duffin – Sto Corp, and Steve
Revnew – Sherwin-Williams, SSPC
GreenCoat 2012, Las Vegas NV, February
2012.
About the AuthorsKenneth A. Trimber, president of KTA-
Tator Inc., is a NACE-certified coatings in-
spector level 3, an SSPC-certified
protective coatings specialist and is certi-
fied at a level III coating
inspection capability in
accordance with ANSI
N45.2.6. Trimber has 40
years of experience in
coatings inspection,
testing and analysis, is
a past president of the Society for Protec-
tive Coatings (SSPC), and is chairman of
the SSPC committees on Surface Prepara-
tion, Visual Standards and Containment,
along with the SSPC Commercial Coatings
Committee (Architectural, Commercial, In-
stitutional).
Kevin J. Brown is manager of the Commer-
cial Services Group for KTA-Tator Inc.,
where he develops and implements main-
tenance programs for commercial clients
with architectural/commercial problems
related to paint failures. He’s a certified XL
tribometrist and regis-
tered roof observer.
Brown has a Bachelor of
Science degree and an
MBA from Gardner-
Webb University in Boil-
ing Springs, N.C., and
has more than 13 years of experience in
the field of retail facility management.
Harold DeCelle is a building inspection
technician for KTA’s Commercial Services
Group. He has more than 35 years of expe-
rience in construction and building design,
and a Bachelor of Science in Civil Engi-
neering (Structural) from the University of
North Carolina at Charlotte. DeCelle evalu-
ates commercial building envelopes for
KTA clients nationwide. He performs de-
structive and non-destructive testing in
forensic evaluations of existing buildings
and performs modeling using WUFI to aid
in restoration design. D+D
Click our Reader e-Card at durabilityanddesign.com/ric