AUTOMATIC CONTROL VALVE
PIPE UP
PIPE DOWN
CAPPED PIPE
DIRECTION OF FLOW
PIPE SLEEVE
CONTINUOUS PIPE
METER
UNION
STRAINER
BACKFLOW PREVENTER
WATER FEEDER ASSEMBLY
FLEXIBLE PIPE CONNECTION
PUMP
PRESSURE GAUGE WITH COCK
THERMOMETER
STARTER
FAN SPEED CONTROLLER
SLEEVE THROUGH BEAM
SLEEVE THROUGH WALL
DOWN THROUGH FLOOR
CONNECT TO EXISTING
ACCESS PANEL
ACCESS DOOR
BACKWATER VALVE WITH ACCESS
BACKWATER VALVE INLINE
VALVE IN RISER
MOTORIZED BUTTERFLY VALVE
3 WAY BUTTERFLY CONTROL VALVE
AUTOMATIC CONTROL VALVE
SAFETY RELIEF VALVE
PRESSURE DIFFERENTIAL VALVE
NEEDLE VALVE
BALANCING VALVE (PLUG)
CIRCUIT BALANCING VALVE
SOLENOID VALVE
FLOW METER, VENTURI
FLOW SWITCH
PRESSURE REDUCING VALVE
PLUG VALVE
LOCKSHIELD VALVE
BUTTERFLY VALVE
SHUT-OFF VALVE AND ACCESS PANEL
GATE VALVE AND FLOW SWITCH
VALVED AND CAPPED PROVISION
HOSE-END DRAIN VALVE
FLOAT VALVE
CHECK VALVE
BALL VALVE
LOCKABLE FLOW CONTROL VALVE
GLOBE VALVE
GATE VALVE
M
ETC ELECTRIC TRACING CABLE
3
TM-01
LEGEND - GENERALNTS
BFP
WFA
PUMPED DRAIN UNDER FLOORPD
PUMPED DRAINPD
SUPERVISED VALVE
FIRE DEPARTMENT VALVE
SPRINKLER STANDPIPE
FIRE STANDPIPE
SV
FDV
SPR
FSP
FIRE EXTINGUISHER WITH CABINET
FIRE EXTINGUISHER
FIRE HOSE RACK
FIRE HOSE CABINET
SIAMESE PUMPER CONNECTION
FG
CMD CARBON MONOXIDE DETECTOR
FIRE GONG
SIDEWALL SPRINKLER HEAD
CONCEALED SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
PENDENT SPRINKLER HEAD
CHECK VALVE WITH BALLDRIP
PREACTION ALARM CHECK VALVE
DRY ALARM CHECK VALVE
WET ALARM CHECK VALVE
SPRINKLER MAIN (GLYCOL)
SPRINKLER MAIN (DRY)
SPRINKLER LINE (WET)
FIRE LINE
RWL
VTR
VS
WS
SS
RAINWATER LEADER
VENT THROUGH ROOF
VENT STACK
WASTE STACK
SOIL STACK
MANHOLE
CATCHBASIN
CD
A
G
SCUPPER DRAIN
FLOOR DRAIN OR ROOF DRAIN
HOSE BIBB/WALL HYDRANT
T
CONDENSATE DRAIN
COMPRESSED AIR
GAS PIPE
DOMESTIC TEMPERED WATER
DOMESTIC HOT WATER RECIRC
DOMESTIC HOT WATER
DOMESTIC COLD WATER
RUNNING TRAP WITH CLEANOUT
RUNNING TRAP WITH CLEANOUT
DRAIN WITH CLEANOUT UP TO FLOOR
DRAIN WITH CLEANOUT UP TO FLOOR
DRAIN WITH CLEANOUT
VENT PIPEV
BURIED STORM DRAINST
STORM DRAINST
BURIED SANITARY DRAINSAN
SANITARY DRAINSAN
HB
MH
CB
WH
F
SP
DSP
GSP
FHC
FHC
FE
FE
CO
CO
GREASE TRAPGT
LS
FLOOR DRAIN (PARKING)
SHOWER HEAD
LIQUID SOAP
2
TM-01
LEGEND - PLUMBING, DRAINAGE AND FIRE PROTECTIONNTS
SINGLE LINE RIGID DUCT
SINGLE LINE DUCT WITH ACOUSTIC LINING
SINGLE LINE FLEXIBLE DUCT
DOUBLE LINE FLEXIBLE DUCT
SUPPLY AIR DIFFUSER
RETURN AIR GRILLE
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
MANUAL BALANCING DAMPERMOTORIZED COMBINATION
THERMOSTAT
HUMIDISTAT
DOOR UNDERCUT
DOOR GRILLE
BD
MD
SD
FS
FD
T
HCAPSIZETYPE
PIPE ANCHOR
DOUBLE LINE DUCT
DUCT WITH ACOUSTIC LINING
SOUND BAFFLE
PIPE GUIDE
EXPANSION JOINT
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
REFRIGERANT LIQUID
CONDENSATE RETURN
STEAM MAIN (PRESSURE AS INDICATED)
HEATED WATER RETURN
HEATED WATER SUPPLYHWS
HWR
S
C
RL
RD
RS
ROUND DUCT DOWN
ROUND DUCT UP
RETURN DUCT DOWN
SUPPLY DUCT DOWN
RETURN OR EXHAUST DUCT
SUPPLY OR OUTSIDE AIR DUCT
SOUND ATTENUATOR
HEATING TERMINAL
SUPPLY AIR CFMGRILLE OR REGISTER SIZE/TYPE
30012/12 D
12/12 E300
GRILLE OR REGISTER SIZE/TYPEEXHAUST OR RETURN AIR CFM
EXHAUST OR RETURN AIR CFMGRILLE OR REGISTER SIZE/TYPE
30012/12 E
12/12 D300
GRILLE OR REGISTER SIZE/TYPESUPPLY AIR CFM
SUPPLY AIR CFMDIFF NECK SIZE/DIFF TYPE
2006"Ø A
FIRE AND SMOKE DAMPER
UC
DG
GLYCOL RETURN
GLYCOL SUPPLY
FUEL OIL RETURN
FUEL OIL SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CHILLED WATER RETURN
CHILLED WATER SUPPLY
RADIATION WATER RETURN
RADIATION WATER SUPPLYRWS
RWR
CHWS
CHWR
CWS
CWR
FOS
FOR
GS
GR
1
TM-01
LEGEND HVACNTS
LOW & MEDIUM DUCT TAKE-OFFSNTS
4
TM-01
NOTE:DEPTH OF DUCT SHALL BE MINIMUM50mm (2") LARGER THAN TAKE-OFFCONNECTION
MEDIUM OR LOWPRESSURE DUCT
HANDLE SPIN ON COLLAR
DAMPER BLADE
WING NUT
RIGID DUCT
ROOF TOP UNIT INSTALLATION (RTU-145-01)NTS
5
TM-01
BOTTOM OF JOISTS
ROOF DECK
ACCOUSTICALLY LINED SUPPLY &RETURN DUCTWORK TERMINATE300mm (12") BELOW ROOF DECK
FACTORY INSTALLED WEATHERPROOFDISCONNECT SWITCH.
ECONOMIZER INTAKE
PROGRAMMABLE HEATING/COOLINGTHERMOSTAT AND 30m (100') OFPLENUM RATED CONTROL WIRINGCOILED AND TEMPORARILYATTACHED TO ROOF STRUCTURE.TYPICAL FOR CRU'S, FOR MALL RTU'SREFER TO FLOOR PLANS.
ROOF TOP MANUFACTURERSUPPLIED INSULATEDPRE-FABRICATED ROOF CURB BYMECHANICAL DIVISION.
T
ROOF SYSTEM
LUBRICATEDGAS SHUTOFF VALVE
SCHEDULE 40 GAS PIPINGSUPPORTED ON ROOF AS PERDETAIL.
POWER WIRING FROM DISCONNECT TOPOWER SOURCE BY ELECTRICALDIVISION, REFER TO ELECTRICALDRAWINGS.
PROVIDE A TRAP FROM THECOOLING COIL DRAIN THAT HAS ADEPTH OF 25mm (1") GREATERTHAN THE TOTAL FAN STATICPRESSURE.
PROVIDE GASKET ROOF TOPAC UNIT
6
TM-01
CLEAN-OUT DETAILSNTS
ALTERNATE LOCATION FOR CLEANOUTAND ACCESS
ACCESS DOOR. SEE SPECIFICATIONS.
IRON FERRULE WITH RAISEDHEAD BRASS PLUG
ACCESS COVER TO SUIT FLOORFINISH MATERIAL. SEESPECIFICATIONS.IRON FERRULE WITH RAISED HEAD BRASSPLUG
IRON FERRULE WITHRAISED HEAD BRASSPLUG
BARRET TYPE,BOLTED COVER,BRASS CAPSCREWS.
ACCESS DOOR. SEESPECIFICATION.
CLEANOUT TEE
SPRINKLER LINE
150m
m (6
")
25mm (1")
25mm (1") PLUG FORFUTURE SPRINKLER
25/25/25mm (1"x1"x1")SCREWED TEE
FINISHED CEILING
SPRINKLER LINE
150m
m (6
")
150 (6")
FIEL
D ME
ASUR
E
25mm
(1")
25mm (1") (1")
25mm
25/25/25mm (1"x1"x1")SCREWED TEE
25mm (1") PLUG FOR FUTURESPRINKLER
FINISHED CEILING
SPRINKLER LINE
150 (6")
FIEL
D ME
ASUR
E
25mm
(1")
25mm(1")
150m
m (6
")
25mm (1")
25/25/25mm (1"x1"x1")SCREWED TEE
25mm (1") PLUG FORFUTURE SPRINKLER
7
TM-01
TYPICAL SPRINKLER HEAD INSTALLATIONNTS
8
TM-01
SUPPORTS FOR GAS PIPING ON ROOFNTS
FRONT ELEVATION
SIDE ELEVATION
ROOF
NOTES:
6.
7. 8. 9. 10.
CADMIUM PLATED No. 12 - 50mm (2") LONG SCREWSSHIM WOOD BLOCKING AS REQUIRED TO COMPENSATE FOR ROOF SLOPEALL PIPING ON ROOF TO BE PAINTED YELLOW BY MECHANICAL DIVISION.
5. SCHEDULE 40 STEEL PIPE
11.
ROOF
2.
3. 4.
1.
W:200mm/ L:300mm/ H:50mm ( 8"/12"/2") LONG PRESSURE TREATED WOODW:100mm/ L:300mm/ H:100mm (4"/12"/4") LONG PRESSURE TREATED WOOD
ROOFMATE INSULATION PLACED ON FINISHED ROOF
NAIL TOGETHER WITHGALVANIZED NAILS
W:450mm/ L:450mm/ H:50mm (18"/18"/2")
(ALL COMPONENTS BY MECHANICAL TRADES)
CARBON STEEL STRAPS - GRINNELL FIG. 262 OR EQUAL - OVERSIZE (1 SIZE LARGER) TO ALLOW FOR PIPE MOVEMENT - PAINTSTRAPS WITH ANTI-CORROSIVE PAINT. PIPE SUPPORTS TO BE 2450mm (8'-2") APART FOR 25mm (1") PIPE & 3000mm (10'-0") APARTFOR 32mm (1 1/4") PIPE & OVER. THERE MUST BE A SUPPORT AT EVERY 90° HORIZONTAL/VERTICAL ELBOW AND TEE FITTINGS.
WHERE GAS PIPING IS ADJACENT TO A VERTICAL WALL, PROVIDE SUPPORTS 750mm (30") APART. PIPE DISTANCE FROMWALL IS TWO (2) TIMES THE HEIGHT OF THE WALL. (IE 4 METRE HIGH WALL PIPE INSTALLED 8 METRES FROM WALL)
ALL VERTICAL PIPING UP SIDE OF WALLS OR ROOF ELEVATION CHANGES PAINTED TO MATCH WALL FINISH ANDBANDED (IDENTIFIED GAS) AT TOP AND BOTTOM BY MECHANICAL CONTRACTOR.
IN LIEU OF ITEMS 3&4 PROVIDE MANUFACTURED, SINGLE PIECE VOLCANIZED RUBBER GAS SUPPORT 100mmx150mmx225mm(4"x6"x9" LONG) COMPLETE WITH STAINLESS STEEL STRUTS. SUPPORTS SHALL WEIGH NO LESS THAN 9LBS.
NOTE:
12. GAS PIPING SHALL NOT BE INSTALLED CLOSER THAN 6'-0" TO EDGE OF ROOF.
W:450mm/ L:450mm/ H:50mm (18"/18"/2") PATIO STONES BY ADHESIVE TO INSULATION. PROVIDE EXCESS CONSTRUCTIONADHESIVE DURING FASTENING SUCH THAT ADHESIVE RUNS DOWN SIDE OF STONES FOR VISIBLE INSPECTION.
SEQUENCE
A6DI
HEAT
ING
COOL
ING
S/S/S A1AI
SF
D4DI
AI A3
D1
NC
A0 C6
OUTSIDE
AIRSUPPLY AIR
S/S/SC6
NC
D3
A0
EFEXHAUST AIR
EXHAUST AIR
AI A1
DI F1 FIRE SIGNAL
OATAI TEMP
DI *D8
ON RESTORATION OF NORMAL CONDITION, SHUT DOWN SYSTEM.
*
*
FILT
ER
THE SYSTEM OPERATES ON A TIME OF DAY SCHEDULE. WHEN SYSTEM IS OFF ALL DAMPERS ARE IN NORMAL POSITION. ONSTART SIGNAL, START EF, THEN START SF. OPEN D1 AND D3 TO MINIMUM POSITION. CONTROL SAT BY MODULATION OF HEATINGAND COOLING SECTIONS IN SEQUENCE MAINTAIN SAT AS HIGH AS POSSIBLE (COOLING MODE) OR AS LOW AS POSSIBLE (HEATINGMODE) TO SATISFY SPACE. RESET SAT FROM EAT. RESET SAT UPWARD IN RESPONSE TO DROP IN EAT (COOLING MODE) ORDOWNWARD IN RESPONSE TO RISE IN EAT (HEATING MODE). WHEN FREE COOLING POTENTIAL EXISTS, MODULATE D1 AND D3 TOMAINTAIN MAT. ENSURE THAT SIMULTANEOUS HEATING AND COOLING DOES NOT OCCUR.
ON SENSING HIGH OR LOW LIMIT TEMPERATURES, SHUT DOWN SYSTEM. ON FIRE SIGNAL, SHUT DOWN SYSTEM.
DIVISION 16 ON COMMAND CACF SHALL OPEN D3, ONCE PROVEN OPEN START EF. FOR 100% EXHAUST.
* WIRE TO CACF BY DIV.16.
9
TM-01
CONSTANT VOLUME SYSTEM NTS
HEAT
REC
OVER
Y W
HEEL
10
TM-01
FUME HOOD NTS
CANOPY TO BESUSPENDED FROMSTEEL STRUCTURE
EXHAUST CANOPY DIMENSIONS4'-0" LONG x 2'-0" WIDE
CANOPY CONSTRUCTIONTO MATCH EXISTING
CANOPY TO TAPER TOWARDSWALL SUCH THAT EXHAUST DUCTCAN RUN VERTICALLY ALONG WALL
EXHAUST CANOPY TO BEMOUNTED 4'-0" ABOVEFINISHED FLOOR
DUCT
EXTERNAL INSULATION &FINISHING AS PER SPECC/W WATER PROOFING
CONTINUOUS SEAL WITHSUITABLE MASTIC OR FOILBACKED TAPE.
CONTINUOUS ANGLE SUPPORT.SUPPORT ANGLE PINNED TOTHE DUCT ALL AROUND.
EXTEND METAL FLASHING100mm (4") BELOW TOP OFCURB.
ROOF
INSULATED ROOF CURB
SECURE FLASHING TO DUCTAND SEAL WATERTIGHT.
SEAL TO COUNTER FLASHING.
ROOF MEMBRANE
GRAVEL
INSULATION
ROOF STRUCTURE
TO/FROM AIR HANDLER.
PROVIDE INSULATION ONINTERIOR DUCTWORK FORSUPPLY SYSTEMS. AS PERSPEC.
13
TM-01
SUPPLY OR RETURN DUCT THROUGH ROOFNTS
NOTE:CURB AND FLASHING BYMECHANICAL DIVISION
CEILING TO CEILING TRANSFER AIR DUCT TOP OPENINGSNTS
12
TM-01
NOTE:DUCT SIZES SHOWN ON PLAN ARECLEAR INSIDE DIMENSIONS.INCREASE DUCT SIZESACCORDINGLY TO ALLOW FORLINING THICKNESS
METAL STRAPHANGERS
ALTERNATE OPENINGSAT SIDE OF DUCT
SEAL AROUND WALL PENETRATION
TOP OPENINGS TO MATCHDUCT SIZE TWO OPENINGSPER DUCT
MAXIMIZECLEARANCE
MINIMUM 1500 (60")LONG ACOUSTICALLYLINED DUCT
PARTITION
NOTE:REFER TO PLAN FORDUCT SIZES
50mm (2")CLEARANCETHIMBLE
INSTALL GAS FIRED INFRA-RED HEATER ACCORDING TOMANUFACTURER'S INSTRUCTION AND RECOMMENDATIONS AND TOALL APPLICABLE CODES AND LOCAL BY-LAWS.SINGLE-WALL GALVANIZED FLUE PIPE OR DURA/CONNECT SINGLEWALL, FLEXIBLE CONNECTORS MUST BE USED. THE PORTION OF THEFLUE PIPE WHICH GOES THROUGH COMBUSTIBLE MATERIAL IN THEBUILDING WALL OR ROOF MUST PASS THROUGH A TYPE "B" VENT TOMAINTAINCLEARANCE.
THE VENTING SYSTEM SHALL TERMINATE AT LEAST 900mm (36")ABOVE ANY OTHER BUILDING OPENING OR ANY GAS REGULATOR.
THE VENTING SYSTEM SHALL TERMINATE AT LEAST 1.8m (6') FROM ACOMBUSTION AIR INLET OR ANOTHER APPLIANCE AND NOT ABOVE AGAS UTILITY METER OR SERVICE REGULATOR.
UNINSULATED SINGLE-WALL VENT PIPE SHALL NOT BE USED.
GAS-FIRED INFRA-REDHEATER (REFER TOSCHEDULE FOR SELECTION)
NOTES:
03.
05.
04.
01.
02.
ROOFFLASHINGCOMBUSTIBLEMATERIAL
APPROVEDVENT CAP
VENTINGTHROUGHROOF
VENTINGTHROUGHSIDEWALL
THE VENT TERMINAL OF A HORIZONTAL VENTING SYSTEM MUST BEINSTALLED TO PREVENT BLOCKAGE BY SNOW AND PROTECTBUILDING MATERIALS FROM DEGRADATION BY FLUE GASES.
HORIZONTAL VENTING MUST MAINTAIN A MINIMUM 150mm (6") FROMTHE VENT TERMINATION TO THE SIDEWALL.BUILDING INCORPORATING VENTED SOFFITS/OVERHANGS MUSTENSURE THAT THE PRODUCTS-OF-COMBUSTION DO NOT ENTER THEATTIC SPACE.
08.
09.
07.
AIR INTAKE
AIR INTAKE CAP W/ BIRD SCREEN
ROOF
600mm (24")
150mm(6")MIN.
APPROVEDVENTCAP
TYPE "B" VENT
BUILDING OVERHANG
900mm (36")
THIMBLE
TYPE "B"VENT
WALL
ALTERNATE AIR INTAKETHROUGH ROOF
CHAIN
900mm (36")
INSULATE INTAKE PIPEAND FINISH WITHALUMINUM JACKET.
11
TM-01
INFRA-RED GAS HEATERNTS
900mm (36")
ROOF TOP UNIT INSTALLATION (RTU-145-01)NTS
14
TM-0.1
BOTTOM OF JOISTS
ROOF DECK
ACCOUSTICALLY LINED SUPPLY &RETURN DUCTWORK TERMINATE300mm (12") BELOW ROOF DECK
FACTORY INSTALLED WEATHERPROOFDISCONNECT SWITCH.
ECONOMIZER INTAKE
PROVIDE FLEXIBLE CONNECTIONAT R/A & S/A OPENING IN BOTTOMOF AC UNIT AND SUPPORTDUCTWORK FROM STRUCTURE.
PROGRAMMABLE HEATING/COOLINGTHERMOSTAT AND 30m (100') OFPLENUM RATED CONTROL WIRINGCOILED AND TEMPORARILYATTACHED TO ROOF STRUCTURE.TYPICAL FOR CRU'S, FOR MALL RTU'SREFER TO FLOOR PLANS.
ROOF TOP MANUFACTURERSUPPLIED INSULATEDPRE-FABRICATED ROOF CURB BYMECHANICAL DIVISION.
T
ROOF SYSTEM
LUBRICATEDGAS SHUTOFF VALVE
SCHEDULE 40 GAS PIPINGSUPPORTED ON ROOF AS PERDETAIL.
POWER WIRING FROM DISCONNECT TOPOWER SOURCE BY ELECTRICALDIVISION, REFER TO ELECTRICALDRAWINGS.
MECHANICAL DIVISION TO PROVIDENON COMBUSTABLE BLOCKING ALLAROUND UNDER CURB.
PROVIDE A TRAP FROM THECOOLING COIL DRAIN THAT HAS ADEPTH OF 25mm (1") GREATERTHAN THE TOTAL FAN STATICPRESSURE.
PROVIDE GASKET ROOF TOPAC UNIT
TM-0.1
MECHANICALLEGEND, DETAILS
& DRAWING LIST
16-1121-000
THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS
285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000
SHEET NUMBER
TITLEApproved
Checked
Drawn
Job Number
ISSUE CHART
15 234
A
D
B
C
KEYPLAN
PROJECT
15 234
A
D
B
C
UTIAS RESEARCH LABSP049-16-138
672 Dupont Street, Suite 500Toronto, Ontario
Canada M6G 1Z6t 416.971.6060f 416.971.6765
www.perkinswill.com
MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01
AIR TERMINAL SCHEDULE
TAG DESCRIPTION MANUFACTURER MODEL MATERIAL FINISH MOUNTING COMMENTS
A ROUND CONE DIFFUSERS EH PRICE RCDA/B12 ALUMINIUM WHITE DUCT MOUNTED NECK SIZE AS NOTED ON PLAN
B DRUM LOUVRES EH PRICE HCD1/F/A/B12 ALUMINIUM WHITE DUCT MOUNTED SIZE AS NOTED ON PLAN
C WALL MOUNT RETURN AND TRANSFER AIR EH PRICE 535/TB/S/D/A/B12 STEEL WHITE WALL BACK TO BACK WALL MOUNTED ARRANGEMENT SIZE AS NOTED ON PLANS
D DUCT MOUNT RETURN EH PRICE 535/F/L/D/A/B12 STEEL WHITE DUCT SIZE AS NOTED ON PLANS
E LASER CUTTER EXHAUST EH PRICE PDDR/1/B12 STEEL WHITE DUCT DIFFUSER AND NECK SIZE AS NOTED ON PLAN. UNIT TO BE HUNG FROM JOISTS WITH CHAINS
NOTES: 1. NECK SIZE NOTED ON PLANS.
GAS-FIRED UNIT HEATER SCHEDULE
TAG MANFACTURER MODEL GAS HEATING ELECTRICAL EMERGENCY WEIGHT COMMENTS
INPUT OUTPUT POWER(MBH) (kW) (MBH) (kW) (V/Ph/Hz) (Y/N) (LBS) (Kg)
IH-1 SCHWANK STS-JZ-80-20 80.0 23.4 40.0 11.7 120/1/60 N 150 68
NOTES: 1. PROVIDE ALL HANGERS AND SUPPORTS REQUIRED.
2. PROVIDE FLEXIBLE GAS CONNECTION TO UNIT.
PUMP SCHEDULE
TAG SERVICE LOCATION MANUFACTURER TYPE/SERIES MODEL FLUID TYPE RPM CAPACITY HEAD MOTOR SIZE VFD BY-PASS VARIABLE SPEED ELECTRICAL EMERGENCY PRESSURE OPERATION COMMENTSBRAKE POWER POWER ON VFD APPLICATION POWER RATING
(USGPM) (L/s) (ft.H2O) (kPa) (HP) (kW) (HP) (kW) (Y/N) (Y/N) (Y/N) (V/Ph/Hz) (Y/N) (PSI) (kPa)
PD-01 ROOM 145 SUMP ROOM 145 - SUMP PIT HYDROMATIC CAST IRON SUMP W-A1 SANITARY WATER 1,550 9.0 0.6 20.0 59.7 0.3 0.2 0.3 0.2 N N/A N 115/1/60 N 150.0 1,034.2 LEAD/LAG PUMP CONTROLLER TO BE BACNET COMPATIBLE
PD-02 ROOM 145 SUMP ROOM 145 - SUMP PIT HYDROMATIC CAST IRON SUMP W-A1 SANITARY WATER 1,550 9.0 0.6 20.0 59.7 0.3 0.2 0.3 0.2 N N/A N 115/1/60 N 150.0 1,034.2 LEAD/LAG PUMP CONTROLLER TO BE BACNET COMPATIBLE
PP-01 ROOM 145 CIRCULATOR ROOM 145 - BELOW SINK XYLEM ECOCIRC B 23-5 DOMESTIC HOT WATER - 0.5 0.0 20.0 59.7 0.1 0.1 0.1 0.1 N N/A N 115/1/60 N 145.0 999.7 RECIRCULATOR
PP-01 ROOM 145 CIRCULATOR ROOM 145 - BELOW SINK XYLEM ECOCIRC B 23-5 DOMESTIC HOT WATER - 0.5 0.0 20.0 59.7 0.1 0.1 0.1 0.1 N N/A N 115/1/60 N 145.0 999.7 RECIRCULATOR
NOTES: 1.
HEATING COIL SCHEDULE (ELECTRIC)
TAG SERVICE MANUFACTURER MODEL HEATING AIR PRESSURE EAT DB LAT DB ELECTRICAL EMERGENCY COMMENTSCAPACITY FLOW DROP POWER
(MBH) (kW) (CFM) (L/s) (in.H20) (Pa) (°F) (°C) (°F) (°C) (V/Ph/Hz) (Y/N)
EHC-1 ROOM 125 THERMOLEC SCD 22.1 6.5 900 425 0.2 49.8 55.0 12.8 77.0 25.0 600/3/60 N
NOTES: 1. ALL COILS TO BE SCR CONTROLLED.
2. PROVIDE AIR FLOW PROOFING SWITCH.
3. PROVIDE LOCAL DISCONNECT.
FRAME
9 (3/8") "Z" CHANEL
WELD
THICKNESS OF STEEELSTOP TO SUIT COVERPLATE USED
RECESSED HEXAGON HEAD BOLTS 158 (61/4") WITH GASKET BETWEEN MACHINEDSURFACES.GASKETED STEEL COVER PLATE AS PERMANUFACTURERS RECOMMENDATIONS &WITH A STRUCTURAL CAPACITY OF 4536kg(10,000 lbs).
32 (1 1/4") STEEL STOPWELDED TO FRAMEALL AROUND
TUBULAR NEOPRENEGASKET
3x25x150 (1/8"x1"x6")STEEL ANGULAR STRAPTWO PER SIDE75x75x9 (3"x3"x3/8")ANGLE FRAME
HEXAGON HEAD BRASS BOLTSWITH BRASS WASHERS
STEEL COVER PLATE WITH ASTRUCTURAL CAPACITY OF4536kg (10,000 lbs)
3x25x150 (1/8"x1"x6") STEELANGULAR STRAP
4
TM-02
SUMP PIT COVER PLATENTS
LADDER RUNGS
PUMPED DISCHARGE
GATE VALVEUNION
SANITARY PIT
DRAININLET
UNION
BASE SUPPORT
9mm (3/8") "Z" CHANNEL
1ST PUMP OUT
2ND PUMP OUT
HIGH LEVEL ALARM2ND PUMP ON1ST PUMP ON
OFFSET PIPING TOALLOW FOR PUMPREMOVAL
CHECK VALVE
PROVIDE AIR TIGHTSEAL AT PIPEPENETRATION.
VENT TO ATMOSPHERE
SUBMERSIBLE PUMPS MOUNTED ON GUIDE RAILSSUCH THAT THEY CAN INDEPENDANTLY BEREMOVED WITH THE REMAINING PUMP BEING INOPERATION.
PROVIDE REMOVABLE SECTION OFCOVER TO ALLOW PUMP REMOVAL.SEAL AIR TIGHT.
1 REFER TO PLANS FOR PIT SIZES,DRAIN SIZES, VENT SIZES, DRAININVERTS AND FLOOR ELEVATIONS.
2 PROVIDE EYEBOLTS IN SLABABOVE PIT FOR MOTOR REMOVAL.
3 PROVIDE GALVANIZED STEELLADDER RUNGS AT 300mm (12")CENTRES FOR PITS DEEPER THAN1050mm (42")
4 PROVIDE A GASKETED, HINGED,900/900 ACCESS HATCH LOCATEDTO ALLOW REMOVAL OF BOTHPUMPS.
100mm (4") min.LIFTCHAINANDHOOK
3x25x150 (1/8"x1"x6")STEEL ANGULARSTRAP TWO PERSIDE
STEEL COVER PLATE WITH ASTRUCTURAL CAPACITY OF10,000 LBS
TUBULAR NEOPRENE GASKET
RECESSED HEX HEAD BOLTS158mm (6-1/4") WITH GASKETBETWEEN MACHINEDSURFACES.
DESIGNER'S NOTE:
FILL IN ELEVATIONS FORPUMP START/STOP.
8
TM-02
SANITARY PIT WITH SUBMERSIBLE PUMPSNTS
3
TM-02
ELECTRIC HEATER CONTROLNTS
H
EXISTING INTERNAL SAFETIESTO INCLUDE HIGH-TEMP & AIRPROOFING.
POWER
AIRFLOW AIRFLOW
SEQUENCE
VARIABLE AIR VOLUME BOX SCHEDULE
TAG MANUFACTURER MODEL UNIT MAXIMUM MINIMUM INLET SIZE OUTLET SIZE ATTENUATORS SOUND POWER LEVEL IN dB RE 10^-12 W SOUND POWER LEVEL IN dB RE 10^-12 WSIZE AIR FLOW AIR FLOW LENGTH WIDTH DISCHARGE INLET LINER MAX DISCHARGE SOUND POWER MAX RADIATED SOUND POWER
(CFM) (L/S) (CFM) (L/S) (INCH) (mm) (INCH) (mm) (INCH) (mm) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz
8 EH PRICE SDV 8 625 295 135 64 8.0 203.2 10.0 254.0 12.0 304.8 5 1.5 FG50 59 53 46 38 22 - 60 49 40 35 29 26
10 EH PRICE SDV 10 1,010 477 220 104 10.0 254.0 12.5 317.5 14.0 355.6 5 1.5 FG50 61 54 48 41 26 25 56 46 40 34 30 26
14 EH PRICE SDV 14 2,250 1,062 440 208 14.0 355.6 17.5 444.5 20.0 508.0 5 1.5 FG50 64 57 56 46 37 36 63 52 51 42 38 31
NOTES: 1. FOR ACTUAL FLOWS REFER TO DRAWINGS.2. MINIMUM AIR FLOWS ARE FOR SELECTION ONLY, SEE MINIMUM AIR FLOW SET POINT ON DRAWINGS.
3. HEATING COILS SHALL HAVE A RATING OF 125 PSI.
4. PROVIDE ALL VAV BOXES WITH BACNET COMPATIBLE CONTROLLER
DX/GAS-FIRED PACKAGED ROOF TOP UNIT SCHEDULE
TAG SERVICE MANUFACTURER MODEL SUPPLY FAN MINIMUM COOLING GAS HEATINGFILTERTYPE
ENERGY RECOVERY ELECTRICAL EMERGENCY DIMENSIONS OPERATING MOUNTING COMMENTSNUMBER FLOW E.S.P. BRAKE POWER POWER VFD OUTDOOR AIR REFRIGERANT TOTAL CAPACITY SENSIBLE CAPACITY EAT DB EAT WB LAT DB LAT WB MAX PRESSURE DROP # OF ECONOMIZER IEER EER INPUT OUTPUT STAGES TYPE V/Ph/Hz MCA MOCP POWER LENGTH WIDTH HEIGHT WEIGHT ARRANGEMENT
(CFM) (L/S) (in.H2O) (Pa) (HP) (kW) (HP) (kW) (Y/N) (CFM) TYPE (MBH) (kW) (MBH) (kW) (°F) (°C) (°F) (°C) (°F) (°C) (°F) (°C) (in.H2O) (Pa) STAGES (Y/N) (MBH) (kW) (MBH) (kW) (A) (A) (Y/N) (INCH) (mm) (INCH) (mm) (INCH) (mm) (LBS) (Kg)
RTU-145-01 ROOM 145 LENNOX LGH150S4M 5,000 2,360 1.00 248.84 4.1 3.1 5.0 3.7 N 850 R-410A 146.9 43.1 116.0 34.0 80.0 26.7 67.0 19.4 57.2 14.0 57.2 14.0 0.20 49.77 2 Y 13.1 10.8 180.0 52.8 144.0 42.2 2 MERV4 DUAL ENTHALPY ECONOMIZER 575/3/60 25 30 N 101.3 2,573.0 60.1 1,526.5 46.9 1,191.3 1,800 816 CURB MOUNTED SIDE DISCHARGE UNIT
RTU-125-01 ROOM 125 LENNOX LGH09H4B 3,100 1,463 1.40 348.38 1.7 1.3 2.0 1.5 N 820 R-410A 93.4 27.4 69.2 20.3 80.0 26.7 67.0 19.4 58.3 14.6 57.0 13.9 0.10 24.88 2 Y 14 12.5 130.0 38.1 104.0 30.5 2 MERV4 DUAL ENTHALPY ECONOMIZER 575/3/60 17 20 N 101.3 2,573.0 60.1 1,526.5 46.9 1,191.3 1,650 748 CURB MOUNTED PROVIDE WITH HUMIDITROL SYSTEM
NOTES: 1. ALL UNITS SHALL BE COMPLETE WITH BACNET COMPATIBLE CONTROLLER, DISCONNECT SWITCH, GFCI WEATHERPROOF COVER, BLOWER BELT AUTO TENSIONER, STANDARD CAP, STATIC POWER EXHAUST FAN, ECONOMIZER, WEATHERPROOF DISCONNECT, GFCI, DUAL ENTHALPY ECONOMIZER, HINGED ACCESS DOORS, ENVIRON COIL SYSTEM, AND AIR FILTERS.
2. ALL ROOF TOP UNITS COMPLETE WITH 24" ROOF CURB
3. EFFICIENCIES CAN NOT BE LESS THAN THOSE LISTED.
1
TM-0.2
CONTROL LEGENDNTS
A4 TEMPERATURE SENSOR, OUTSIDE SHIELDED
D10 CONDUCTIVITY CONTROLLER
D1 MOTOR CONTROL RELAY
A3 TEMPERATURE SENSOR, AVERAGING TYPE
CONTROL LEGEND
F4 LIGHTING CONTROL CONTACTS
D3 -
D9 CONTINUOUS LEVEL SENSOR (ULTRASONIC) D8 LEVEL SENSOR (FLOAT/STILLING WELL) D7 DIFFERENTIAL PRESSURE TRANSMITTER
K4 AIRFLOW CALCULATED FROM D.P. K3 AIRFLOW MEASURING DEVICE, HEATED THERMISTOR TYPE
K1 WATERFLOW MEASURING DEVICE, TURBINE TYPE
D6 FLOAT SWITCH, PIT MOUNTED D5 FLOAT SWITCH, TANK MOUNTED D4 DIFFERENTIAL PRESSURE SWITCH
D2 CURRENT SENSOR
F3 ACTUATOR FEEDBACK F2 VIBRATION DETECTOR
K6 ENERGY METER, FLOW AND TEMP. DIFF, WATER TYPE
F1 INTERFACE CONTACT TO CACF
B2 COMBINED HUMIDITY/TEMPERATURE SENSOR
C6 DAMPER STATUS SWITCH C5 WATERFLOW SWITCH
C7 OUTPUT TO VARIABLE SPEED DRIVE
C4 PRESSURE/ELECTRIC SWITCH C3 STATIC PRESSURE SENSOR C2 PNEUMATIC/CURRENT TRANSDUCER C1 PRESSURE/CURRENT TRANSMITTER
B3 OUTDOOR DEWPOINT SENSOR
C9 LEAK/MOISTURE DETECTOR C8 PULSED OUTPUT
A2 TEMPERATURE SENSOR, PIPE MOUNTED A1 TEMPERATURE SENSOR, DUCT MOUNTED
SENSOR AND INSTRUMENT CODES
B1 HUMIDITY TRANSMITTER, DUCT MOUNTED
A7 TEMPERATURE SWITCH, HIGH LIMIT A6 TEMPERATURE SWITCH, LOW LIMIT A5 TEMPERATURE SENSOR, ROOM TYPE
ABBREVIATIONS
C10 OUTPUT TO VIV
F5 OCCUPANCY SENSOR (MOTION)
K2 WATERFLOW MEASURING DEVICE, ELECTRO MAGNETIC
K7 PULSED OUTPUT WATER/GAS METER
START/STOP RELAYS FOR MOTOR CONTROL
START/STOP/STATUS RELAYS FOR MOTOR CONTROL
C6
S/S/S
S/S
A0
NORMALLY CLOSED PORT3-WAY CONTROL VALVE
COMMON PORT
NORMALLY OPEN PORT
SENSOR CODE
SIGNAL TYPE
DEVICE WITHOUT ADDITIONAL SENSORSANALOG OUTPUT TO CONTROLLEDA0 --
A0 C6
B4 SPACE CO2 SENSOR
C11 VALVE POSITION STATUS C12 INPUT FROM VARIABLE SPEED DRIVE
F6 INTERFACE CONTACT - ANALOG F7 INTERFACE CONTACT - DIGITAL F8 MULTIFUNCTION 2-WAY INTERFACE CONTACT- BACNET
ES END SWITCH (HARD WIRED TO STARTER)
BACNET DENOTES THE REQUIREMENT FORA MULTI-FUNCTION 2-WAY BACNETINTERFACE POINT. OTHERCONTROL POINTS LISTED CAN BEPROVIDED THROUGH THEMULTIFUNCTION POINT, BUT ALLINDIVIDUAL CONTROL POINTSLISTED MUST BE SHOWN ONOPERATORS WORK STATION.NOTE THAT SPEED CONTROLINPUT TO VFD'S SHALL ALWAYS BEHARDWIRED SUCH THAT ON LOSSOF CENTRAL SYSTEM, VFD SYSTEMCAN OPERATE AND CONTROL IN ASTANDALONE MODE.
K8 STEAM METER K9 GAS DETECTOR CO
K11 GAS DETECTOR - OTHERK10 GAS DETECTOR - CO2
K5 ENERGY METER, FLOW AND TEMP. DIFF, AIR TYPE
UH
ST STP
TUC
SARH SA RTT
RARH RA OAT
RAT
- STATIC PRESSURE
- TERMINAL UNIT CONTROLLER
- SETPOINT
- OUTSIDE AIR TEMPERATURE
- RETURN AIR RELATIVE HUMIDITY - RETURN AIR TEMPERATURE
- SUPPLY AIR TEMPERATURE
- SUPPLY AIR
- RETURN AIR
- SUPPLY FAN
- CENTRAL ALARM & CONTROL FACILITY
- RETURN FAN
- CONDENSER WATER RETURN
LWT
LL
OARH
MAT
FCU
HWS
EAT
FCS FPVAV
DO
DS DP
- FAN COIL UNIT
- HEATED WATER SUPPLY
- LEAVING WATER TEMPERATURE - MIXED AIR TEMPERATURE
- HEATING
- DIGITAL OUTPUT
- EXHAUST FAN
- DAMPER END SWITCH - DIFFERENTIAL PRESSURE
- EXHAUST AIR TEMPERATURE
- FAN POWERED VAV TERMINAL
- FAN COIL RETURN
CACF
CHWR CHWS
CLG
AO AI - ANALOG INPUT
- BUILDING AUTOMATION SYSTEM
- CHILLED WATER RETURN - COOLING
EA - EXHAUST AIR
- OUTSIDE AIR OA
HGS - HEATING GLYCOL SUPPLY - HEATING GLYCOL RETURN
- HIGH PRESSURE STEAMHPS
LPS - LOW PRESSURE STEAM - LOW PRESSURE CONDENSATE
MV
SP
STS
SF SAT
RF
- SPACE TEMPERATURE
- SPACE TEMPERATURE SENSOR
- UNIT HEATER
- RUN TIME TOTALIZATION
- SUPPLY AIR RELATIVE HUMIDITY
- OUTSIDE AIR RELATIVE HUMIDITY
CWR
HTG
HL
FS
HWR
EWT EF
FCR
DI
- FLOW SENSOR
- HEATED WATER RETURN
- LOW LIMIT
- HIGH LIMIT
- DIGITAL INPUT
- ENTERING WATER TEMPERATURE
- FAN COIL SUPPLY
CWS
ADJ
BAS
- CHILLED WATER SUPPLY
- CONDENSER WATER SUPPLY
- ANALOG OUTPUT
- ADJUSTABLE
VAV - VARIABLE AIR VOLUME
HGR
HPC - HIGH PRESSURE CONDENSATE
LPC
- MOTORIZED 2 POSITION VALVENOX - NITROUS OXIDE
CO - CARBON MONOXIDE - CARBON DIOXIDECO2
DAMPER CONTROL (AO) WITH DAMPEREND SWITCH- WIRE SWITCH TO CACF & STARTER- MONITOR OPEN AND CLOSED POSITION
- MODULATING CONTROL VALVE CV
CONSTANT VOLUME HIGH PRESSURE DUCT BALANCING DAMPERNTS
6
TM-0.2
AIR FLOW
100mm(4") (4")
100mm
3mm (1/8") CLEARANCE BETWEENSLEEVE AND BLADE
10 GAUGE PERFORATED PLATE6mm (1/4") DIA HOLES ON 9mm(3/8") CENTRES
STEEL PIPE CAP
WELD
9mm (3/8") PIPE COUPLING
9mm (3/8") OD x 9mm (3/8") MPTCOMPRESSION FITTING ANDCOMPRESSION SLEEVE
9mm (3/8") STEEL ROD
9mm (3/8")6mm (1/4")3mm (1/8")
SLEEVE
3mm (1/8")GALVANIZED WIRE
TACK WELD ANDGRIND BURRS
HOLES PUNCHED FROM THIS SIDEOF DAMPER BLADE IN DIRECTION OFAIR FLOW
6mm (1/4") DIA ROD ACROSS SLEEVE,WELDED AT EACH END PARALLEL TODAMPER SHAFT TO ACT AS BLADESTOP.
BEAD
BLADE AND HANDLETO BE PARALLEL
WELD
DI F1 FIRE SIGNAL
A1AI
AI B1EXHAUST AIR
RETURN AIREF
A0
D3
NC
C6
TO VAV BOXESD2 NO
A0 C6
AIR
OUTSIDE
C6A0
NC
D1
A3AI NC
--AODI D4
SF
AI A1
S/S/S
COOL
ING
DI A7 C1AI
AO C7
C7AO
S/S/S
AI C1
SEQUENCE:
7
TM-0.2
VAV SYSTEM(HEATING & COOLING & STEAM HUMIDIFICATION)
OA7AI TEMP
ON COMMAND CACF SHALL OPEN D3, CLOSE D2. ONCE PROVEN OPEN START RF. FOR 100% EXHAUST.
ON RESTORATION OF NORMAL CONDITION, SHUT DOWN SYSTEM.
ELECTRICAL DIVISION
* DI D8 *
*
*
*N0
--AO
HEAT
ING
FILT
ER
WIRE TO CACF BY ELECTRICALDIVISION
WHEN SYSTEM IS OFF ALL VALVES AND DAMPERS ARE IN NORMAL POSITION.
ON START SIGNAL, START RF AT 25% FLOW, THEN START SF AT 25% FLOW. OPEN D1 AND D3 TO MINIMUM POSITION. INCREASE FANVOLUMES UNTIL DUCT SP SET POINT IS REACHED 250 PA (1 IN). CONTROL SAT BY MODULATION OF COOLING AND HEATING VALVES INSEQUENCE. MAINTAIN SAT AS HIGH AS POSSIBLE (IN COOLING MODE) OR AS LOW AS POSSIBLE (IN HEATING MODE) TO SATISFYSPACE. WHEN DUCT SP INCREASE BEYOND SET POINT, REDUCE SF VOLUME TO ACHIEVE SET POINT. REDUCE RF VOLUME TOACHIEVE RA PLENUM PRESSURE OF 25 PA (0.1 IN). RESET SAT UPWARD IN RESPONSE TO DROP IN RAT (COOLING MODE) ANDDOWNWARD IN RESPONSE TO RISE IN RAT (IN HEATING MODE) WHEN FREE COOLING POTENTIAL EXISTS, MODULATE D1, D2 AND D3 INSEQUENCE TO MAINTAIN MAT. SENSE RARH AND MODULATE STEAM VALVE TO MAINTAIN THE FOLLOWING:
OAT RARH0 °C 15%24 °C 55%
ON SENSING HIGH OR LOW LIMIT TEMPERATURES, ALARM BAS AND SHUT DOWN SYSTEM. ON FIRE SIGNAL, SHUT DOWN SYSTEM.
A5AI
C
ELECTRIC HEATING COIL
TM-0.2
MECHANICALSCHEDULES
16-1121-000
THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS
285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000
SHEET NUMBER
TITLEApproved
Checked
Drawn
Job Number
ISSUE CHART
15 234
A
D
B
C
KEYPLAN
PROJECT
15 234
A
D
B
C
UTIAS RESEARCH LABSP049-16-138
672 Dupont Street, Suite 500Toronto, Ontario
Canada M6G 1Z6t 416.971.6060f 416.971.6765
www.perkinswill.com
MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01
2 3 4
A
B
145A
WEST OFFICE145C
EAST OFFICE145B
-2'-0"
EXIS
T.TA
BLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
4FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
1
ROBOTICS LAB
0"
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
10/12
20/1028/12 20/10
10/12
9/6 - B625 CFM
36/16
PROVIDE 24/8TRANSFER AIRDUCT
OPEN ENDED DUCTAT HIGH LEVEL
36/16
2"Ø
GAS
COMBUSTION AIR INTAKEAND EXHAUST FLUE UPTHROUGH ROOF
PROVIDE GAS FIRED HEATER IH-1 MOUNTED FROM CEILING18" NORTH OF GARAGE DOOR TRACKS AT 45° ANGLE
HEATER AND ALL ASSOCIATED WORK TO BE LISTED ASSEPARATE IDENTIFIED PRICE.
2"Ø GAS DOWNTHROUGH ROOF
PROVIDE ROOF TOP UNIT TO BEMOUNTED ON ROOF OF ROOM 144(REFER TO STRUCTURAL DRAWINGS)RTU-145-01, COMPLETE WITH 24" SIDEDISCHARGE CURB
2"Ø GAS
2"Ø GAS ON ROOF
(TYPICAL OF 2)
FD
3"Ø
8"Ø - 'A'225 CFM
10"Ø - 'A'400 CFM
EXIS
TING
GAS
LINE
ON
ROOF
2"Ø GASCONNECT TO EXISTINGGAS MAIN ON ROOF
8"Ø - 'A'225 CFM
10"Ø - 'A'400 CFM
PROVIDE 24/8TRANSFER AIRDUCT
1 1/2"Ø
1 1/2"
Ø
9/6 - 'B'625 CFM
(TYPICAL OF 4)
36/16 36/16
DUCTWORK ON ROOF
DUCTWORK DN THROUGH ROOF
BD 10"Ø
BD 8"Ø
10/12
10/1210/12
BD
8"Ø
10/12
BD
10"Ø
10/12
1 2 3 4
A
B
10/10 14/10 10/1014/10
20/14
22/22
REMOVE EXISTINGCEILING FAN
ROOF MOUNTEDCONDENSING UNITTO BE REMOVED
REMOVE EXISTING SPLIT D/X A/CUNIT IN ITS ENTIRETY INCLUDING,ELECTRIC DUCT HEATER ANDCONDENSATE PUMP AND PIPING
REMOVE ROOF MOUNTEDEXHAUST FAN IN IT'SENTIRETY INCLUDING ALLCONTROLS
REMOVE EXISTING ROOF MOUNTEDEXHAUST FAN IN IT'S ENTIRETYINCLUDING ALL CONTROLS
REMOVE EXISTING BASEBOARDHEATER IN IT'S ENTIRETYINCLUDING ALL CONTROLS
REMOVE EXISTING ELECTRIC UNITHEATER IN IT'S ENTIRETYINCLUDING ALL CONTROLS
REMOVE EXISTING EXHAUSTFAN, DAMPER AND DUCTWORKIN IT'S ENTIRETY INCLUDING ALLCONTROLS
REMOVE EXISTINGWALL MOUNTEDA/C UNIT
REMOVE HVAC CONTROLSREFER TO ELECTRICAL
REMOVE EXISTING BASEBOARDHEATER IN IT'S ENTIRETYINCLUDING ALL CONTROLS
REMOVE EXISTING EXHAUSTFAN, DAMPER AND DUCTWORKIN IT'S ENTIRETY INCLUDING ALLCONTROLS
EXIS
TING
GAS
LINE
ON
ROOF
TM-1.6
'ROBOTICS RESEARCHLAB' FLOOR PLAN
DEMOLITION AND NEWLAYOUT - HVAC
1/4" = 1'-0"PROPOSED CONSTRUCTION PLAN - ROBOTICS LAB
16-1121-000
THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS
285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000
SHEET NUMBER
TITLEApproved
Checked
Drawn
Job Number
ISSUE CHART
15 234
A
D
B
C
KEYPLAN
PROJECT
15 234
A
D
B
C
UTIAS RESEARCH LABSP049-16-138
672 Dupont Street, Suite 500Toronto, Ontario
Canada M6G 1Z6t 416.971.6060f 416.971.6765
www.perkinswill.com
MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01
1/4" = 1'-0"DEMOLITION PLAN - ROBOTIC RESEARCH LAB
2 3 4
A
B
145A
WEST OFFICE145C
EAST OFFICE145B
-2'-0"
EXIS
T.TA
BLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
4FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
1
ROBOTICS LAB
0"
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
EXIST.TABLE
5FT
REINSTALL RELOCATED AIR COMPRESSORC/W 1" COMPRESSED AIR PIPING AND 1/4TURN SHUT OFF VALVE WITH FEMALEQUICK CONNECT, PROVIDE 100' OF COILEDCOMPRESSED AIR TUBING
NON-FREEZEHOSE BIBB HB-2
SINK S-1
CTE
FLOORDRAIN
SAN
2"Ø PUMPED SANITARYDRAIN TO CONNECT TOEXISTING SERVICE INADJACENT BUILDING
3/4"Ø DCW
4"Ø
3/4"Ø DCW AND DHWDOWN TO S-1.
EXISTING SPRINKLERSAND ASSOCIATED PIPINGTO REMAIN. (TYPICAL)
EXISTING FIRE HOSECABINET TO REMAIN.
EXISTING DCWPIPING TO REMAIN.(TYPICAL)
PD
2"Ø SANITARY TOCONNECT TO EXISTINGBELOW GRADE SANITARYPIPING.
CO
PD-1 & PD-2SUMP PUMPS.
60" (1500mm) DEEP BY 48" (1200mm) DIAMETER PREFABRICATED SANITARY DRAINAGE PIT COMPLETEWITH TRAFFIC RATED COVER TO BE INSTALLED INOPENING BY GEN. CONTRACTOR.PROVIDE EYE BOLTON BEAM ABOVE SUMP PIT.
CTE
FD
FD
3"Ø
CO4"ØSINK S-2
1"Ø DCW
3/4"Ø
DCW
3/4"Ø DCW AND DHWDOWN TO S-2.
EXIS
TING
GAS
LINE
ON
ROOF
PUMPCONTROLLER
NEW NON-FREEZEHOSE BIBB HB-2
CTE
FREEZE BRANCH PIPINGFOR DEMOLITION.
CO-ORDINATE SHUTDOWNWITH OWNER
CO
PROVIDE DOM. H.W.RE-CIRCULATION PUMPPP-1 BELOW SINK
PROVIDE DOM. H.W.RE-CIRCULATION PUMPPP-2 BELOW SINK
1/2"Ø
1/2"Ø
CAP
CTE
NEW 1"Ø DOM. H.W. PIPING TOCONNECT TO EXISTING PIPING.ROUTE PIPING THROUGHEXISTING WALL PENETRATION.
1 1/2"Ø
1 1/2"
Ø
3/4"Ø DHW3/4"Ø DHW
3/4"Ø
DHW
3/4"Ø
DHW
1"Ø DHW
1"Ø
DHW
1"Ø
DHW
1 2 3 4
A
B
HOSE BIBB TOBE REMOVED
REMOVE ANDRELOCATED AIRCOMPRESSOR
REMOVECOMPRESSEDAIR PIPING
EXISTING SPRINKLERSAND ASSOCIATED PIPINGTO REMAIN. (TYPICAL)
EXISTING FIRE HOSECABINET TO REMAIN.
REMOVE EXISTINGHOSE BIBB
EXISTING DCWPIPING TO REMAIN.(TYPICAL)
FD
3"Ø
EXIS
TING
GAS
LINE
ON
ROOF
1 1/2"Ø
REMOVE EXISTINGABANDONED DOM.H.W. PIPING
TM-1.7
'ROBOTICS RESEARCHLAB' FLOOR PLAN
DEMOLITION AND NEWLAYOUT - PD & FP
1/4" = 1'-0"PROPOSED CONSTRUCTION PLAN - ROBOTICS LAB
16-1121-000
THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS
285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000
SHEET NUMBER
TITLEApproved
Checked
Drawn
Job Number
ISSUE CHART
15 234
A
D
B
C
KEYPLAN
PROJECT
15 234
A
D
B
C
UTIAS RESEARCH LABSP049-16-138
672 Dupont Street, Suite 500Toronto, Ontario
Canada M6G 1Z6t 416.971.6060f 416.971.6765
www.perkinswill.com
MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01
1/4" = 1'-0"DEMOLITION PLAN - ROBOTIC RESEARCH LAB
12CL
A
REMOVE EXIST. TRANE UNIT INITS ENTIRETY INCLUDING ROOFMOUNTED CONDENSER,REFRIGERANT PIPING, ANDCONTROLS. PATCH AND MAKEGOOD ALL ROOF OPENINGS.
20/14
ST
CHWSCHWR
ST
CHWSCHWR
REMOVE EXISTINGEXHAUST FAN ANDALL ASSOCIATEDDUCTWORK ANDCONTROLS.
REMOVE EXISTINGEXHAUST CANOPYAND ASSOCIATEDDUCTWORK.
CHW
SCH
WR
EXISTINGTRANSFERAIR DUCTTO REMAIN.
REMOVE ALL EXISTING SUPPLYAIR DUCTWORK SERVED BYTRANE UNIT IN ITS ENTIRETYINCLUDING ALL SUPPORTSAND DIFFUSERS.
EXISTING STEAMPIPING T0 REMAIN
EXISTINGDUCTWORK TOREMAIN. (TYPICAL)
EXISTING CHILLEDWATER SUPPLY &RETURN TO REMAIN.
EXIST GAS LINE ON ROOF G
REMOVE AND RELOCATEEXISTING STEAMHEATER
BALANCER TOAUDIT AIR FLOW
REMOVE EXISTING DUCTWORKABOVE ROOF. PATCH AND MAKEGOOD ROOF OPENING.
REMOVE EXISTING ROOF MOUNTED FAN INIT'S ENTIRETY INCLUDING ALL CONTROLS.
FREEZE BRANCH PIPINGFOR DEMOLITION.
UAS DESIGN LAB(125D)
125D
EXIST. CORRIDOR
UAS DESIGN LAB(125)
125
Room125A
FOAM CUTTER
STORAGE
GROUP 11 GROUP 10 GROUP 09 GROUP 08 GROUP 07
GROU
P 02
NEW
CAN
OPY
HOOD
NEW IT125E
LB6 LB6
LB6LB6
LB5
LB5LB5
GROUP 5 GROUP 6
LB5
LB5
GROU
P 01
GROU
P 03
LB5LB5LB5LB5LB5
LB5
LB5
LB5
LB5
GROU
P 15
GROU
P 14
GROU
P 13
GROU
P 12
LB6A
LASE
R /3D
PRIN
TER
LB4
GROU
P 04
LB5
LB5
LB5
LB5
LB5
LB5
LB5
LB5
LB5
LB5
EPOXYFLOORING W/COVE BASES
EPOXY FLOORINGW/ COVE BASES
12
PROVIDE 24/12TRANSFER AIRDUCT
ST
CHWSCHWR
ST
CHWSCHWR
16"Ø
14"Ø
18/12
22/12
22/12
18/12
12/12
PROVIDE RETURN AIR EXHAUSTDN TO 9'-0" AFF C/W DUCTMOUNTED RETURN AIR GRILLE
18/10
8/12
VALVE AND CAPEXISTING CHWS&R
EXISTINGTRANSFERAIR DUCTTO REMAIN.
CTE
CAP
CAP
16/8
10"Ø 10"Ø
PROVIDE EXHAUST DN TO 9'-0" AFF C/WFLEX DUCT CONNECTION TO 3D PRINTER
PROVIDE 12/12TRANSFER AIRDUCT (TYP OF 2)
14"Ø
8"Ø - 'A'380 CFM
22/12
6.5 KW ELECTRICHEATING COIL EHC-1ENSURE MINIMUM 12" OFSTRAIGHT DUCT BOTHUPSTREAM ANDDOWNSTREAM OF COIL
12/12 - C-
12/12 - C-
24/12 - C-
PROVIDE 24/12TRANSFER AIRDUCT
24/12 - C-
(TYP. 5)
10"Ø - 'A'410 CFM(TYP. 3)
EXISTING STEAMPIPING T0 REMAIN
EXISTINGDUCTWORK TOREMAIN. (TYPICAL)
NEW ROOF TOP UNIT RTU-125-01TO BE MOUNTED ON 24" CURB.
EXISTING CHILLEDWATER SUPPLY &RETURN TO REMAIN.
PROVIDE NEW48/24 RETURN AIRCANOPY FOR HEATCOLLECTIONBALANCED TO 1230CFM. CANOPY TOMATCH EXISTING.
12/8
12/8
10/10 - D0 CFM
BD BD
BD
BD
48/24 - E1100 CFM
CTE
400CFM
400CFM
8"Ø - ABALANCE TO AIR FLOWFROM REMOVED DIFFUSER
SLOP
E UP
SLOP
E UP
SLOP
E UP
SLOP
E UP
EXIST GAS LINE ON ROOF GCTE
2" GAS, CONNECTTO MAU-125-01
RELOCATED EXISTING STEAMHEATER. RECONNECT TO EXISTINGSTEAM AND CONDENSATE PIPING
CTE
16/18
ALL WORK ASSOCIATED WITHNEW I.T. CLOSET TO BELISTED AS SEPARATEIDENTIFIED PRICE.
PROVIDE DISPOSABLECARTRIDGE CARBON FILTERCAMFIL OPRCC-24012/2185-0
28/24
18/10
BD
28/24
16/18
22/12
22/12 16/18
BD
16/8
BD
BD
BD
BD
8"Ø
8"Ø
12/12BD
8"Ø
8"Ø
BD
22/12
BD
BD
BD
10"Ø
10"Ø
BD
8"Ø
BD10"Ø
8/12
BD
8"Ø
10/10 - D0 CFM
UAS DESIGN LAB(125D)
125D
EXIST. CORRIDOR
UAS DESIGN LAB(125)
125
Room125A
FOAM CUTTER
STORAGE
GROUP 11 GROUP 10 GROUP 09 GROUP 08 GROUP 07
GROU
P 02
NEW
CAN
OPY
HOOD
NEW IT125E
LB6 LB6
LB6LB6
LB5
LB5LB5
GROUP 5 GROUP 6
LB5
LB5
GROU
P 01
GROU
P 03
LB5LB5LB5LB5LB5
LB5
LB5
LB5
LB5
GROU
P 15
GROU
P 14
GROU
P 13
GROU
P 12
LB6A
LASE
R /3D
PRIN
TER
LB4
GROU
P 04
LB5
LB5
LB5
LB5
LB5
LB5
LB5
LB5
LB5
LB5
EPOXYFLOORING W/COVE BASES
EPOXY FLOORINGW/ COVE BASES
12
SINK S-1
SINK S-1
CA
SP SP
CA
3/4" CA
RELOCATEDCOMPRESSEDAIR FILTER
200' (1/2") COMP.AIR TUBING TO BETURNED OVER TOOWNER
1/2"Ø COMPRESSEDAIR PROTOCOLSTATION.(TYPICAL)
1/2" CA
1/2" CA
CTE
CTE
4"Ø
SAN
C0
NEW UPRIGHTSPRINKLER HEAD(TYP OF 6)
NN
N N
N N
4"Ø SAN
CTE
3/4"Ø DCW ANDDHW DOWN TO S-1.
EXISTING SPRINKLERMAIN T0 REMAINEXISTING COMPRESSED
AIR MAIN T0 REMAIN
CTE
3/4"Ø
1"Ø
3/4"Ø
EXISTING FIREEXTINGUISHERT0 REMAIN
N N
N N
N N N N
N N
N N
N N N NN
N
N N
N
1/2"Ø COMPRESSED AIRPROTOCOL STATION(TYPICAL)
ORDINARY HAZARD GROUP II - 0.2 GPM / 2000 SQ. FT.
N
N
N
N
ALL WORK ASSOCIATED WITHNEW I.T. CLOSET TO BELISTED AS SEPARATEIDENTIFIED PRICE.
CTE
CTE1/2"
1/2" CBV
2 1/2"Ø
2"Ø
EXISTING DOM.H.W. HEATERSTO REMAIN
EXISTING FIREHOSE CABINETT0 REMAIN
12CL
A
CA
SP SP
CA CA
COMP. AIR TUBINGTO BE REMOVEDAND TURNED OVERTO OWNER.
EXISTING COMP. AIR FILTER TOBE REMOVED AND RELOCATED
REMOVE EXISTING FLOORDRAIN AND CUT BACKEXISTING SANITARY PIPING
R
R R
R R
REMOVE EXISTINGSPRINKLER HEAD(TYP OF 6)
R
EXISTING SPRINKLERMAIN T0 REMAINEXISTING COMPRESSED
AIR MAIN T0 REMAIN
4"Ø
SAN
1"Ø
FREEZE BRANCH PIPINGFOR DEMOLITION.
CO-ORDINATE SHUTDOWNWITH OWNER
CO
EXISTING FIREEXTINGUISHERT0 REMAIN
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
REMOVE EXISTING CONDENSATEDRAINAGE PIPING IN IT'SENTIRETY .PATCH AND MAKEGOOD FLOOR OPENING.
2 1/2"Ø
2"Ø
EXISTING DOM.H.W. HEATERSTO REMAIN
EXISTING FIREHOSE CABINETT0 REMAIN
TM-1.0
'UAS DESIGN LAB'FLOOR PLAN DEMOLITION
& NEW LAYOUT - HVAC & PDFP
1/4" = 1'-0"DEMOLITION PLAN - ROOM 125 - HVAC
1/4" = 1'-0"CONSTRUCTION PLAN - ROOM 125 - HVAC
16-1121-000
THE MITCHELL PARTNERSHIP INC.CONSULTING ENGINEERS
285 YORKLAND BLVD, TORONTO,ONTARIO IM2J1S5 416.499.8000
SHEET NUMBER
TITLEApproved
Checked
Drawn
Job Number
ISSUE CHART
15 234
A
D
B
C
KEYPLAN
PROJECT
15 234
A
D
B
C
UTIAS RESEARCH LABSP049-16-138
672 Dupont Street, Suite 500Toronto, Ontario
Canada M6G 1Z6t 416.971.6060f 416.971.6765
www.perkinswill.com
MARK ISSUE DATE1 ISSUED FOR SD COSTING 2017-01-112 ISSUED FOR CD COSTING 2017-03-133 ISSUED FOR PERMIT 2017-04-214 ISSUED FOR TENDER 2017-05-01
1/4" = 1'-0"DEMOLITION PLAN - ROOM 125 - PD+FP
1/4" = 1'-0"CONSTRUCTION PLAN - ROOM 125 - PD+FP