    4.1

    Chapter 4: Load Tracing

    4.1 Load Tracing

    During the initial stages of a project, the designer makes assumptions regarding

    the way loads (forces) are transferred through the structure to the foundation

    (ground). These loads (forces) travel along load paths.

    The analysis method is known as load tracing.

    Definition: Load tracinginvolves the systematic process of determining loads and

    support reactions of individual structural members and how these loads aretransferred to other structural elements.

    Simple determinate structures are analyzed using the following.

    Free-body diagrams (FBDs).

    Basic equations of equilibrium.

    The process starts at the top (with the uppermost roof element), tracing theloads down through the structure to the foundation.

    Load PathsThe economy and efficiency of the structure is improved by the following.

    Minimizing the load path to the foundation.

    Involving fewer structural elements. Using the unique and inherent strengths of the materials (e.g. tension in steel,

    compression in concrete)

    Tributary Area

    Loads uniformly distributed over an area of roof or floor are assigned to individualmembers (rafters, joists, beams, girders) based on the concept of tributary area.

    This concept typically considers the tributary areathat a member must supportas being halfway between the adjacent similar members.

    Consider the wood floor framingsystem shown at the right with auniform load over the entire deck

    area of 50 psf. Each beam has a span length of 16.

  • 7/23/2019 CN Chap04 - Load Tracing

    2/25

    4.2

    Beams A and DTributary width for edge Beam A = half the distance between A and B.

    The tributary width for edge Beam A = 2.

    Similarly, the tributary width for edge Beam D = 2.

    Beams B and C

    Tributary width for interior Beam B = half the distance between A and B plus halfthe distance between B and C. Tributary width for interior Beam B = 2 + 2 = 4

    Similarly, the tributary width for interior Beam C = 4.

    Beam load = distributed load (psf) times the tributary width. The load on Beams A and D:

    wA = wD= 50 psf x 2 = 100 lb/ft

    The load on Beams B and C:

    wB = wC= 50 psf x 4 = 200 lb/ft

    Framing Design Criteria: Direction of Span

    Architectural character Exposed structural framing can contribute to the architectural expression of

    buildings.

    Differences in the depth of the structural elements can help define individualstructural bays of a building (e.g. short/shallow joists loading long/deep beams).

    Structural efficiency and economyConsiderations for structural efficiency and economy should include the following.

    The appropriateness of materials (e.g. wood, steel, concrete) selected for thestructural system.

    The span capacity and intermediate supports.

    The availability of material and skilled labor locally.

    Standard sections and repetitive spacing of uniform members are generallymore economical.

  • 7/23/2019 CN Chap04 - Load Tracing

    3/25

    4.3

    Mechanical and electrical system requirementsThe location and direction of mechanical systems should be coordinated with the

    intended structural system. Layering the structural system provides space for ducts and pipes to cross

    structural members, eliminating the need to cut openings in the beams.

    Flush or butt framing saves space in situations where it is desirable ornecessary to limit floor-to-floor dimensions.

    Openings for stairs and vertical penetrationsMost framing systems accommodate openings.

    It is generally economical to make openings parallel to the principal spanningdirection.

    If openings are not parallel, additional headers and connections create pointloads on members that would otherwise be designed for light, uniform loads,

    increasing their size.

    Construction and Load Paths: Pitched Roof Systems

    Figures 4.8 to 4.11 (pp. 200 - 201 of the textbook) illustrate the construction andload paths of typical pitched roof systems.

    Single-level framing Construction: Single-level framing construction is a common roof system for

    residential structures.

    - The single-level framing systemconsists of sheathing (plywood, otherstructural panels, or boards), roofrafters, ridge board, and ceiling

    joists.

    - The roof rafters, ridge board, andceiling joists combine to form a simpletruss spanning between bearing walls.

    Load path

    - Loads on the roof are initially supported by the sheathing.

    - The sheathing transfers the loads to

    the roof rafters.

    - The roof rafters transfer the loadsto the ceiling joists and to the bearing

    walls that support the trusses.

  • 7/23/2019 CN Chap04 - Load Tracing

    4/25

    4.4

    Double-level framing Construction: Double-level framing construction is another common roof framing

    system.- The double-level framing system consists

    of decking or sheathing (plywood, other

    structural panels, or boards), rafterbeams, and a ridge beam.

    - The rafter beams are supported at one

    end by the ridge beam (usually at thepeak of the roof) and supported at the

    other end by a bearing wall or by aheader beam.

    - The ridge beam is supported at each end by a column or by a bearing wall.

    Load path- Loads on the roof are initially supported by the decking or sheathing.

    - The decking or sheathing transfers the loads to the rafter beams.

    - The rafter beams transfer the loadsto the ridge beam at one end and to abearing wall or header beam at the

    other end.

    - The ridge beam transfers the loads to the supporting column or bearing wall.

    Notice that each level of the structural framing spans in a perpendicular directionto the next layer.

    The sheathing is perpendicular to rafters.

    The rafters are perpendicular to ridge beam and bearing walls.

    Three-level framing Construction: A third method makes use of heavier roof beams (rather than

    roof rafters or rafter beams).

    - The three-level framing systemconsists of decking, purlins, roofbeams, and a ridge beam.

    - The center-to-center spacing betweenthe roof beams ranges from 4 to 12(compared to 16 to 24 for roof

    rafters or rafter beams).

  • 7/23/2019 CN Chap04 - Load Tracing

    5/25

    4.5

    - The ridge beam is supported at each end by a column or by a bearing wall.

    - The purlins, spaced 1-6 to 4-0 on centers,are installed between the roof

    beams and support the decking.

    - The roof beams are supported by the ridge beam at one end (generally atthe peak of the roof) and supported by a bearing wall or header beam at the

    other end.

    Load path- Loads on the roof are initially supported by the decking.

    - The decking transfers the load to the purlins.

    - The purlins transfer the loads to theroof beams as concentrated loads.

    - The roof beams transmit the loads to the

    ridge beam at one end and a bearing wallor header beam at the other.

    - Columns or wall framing support the ends of the ridge beam.

    Load Paths: Wall Systems

    Figures 4.12 to 4.17 (pp. 202 - 203 of the textbook) illustrate the load paths forvarious types of loads acting on typical wall systems.

    Bearing wall

    A bearing wall is a vertical support system that transmits compressive forcesthrough the wall plane and to the foundation. Bearing wall systems can be constructed with masonry, cast-in-place concrete,

    pre-cast concrete panels, or studs (wood or light-gauge metal framing).

    Load Paths

    Uniform distributionUniform compressive forces acting along the length of the wall result in arelatively uniform distribution of force.

    Roof or floor joists (in typical light-wood framing) are closely spaced at 16 or24 on center.

    This regular, close spacing is assumed as a uniformly distributed load along the

    top of the wall.

    If there are no openings to disrupt the load path from the top to the bottom ofthe wall, a uniform load will result on top of the footing.

  • 7/23/2019 CN Chap04 - Load Tracing

    6/25

    4.6

    Non-uniform distributionConcentrated loads develop at the top of a wall when beams are spaced at wide

    intervals. The effect of the concentrated load

    spreads out as it moves down the wall.

    - Depending on the wall material, thearea of influence of the concentratedload is generally defined by an angleof 45 or 60.

    The resulting footing load will be non-

    uniform with the largest forces directlyunder the applied load.

    Disruptions in the structural continuity of the wall (e.g. a large window or dooropening) result in a non-uniform distribution of the compressive forces on the

    footing.

    Arching action over an openingOpenings in walls redirect the loads to either side of the opening. The natural stiffness of a concrete wall under compression produces an arching

    action that contributes to the lateral distribution of the loads.

    Openings in a stud wallStud walls (wood and metal) are generally idealized as monolithic walls (except for

    openings) when loaded uniformly from above. Openings require the use of headers (beams) that redirect the loads to either

    side of the opening.

    Concentrated loads from the header reactions must be supported by a buildup

    of studs resembling a column.

    Concentrated loads pilasters

    In special cases where the concentrated loads are very large, walls may need to bereinforced with pilasters directly under the beam.

    Pilasters are essentially columns and carry the large concentrated loads directlyto the footing.

    The walls between the pilasters are now considered as non-bearing walls exceptfor carrying their own weight.

  • 7/23/2019 CN Chap04 - Load Tracing

    7/25

    4.7

    Example Problems - Load Tracing

    Problems 4.1 and 4.2These homework problems will be worked together in class using the homeworkproblem worksheet available from the website.

  • 7/23/2019 CN Chap04 - Load Tracing

    8/25

    4.8

    Load Paths: Roof and Floor Systems

    Figures 4.18 to 4.23 (pp. 204 - 205 of the textbook) illustrate the load paths for

    common roof and floor systems.

    One-level framing

    Construction: Pre-cast hollow-coreconcrete planks or heavy timber-plankdecking is used to span closely spacedbearing walls or beams.- This is not a common framing system.

    - Spacing of the supports (the distance between the bearing walls) is based onthe span capability of the concrete planks or timber decking.

    Load path- Loads acting on the concrete planks or

    timber-plank decking are transmitteddirectly to the bearing walls.

    Two-level framing Construction: Two-level framing is a very common type of floor system.

    - The two-level framing consists of decking with closely spaced beams (called

    joists) to support the deck.

    - The decking is laid perpendicular to thebeam (joist) framing.

    - Efficient structural sections of wood orsteel beams (joists) allow relatively long

    spans between bearing walls.

    - Lighter deck materials such as plywoodpanels can be used to span between the

    closely spaced beams (joists).

    - Span (distances) between bearing walls and beams affect the size andspacing of the joists.

    Load path- Loads on the decking are transmitted to

    beams (joists).

    - The beams transmit loads to the bearingwalls.

  • 7/23/2019 CN Chap04 - Load Tracing

    9/25

    4.9

    Notice, again, that each level of structural framing spans in a perpendiculardirection to the next layer.

    The decking is perpendicular to the beams/joists, and the beams/joists areperpendicular to the bearing walls.

    Three-level framing Construction: This type of construction is used for buildings requiring largeopen floor areas.- The three-level framing consists of

    decking or sheathing, joists, beams,

    and girders, trusses, columns, orbearing walls.

    - Floor space is free of bearing walls

    and with a minimum number of

    columns.- Construction typically relies on the

    long span capacity of joists supportedby trusses or girders.

    - The spacing of the primary structure and the layering of the secondary

    structural members establish regular bays that subdivide the space.

    Load path- Loads on the decking or sheathing are supported by the joists.

    - The decking transfers the loads tothe joists.

    - The joists transfer the loads to thebeams.

    - The beams transfer the loads to

    girders or trusses.

    - The girders or trusses transfer the loads to columns or bearing walls.

    Each level of framing is arranged perpendicular to the level directly above it.

  • 7/23/2019 CN Chap04 - Load Tracing

    10/25

    4.10

    Example Problems - Load Tracing

    Problems 4.3 and 4,.4These homework problems will be worked together in class using the homeworkproblem worksheet available from the website.

  • 7/23/2019 CN Chap04 - Load Tracing

    11/25

    4.11

    Load Paths: Foundation Systems

    Figures 4.24 to 4.29 (pp. 206 - 207 of the textbook) illustrate common foundation

    systems.

    The foundation system for a particular structure or building depends on the

    following. The use and size of the structure.

    Subsurface soil (geology) conditions at the site.

    - A geologist or soils engineer will likely be part of the project team.

    The cost of the foundation system to be used.

    A large building with heavy loads can often be supported on relatively inexpensiveshallow footings if the subsurface soils are dense and stable.

    A large building constructed at a site with soft soils, compressive clay soil, orpoorly graded soils (e.g. beach sand or sugar sand) may require expensive

    foundations or soil stabilization. One such stabilization technique might be over-excavation and refill with

    borrow material (such as stone) and the use of geo-textiles (geo-grids).

    - This technique requires the removal, hauling, and dumping of poor materials.

    - This technique requires the purchase, hauling, spreading and compaction ofborrow materials.

    - This technique requires the purchase, handling, and placing of the geo-textile materials.

    Chemical stabilization (using lime or cement) may provide a remedy for shallowfoundations.

    Pile or caisson foundations may be necessary in areas where poor soils are

    present for significant depths below the ground surface.

    Foundations are generally divided into two major categories: shallow foundations

    and deep foundations.

    Shallow foundations Shallow foundations essentially obtain their support on soil or rock.

    - Soils with moderate to high soil-bearing capacities can provide adequatesupport for most construction.

    - Rock located just below the bottom of the structure can provide support in

    direct bearing.

  • 7/23/2019 CN Chap04 - Load Tracing

    12/25

    4.12

    - Rock located just below the structure may offer challenges and increase thecosts of extending underground utilities.

    Vertical loads are transmitted from walls or columns to a footing.- The footing then distributes the load over a large enough area so that the

    allowable load-carrying capacity of the soil is not exceeded and settlement

    (including differential settlement) is minimized.

    Shallow foundations are of three basic types.

    1. Spread footingssupport an individual column. The spread footing is usually square or circular in plan.

    The spread footing is generally simple and

    economical for moderate to high soil-bearingcapacities.- The footings are generally shallow.

    - Simple wood framed forms are used.

    - Pedestals and footings are reinforcedwith little to no steel.

    The purpose of this footing is to distributethe load over a large area of soil.

    2. Wall footings (continuous strip footings) support bearing walls. Continuous strip footings are one of the most common types of footings used

    to support a bearing wall.

    - For example, a continuous strip footing iscommonly used to support a concrete

    block foundation wall for a typicalresidential structure.

    - Continuous strip footings usually support

    uniform bearing wall loads.

    The continuous strip footing is simple andeconomical for moderate to high soil-bearing

    capacities.- The footings are generally shallow.

    - Simple wood framed forms or metal forms are used.

    - Pedestals and footings are reinforced with little to no steel.

    The wall footing width remains constant throughout its length if no largeconcentrated loads occur.

  • 7/23/2019 CN Chap04 - Load Tracing

    13/25

    4.13

    3. Mat or raft foundationscover the entire plan area of the building. Mat foundations are used when soil

    bearing is relatively low or whereloads are heavy in relation to soil-bearing capacities.

    This foundation type is essentially onelarge footing under the entire buildingand the load is distributed over the

    entire mat.

    A mat foundation is referred to as a raft foundationwhen it is placed deepenough in the soil that the soil removed during excavation equals most or all

    of the buildings weight.

    Deep foundations

    Deep foundations are generally piles, piers, or caissons installed in a variety ofways.

    The function of a deep foundation is to carry building loads beneath a layer ofunsatisfactory soil to a satisfactory bearing stratum.

    Building loads are distributed to the soil in contact with the surface area of the

    pile through skin friction (friction piles), in direct end-bearing (bearing piles) atthe bottom of the pile on a sound stratum of earth or rock, or a combination ofskin friction and direct bearing.

    Deep foundations are of three basic types.1. Pile foundations are the most common deep-foundation system.

    Piles are driven into the earth by pile-driving hammers powered with drophammers, compressed air, or diesel engines.

    Friction piles: Timber piles arenormally used as friction piles;however, timber piles can rot if the

    water table fluctuates.

    Bearing piles: Concrete and steel pilesare generally used as bearing piles.

    - A combination of steel andconcrete is used when bearing pilesmust be driven to great depths to

    reach suitable bearing.

  • 7/23/2019 CN Chap04 - Load Tracing

    14/25

    4.14

    - Hollow steel casings are driven into the ground to a predeterminedbearing point, reinforcing steel (cages) may be placed within the casing,

    and then the casings are filled with concrete. As each hollow steel casing section (typically 20 long) is driven into

    the ground, additional sections are welded to the end and then driven.

    2. Pile capsare used when individual building columns are supported by more than asingle pile.

    The thick reinforced concrete cap that is

    poured on top of a pile group distributesthe column load to all the piles in the

    group.

    3. Grade beamsare used to transfer the loads from a building wall to a group ofpiles.

    Piles or piers supporting bearing wallsare generally spaced at regularintervals and are connected with a

    continuous reinforced concrete gradebeam.

  • 7/23/2019 CN Chap04 - Load Tracing

    15/25

    4.15

    Example Problems - Load Tracing

    Problems 4.5 and 4.6These homework problems will be worked together in class using the homeworkproblem worksheet available from the website.

  • 7/23/2019 CN Chap04 - Load Tracing

    16/25

    4.16

    4.2 Lateral Stability Load Tracing

    Geometric stability refers to a configuration property that preserves the

    geometry of a structure. Geometric stability is achieved by the way the structural elements are

    strategically arranged.

    Geometric stability is achieved by the way the structural elements interact toresist loads.

    All building structures require a bracing system. A bracing system provides the stability for the entire structure.

    The type and location of the bracing system directly affects the organizational

    plan of the building and its final appearance.

    The primary concerns in the design of any structure include the following.

    To provide sufficient stability to resist collapse.

    To prevent excessive deformation (deflection and racking), which may result in

    the cracking of brittle surfaces and glass.

    To be adequately stiffened against gravity-induced loads.

    To be stable against horizontal forces (e.g. wind and seismic forces) coming

    from two perpendicular directions.

    The use of horizontal diaphragms (i.e. roof and floor planes) is the most common

    system to resist lateral loads in wood-frame buildings. The roof sheathing can be designed economically to serve as both a vertical-

    load and lateral-load carrying element.

    Ways to achieve stabilityThere are several ways of achieving stability and counteracting the rackingof theframe under vertical and/or horizontal loading.

    Each solution has architectural implications.

    The selection of the bracing system must be made for reasons beyond being themost efficient structurally.- The most efficient systems may interfere with openings (such as doors,

    windows, and internal passages).

    Figures 4.37 to 4.42, 4.44, 4.46 - 4.48 (pp. 234 - 237 of the textbook) illustrate

    common ways of achieving stability.

  • 7/23/2019 CN Chap04 - Load Tracing

    17/25

    4.17

    Diagonal Truss MemberA simple way of providing lateral stability is to introduce a simple diagonal member

    connecting two diagonally opposite corners. In effect, a truss is created, and stability is

    achieved through triangulation.

    - If a single diagonal member is used, it mustbe capable of resisting both tension andcompression forces, since lateral loads areassumed to occur in either direction.

    - The members need to be sized similarly to truss members in compression.

    Members subjected to compression have a tendency to buckle.

    X-Bracing Members

    Another strategy involves the use of two cross-bracing members with smaller

    cross-sectional areas. These X-braces are also known as diagonal

    tension counters(discussed in Section 3.3).- Only one counter is effective in resisting

    the directional lateral load.

    Knee-BracingA commonly used arrangement in carports and elevated wood decks is knee-bracing. This stiffening method triangulates the beam-column connection to provide a

    degree of rigidity at the joint.- The larger the knee-braces are, the more

    effective their ability to control racking.

    - Bracing is usually placed as close to 45 aspossible but will sometimes range between

    30 and 60. Knee-braces develop tension and compression

    forces (like truss members) depending on thelateral force direction.

    Some movement will still occur because of the pin connections at the base ofthe columns.

  • 7/23/2019 CN Chap04 - Load Tracing

    18/25

    4.18

    Gusset PlatesLarge gusset plates at each beam-column connection can also provide the required

    rigidity to stabilize the frame. Some movement will occur because of the pin

    connections at the base of the columns.

    Modifying the base into a more rigid connectioncan add to the rigidity of the frame.- Rigid connections induce bending moments in

    the beams and columns.

    Rigid Base ConditionColumns placed at some depth into the ground and set in concrete can provide arigid base condition.

    Resistance to lateral loads comes through the

    columns acting as large vertical cantilevers. The horizontal beam transfers loads between

    the columns.

    Combination Knee-Brace and Rigid Column BaseKnee-braces may be used in conjunction with rigid column bases. All connections of the frame are rigid.

    The lateral loads are resisted through thebending resistance offered by the beam andcolumns.

    The lateral displacements are less than thethree previous examples (i.e. knee bracing,

    gusset plates, and rigid base).

    Rigid Beam/Column Joints

    Connections may be made so that the beam and column form a rigid type of

    connection. Steel-framed structures: The connections

    may be made using bolts, welds, andstiffener plates in specific arrangements.

  • 7/23/2019 CN Chap04 - Load Tracing

    19/25

    4.19

    Concrete structures: A rigid connection maybe formed using reinforcing steel and

    monolithically cast beams and columns.

    Knee-Braced Structure with Roof TrussA truss supported on two pin-connected columns is unstable.

    Knee-braces provide stability forthe truss to develop resistance to

    racking.

    Shear wallsMany residential and small- to mid-scale commercial buildings depend on the walls

    (bearing and non-bearing) of the structure to develop the necessary resistance tolateral forces.

    This type of lateral restraint, referred

    to as a shearwall, depends on the verticalcantilever capacity of the wall.

    Commonly used materials for shear walls

    are concrete, concrete blocks, bricks,

    and wood sheathing products such asplywood, oriented strand board (OSB),and wafer boards.

  • 7/23/2019 CN Chap04 - Load Tracing

    20/25

    4.20

    Example Problems Lateral Stability

    Problem 4.9 (p. 249)

    Given: The frame with the lateral

    load shown.

    Find: The reaction forces at A andB, and all other member forces.

    Assume Ax= Bx

    Solution

    Find the reactions at the supports.

    FBD: Entire frame

    MA= 0 = - 1200 (16) + By(14)

    14 By= 1200 (16) = 19,200By= + 1371.4 lb

    By= 1371.4 lb

    MB= 0 = - 1200 (16) - Ay(14)14 Ay= - 1200 (16) = - 19,200

    Ay= - 1371.4 lb Ay= 1371.4 lb

    Fx= 0 = Ax+ Bx+ 1200 (Assume Ax= Bx)0 = Bx+ Bx+ 12002 Bx= - 1200

    Bx= - 600 Ax= Bx= 600 lb

    Find the forces acting on members AHG and FH.

    FBD: Member AHG

    MG= 0 = - 600 (16) + (1/ 2 ) HF (4)0 = - 600 (16) + 2.828 HF2.828 HF = 600 (16) = 9600

    HF = + 3394.6 lb

    HF = 3394.6 lb (T)

  • 7/23/2019 CN Chap04 - Load Tracing

    21/25

    4.21

    Fx= 0 = Gx+ (1/ 2 ) HF 600 + 12000 = Gx+ 0.707 (3394.6) 600 + 1200

    Gx= - 2400 + 600 1200 = - 3000

    Gx= 3000 lb on AHG

    Fy= 0 = Gy+ (1/ 2 ) HF - 1371.40 = Gy+ 0.707 (3394.6) 1371.4

    Gy= - 2400 + 1371.4 = - 1028.6

    Gy= 1028.6 lb on AHG

    Find the forces acting on members BCD and CE.

    FBD: Member BCD

    MD= 0 = - 600 (16) - (1/ 2

    ) CE (4)0 = - 600 (16) 2.828 CE

    2.828 CE = - 600 (16) = - 9600CE = - 3394.6

    CE = 3394.6 lb (C)

    Fx= 0 = Dx- (1/ 2 ) CE 600

    0 = Dx0.707 (- 3394.6) 600Dx= 0.707 (- 3394.6) + 600

    Dx= - 2400 + 600 = - 1800Dx= 1800 lb on BCD

    Fy= 0 = Dy+ (1/ 2 ) CE + 1371.4

    0 = Dy+ 0.707 (- 3394.6) + 1371.4Dy= - 0.707 (- 3394.6) - 1371.4Dy= + 2400 1371.4 = + 1028.6 lb

    Dy= 1028.6 lb on BCD

  • 7/23/2019 CN Chap04 - Load Tracing

    22/25

    4.22

    Multiple baysThe previous discussion of frame stability from lateral loads was limited to single-

    bay (panel) frames; however, most buildings contain multiple bays in the horizontaland vertical directions. The principles that apply to single-bay frames also hold true for multiple-bay

    frame structures. Often only one panel needs to be braced for the entire frame to be stabilized.

    - It is rarely necessary for every panel to be braced to achieve stability.

    Figure 4.50 (p. 238 of the textbook) illustrates the following common ways of

    achieving stability in structures with multiple horizontal bays.

    Shear walls, diagonal tension counters, and diagonal truss brace.

    Multistory and Multi-bay Structures

    Multistory and multi-bay structures also use the same bracing principles aspreviously discussed with some modifications.

    As the structures become taller, only certain types of bracing systems andmaterials of construction remain practical from a structural and/or economicstandpoint.- For example, knee-braces, although appropriate for smaller one- or two-

    story structures, are not nearly as effective for larger structures.

    The horizontal force component within the knee-brace acts on the column

    and produces a significant bending moment, which requires a larger

    column size. Larger diagonal braces that go across an entire panel from opposite diagonal

    points are found to be much more effective structurally.- Bracing techniques are generally limited to the exterior wall planes of the

    building to permit more flexibility for interior spaces.

    - Diagonals, X-bracing, and K-trussing on multistory frames essentially formvertical cantilever trusses that transmit lateral loads to the foundation.

    Reinforced concrete (or masonry) and braced steel framing used for stairwells

    and elevators are often used as part of the lateral force strategy. Bracing systems must be provided at each story level.

    Combinations of bracing, shear wall, and/or rigid frames are used in many buildings. Larger multi-story buildings contain utility/service cores, which include

    elevators, stairs, ducts, and plumbing chases.

  • 7/23/2019 CN Chap04 - Load Tracing

    23/25

    4.23

    - These utility cores are strategically placed to meet functional and structuralcriteria.

    - Because these cores are generally solid to meet fireproofing requirements,they can often function as excellent lateral resisting elements, in isolation oras part of a larger overall strategy.

    Figure 4.51 (p. 239 of the textbook) illustrates the following common ways ofachieving stability in multistory structures.

    X-bracing, eccentric braced frame, K-trussing, shear walls, and rigid frame.

    Three-Dimensional FramesBuildings are three-dimensional frameworks, as indicated in Figure 4.53 (p. 240 ofthe textbook).

    Each planar frame represents just one of several (or many) frames that

    constitute the structure. A fundamental requirement of geometric stability for a three-dimensional

    structure is its ability to resist loads from three orthogonal directions (i.e.vertically and both directions horizontally).

    A three-dimensional frame can be stabilized by use of bracing elements or

    shear walls in a limited number of panels in the vertical and horizontal planes.- In multistory structures, these bracing systems must be provided at each

    and every story level.

    The exterior walls of a building transfer the wind forces to the roof and floors,which in turn direct them to the lateral load resisting system (e.g. shear walls orbraced frames). In wood-framed buildings or buildings with wood roof and floor systems, the

    roof and floor sheathing is designed to connect to the supporting framingmembers to function as horizontal diaphragms capable of transferring lateralloads to the lateral load resisting system.

    In buildings with concrete roof and floor slabs, the slabs are designed to

    function as diaphragms.

    If the wood sheathing or reinforced concrete slab is designed to function as ahorizontal diaphragm for lateral forces in one direction, it probably can bedesigned to function as a diaphragm for forces applied in the other direction.

  • 7/23/2019 CN Chap04 - Load Tracing

    24/25

    4.24

    If the roof or floor sheathing is too light or flexible and unable to carry thediaphragm forces, the horizontal framework must be designed with bracing

    similar to braced walls or shear walls.- Horizontal bracing may consist of tension counters, trusses, or stiff panels

    in strategic locations (ref. Figure 4.53, p. 240 of the textbook).

    Bracing ConfigurationsOnce the roof plane (or floors) has been configured to function as a diaphragm, aminimum requirement for stabilizing the roof is three braced (or shear) walls thatare neither all parallel nor concurrent to a common point.

    The arrangement of the walls is crucial in resisting loads from multipledirections.- More than three braced (or shear) walls are usually provided increasing the

    structural stiffness of the framework in resisting lateral displacements.

    Braced (or shear) walls are located strategically throughout the structure tominimize the potential of torsional displacements and moments.

    - A common solution is to have two shear walls parallel to one another (areasonable distance apart) and a third wall (or perhaps more) perpendicularto the other two.

    - Figure 4.54 (p. 241 of the textbook) illustrates various shear wallarrangements some stable and others unstable.

    Multistory Structures

    In multistory structures, lateral loads (from wind and earthquake forces) aredistributed to each of the roof and floor (diaphragm) levels. At any given floor level, there must be an adequate number of braced (shear)

    walls to transfer the cumulative lateral forces from the diaphragms above.

    - Each story level is similar to the simple structures examined previously, inwhich the diaphragm load was transferred from the upper level (roof) to thelower level (ground).

    Multistory structures are generally braced with a minimum of four braced planes

    per story, with each wall being positioned to minimize torsional moments anddisplacements. Although it is often desirable to position the braced walls in the same position

    at each floor level, it is not always necessary.

    - The transfer of shear through any one level may be examined as an isolatedproblem.

  • 7/23/2019 CN Chap04 - Load Tracing

    25/25

    Example Problems - Lateral Stability/Diaphragms and Shear walls

    Problems 4.11 and 4.12These homework problems will be worked together in class using the homeworkproblem worksheet available from the website.