AD AP CTE DTF STW STB AUTOMATIC CONTROL VALVE PIPE UP PIPE DOWN CAPPED PIPE DIRECTION OF FLOW PIPE SLEEVE CONTINUOUS PIPE METER UNION STRAINER BACKFLOW PREVENTER WATER FEEDER ASSEMBLY FLEXIBLE PIPE CONNECTION PUMP PRESSURE GAUGE WITH COCK THERMOMETER STARTER FAN SPEED CONTROLLER SLEEVE THROUGH BEAM SLEEVE THROUGH WALL DOWN THROUGH FLOOR CONNECT TO EXISTING ACCESS PANEL ACCESS DOOR BACKWATER VALVE WITH ACCESS BACKWATER VALVE INLINE VALVE IN RISER MOTORIZED BUTTERFLY VALVE 3 WAY BUTTERFLY CONTROL VALVE AUTOMATIC CONTROL VALVE SAFETY RELIEF VALVE PRESSURE DIFFERENTIAL VALVE NEEDLE VALVE BALANCING VALVE (PLUG) CIRCUIT BALANCING VALVE SOLENOID VALVE FLOW METER, VENTURI FLOW SWITCH PRESSURE REDUCING VALVE PLUG VALVE LOCKSHIELD VALVE BUTTERFLY VALVE SHUT-OFF VALVE AND ACCESS PANEL GATE VALVE AND FLOW SWITCH VALVED AND CAPPED PROVISION HOSE-END DRAIN VALVE FLOAT VALVE CHECK VALVE BALL VALVE LOCKABLE FLOW CONTROL VALVE GLOBE VALVE GATE VALVE M ETC ELECTRIC TRACING CABLE 3 TM-01 LEGEND - GENERAL NTS BFP WFA PUMPED DRAIN UNDER FLOOR PD PUMPED DRAIN PD SUPERVISED VALVE FIRE DEPARTMENT VALVE SPRINKLER STANDPIPE FIRE STANDPIPE SV FDV SPR FSP FIRE EXTINGUISHER WITH CABINET FIRE EXTINGUISHER FIRE HOSE RACK FIRE HOSE CABINET SIAMESE PUMPER CONNECTION FG CMD CARBON MONOXIDE DETECTOR FIRE GONG SIDEWALL SPRINKLER HEAD CONCEALED SPRINKLER HEAD UPRIGHT SPRINKLER HEAD PENDENT SPRINKLER HEAD CHECK VALVE WITH BALLDRIP PREACTION ALARM CHECK VALVE DRY ALARM CHECK VALVE WET ALARM CHECK VALVE SPRINKLER MAIN (GLYCOL) SPRINKLER MAIN (DRY) SPRINKLER LINE (WET) FIRE LINE RWL VTR VS WS SS RAINWATER LEADER VENT THROUGH ROOF VENT STACK WASTE STACK SOIL STACK MANHOLE CATCHBASIN CD A G SCUPPER DRAIN FLOOR DRAIN OR ROOF DRAIN HOSE BIBB/WALL HYDRANT T CONDENSATE DRAIN COMPRESSED AIR GAS PIPE DOMESTIC TEMPERED WATER DOMESTIC HOT WATER RECIRC DOMESTIC HOT WATER DOMESTIC COLD WATER RUNNING TRAP WITH CLEANOUT RUNNING TRAP WITH CLEANOUT DRAIN WITH CLEANOUT UP TO FLOOR DRAIN WITH CLEANOUT UP TO FLOOR DRAIN WITH CLEANOUT VENT PIPE V BURIED STORM DRAIN ST STORM DRAIN ST BURIED SANITARY DRAIN SAN SANITARY DRAIN SAN HB MH CB WH F SP DSP GSP FHC FHC FE FE CO CO GREASE TRAP GT LS FLOOR DRAIN (PARKING) SHOWER HEAD LIQUID SOAP 2 TM-01 LEGEND - PLUMBING, DRAINAGE AND FIRE PROTECTION NTS SINGLE LINE RIGID DUCT SINGLE LINE DUCT WITH ACOUSTIC LINING SINGLE LINE FLEXIBLE DUCT DOUBLE LINE FLEXIBLE DUCT SUPPLY AIR DIFFUSER RETURN AIR GRILLE FIRE DAMPER SMOKE DAMPER MOTORIZED DAMPER MANUAL BALANCING DAMPER MOTORIZED COMBINATION THERMOSTAT HUMIDISTAT DOOR UNDERCUT DOOR GRILLE BD MD SD FS FD T H CAP SIZE TYPE PIPE ANCHOR DOUBLE LINE DUCT DUCT WITH ACOUSTIC LINING SOUND BAFFLE PIPE GUIDE EXPANSION JOINT REFRIGERANT SUCTION REFRIGERANT DISCHARGE REFRIGERANT LIQUID CONDENSATE RETURN STEAM MAIN (PRESSURE AS INDICATED) HEATED WATER RETURN HEATED WATER SUPPLY HWS HWR S C RL RD RS ROUND DUCT DOWN ROUND DUCT UP RETURN DUCT DOWN SUPPLY DUCT DOWN RETURN OR EXHAUST DUCT SUPPLY OR OUTSIDE AIR DUCT SOUND ATTENUATOR HEATING TERMINAL SUPPLY AIR CFM GRILLE OR REGISTER SIZE/TYPE 300 12/12 D 12/12 E 300 GRILLE OR REGISTER SIZE/TYPE EXHAUST OR RETURN AIR CFM EXHAUST OR RETURN AIR CFM GRILLE OR REGISTER SIZE/TYPE 300 12/12 E 12/12 D 300 GRILLE OR REGISTER SIZE/TYPE SUPPLY AIR CFM SUPPLY AIR CFM DIFF NECK SIZE/DIFF TYPE 200 6"Ø A FIRE AND SMOKE DAMPER UC DG GLYCOL RETURN GLYCOL SUPPLY FUEL OIL RETURN FUEL OIL SUPPLY CONDENSER WATER RETURN CONDENSER WATER SUPPLY CHILLED WATER RETURN CHILLED WATER SUPPLY RADIATION WATER RETURN RADIATION WATER SUPPLY RWS RWR CHWS CHWR CWS CWR FOS FOR GS GR 1 TM-01 LEGEND HVAC NTS LOW & MEDIUM DUCT TAKE-OFFS NTS 4 TM-01 NOTE: DEPTH OF DUCT SHALL BE MINIMUM 50mm (2") LARGER THAN TAKE-OFF CONNECTION MEDIUM OR LOW PRESSURE DUCT HANDLE SPIN ON COLLAR DAMPER BLADE WING NUT RIGID DUCT ROOF TOP UNIT INSTALLATION (RTU-145-01) NTS 5 TM-01 BOTTOM OF JOISTS ROOF DECK ACCOUSTICALLY LINED SUPPLY & RETURN DUCTWORK TERMINATE 300mm (12") BELOW ROOF DECK FACTORY INSTALLED WEATHERPROOF DISCONNECT SWITCH. ECONOMIZER INTAKE PROGRAMMABLE HEATING/COOLING THERMOSTAT AND 30m (100') OF PLENUM RATED CONTROL WIRING COILED AND TEMPORARILY ATTACHED TO ROOF STRUCTURE. TYPICAL FOR CRU'S, FOR MALL RTU'S REFER TO FLOOR PLANS. ROOF TOP MANUFACTURER SUPPLIED INSULATED PRE-FABRICATED ROOF CURB BY MECHANICAL DIVISION. T ROOF SYSTEM LUBRICATED GAS SHUT OFF VALVE SCHEDULE 40 GAS PIPING SUPPORTED ON ROOF AS PER DETAIL. POWER WIRING FROM DISCONNECT TO POWER SOURCE BY ELECTRICAL DIVISION, REFER TO ELECTRICAL DRAWINGS. PROVIDE A TRAP FROM THE COOLING COIL DRAIN THAT HAS A DEPTH OF 25mm (1") GREATER THAN THE TOTAL FAN STATIC PRESSURE. PROVIDE GASKET ROOF TOP AC UNIT 6 TM-01 CLEAN-OUT DETAILS NTS ALTERNATE LOCATION FOR CLEANOUT AND ACCESS ACCESS DOOR. SEE SPECIFICATIONS. IRON FERRULE WITH RAISED HEAD BRASS PLUG ACCESS COVER TO SUIT FLOOR FINISH MATERIAL. SEE SPECIFICATIONS. IRON FERRULE WITH RAISED HEAD BRASS PLUG IRON FERRULE WITH RAISED HEAD BRASS PLUG BARRET TYPE, BOLTED COVER, BRASS CAP SCREWS. ACCESS DOOR. SEE SPECIFICATION. CLEANOUT TEE SPRINKLER LINE 150mm (6") 25mm (1") 25mm (1") PLUG FOR FUTURE SPRINKLER 25/25/25mm (1"x1"x1") SCREWED TEE FINISHED CEILING SPRINKLER LINE 150mm (6") 150 (6") FIELD MEASURE 25mm (1") 25mm (1") (1") 25mm 25/25/25mm (1"x1"x1") SCREWED TEE 25mm (1") PLUG FOR FUTURE SPRINKLER FINISHED CEILING SPRINKLER LINE 150 (6") FIELD MEASURE 25mm (1") 25mm (1") 150mm (6") 25mm (1") 25/25/25mm (1"x1"x1") SCREWED TEE 25mm (1") PLUG FOR FUTURE SPRINKLER 7 TM-01 TYPICAL SPRINKLER HEAD INSTALLATION NTS 8 TM-01 SUPPORTS FOR GAS PIPING ON ROOF NTS FRONT ELEVATION SIDE ELEVATION ROOF NOTES: 6. 7. 8. 9. 10. CADMIUM PLATED No. 12 - 50mm (2") LONG SCREWS SHIM WOOD BLOCKING AS REQUIRED TO COMPENSATE FOR ROOF SLOPE ALL PIPING ON ROOF TO BE PAINTED YELLOW BY MECHANICAL DIVISION. 5. SCHEDULE 40 STEEL PIPE 11. ROOF 2. 3. 4. 1. W:200mm/ L:300mm/ H:50mm ( 8"/12"/2") LONG PRESSURE TREATED WOOD W:100mm/ L:300mm/ H:100mm (4"/12"/4") LONG PRESSURE TREATED WOOD ROOFMATE INSULATION PLACED ON FINISHED ROOF NAIL TOGETHER WITH GALVANIZED NAILS W:450mm/ L:450mm/ H:50mm (18"/18"/2") (ALL COMPONENTS BY MECHANICAL TRADES) CARBON STEEL STRAPS - GRINNELL FIG. 262 OR EQUAL - OVERSIZE (1 SIZE LARGER) TO ALLOW FOR PIPE MOVEMENT - PAINT STRAPS WITH ANTI-CORROSIVE PAINT. PIPE SUPPORTS TO BE 2450mm (8'-2") APART FOR 25mm (1") PIPE & 3000mm (10'-0") APART FOR 32mm (1 1/4") PIPE & OVER. THERE MUST BE A SUPPORT AT EVERY 90° HORIZONTAL/VERTICAL ELBOW AND TEE FITTINGS. WHERE GAS PIPING IS ADJACENT TO A VERTICAL WALL, PROVIDE SUPPORTS 750mm (30") APART. PIPE DISTANCE FROM WALL IS TWO (2) TIMES THE HEIGHT OF THE WALL. (IE 4 METRE HIGH WALL PIPE INSTALLED 8 METRES FROM WALL) ALL VERTICAL PIPING UP SIDE OF WALLS OR ROOF ELEVATION CHANGES PAINTED TO MATCH WALL FINISH AND BANDED (IDENTIFIED GAS) AT TOP AND BOTTOM BY MECHANICAL CONTRACTOR. IN LIEU OF ITEMS 3&4 PROVIDE MANUFACTURED, SINGLE PIECE VOLCANIZED RUBBER GAS SUPPORT 100mmx150mmx225mm (4"x6"x9" LONG) COMPLETE WITH STAINLESS STEEL STRUTS. SUPPORTS SHALL WEIGH NO LESS THAN 9LBS. NOTE: 12. GAS PIPING SHALL NOT BE INSTALLED CLOSER THAN 6'-0" TO EDGE OF ROOF. W:450mm/ L:450mm/ H:50mm (18"/18"/2") PATIO STONES BY ADHESIVE TO INSULATION. PROVIDE EXCESS CONSTRUCTION ADHESIVE DURING FASTENING SUCH THAT ADHESIVE RUNS DOWN SIDE OF STONES FOR VISIBLE INSPECTION. SEQUENCE A6 DI HEATING COOLING S/S/S A1 AI SF D4 DI AI A3 D1 NC A0 C6 OUTSIDE AIR SUPPLY AIR S/S/S C6 NC D3 A0 EF EXHAUST AIR EXHAUST AIR AI A1 DI F1 FIRE SIGNAL OAT AI TEMP DI * D8 ON RESTORATION OF NORMAL CONDITION, SHUT DOWN SYSTEM. * * FILTER THE SYSTEM OPERATES ON A TIME OF DAY SCHEDULE. WHEN SYSTEM IS OFF ALL DAMPERS ARE IN NORMAL POSITION. ON START SIGNAL, START EF, THEN START SF. OPEN D1 AND D3 TO MINIMUM POSITION. CONTROL SAT BY MODULATION OF HEATING AND COOLING SECTIONS IN SEQUENCE MAINTAIN SAT AS HIGH AS POSSIBLE (COOLING MODE) OR AS LOW AS POSSIBLE (HEATING MODE) TO SATISFY SPACE. RESET SAT FROM EAT. RESET SAT UPWARD IN RESPONSE TO DROP IN EAT (COOLING MODE) OR DOWNWARD IN RESPONSE TO RISE IN EAT (HEATING MODE). WHEN FREE COOLING POTENTIAL EXISTS, MODULATE D1 AND D3 TO MAINTAIN MAT. ENSURE THAT SIMULTANEOUS HEATING AND COOLING DOES NOT OCCUR. ON SENSING HIGH OR LOW LIMIT TEMPERATURES, SHUT DOWN SYSTEM. ON FIRE SIGNAL, SHUT DOWN SYSTEM. DIVISION 16 ON COMMAND CACF SHALL OPEN D3, ONCE PROVEN OPEN START EF. FOR 100% EXHAUST. * WIRE TO CACF BY DIV.16. 9 TM-01 CONSTANT VOLUME SYSTEM NTS HEAT RECOVERY WHEEL 10 TM-01 FUME HOOD NTS CANOPY TO BE SUSPENDED FROM STEEL STRUCTURE EXHAUST CANOPY DIMENSIONS 4'-0" LONG x 2'-0" WIDE CANOPY CONSTRUCTION TO MATCH EXISTING CANOPY TO TAPER TOWARDS WALL SUCH THAT EXHAUST DUCT CAN RUN VERTICALLY ALONG WALL EXHAUST CANOPY TO BE MOUNTED 4'-0" ABOVE FINISHED FLOOR DUCT EXTERNAL INSULATION & FINISHING AS PER SPEC C/W WATER PROOFING CONTINUOUS SEAL WITH SUITABLE MASTIC OR FOIL BACKED TAPE. CONTINUOUS ANGLE SUPPORT. SUPPORT ANGLE PINNED TO THE DUCT ALL AROUND. EXTEND METAL FLASHING 100mm (4") BELOW TOP OF CURB. ROOF INSULATED ROOF CURB SECURE FLASHING TO DUCT AND SEAL WATERTIGHT. SEAL TO COUNTER FLASHING. ROOF MEMBRANE GRAVEL INSULATION ROOF STRUCTURE TO/FROM AIR HANDLER. PROVIDE INSULATION ON INTERIOR DUCTWORK FOR SUPPLY SYSTEMS. AS PER SPEC. 13 TM-01 SUPPLY OR RETURN DUCT THROUGH ROOF NTS NOTE: CURB AND FLASHING BY MECHANICAL DIVISION CEILING TO CEILING TRANSFER AIR DUCT TOP OPENINGS NTS 12 TM-01 NOTE: DUCT SIZES SHOWN ON PLAN ARE CLEAR INSIDE DIMENSIONS. INCREASE DUCT SIZES ACCORDINGLY TO ALLOW FOR LINING THICKNESS METAL STRAP HANGERS ALTERNATE OPENINGS AT SIDE OF DUCT SEAL AROUND WALL PENETRATION TOP OPENINGS TO MATCH DUCT SIZE TWO OPENINGS PER DUCT MAXIMIZE CLEARANCE MINIMUM 1500 (60") LONG ACOUSTICALLY LINED DUCT PARTITION NOTE: REFER TO PLAN FOR DUCT SIZES 50mm (2") CLEARANCE THIMBLE INSTALL GAS FIRED INFRA-RED HEATER ACCORDING TO MANUFACTURER'S INSTRUCTION AND RECOMMENDATIONS AND TO ALL APPLICABLE CODES AND LOCAL BY-LAWS. SINGLE-WALL GALVANIZED FLUE PIPE OR DURA/CONNECT SINGLE WALL, FLEXIBLE CONNECTORS MUST BE USED. THE PORTION OF THE FLUE PIPE WHICH GOES THROUGH COMBUSTIBLE MATERIAL IN THE BUILDING WALL OR ROOF MUST PASS THROUGH A TYPE "B" VENT TO MAINTAIN CLEARANCE. THE VENTING SYSTEM SHALL TERMINATE AT LEAST 900mm (36") ABOVE ANY OTHER BUILDING OPENING OR ANY GAS REGULATOR. THE VENTING SYSTEM SHALL TERMINATE AT LEAST 1.8m (6') FROM A COMBUSTION AIR INLET OR ANOTHER APPLIANCE AND NOT ABOVE A GAS UTILITY METER OR SERVICE REGULATOR. UNINSULATED SINGLE-WALL VENT PIPE SHALL NOT BE USED. GAS-FIRED INFRA-RED HEATER (REFER TO SCHEDULE FOR SELECTION) NOTES: 03. 05. 04. 01. 02. ROOF FLASHING COMBUSTIBLE MATERIAL APPROVED VENT CAP VENTING THROUGH ROOF VENTING THROUGH SIDEWALL THE VENT TERMINAL OF A HORIZONTAL VENTING SYSTEM MUST BE INSTALLED TO PREVENT BLOCKAGE BY SNOW AND PROTECT BUILDING MATERIALS FROM DEGRADATION BY FLUE GASES. HORIZONTAL VENTING MUST MAINTAIN A MINIMUM 150mm (6") FROM THE VENT TERMINATION TO THE SIDEWALL. BUILDING INCORPORATING VENTED SOFFITS/OVERHANGS MUST ENSURE THAT THE PRODUCTS-OF-COMBUSTION DO NOT ENTER THE ATTIC SPACE. 08. 09. 07. AIR INTAKE AIR INTAKE CAP W/ BIRD SCREEN ROOF 600mm (24") 150 mm (6") MIN. APPROVED VENT CAP TYPE "B" VENT BUILDING OVERHANG 900mm (36") THIMBLE TYPE "B" VENT WALL ALTERNATE AIR INTAKE THROUGH ROOF CHAIN 900mm (36") INSULATE INTAKE PIPE AND FINISH WITH ALUMINUM JACKET. 11 TM-01 INFRA-RED GAS HEATER NTS 900mm (36") ROOF TOP UNIT INSTALLATION (RTU-145-01) NTS 14 TM-0.1 BOTTOM OF JOISTS ROOF DECK ACCOUSTICALLY LINED SUPPLY & RETURN DUCTWORK TERMINATE 300mm (12") BELOW ROOF DECK FACTORY INSTALLED WEATHERPROOF DISCONNECT SWITCH. ECONOMIZER INTAKE PROVIDE FLEXIBLE CONNECTION AT R/A & S/A OPENING IN BOTTOM OF AC UNIT AND SUPPORT DUCTWORK FROM STRUCTURE. PROGRAMMABLE HEATING/COOLING THERMOSTAT AND 30m (100') OF PLENUM RATED CONTROL WIRING COILED AND TEMPORARILY ATTACHED TO ROOF STRUCTURE. TYPICAL FOR CRU'S, FOR MALL RTU'S REFER TO FLOOR PLANS. ROOF TOP MANUFACTURER SUPPLIED INSULATED PRE-FABRICATED ROOF CURB BY MECHANICAL DIVISION. T ROOF SYSTEM LUBRICATED GAS SHUT OFF VALVE SCHEDULE 40 GAS PIPING SUPPORTED ON ROOF AS PER DETAIL. POWER WIRING FROM DISCONNECT TO POWER SOURCE BY ELECTRICAL DIVISION, REFER TO ELECTRICAL DRAWINGS. MECHANICAL DIVISION TO PROVIDE NON COMBUSTABLE BLOCKING ALL AROUND UNDER CURB. PROVIDE A TRAP FROM THE COOLING COIL DRAIN THAT HAS A DEPTH OF 25mm (1") GREATER THAN THE TOTAL FAN STATIC PRESSURE. PROVIDE GASKET ROOF TOP AC UNIT TM-0.1 MECHANICAL LEGEND, DETAILS & DRAWING LIST 16-1121-000 THE MITCHELL PARTNERSHIP INC. CONSULTING ENGINEERS 285 YORKLAND BLVD, TORONTO, ONTARIO I M2J 1S5 416.499.8000 SHEET NUMBER TITLE Approved Checked Drawn Job Number ISSUE CHART 1 5 2 3 4 A D B C KEYPLAN PROJECT 1 5 2 3 4 A D B C UTIAS RESEARCH LABS P049-16-138 672 Dupont Street, Suite 500 Toronto, Ontario Canada M6G 1Z6 t 416.971.6060 f 416.971.6765 www.perkinswill.com MARK ISSUE DATE 1 ISSUED FOR SD COSTING 2017-01-11 2 ISSUED FOR CD COSTING 2017-03-13 3 ISSUED FOR PERMIT 2017-04-21 4 ISSUED FOR TENDER 2017-05-01

CO...PROGRAMMABLE HEATING/COOLING THERMOSTAT AND 30m (100') OF PLENUM RATED CONTROL WIRING COILED AND TEMPORARILY ATTACHED TO ROOF STRUCTURE. TYPICAL FOR CRU'S, FOR MALL RTU'S

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CO...PROGRAMMABLE HEATING/COOLING THERMOSTAT AND 30m (100') OF PLENUM RATED CONTROL WIRING COILED AND TEMPORARILY ATTACHED TO ROOF STRUCTURE. TYPICAL FOR CRU'S, FOR MALL RTU'S

AD

AP

CTE

DTF

STW

STB

AUTOMATIC CONTROL VALVE

PIPE UP

PIPE DOWN

CAPPED PIPE

DIRECTION OF FLOW

PIPE SLEEVE

CONTINUOUS PIPE

METER

UNION

STRAINER

BACKFLOW PREVENTER

WATER FEEDER ASSEMBLY

FLEXIBLE PIPE CONNECTION

PUMP

PRESSURE GAUGE WITH COCK

THERMOMETER

STARTER

FAN SPEED CONTROLLER

SLEEVE THROUGH BEAM

SLEEVE THROUGH WALL

DOWN THROUGH FLOOR

CONNECT TO EXISTING

ACCESS PANEL

ACCESS DOOR

BACKWATER VALVE WITH ACCESS

BACKWATER VALVE INLINE

VALVE IN RISER

MOTORIZED BUTTERFLY VALVE

3 WAY BUTTERFLY CONTROL VALVE

AUTOMATIC CONTROL VALVE

SAFETY RELIEF VALVE

PRESSURE DIFFERENTIAL VALVE

NEEDLE VALVE

BALANCING VALVE (PLUG)

CIRCUIT BALANCING VALVE

SOLENOID VALVE

FLOW METER, VENTURI

FLOW SWITCH

PRESSURE REDUCING VALVE

PLUG VALVE

LOCKSHIELD VALVE

BUTTERFLY VALVE

SHUT-OFF VALVE AND ACCESS PANEL

GATE VALVE AND FLOW SWITCH

VALVED AND CAPPED PROVISION

HOSE-END DRAIN VALVE

FLOAT VALVE

CHECK VALVE

BALL VALVE

LOCKABLE FLOW CONTROL VALVE

GLOBE VALVE

GATE VALVE

M

ETC ELECTRIC TRACING CABLE

3

TM-01

LEGEND - GENERALNTS

BFP

WFA

PUMPED DRAIN UNDER FLOORPD

PUMPED DRAINPD

SUPERVISED VALVE

FIRE DEPARTMENT VALVE

SPRINKLER STANDPIPE

FIRE STANDPIPE

SV

FDV

SPR

FSP

FIRE EXTINGUISHER WITH CABINET

FIRE EXTINGUISHER

FIRE HOSE RACK

FIRE HOSE CABINET

SIAMESE PUMPER CONNECTION

FG

CMD CARBON MONOXIDE DETECTOR

FIRE GONG

SIDEWALL SPRINKLER HEAD

CONCEALED SPRINKLER HEAD

UPRIGHT SPRINKLER HEAD

PENDENT SPRINKLER HEAD

CHECK VALVE WITH BALLDRIP

PREACTION ALARM CHECK VALVE

DRY ALARM CHECK VALVE

WET ALARM CHECK VALVE

SPRINKLER MAIN (GLYCOL)

SPRINKLER MAIN (DRY)

SPRINKLER LINE (WET)

FIRE LINE

RWL

VTR

VS

WS

SS

RAINWATER LEADER

VENT THROUGH ROOF

VENT STACK

WASTE STACK

SOIL STACK

MANHOLE

CATCHBASIN

CD

A

G

SCUPPER DRAIN

FLOOR DRAIN OR ROOF DRAIN

HOSE BIBB/WALL HYDRANT

T

CONDENSATE DRAIN

COMPRESSED AIR

GAS PIPE

DOMESTIC TEMPERED WATER

DOMESTIC HOT WATER RECIRC

DOMESTIC HOT WATER

DOMESTIC COLD WATER

RUNNING TRAP WITH CLEANOUT

RUNNING TRAP WITH CLEANOUT

DRAIN WITH CLEANOUT UP TO FLOOR

DRAIN WITH CLEANOUT UP TO FLOOR

DRAIN WITH CLEANOUT

VENT PIPEV

BURIED STORM DRAINST

STORM DRAINST

BURIED SANITARY DRAINSAN

SANITARY DRAINSAN

HB

MH

CB

WH

F

SP

DSP

GSP

FHC

FHC

FE

FE

CO

CO

GREASE TRAPGT

LS

FLOOR DRAIN (PARKING)

SHOWER HEAD

LIQUID SOAP

2

TM-01

LEGEND - PLUMBING, DRAINAGE AND FIRE PROTECTIONNTS

SINGLE LINE RIGID DUCT

SINGLE LINE DUCT WITH ACOUSTIC LINING

SINGLE LINE FLEXIBLE DUCT

DOUBLE LINE FLEXIBLE DUCT

SUPPLY AIR DIFFUSER

RETURN AIR GRILLE

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

MANUAL BALANCING DAMPERMOTORIZED COMBINATION

THERMOSTAT

HUMIDISTAT

DOOR UNDERCUT

DOOR GRILLE

BD

MD

SD

FS

FD

T

HCAPSIZETYPE

PIPE ANCHOR

DOUBLE LINE DUCT

DUCT WITH ACOUSTIC LINING

SOUND BAFFLE

PIPE GUIDE

EXPANSION JOINT

REFRIGERANT SUCTION

REFRIGERANT DISCHARGE

REFRIGERANT LIQUID

CONDENSATE RETURN

STEAM MAIN (PRESSURE AS INDICATED)

HEATED WATER RETURN

HEATED WATER SUPPLYHWS

HWR

S

C

RL

RD

RS

ROUND DUCT DOWN

ROUND DUCT UP

RETURN DUCT DOWN

SUPPLY DUCT DOWN

RETURN OR EXHAUST DUCT

SUPPLY OR OUTSIDE AIR DUCT

SOUND ATTENUATOR

HEATING TERMINAL

SUPPLY AIR CFMGRILLE OR REGISTER SIZE/TYPE

30012/12 D

12/12 E300

GRILLE OR REGISTER SIZE/TYPEEXHAUST OR RETURN AIR CFM

EXHAUST OR RETURN AIR CFMGRILLE OR REGISTER SIZE/TYPE

30012/12 E

12/12 D300

GRILLE OR REGISTER SIZE/TYPESUPPLY AIR CFM

SUPPLY AIR CFMDIFF NECK SIZE/DIFF TYPE

2006"Ø A

FIRE AND SMOKE DAMPER

UC

DG

GLYCOL RETURN

GLYCOL SUPPLY

FUEL OIL RETURN

FUEL OIL SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

CHILLED WATER RETURN

CHILLED WATER SUPPLY

RADIATION WATER RETURN

RADIATION WATER SUPPLYRWS

RWR

CHWS

CHWR

CWS

CWR

FOS

FOR

GS

GR

1

TM-01

LEGEND HVACNTS

LOW & MEDIUM DUCT TAKE-OFFSNTS

4

TM-01

NOTE:DEPTH OF DUCT SHALL BE MINIMUM50mm (2") LARGER THAN TAKE-OFFCONNECTION

MEDIUM OR LOWPRESSURE DUCT

HANDLE SPIN ON COLLAR

DAMPER BLADE

WING NUT

RIGID DUCT

ROOF TOP UNIT INSTALLATION (RTU-145-01)NTS

5

TM-01

BOTTOM OF JOISTS

ROOF DECK

ACCOUSTICALLY LINED SUPPLY &RETURN DUCTWORK TERMINATE300mm (12") BELOW ROOF DECK

FACTORY INSTALLED WEATHERPROOFDISCONNECT SWITCH.

ECONOMIZER INTAKE

PROGRAMMABLE HEATING/COOLINGTHERMOSTAT AND 30m (100') OFPLENUM RATED CONTROL WIRINGCOILED AND TEMPORARILYATTACHED TO ROOF STRUCTURE.TYPICAL FOR CRU'S, FOR MALL RTU'SREFER TO FLOOR PLANS.

ROOF TOP MANUFACTURERSUPPLIED INSULATEDPRE-FABRICATED ROOF CURB BYMECHANICAL DIVISION.

T

ROOF SYSTEM

LUBRICATEDGAS SHUTOFF VALVE

SCHEDULE 40 GAS PIPINGSUPPORTED ON ROOF AS PERDETAIL.

POWER WIRING FROM DISCONNECT TOPOWER SOURCE BY ELECTRICALDIVISION, REFER TO ELECTRICALDRAWINGS.

PROVIDE A TRAP FROM THECOOLING COIL DRAIN THAT HAS ADEPTH OF 25mm (1") GREATERTHAN THE TOTAL FAN STATICPRESSURE.

PROVIDE GASKET ROOF TOPAC UNIT

6

TM-01

CLEAN-OUT DETAILSNTS

ALTERNATE LOCATION FOR CLEANOUTAND ACCESS

ACCESS DOOR. SEE SPECIFICATIONS.

IRON FERRULE WITH RAISEDHEAD BRASS PLUG

ACCESS COVER TO SUIT FLOORFINISH MATERIAL. SEESPECIFICATIONS.IRON FERRULE WITH RAISED HEAD BRASSPLUG

IRON FERRULE WITHRAISED HEAD BRASSPLUG

BARRET TYPE,BOLTED COVER,BRASS CAPSCREWS.

ACCESS DOOR. SEESPECIFICATION.

CLEANOUT TEE

SPRINKLER LINE

150m

m (6

")

25mm (1")

25mm (1") PLUG FORFUTURE SPRINKLER

25/25/25mm (1"x1"x1")SCREWED TEE

FINISHED CEILING

SPRINKLER LINE

150m

m (6

")

150 (6")

FIEL

D ME

ASUR

E

25mm

(1")

25mm (1") (1")

25mm

25/25/25mm (1"x1"x1")SCREWED TEE

25mm (1") PLUG FOR FUTURESPRINKLER

FINISHED CEILING

SPRINKLER LINE

150 (6")

FIEL

D ME

ASUR

E

25mm

(1")

25mm(1")

150m

m (6

")

25mm (1")

25/25/25mm (1"x1"x1")SCREWED TEE

25mm (1") PLUG FORFUTURE SPRINKLER

7

TM-01

TYPICAL SPRINKLER HEAD INSTALLATIONNTS

8

TM-01

SUPPORTS FOR GAS PIPING ON ROOFNTS

FRONT ELEVATION

SIDE ELEVATION

ROOF

NOTES:

6.

7. 8. 9. 10.

CADMIUM PLATED No. 12 - 50mm (2") LONG SCREWSSHIM WOOD BLOCKING AS REQUIRED TO COMPENSATE FOR ROOF SLOPEALL PIPING ON ROOF TO BE PAINTED YELLOW BY MECHANICAL DIVISION.

5. SCHEDULE 40 STEEL PIPE

11.

ROOF

2.

3. 4.

1.

W:200mm/ L:300mm/ H:50mm ( 8"/12"/2") LONG PRESSURE TREATED WOODW:100mm/ L:300mm/ H:100mm (4"/12"/4") LONG PRESSURE TREATED WOOD

ROOFMATE INSULATION PLACED ON FINISHED ROOF

NAIL TOGETHER WITHGALVANIZED NAILS

W:450mm/ L:450mm/ H:50mm (18"/18"/2")

(ALL COMPONENTS BY MECHANICAL TRADES)

CARBON STEEL STRAPS - GRINNELL FIG. 262 OR EQUAL - OVERSIZE (1 SIZE LARGER) TO ALLOW FOR PIPE MOVEMENT - PAINTSTRAPS WITH ANTI-CORROSIVE PAINT. PIPE SUPPORTS TO BE 2450mm (8'-2") APART FOR 25mm (1") PIPE & 3000mm (10'-0") APARTFOR 32mm (1 1/4") PIPE & OVER. THERE MUST BE A SUPPORT AT EVERY 90° HORIZONTAL/VERTICAL ELBOW AND TEE FITTINGS.

WHERE GAS PIPING IS ADJACENT TO A VERTICAL WALL, PROVIDE SUPPORTS 750mm (30") APART. PIPE DISTANCE FROMWALL IS TWO (2) TIMES THE HEIGHT OF THE WALL. (IE 4 METRE HIGH WALL PIPE INSTALLED 8 METRES FROM WALL)

ALL VERTICAL PIPING UP SIDE OF WALLS OR ROOF ELEVATION CHANGES PAINTED TO MATCH WALL FINISH ANDBANDED (IDENTIFIED GAS) AT TOP AND BOTTOM BY MECHANICAL CONTRACTOR.

IN LIEU OF ITEMS 3&4 PROVIDE MANUFACTURED, SINGLE PIECE VOLCANIZED RUBBER GAS SUPPORT 100mmx150mmx225mm(4"x6"x9" LONG) COMPLETE WITH STAINLESS STEEL STRUTS. SUPPORTS SHALL WEIGH NO LESS THAN 9LBS.

NOTE:

12. GAS PIPING SHALL NOT BE INSTALLED CLOSER THAN 6'-0" TO EDGE OF ROOF.

W:450mm/ L:450mm/ H:50mm (18"/18"/2") PATIO STONES BY ADHESIVE TO INSULATION. PROVIDE EXCESS CONSTRUCTIONADHESIVE DURING FASTENING SUCH THAT ADHESIVE RUNS DOWN SIDE OF STONES FOR VISIBLE INSPECTION.

SEQUENCE

A6DI

HEAT

ING

COOL

ING

S/S/S A1AI

SF

D4DI

AI A3

D1

NC

A0 C6

OUTSIDE

AIRSUPPLY AIR

S/S/SC6

NC

D3

A0

EFEXHAUST AIR

EXHAUST AIR

AI A1

DI F1 FIRE SIGNAL

OATAI TEMP

DI *D8

ON RESTORATION OF NORMAL CONDITION, SHUT DOWN SYSTEM.

*

*

FILT

ER

THE SYSTEM OPERATES ON A TIME OF DAY SCHEDULE. WHEN SYSTEM IS OFF ALL DAMPERS ARE IN NORMAL POSITION. ONSTART SIGNAL, START EF, THEN START SF. OPEN D1 AND D3 TO MINIMUM POSITION. CONTROL SAT BY MODULATION OF HEATINGAND COOLING SECTIONS IN SEQUENCE MAINTAIN SAT AS HIGH AS POSSIBLE (COOLING MODE) OR AS LOW AS POSSIBLE (HEATINGMODE) TO SATISFY SPACE. RESET SAT FROM EAT. RESET SAT UPWARD IN RESPONSE TO DROP IN EAT (COOLING MODE) ORDOWNWARD IN RESPONSE TO RISE IN EAT (HEATING MODE). WHEN FREE COOLING POTENTIAL EXISTS, MODULATE D1 AND D3 TOMAINTAIN MAT. ENSURE THAT SIMULTANEOUS HEATING AND COOLING DOES NOT OCCUR.

ON SENSING HIGH OR LOW LIMIT TEMPERATURES, SHUT DOWN SYSTEM. ON FIRE SIGNAL, SHUT DOWN SYSTEM.

DIVISION 16 ON COMMAND CACF SHALL OPEN D3, ONCE PROVEN OPEN START EF. FOR 100% EXHAUST.

* WIRE TO CACF BY DIV.16.

9

TM-01

CONSTANT VOLUME SYSTEM NTS

HEAT

REC

OVER

Y W

HEEL

10

TM-01

FUME HOOD NTS

CANOPY TO BESUSPENDED FROMSTEEL STRUCTURE

EXHAUST CANOPY DIMENSIONS4'-0" LONG x 2'-0" WIDE

CANOPY CONSTRUCTIONTO MATCH EXISTING

CANOPY TO TAPER TOWARDSWALL SUCH THAT EXHAUST DUCTCAN RUN VERTICALLY ALONG WALL

EXHAUST CANOPY TO BEMOUNTED 4'-0" ABOVEFINISHED FLOOR

DUCT

EXTERNAL INSULATION &FINISHING AS PER SPECC/W WATER PROOFING

CONTINUOUS SEAL WITHSUITABLE MASTIC OR FOILBACKED TAPE.

CONTINUOUS ANGLE SUPPORT.SUPPORT ANGLE PINNED TOTHE DUCT ALL AROUND.

EXTEND METAL FLASHING100mm (4") BELOW TOP OFCURB.

ROOF

INSULATED ROOF CURB

SECURE FLASHING TO DUCTAND SEAL WATERTIGHT.

SEAL TO COUNTER FLASHING.

ROOF MEMBRANE

GRAVEL

INSULATION

ROOF STRUCTURE

TO/FROM AIR HANDLER.

PROVIDE INSULATION ONINTERIOR DUCTWORK FORSUPPLY SYSTEMS. AS PERSPEC.

13

TM-01

SUPPLY OR RETURN DUCT THROUGH ROOFNTS

NOTE:CURB AND FLASHING BYMECHANICAL DIVISION

CEILING TO CEILING TRANSFER AIR DUCT TOP OPENINGSNTS

12

TM-01

NOTE:DUCT SIZES SHOWN ON PLAN ARECLEAR INSIDE DIMENSIONS.INCREASE DUCT SIZESACCORDINGLY TO ALLOW FORLINING THICKNESS

METAL STRAPHANGERS

ALTERNATE OPENINGSAT SIDE OF DUCT

SEAL AROUND WALL PENETRATION

TOP OPENINGS TO MATCHDUCT SIZE TWO OPENINGSPER DUCT

MAXIMIZECLEARANCE

MINIMUM 1500 (60")LONG ACOUSTICALLYLINED DUCT

PARTITION

NOTE:REFER TO PLAN FORDUCT SIZES

50mm (2")CLEARANCETHIMBLE

INSTALL GAS FIRED INFRA-RED HEATER ACCORDING TOMANUFACTURER'S INSTRUCTION AND RECOMMENDATIONS AND TOALL APPLICABLE CODES AND LOCAL BY-LAWS.SINGLE-WALL GALVANIZED FLUE PIPE OR DURA/CONNECT SINGLEWALL, FLEXIBLE CONNECTORS MUST BE USED. THE PORTION OF THEFLUE PIPE WHICH GOES THROUGH COMBUSTIBLE MATERIAL IN THEBUILDING WALL OR ROOF MUST PASS THROUGH A TYPE "B" VENT TOMAINTAINCLEARANCE.

THE VENTING SYSTEM SHALL TERMINATE AT LEAST 900mm (36")ABOVE ANY OTHER BUILDING OPENING OR ANY GAS REGULATOR.

THE VENTING SYSTEM SHALL TERMINATE AT LEAST 1.8m (6') FROM ACOMBUSTION AIR INLET OR ANOTHER APPLIANCE AND NOT ABOVE AGAS UTILITY METER OR SERVICE REGULATOR.

UNINSULATED SINGLE-WALL VENT PIPE SHALL NOT BE USED.

GAS-FIRED INFRA-REDHEATER (REFER TOSCHEDULE FOR SELECTION)

NOTES:

03.

05.

04.

01.

02.

ROOFFLASHINGCOMBUSTIBLEMATERIAL

APPROVEDVENT CAP

VENTINGTHROUGHROOF

VENTINGTHROUGHSIDEWALL

THE VENT TERMINAL OF A HORIZONTAL VENTING SYSTEM MUST BEINSTALLED TO PREVENT BLOCKAGE BY SNOW AND PROTECTBUILDING MATERIALS FROM DEGRADATION BY FLUE GASES.

HORIZONTAL VENTING MUST MAINTAIN A MINIMUM 150mm (6") FROMTHE VENT TERMINATION TO THE SIDEWALL.BUILDING INCORPORATING VENTED SOFFITS/OVERHANGS MUSTENSURE THAT THE PRODUCTS-OF-COMBUSTION DO NOT ENTER THEATTIC SPACE.

08.

09.

07.

AIR INTAKE

AIR INTAKE CAP W/ BIRD SCREEN

ROOF

600mm (24")

150mm(6")MIN.

APPROVEDVENTCAP

TYPE "B" VENT

BUILDING OVERHANG

900mm (36")

THIMBLE

TYPE "B"VENT

WALL

ALTERNATE AIR INTAKETHROUGH ROOF

CHAIN

900mm (36")

INSULATE INTAKE PIPEAND FINISH WITHALUMINUM JACKET.

11

TM-01

INFRA-RED GAS HEATERNTS

900mm (36")

ROOF TOP UNIT INSTALLATION (RTU-145-01)NTS

14

TM-0.1

BOTTOM OF JOISTS

ROOF DECK

ACCOUSTICALLY LINED SUPPLY &RETURN DUCTWORK TERMINATE300mm (12") BELOW ROOF DECK

FACTORY INSTALLED WEATHERPROOFDISCONNECT SWITCH.

ECONOMIZER INTAKE

PROVIDE FLEXIBLE CONNECTIONAT R/A & S/A OPENING IN BOTTOMOF AC UNIT AND SUPPORTDUCTWORK FROM STRUCTURE.

PROGRAMMABLE HEATING/COOLINGTHERMOSTAT AND 30m (100') OFPLENUM RATED CONTROL WIRINGCOILED AND TEMPORARILYATTACHED TO ROOF STRUCTURE.TYPICAL FOR CRU'S, FOR MALL RTU'SREFER TO FLOOR PLANS.

ROOF TOP MANUFACTURERSUPPLIED INSULATEDPRE-FABRICATED ROOF CURB BYMECHANICAL DIVISION.

T

ROOF SYSTEM

LUBRICATEDGAS SHUTOFF VALVE

SCHEDULE 40 GAS PIPINGSUPPORTED ON ROOF AS PERDETAIL.

POWER WIRING FROM DISCONNECT TOPOWER SOURCE BY ELECTRICALDIVISION, REFER TO ELECTRICALDRAWINGS.

MECHANICAL DIVISION TO PROVIDENON COMBUSTABLE BLOCKING ALLAROUND UNDER CURB.

PROVIDE A TRAP FROM THECOOLING COIL DRAIN THAT HAS ADEPTH OF 25mm (1") GREATERTHAN THE TOTAL FAN STATICPRESSURE.

PROVIDE GASKET ROOF TOPAC UNIT

TM-0.1

MECHANICALLEGEND, DETAILS

& DRAWING LIST

16-1121-000

THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS

285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000

SHEET NUMBER

TITLEApproved

Checked

Drawn

Job Number

ISSUE CHART

15 234

A

D

B

C

KEYPLAN

PROJECT

15 234

A

D

B

C

UTIAS RESEARCH LABSP049-16-138

672 Dupont Street, Suite 500Toronto, Ontario

Canada M6G 1Z6t 416.971.6060f 416.971.6765

www.perkinswill.com

MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01

Page 2: CO...PROGRAMMABLE HEATING/COOLING THERMOSTAT AND 30m (100') OF PLENUM RATED CONTROL WIRING COILED AND TEMPORARILY ATTACHED TO ROOF STRUCTURE. TYPICAL FOR CRU'S, FOR MALL RTU'S

AIR TERMINAL SCHEDULE

TAG DESCRIPTION MANUFACTURER MODEL MATERIAL FINISH MOUNTING COMMENTS

A ROUND CONE DIFFUSERS EH PRICE RCDA/B12 ALUMINIUM WHITE DUCT MOUNTED NECK SIZE AS NOTED ON PLAN

B DRUM LOUVRES EH PRICE HCD1/F/A/B12 ALUMINIUM WHITE DUCT MOUNTED SIZE AS NOTED ON PLAN

C WALL MOUNT RETURN AND TRANSFER AIR EH PRICE 535/TB/S/D/A/B12 STEEL WHITE WALL BACK TO BACK WALL MOUNTED ARRANGEMENT SIZE AS NOTED ON PLANS

D DUCT MOUNT RETURN EH PRICE 535/F/L/D/A/B12 STEEL WHITE DUCT SIZE AS NOTED ON PLANS

E LASER CUTTER EXHAUST EH PRICE PDDR/1/B12 STEEL WHITE DUCT DIFFUSER AND NECK SIZE AS NOTED ON PLAN. UNIT TO BE HUNG FROM JOISTS WITH CHAINS

NOTES: 1. NECK SIZE NOTED ON PLANS.

GAS-FIRED UNIT HEATER SCHEDULE

TAG MANFACTURER MODEL GAS HEATING ELECTRICAL EMERGENCY WEIGHT COMMENTS

INPUT OUTPUT POWER(MBH) (kW) (MBH) (kW) (V/Ph/Hz) (Y/N) (LBS) (Kg)

IH-1 SCHWANK STS-JZ-80-20 80.0 23.4 40.0 11.7 120/1/60 N 150 68

NOTES: 1. PROVIDE ALL HANGERS AND SUPPORTS REQUIRED.

2. PROVIDE FLEXIBLE GAS CONNECTION TO UNIT.

PUMP SCHEDULE

TAG SERVICE LOCATION MANUFACTURER TYPE/SERIES MODEL FLUID TYPE RPM CAPACITY HEAD MOTOR SIZE VFD BY-PASS VARIABLE SPEED ELECTRICAL EMERGENCY PRESSURE OPERATION COMMENTSBRAKE POWER POWER ON VFD APPLICATION POWER RATING

(USGPM) (L/s) (ft.H2O) (kPa) (HP) (kW) (HP) (kW) (Y/N) (Y/N) (Y/N) (V/Ph/Hz) (Y/N) (PSI) (kPa)

PD-01 ROOM 145 SUMP ROOM 145 - SUMP PIT HYDROMATIC CAST IRON SUMP W-A1 SANITARY WATER 1,550 9.0 0.6 20.0 59.7 0.3 0.2 0.3 0.2 N N/A N 115/1/60 N 150.0 1,034.2 LEAD/LAG PUMP CONTROLLER TO BE BACNET COMPATIBLE

PD-02 ROOM 145 SUMP ROOM 145 - SUMP PIT HYDROMATIC CAST IRON SUMP W-A1 SANITARY WATER 1,550 9.0 0.6 20.0 59.7 0.3 0.2 0.3 0.2 N N/A N 115/1/60 N 150.0 1,034.2 LEAD/LAG PUMP CONTROLLER TO BE BACNET COMPATIBLE

PP-01 ROOM 145 CIRCULATOR ROOM 145 - BELOW SINK XYLEM ECOCIRC B 23-5 DOMESTIC HOT WATER - 0.5 0.0 20.0 59.7 0.1 0.1 0.1 0.1 N N/A N 115/1/60 N 145.0 999.7 RECIRCULATOR

PP-01 ROOM 145 CIRCULATOR ROOM 145 - BELOW SINK XYLEM ECOCIRC B 23-5 DOMESTIC HOT WATER - 0.5 0.0 20.0 59.7 0.1 0.1 0.1 0.1 N N/A N 115/1/60 N 145.0 999.7 RECIRCULATOR

NOTES: 1.

HEATING COIL SCHEDULE (ELECTRIC)

TAG SERVICE MANUFACTURER MODEL HEATING AIR PRESSURE EAT DB LAT DB ELECTRICAL EMERGENCY COMMENTSCAPACITY FLOW DROP POWER

(MBH) (kW) (CFM) (L/s) (in.H20) (Pa) (°F) (°C) (°F) (°C) (V/Ph/Hz) (Y/N)

EHC-1 ROOM 125 THERMOLEC SCD 22.1 6.5 900 425 0.2 49.8 55.0 12.8 77.0 25.0 600/3/60 N

NOTES: 1. ALL COILS TO BE SCR CONTROLLED.

2. PROVIDE AIR FLOW PROOFING SWITCH.

3. PROVIDE LOCAL DISCONNECT.

FRAME

9 (3/8") "Z" CHANEL

WELD

THICKNESS OF STEEELSTOP TO SUIT COVERPLATE USED

RECESSED HEXAGON HEAD BOLTS 158 (61/4") WITH GASKET BETWEEN MACHINEDSURFACES.GASKETED STEEL COVER PLATE AS PERMANUFACTURERS RECOMMENDATIONS &WITH A STRUCTURAL CAPACITY OF 4536kg(10,000 lbs).

32 (1 1/4") STEEL STOPWELDED TO FRAMEALL AROUND

TUBULAR NEOPRENEGASKET

3x25x150 (1/8"x1"x6")STEEL ANGULAR STRAPTWO PER SIDE75x75x9 (3"x3"x3/8")ANGLE FRAME

HEXAGON HEAD BRASS BOLTSWITH BRASS WASHERS

STEEL COVER PLATE WITH ASTRUCTURAL CAPACITY OF4536kg (10,000 lbs)

3x25x150 (1/8"x1"x6") STEELANGULAR STRAP

4

TM-02

SUMP PIT COVER PLATENTS

LADDER RUNGS

PUMPED DISCHARGE

GATE VALVEUNION

SANITARY PIT

DRAININLET

UNION

BASE SUPPORT

9mm (3/8") "Z" CHANNEL

1ST PUMP OUT

2ND PUMP OUT

HIGH LEVEL ALARM2ND PUMP ON1ST PUMP ON

OFFSET PIPING TOALLOW FOR PUMPREMOVAL

CHECK VALVE

PROVIDE AIR TIGHTSEAL AT PIPEPENETRATION.

VENT TO ATMOSPHERE

SUBMERSIBLE PUMPS MOUNTED ON GUIDE RAILSSUCH THAT THEY CAN INDEPENDANTLY BEREMOVED WITH THE REMAINING PUMP BEING INOPERATION.

PROVIDE REMOVABLE SECTION OFCOVER TO ALLOW PUMP REMOVAL.SEAL AIR TIGHT.

1 REFER TO PLANS FOR PIT SIZES,DRAIN SIZES, VENT SIZES, DRAININVERTS AND FLOOR ELEVATIONS.

2 PROVIDE EYEBOLTS IN SLABABOVE PIT FOR MOTOR REMOVAL.

3 PROVIDE GALVANIZED STEELLADDER RUNGS AT 300mm (12")CENTRES FOR PITS DEEPER THAN1050mm (42")

4 PROVIDE A GASKETED, HINGED,900/900 ACCESS HATCH LOCATEDTO ALLOW REMOVAL OF BOTHPUMPS.

100mm (4") min.LIFTCHAINANDHOOK

3x25x150 (1/8"x1"x6")STEEL ANGULARSTRAP TWO PERSIDE

STEEL COVER PLATE WITH ASTRUCTURAL CAPACITY OF10,000 LBS

TUBULAR NEOPRENE GASKET

RECESSED HEX HEAD BOLTS158mm (6-1/4") WITH GASKETBETWEEN MACHINEDSURFACES.

DESIGNER'S NOTE:

FILL IN ELEVATIONS FORPUMP START/STOP.

8

TM-02

SANITARY PIT WITH SUBMERSIBLE PUMPSNTS

3

TM-02

ELECTRIC HEATER CONTROLNTS

H

EXISTING INTERNAL SAFETIESTO INCLUDE HIGH-TEMP & AIRPROOFING.

POWER

AIRFLOW AIRFLOW

SEQUENCE

VARIABLE AIR VOLUME BOX SCHEDULE

TAG MANUFACTURER MODEL UNIT MAXIMUM MINIMUM INLET SIZE OUTLET SIZE ATTENUATORS SOUND POWER LEVEL IN dB RE 10^-12 W SOUND POWER LEVEL IN dB RE 10^-12 WSIZE AIR FLOW AIR FLOW LENGTH WIDTH DISCHARGE INLET LINER MAX DISCHARGE SOUND POWER MAX RADIATED SOUND POWER

(CFM) (L/S) (CFM) (L/S) (INCH) (mm) (INCH) (mm) (INCH) (mm) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

8 EH PRICE SDV 8 625 295 135 64 8.0 203.2 10.0 254.0 12.0 304.8 5 1.5 FG50 59 53 46 38 22 - 60 49 40 35 29 26

10 EH PRICE SDV 10 1,010 477 220 104 10.0 254.0 12.5 317.5 14.0 355.6 5 1.5 FG50 61 54 48 41 26 25 56 46 40 34 30 26

14 EH PRICE SDV 14 2,250 1,062 440 208 14.0 355.6 17.5 444.5 20.0 508.0 5 1.5 FG50 64 57 56 46 37 36 63 52 51 42 38 31

NOTES: 1. FOR ACTUAL FLOWS REFER TO DRAWINGS.2. MINIMUM AIR FLOWS ARE FOR SELECTION ONLY, SEE MINIMUM AIR FLOW SET POINT ON DRAWINGS.

3. HEATING COILS SHALL HAVE A RATING OF 125 PSI.

4. PROVIDE ALL VAV BOXES WITH BACNET COMPATIBLE CONTROLLER

DX/GAS-FIRED PACKAGED ROOF TOP UNIT SCHEDULE

TAG SERVICE MANUFACTURER MODEL SUPPLY FAN MINIMUM COOLING GAS HEATINGFILTERTYPE

ENERGY RECOVERY ELECTRICAL EMERGENCY DIMENSIONS OPERATING MOUNTING COMMENTSNUMBER FLOW E.S.P. BRAKE POWER POWER VFD OUTDOOR AIR REFRIGERANT TOTAL CAPACITY SENSIBLE CAPACITY EAT DB EAT WB LAT DB LAT WB MAX PRESSURE DROP # OF ECONOMIZER IEER EER INPUT OUTPUT STAGES TYPE V/Ph/Hz MCA MOCP POWER LENGTH WIDTH HEIGHT WEIGHT ARRANGEMENT

(CFM) (L/S) (in.H2O) (Pa) (HP) (kW) (HP) (kW) (Y/N) (CFM) TYPE (MBH) (kW) (MBH) (kW) (°F) (°C) (°F) (°C) (°F) (°C) (°F) (°C) (in.H2O) (Pa) STAGES (Y/N) (MBH) (kW) (MBH) (kW) (A) (A) (Y/N) (INCH) (mm) (INCH) (mm) (INCH) (mm) (LBS) (Kg)

RTU-145-01 ROOM 145 LENNOX LGH150S4M 5,000 2,360 1.00 248.84 4.1 3.1 5.0 3.7 N 850 R-410A 146.9 43.1 116.0 34.0 80.0 26.7 67.0 19.4 57.2 14.0 57.2 14.0 0.20 49.77 2 Y 13.1 10.8 180.0 52.8 144.0 42.2 2 MERV4 DUAL ENTHALPY ECONOMIZER 575/3/60 25 30 N 101.3 2,573.0 60.1 1,526.5 46.9 1,191.3 1,800 816 CURB MOUNTED SIDE DISCHARGE UNIT

RTU-125-01 ROOM 125 LENNOX LGH09H4B 3,100 1,463 1.40 348.38 1.7 1.3 2.0 1.5 N 820 R-410A 93.4 27.4 69.2 20.3 80.0 26.7 67.0 19.4 58.3 14.6 57.0 13.9 0.10 24.88 2 Y 14 12.5 130.0 38.1 104.0 30.5 2 MERV4 DUAL ENTHALPY ECONOMIZER 575/3/60 17 20 N 101.3 2,573.0 60.1 1,526.5 46.9 1,191.3 1,650 748 CURB MOUNTED PROVIDE WITH HUMIDITROL SYSTEM

NOTES: 1. ALL UNITS SHALL BE COMPLETE WITH BACNET COMPATIBLE CONTROLLER, DISCONNECT SWITCH, GFCI WEATHERPROOF COVER, BLOWER BELT AUTO TENSIONER, STANDARD CAP, STATIC POWER EXHAUST FAN, ECONOMIZER, WEATHERPROOF DISCONNECT, GFCI, DUAL ENTHALPY ECONOMIZER, HINGED ACCESS DOORS, ENVIRON COIL SYSTEM, AND AIR FILTERS.

2. ALL ROOF TOP UNITS COMPLETE WITH 24" ROOF CURB

3. EFFICIENCIES CAN NOT BE LESS THAN THOSE LISTED.

1

TM-0.2

CONTROL LEGENDNTS

A4 TEMPERATURE SENSOR, OUTSIDE SHIELDED

D10 CONDUCTIVITY CONTROLLER

D1 MOTOR CONTROL RELAY

A3 TEMPERATURE SENSOR, AVERAGING TYPE

CONTROL LEGEND

F4 LIGHTING CONTROL CONTACTS

D3 -

D9 CONTINUOUS LEVEL SENSOR (ULTRASONIC) D8 LEVEL SENSOR (FLOAT/STILLING WELL) D7 DIFFERENTIAL PRESSURE TRANSMITTER

K4 AIRFLOW CALCULATED FROM D.P. K3 AIRFLOW MEASURING DEVICE, HEATED THERMISTOR TYPE

K1 WATERFLOW MEASURING DEVICE, TURBINE TYPE

D6 FLOAT SWITCH, PIT MOUNTED D5 FLOAT SWITCH, TANK MOUNTED D4 DIFFERENTIAL PRESSURE SWITCH

D2 CURRENT SENSOR

F3 ACTUATOR FEEDBACK F2 VIBRATION DETECTOR

K6 ENERGY METER, FLOW AND TEMP. DIFF, WATER TYPE

F1 INTERFACE CONTACT TO CACF

B2 COMBINED HUMIDITY/TEMPERATURE SENSOR

C6 DAMPER STATUS SWITCH C5 WATERFLOW SWITCH

C7 OUTPUT TO VARIABLE SPEED DRIVE

C4 PRESSURE/ELECTRIC SWITCH C3 STATIC PRESSURE SENSOR C2 PNEUMATIC/CURRENT TRANSDUCER C1 PRESSURE/CURRENT TRANSMITTER

B3 OUTDOOR DEWPOINT SENSOR

C9 LEAK/MOISTURE DETECTOR C8 PULSED OUTPUT

A2 TEMPERATURE SENSOR, PIPE MOUNTED A1 TEMPERATURE SENSOR, DUCT MOUNTED

SENSOR AND INSTRUMENT CODES

B1 HUMIDITY TRANSMITTER, DUCT MOUNTED

A7 TEMPERATURE SWITCH, HIGH LIMIT A6 TEMPERATURE SWITCH, LOW LIMIT A5 TEMPERATURE SENSOR, ROOM TYPE

ABBREVIATIONS

C10 OUTPUT TO VIV

F5 OCCUPANCY SENSOR (MOTION)

K2 WATERFLOW MEASURING DEVICE, ELECTRO MAGNETIC

K7 PULSED OUTPUT WATER/GAS METER

START/STOP RELAYS FOR MOTOR CONTROL

START/STOP/STATUS RELAYS FOR MOTOR CONTROL

C6

S/S/S

S/S

A0

NORMALLY CLOSED PORT3-WAY CONTROL VALVE

COMMON PORT

NORMALLY OPEN PORT

SENSOR CODE

SIGNAL TYPE

DEVICE WITHOUT ADDITIONAL SENSORSANALOG OUTPUT TO CONTROLLEDA0 --

A0 C6

B4 SPACE CO2 SENSOR

C11 VALVE POSITION STATUS C12 INPUT FROM VARIABLE SPEED DRIVE

F6 INTERFACE CONTACT - ANALOG F7 INTERFACE CONTACT - DIGITAL F8 MULTIFUNCTION 2-WAY INTERFACE CONTACT- BACNET

ES END SWITCH (HARD WIRED TO STARTER)

BACNET DENOTES THE REQUIREMENT FORA MULTI-FUNCTION 2-WAY BACNETINTERFACE POINT. OTHERCONTROL POINTS LISTED CAN BEPROVIDED THROUGH THEMULTIFUNCTION POINT, BUT ALLINDIVIDUAL CONTROL POINTSLISTED MUST BE SHOWN ONOPERATORS WORK STATION.NOTE THAT SPEED CONTROLINPUT TO VFD'S SHALL ALWAYS BEHARDWIRED SUCH THAT ON LOSSOF CENTRAL SYSTEM, VFD SYSTEMCAN OPERATE AND CONTROL IN ASTANDALONE MODE.

K8 STEAM METER K9 GAS DETECTOR CO

K11 GAS DETECTOR - OTHERK10 GAS DETECTOR - CO2

K5 ENERGY METER, FLOW AND TEMP. DIFF, AIR TYPE

UH

ST STP

TUC

SARH SA RTT

RARH RA OAT

RAT

- STATIC PRESSURE

- TERMINAL UNIT CONTROLLER

- SETPOINT

- OUTSIDE AIR TEMPERATURE

- RETURN AIR RELATIVE HUMIDITY - RETURN AIR TEMPERATURE

- SUPPLY AIR TEMPERATURE

- SUPPLY AIR

- RETURN AIR

- SUPPLY FAN

- CENTRAL ALARM & CONTROL FACILITY

- RETURN FAN

- CONDENSER WATER RETURN

LWT

LL

OARH

MAT

FCU

HWS

EAT

FCS FPVAV

DO

DS DP

- FAN COIL UNIT

- HEATED WATER SUPPLY

- LEAVING WATER TEMPERATURE - MIXED AIR TEMPERATURE

- HEATING

- DIGITAL OUTPUT

- EXHAUST FAN

- DAMPER END SWITCH - DIFFERENTIAL PRESSURE

- EXHAUST AIR TEMPERATURE

- FAN POWERED VAV TERMINAL

- FAN COIL RETURN

CACF

CHWR CHWS

CLG

AO AI - ANALOG INPUT

- BUILDING AUTOMATION SYSTEM

- CHILLED WATER RETURN - COOLING

EA - EXHAUST AIR

- OUTSIDE AIR OA

HGS - HEATING GLYCOL SUPPLY - HEATING GLYCOL RETURN

- HIGH PRESSURE STEAMHPS

LPS - LOW PRESSURE STEAM - LOW PRESSURE CONDENSATE

MV

SP

STS

SF SAT

RF

- SPACE TEMPERATURE

- SPACE TEMPERATURE SENSOR

- UNIT HEATER

- RUN TIME TOTALIZATION

- SUPPLY AIR RELATIVE HUMIDITY

- OUTSIDE AIR RELATIVE HUMIDITY

CWR

HTG

HL

FS

HWR

EWT EF

FCR

DI

- FLOW SENSOR

- HEATED WATER RETURN

- LOW LIMIT

- HIGH LIMIT

- DIGITAL INPUT

- ENTERING WATER TEMPERATURE

- FAN COIL SUPPLY

CWS

ADJ

BAS

- CHILLED WATER SUPPLY

- CONDENSER WATER SUPPLY

- ANALOG OUTPUT

- ADJUSTABLE

VAV - VARIABLE AIR VOLUME

HGR

HPC - HIGH PRESSURE CONDENSATE

LPC

- MOTORIZED 2 POSITION VALVENOX - NITROUS OXIDE

CO - CARBON MONOXIDE - CARBON DIOXIDECO2

DAMPER CONTROL (AO) WITH DAMPEREND SWITCH- WIRE SWITCH TO CACF & STARTER- MONITOR OPEN AND CLOSED POSITION

- MODULATING CONTROL VALVE CV

CONSTANT VOLUME HIGH PRESSURE DUCT BALANCING DAMPERNTS

6

TM-0.2

AIR FLOW

100mm(4") (4")

100mm

3mm (1/8") CLEARANCE BETWEENSLEEVE AND BLADE

10 GAUGE PERFORATED PLATE6mm (1/4") DIA HOLES ON 9mm(3/8") CENTRES

STEEL PIPE CAP

WELD

9mm (3/8") PIPE COUPLING

9mm (3/8") OD x 9mm (3/8") MPTCOMPRESSION FITTING ANDCOMPRESSION SLEEVE

9mm (3/8") STEEL ROD

9mm (3/8")6mm (1/4")3mm (1/8")

SLEEVE

3mm (1/8")GALVANIZED WIRE

TACK WELD ANDGRIND BURRS

HOLES PUNCHED FROM THIS SIDEOF DAMPER BLADE IN DIRECTION OFAIR FLOW

6mm (1/4") DIA ROD ACROSS SLEEVE,WELDED AT EACH END PARALLEL TODAMPER SHAFT TO ACT AS BLADESTOP.

BEAD

BLADE AND HANDLETO BE PARALLEL

WELD

DI F1 FIRE SIGNAL

A1AI

AI B1EXHAUST AIR

RETURN AIREF

A0

D3

NC

C6

TO VAV BOXESD2 NO

A0 C6

AIR

OUTSIDE

C6A0

NC

D1

A3AI NC

--AODI D4

SF

AI A1

S/S/S

COOL

ING

DI A7 C1AI

AO C7

C7AO

S/S/S

AI C1

SEQUENCE:

7

TM-0.2

VAV SYSTEM(HEATING & COOLING & STEAM HUMIDIFICATION)

OA7AI TEMP

ON COMMAND CACF SHALL OPEN D3, CLOSE D2. ONCE PROVEN OPEN START RF. FOR 100% EXHAUST.

ON RESTORATION OF NORMAL CONDITION, SHUT DOWN SYSTEM.

ELECTRICAL DIVISION

* DI D8 *

*

*

*N0

--AO

HEAT

ING

FILT

ER

WIRE TO CACF BY ELECTRICALDIVISION

WHEN SYSTEM IS OFF ALL VALVES AND DAMPERS ARE IN NORMAL POSITION.

ON START SIGNAL, START RF AT 25% FLOW, THEN START SF AT 25% FLOW. OPEN D1 AND D3 TO MINIMUM POSITION. INCREASE FANVOLUMES UNTIL DUCT SP SET POINT IS REACHED 250 PA (1 IN). CONTROL SAT BY MODULATION OF COOLING AND HEATING VALVES INSEQUENCE. MAINTAIN SAT AS HIGH AS POSSIBLE (IN COOLING MODE) OR AS LOW AS POSSIBLE (IN HEATING MODE) TO SATISFYSPACE. WHEN DUCT SP INCREASE BEYOND SET POINT, REDUCE SF VOLUME TO ACHIEVE SET POINT. REDUCE RF VOLUME TOACHIEVE RA PLENUM PRESSURE OF 25 PA (0.1 IN). RESET SAT UPWARD IN RESPONSE TO DROP IN RAT (COOLING MODE) ANDDOWNWARD IN RESPONSE TO RISE IN RAT (IN HEATING MODE) WHEN FREE COOLING POTENTIAL EXISTS, MODULATE D1, D2 AND D3 INSEQUENCE TO MAINTAIN MAT. SENSE RARH AND MODULATE STEAM VALVE TO MAINTAIN THE FOLLOWING:

OAT RARH0 °C 15%24 °C 55%

ON SENSING HIGH OR LOW LIMIT TEMPERATURES, ALARM BAS AND SHUT DOWN SYSTEM. ON FIRE SIGNAL, SHUT DOWN SYSTEM.

A5AI

C

ELECTRIC HEATING COIL

TM-0.2

MECHANICALSCHEDULES

16-1121-000

THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS

285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000

SHEET NUMBER

TITLEApproved

Checked

Drawn

Job Number

ISSUE CHART

15 234

A

D

B

C

KEYPLAN

PROJECT

15 234

A

D

B

C

UTIAS RESEARCH LABSP049-16-138

672 Dupont Street, Suite 500Toronto, Ontario

Canada M6G 1Z6t 416.971.6060f 416.971.6765

www.perkinswill.com

MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01

Page 3: CO...PROGRAMMABLE HEATING/COOLING THERMOSTAT AND 30m (100') OF PLENUM RATED CONTROL WIRING COILED AND TEMPORARILY ATTACHED TO ROOF STRUCTURE. TYPICAL FOR CRU'S, FOR MALL RTU'S

2 3 4

A

B

145A

WEST OFFICE145C

EAST OFFICE145B

-2'-0"

EXIS

T.TA

BLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

4FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

1

ROBOTICS LAB

0"

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

10/12

20/1028/12 20/10

10/12

9/6 - B625 CFM

36/16

PROVIDE 24/8TRANSFER AIRDUCT

OPEN ENDED DUCTAT HIGH LEVEL

36/16

2"Ø

GAS

COMBUSTION AIR INTAKEAND EXHAUST FLUE UPTHROUGH ROOF

PROVIDE GAS FIRED HEATER IH-1 MOUNTED FROM CEILING18" NORTH OF GARAGE DOOR TRACKS AT 45° ANGLE

HEATER AND ALL ASSOCIATED WORK TO BE LISTED ASSEPARATE IDENTIFIED PRICE.

2"Ø GAS DOWNTHROUGH ROOF

PROVIDE ROOF TOP UNIT TO BEMOUNTED ON ROOF OF ROOM 144(REFER TO STRUCTURAL DRAWINGS)RTU-145-01, COMPLETE WITH 24" SIDEDISCHARGE CURB

2"Ø GAS

2"Ø GAS ON ROOF

(TYPICAL OF 2)

FD

3"Ø

8"Ø - 'A'225 CFM

10"Ø - 'A'400 CFM

EXIS

TING

GAS

LINE

ON

ROOF

2"Ø GASCONNECT TO EXISTINGGAS MAIN ON ROOF

8"Ø - 'A'225 CFM

10"Ø - 'A'400 CFM

PROVIDE 24/8TRANSFER AIRDUCT

1 1/2"Ø

1 1/2"

Ø

9/6 - 'B'625 CFM

(TYPICAL OF 4)

36/16 36/16

DUCTWORK ON ROOF

DUCTWORK DN THROUGH ROOF

BD 10"Ø

BD 8"Ø

10/12

10/1210/12

BD

8"Ø

10/12

BD

10"Ø

10/12

1 2 3 4

A

B

10/10 14/10 10/1014/10

20/14

22/22

REMOVE EXISTINGCEILING FAN

ROOF MOUNTEDCONDENSING UNITTO BE REMOVED

REMOVE EXISTING SPLIT D/X A/CUNIT IN ITS ENTIRETY INCLUDING,ELECTRIC DUCT HEATER ANDCONDENSATE PUMP AND PIPING

REMOVE ROOF MOUNTEDEXHAUST FAN IN IT'SENTIRETY INCLUDING ALLCONTROLS

REMOVE EXISTING ROOF MOUNTEDEXHAUST FAN IN IT'S ENTIRETYINCLUDING ALL CONTROLS

REMOVE EXISTING BASEBOARDHEATER IN IT'S ENTIRETYINCLUDING ALL CONTROLS

REMOVE EXISTING ELECTRIC UNITHEATER IN IT'S ENTIRETYINCLUDING ALL CONTROLS

REMOVE EXISTING EXHAUSTFAN, DAMPER AND DUCTWORKIN IT'S ENTIRETY INCLUDING ALLCONTROLS

REMOVE EXISTINGWALL MOUNTEDA/C UNIT

REMOVE HVAC CONTROLSREFER TO ELECTRICAL

REMOVE EXISTING BASEBOARDHEATER IN IT'S ENTIRETYINCLUDING ALL CONTROLS

REMOVE EXISTING EXHAUSTFAN, DAMPER AND DUCTWORKIN IT'S ENTIRETY INCLUDING ALLCONTROLS

EXIS

TING

GAS

LINE

ON

ROOF

TM-1.6

'ROBOTICS RESEARCHLAB' FLOOR PLAN

DEMOLITION AND NEWLAYOUT - HVAC

1/4" = 1'-0"PROPOSED CONSTRUCTION PLAN - ROBOTICS LAB

16-1121-000

THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS

285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000

SHEET NUMBER

TITLEApproved

Checked

Drawn

Job Number

ISSUE CHART

15 234

A

D

B

C

KEYPLAN

PROJECT

15 234

A

D

B

C

UTIAS RESEARCH LABSP049-16-138

672 Dupont Street, Suite 500Toronto, Ontario

Canada M6G 1Z6t 416.971.6060f 416.971.6765

www.perkinswill.com

MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01

1/4" = 1'-0"DEMOLITION PLAN - ROBOTIC RESEARCH LAB

Page 4: CO...PROGRAMMABLE HEATING/COOLING THERMOSTAT AND 30m (100') OF PLENUM RATED CONTROL WIRING COILED AND TEMPORARILY ATTACHED TO ROOF STRUCTURE. TYPICAL FOR CRU'S, FOR MALL RTU'S

2 3 4

A

B

145A

WEST OFFICE145C

EAST OFFICE145B

-2'-0"

EXIS

T.TA

BLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

4FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

1

ROBOTICS LAB

0"

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

EXIST.TABLE

5FT

REINSTALL RELOCATED AIR COMPRESSORC/W 1" COMPRESSED AIR PIPING AND 1/4TURN SHUT OFF VALVE WITH FEMALEQUICK CONNECT, PROVIDE 100' OF COILEDCOMPRESSED AIR TUBING

NON-FREEZEHOSE BIBB HB-2

SINK S-1

CTE

FLOORDRAIN

SAN

2"Ø PUMPED SANITARYDRAIN TO CONNECT TOEXISTING SERVICE INADJACENT BUILDING

3/4"Ø DCW

4"Ø

3/4"Ø DCW AND DHWDOWN TO S-1.

EXISTING SPRINKLERSAND ASSOCIATED PIPINGTO REMAIN. (TYPICAL)

EXISTING FIRE HOSECABINET TO REMAIN.

EXISTING DCWPIPING TO REMAIN.(TYPICAL)

PD

2"Ø SANITARY TOCONNECT TO EXISTINGBELOW GRADE SANITARYPIPING.

CO

PD-1 & PD-2SUMP PUMPS.

60" (1500mm) DEEP BY 48" (1200mm) DIAMETER PREFABRICATED SANITARY DRAINAGE PIT COMPLETEWITH TRAFFIC RATED COVER TO BE INSTALLED INOPENING BY GEN. CONTRACTOR.PROVIDE EYE BOLTON BEAM ABOVE SUMP PIT.

CTE

FD

FD

3"Ø

CO4"ØSINK S-2

1"Ø DCW

3/4"Ø

DCW

3/4"Ø DCW AND DHWDOWN TO S-2.

EXIS

TING

GAS

LINE

ON

ROOF

PUMPCONTROLLER

NEW NON-FREEZEHOSE BIBB HB-2

CTE

FREEZE BRANCH PIPINGFOR DEMOLITION.

CO-ORDINATE SHUTDOWNWITH OWNER

CO

PROVIDE DOM. H.W.RE-CIRCULATION PUMPPP-1 BELOW SINK

PROVIDE DOM. H.W.RE-CIRCULATION PUMPPP-2 BELOW SINK

1/2"Ø

1/2"Ø

CAP

CTE

NEW 1"Ø DOM. H.W. PIPING TOCONNECT TO EXISTING PIPING.ROUTE PIPING THROUGHEXISTING WALL PENETRATION.

1 1/2"Ø

1 1/2"

Ø

3/4"Ø DHW3/4"Ø DHW

3/4"Ø

DHW

3/4"Ø

DHW

1"Ø DHW

1"Ø

DHW

1"Ø

DHW

1 2 3 4

A

B

HOSE BIBB TOBE REMOVED

REMOVE ANDRELOCATED AIRCOMPRESSOR

REMOVECOMPRESSEDAIR PIPING

EXISTING SPRINKLERSAND ASSOCIATED PIPINGTO REMAIN. (TYPICAL)

EXISTING FIRE HOSECABINET TO REMAIN.

REMOVE EXISTINGHOSE BIBB

EXISTING DCWPIPING TO REMAIN.(TYPICAL)

FD

3"Ø

EXIS

TING

GAS

LINE

ON

ROOF

1 1/2"Ø

REMOVE EXISTINGABANDONED DOM.H.W. PIPING

TM-1.7

'ROBOTICS RESEARCHLAB' FLOOR PLAN

DEMOLITION AND NEWLAYOUT - PD & FP

1/4" = 1'-0"PROPOSED CONSTRUCTION PLAN - ROBOTICS LAB

16-1121-000

THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS

285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000

SHEET NUMBER

TITLEApproved

Checked

Drawn

Job Number

ISSUE CHART

15 234

A

D

B

C

KEYPLAN

PROJECT

15 234

A

D

B

C

UTIAS RESEARCH LABSP049-16-138

672 Dupont Street, Suite 500Toronto, Ontario

Canada M6G 1Z6t 416.971.6060f 416.971.6765

www.perkinswill.com

MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01

1/4" = 1'-0"DEMOLITION PLAN - ROBOTIC RESEARCH LAB

Page 5: CO...PROGRAMMABLE HEATING/COOLING THERMOSTAT AND 30m (100') OF PLENUM RATED CONTROL WIRING COILED AND TEMPORARILY ATTACHED TO ROOF STRUCTURE. TYPICAL FOR CRU'S, FOR MALL RTU'S

12CL

A

REMOVE EXIST. TRANE UNIT INITS ENTIRETY INCLUDING ROOFMOUNTED CONDENSER,REFRIGERANT PIPING, ANDCONTROLS. PATCH AND MAKEGOOD ALL ROOF OPENINGS.

20/14

ST

CHWSCHWR

ST

CHWSCHWR

REMOVE EXISTINGEXHAUST FAN ANDALL ASSOCIATEDDUCTWORK ANDCONTROLS.

REMOVE EXISTINGEXHAUST CANOPYAND ASSOCIATEDDUCTWORK.

CHW

SCH

WR

EXISTINGTRANSFERAIR DUCTTO REMAIN.

REMOVE ALL EXISTING SUPPLYAIR DUCTWORK SERVED BYTRANE UNIT IN ITS ENTIRETYINCLUDING ALL SUPPORTSAND DIFFUSERS.

EXISTING STEAMPIPING T0 REMAIN

EXISTINGDUCTWORK TOREMAIN. (TYPICAL)

EXISTING CHILLEDWATER SUPPLY &RETURN TO REMAIN.

EXIST GAS LINE ON ROOF G

REMOVE AND RELOCATEEXISTING STEAMHEATER

BALANCER TOAUDIT AIR FLOW

REMOVE EXISTING DUCTWORKABOVE ROOF. PATCH AND MAKEGOOD ROOF OPENING.

REMOVE EXISTING ROOF MOUNTED FAN INIT'S ENTIRETY INCLUDING ALL CONTROLS.

FREEZE BRANCH PIPINGFOR DEMOLITION.

UAS DESIGN LAB(125D)

125D

EXIST. CORRIDOR

UAS DESIGN LAB(125)

125

Room125A

FOAM CUTTER

STORAGE

GROUP 11 GROUP 10 GROUP 09 GROUP 08 GROUP 07

GROU

P 02

NEW

CAN

OPY

HOOD

NEW IT125E

LB6 LB6

LB6LB6

LB5

LB5LB5

GROUP 5 GROUP 6

LB5

LB5

GROU

P 01

GROU

P 03

LB5LB5LB5LB5LB5

LB5

LB5

LB5

LB5

GROU

P 15

GROU

P 14

GROU

P 13

GROU

P 12

LB6A

LASE

R /3D

PRIN

TER

LB4

GROU

P 04

LB5

LB5

LB5

LB5

LB5

LB5

LB5

LB5

LB5

LB5

EPOXYFLOORING W/COVE BASES

EPOXY FLOORINGW/ COVE BASES

12

PROVIDE 24/12TRANSFER AIRDUCT

ST

CHWSCHWR

ST

CHWSCHWR

16"Ø

14"Ø

18/12

22/12

22/12

18/12

12/12

PROVIDE RETURN AIR EXHAUSTDN TO 9'-0" AFF C/W DUCTMOUNTED RETURN AIR GRILLE

18/10

8/12

VALVE AND CAPEXISTING CHWS&R

EXISTINGTRANSFERAIR DUCTTO REMAIN.

CTE

CAP

CAP

16/8

10"Ø 10"Ø

PROVIDE EXHAUST DN TO 9'-0" AFF C/WFLEX DUCT CONNECTION TO 3D PRINTER

PROVIDE 12/12TRANSFER AIRDUCT (TYP OF 2)

14"Ø

8"Ø - 'A'380 CFM

22/12

6.5 KW ELECTRICHEATING COIL EHC-1ENSURE MINIMUM 12" OFSTRAIGHT DUCT BOTHUPSTREAM ANDDOWNSTREAM OF COIL

12/12 - C-

12/12 - C-

24/12 - C-

PROVIDE 24/12TRANSFER AIRDUCT

24/12 - C-

(TYP. 5)

10"Ø - 'A'410 CFM(TYP. 3)

EXISTING STEAMPIPING T0 REMAIN

EXISTINGDUCTWORK TOREMAIN. (TYPICAL)

NEW ROOF TOP UNIT RTU-125-01TO BE MOUNTED ON 24" CURB.

EXISTING CHILLEDWATER SUPPLY &RETURN TO REMAIN.

PROVIDE NEW48/24 RETURN AIRCANOPY FOR HEATCOLLECTIONBALANCED TO 1230CFM. CANOPY TOMATCH EXISTING.

12/8

12/8

10/10 - D0 CFM

BD BD

BD

BD

48/24 - E1100 CFM

CTE

400CFM

400CFM

8"Ø - ABALANCE TO AIR FLOWFROM REMOVED DIFFUSER

SLOP

E UP

SLOP

E UP

SLOP

E UP

SLOP

E UP

EXIST GAS LINE ON ROOF GCTE

2" GAS, CONNECTTO MAU-125-01

RELOCATED EXISTING STEAMHEATER. RECONNECT TO EXISTINGSTEAM AND CONDENSATE PIPING

CTE

16/18

ALL WORK ASSOCIATED WITHNEW I.T. CLOSET TO BELISTED AS SEPARATEIDENTIFIED PRICE.

PROVIDE DISPOSABLECARTRIDGE CARBON FILTERCAMFIL OPRCC-24012/2185-0

28/24

18/10

BD

28/24

16/18

22/12

22/12 16/18

BD

16/8

BD

BD

BD

BD

8"Ø

8"Ø

12/12BD

8"Ø

8"Ø

BD

22/12

BD

BD

BD

10"Ø

10"Ø

BD

8"Ø

BD10"Ø

8/12

BD

8"Ø

10/10 - D0 CFM

UAS DESIGN LAB(125D)

125D

EXIST. CORRIDOR

UAS DESIGN LAB(125)

125

Room125A

FOAM CUTTER

STORAGE

GROUP 11 GROUP 10 GROUP 09 GROUP 08 GROUP 07

GROU

P 02

NEW

CAN

OPY

HOOD

NEW IT125E

LB6 LB6

LB6LB6

LB5

LB5LB5

GROUP 5 GROUP 6

LB5

LB5

GROU

P 01

GROU

P 03

LB5LB5LB5LB5LB5

LB5

LB5

LB5

LB5

GROU

P 15

GROU

P 14

GROU

P 13

GROU

P 12

LB6A

LASE

R /3D

PRIN

TER

LB4

GROU

P 04

LB5

LB5

LB5

LB5

LB5

LB5

LB5

LB5

LB5

LB5

EPOXYFLOORING W/COVE BASES

EPOXY FLOORINGW/ COVE BASES

12

SINK S-1

SINK S-1

CA

SP SP

CA

3/4" CA

RELOCATEDCOMPRESSEDAIR FILTER

200' (1/2") COMP.AIR TUBING TO BETURNED OVER TOOWNER

1/2"Ø COMPRESSEDAIR PROTOCOLSTATION.(TYPICAL)

1/2" CA

1/2" CA

CTE

CTE

4"Ø

SAN

C0

NEW UPRIGHTSPRINKLER HEAD(TYP OF 6)

NN

N N

N N

4"Ø SAN

CTE

3/4"Ø DCW ANDDHW DOWN TO S-1.

EXISTING SPRINKLERMAIN T0 REMAINEXISTING COMPRESSED

AIR MAIN T0 REMAIN

CTE

3/4"Ø

1"Ø

3/4"Ø

EXISTING FIREEXTINGUISHERT0 REMAIN

N N

N N

N N N N

N N

N N

N N N NN

N

N N

N

1/2"Ø COMPRESSED AIRPROTOCOL STATION(TYPICAL)

ORDINARY HAZARD GROUP II - 0.2 GPM / 2000 SQ. FT.

N

N

N

N

ALL WORK ASSOCIATED WITHNEW I.T. CLOSET TO BELISTED AS SEPARATEIDENTIFIED PRICE.

CTE

CTE1/2"

1/2" CBV

2 1/2"Ø

2"Ø

EXISTING DOM.H.W. HEATERSTO REMAIN

EXISTING FIREHOSE CABINETT0 REMAIN

12CL

A

CA

SP SP

CA CA

COMP. AIR TUBINGTO BE REMOVEDAND TURNED OVERTO OWNER.

EXISTING COMP. AIR FILTER TOBE REMOVED AND RELOCATED

REMOVE EXISTING FLOORDRAIN AND CUT BACKEXISTING SANITARY PIPING

R

R R

R R

REMOVE EXISTINGSPRINKLER HEAD(TYP OF 6)

R

EXISTING SPRINKLERMAIN T0 REMAINEXISTING COMPRESSED

AIR MAIN T0 REMAIN

4"Ø

SAN

1"Ø

FREEZE BRANCH PIPINGFOR DEMOLITION.

CO-ORDINATE SHUTDOWNWITH OWNER

CO

EXISTING FIREEXTINGUISHERT0 REMAIN

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

REMOVE EXISTING CONDENSATEDRAINAGE PIPING IN IT'SENTIRETY .PATCH AND MAKEGOOD FLOOR OPENING.

2 1/2"Ø

2"Ø

EXISTING DOM.H.W. HEATERSTO REMAIN

EXISTING FIREHOSE CABINETT0 REMAIN

TM-1.0

'UAS DESIGN LAB'FLOOR PLAN DEMOLITION

& NEW LAYOUT - HVAC & PDFP

1/4" = 1'-0"DEMOLITION PLAN - ROOM 125 - HVAC

1/4" = 1'-0"CONSTRUCTION PLAN - ROOM 125 - HVAC

16-1121-000

THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS

285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000

SHEET NUMBER

TITLEApproved

Checked

Drawn

Job Number

ISSUE CHART

15 234

A

D

B

C

KEYPLAN

PROJECT

15 234

A

D

B

C

UTIAS RESEARCH LABSP049-16-138

672 Dupont Street, Suite 500Toronto, Ontario

Canada M6G 1Z6t 416.971.6060f 416.971.6765

www.perkinswill.com

MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01

1/4" = 1'-0"DEMOLITION PLAN - ROOM 125 - PD+FP

1/4" = 1'-0"CONSTRUCTION PLAN - ROOM 125 - PD+FP