    University of Wisconsin - MadisonUtility Master Plan Status Report

    April 2005

  • 8/12/2019 City Presentation April 2005 SMT2

    2/52

    Current Campus Master Plan

  • 8/12/2019 City Presentation April 2005 SMT2

    3/52

    Summary of Existing Utilities

    Planning Criteria Load Management

    Load Projections

    Options for Exploring

    Agenda

  • 8/12/2019 City Presentation April 2005 SMT2

    4/52

    High Pressure Steam and Condensate

    Low Pressure Steam and Condensate Chilled Water

    Compressed Air

    Electric Power

    IT Systems Domestic Water

    Sanitary Sewer

    Storm Sewer

    Utilities Included

  • 8/12/2019 City Presentation April 2005 SMT2

    5/52

    Existing Campus Utility Services

    Steam and Condensate Piping Distribution Map

  • 8/12/2019 City Presentation April 2005 SMT2

    6/52

    Existing Campus Utility Services

    Chilled Water Piping Distribution Map

  • 8/12/2019 City Presentation April 2005 SMT2

    7/52

    Existing Campus Utility Services

    Compressed Air Piping Distribution Map

  • 8/12/2019 City Presentation April 2005 SMT2

    8/52

    Existing Campus Utility Services

    Electrical Distribution Map

  • 8/12/2019 City Presentation April 2005 SMT2

    9/52

    Existing Campus Utility Services

    Water Distribution MapAdditional pipingin Eagle Heights

  • 8/12/2019 City Presentation April 2005 SMT2

    10/52

    Sanitary Sewer Distribution MapAdditional piping

    in Eagle Heights

  • 8/12/2019 City Presentation April 2005 SMT2

    11/52

    Storm Sewer Distribution MapAdditional piping

    in Eagle Heights

  • 8/12/2019 City Presentation April 2005 SMT2

    12/52

    Existing Campus Utility Services

    Composite Utility Distribution

  • 8/12/2019 City Presentation April 2005 SMT2

    13/52

    System Type 70% Walkable Tunnel

    28% Box Conduit

    2% Direct Buried

    Age Distribution (over 25miles of piping)

    1% +80 Years 2% 60-80 Years

    8% 40-60 Years

    16% 20-40 Years

    22% 0-20 Years

    50% Unknown

    Steam and Condensate Overview

    C O

  • 8/12/2019 City Presentation April 2005 SMT2

    14/52

    System Type

    15% Walkable Tunnel 0% Box Conduit

    85% Direct Buried

    Age Distribution (over 8 miles of piping) 45% 20-40 Years

    55% 0-20 Years

    Chilled Water Overview

    Th l U ili U d

  • 8/12/2019 City Presentation April 2005 SMT2

    15/52

    Correct Deficiencies

    Upgrade Control Systems

    Alleviate Distribution Piping Bottlenecks

    Replace Aging Equipment

    Cleanup Charter Street site????

    Add capacity to accommodate future growth

    Add energy meters at all significant buildings

    Thermal Utility Upgrades

    Th l Utilit P d ti O i

  • 8/12/2019 City Presentation April 2005 SMT2

    16/52

    Walnut Street Plant 600,000 #/hr steam

    (heating for ~7,500 homes) 18,000 tons chilled water

    (cooling for ~9,000 homes)

    Charter Street Plant 800,000 #/hr steam

    (heating for ~9,000 homes)

    26,000 tons chilled water(cooling for ~13,000 homes)

    9 MWe ElectricProduction (power for~900 homes)

    Thermal Utility Production Overview

    Th l Utilit P d ti O i

  • 8/12/2019 City Presentation April 2005 SMT2

    17/52

    West CampusCogeneration Facility

    500,000 #/hr steam(heating for ~6,250 homes)

    20,000 tons chilled water(cooling for ~10,000 homes)

    150 MWe ElectricProduction (power for~15,000 homes) supplied toMadison area grid

    Thermal Utility Production Overview

    El t i l S b t ti O i

  • 8/12/2019 City Presentation April 2005 SMT2

    18/52

    East Campus Substation 14.0 MVA (~1,400 homes)

    West Campus Substation 14.0 MVA (~1,400 homes)

    Charter Street Substation 14.3 MVA (~1,400 homes)Walnut Street Substation 112 MVA (~11,200 homes)

    Randall Substation 7 MVA (~700 homes)

    Kohl Center Switching Stn 28.6 MVA (~2,900 homes)

    Athletic Off. Switching Stn 18.8 MVA (~1,900 homes)

    Total Capacity 208.7 MVA (~20,900 homes)

    20,000 homes 80,000 people or

    approximately the size of

    Janesville, WI

    1 MVA = million volt-amperes

    (Size of electrical facilities is listed in

    MVA, just as size of a storage tank

    might be listed in gallons.)

    Electrical Substation Overview

    El t i l Di t ib ti O i

  • 8/12/2019 City Presentation April 2005 SMT2

    19/52

    Installed in Ductbankand Manhole System

    ~230,000 circuit feet(~175 miles of wirewith 4 wires percircuit)

    Age Distribution 8% +40 Years

    44% 20-40 Years

    23% 0-20 Years 25% Undetermined

    Age

    Electrical Distribution Overview

    El t i l Di t ib ti U d

  • 8/12/2019 City Presentation April 2005 SMT2

    20/52

    Reinforce the system to improve

    reliability Recircuit/re-cable overloaded circuits

    Relocate cables from steam tunnels

    Separate instances where primary and

    backup feeders are in the same ductbankand manholes

    Improve system monitoring to mitigateoutages

    Add substation capacity forreliability/flexibility and cost control

    Electrical Distribution Upgrades

    IT/Si l O i

  • 8/12/2019 City Presentation April 2005 SMT2

    21/52

    Systems include: Computer networks

    Internet access Electronic file storage Email

    Installed in Ductbank andManhole System

    +180 Manholes +10 Miles of Underground

    Fiber Optic Ductbank +200 Building Service

    Entrances

    Age Distribution ~10% +20 Years ~90% 0-20 Years

    IT/Signal Overview

    IT/Si l U d

  • 8/12/2019 City Presentation April 2005 SMT2

    22/52

    Relocate cabling from steam tunnels to

    new ductbank locations 21stCentury Network

    Upgrade network speed to a 10-gigabytebackbone speed

    Upgrade security Reinforce the capacity of the three super

    nodes powering the network

    Add access points for wireless access

    IT/Signal Upgrades

    D ti W t O i

  • 8/12/2019 City Presentation April 2005 SMT2

    23/52

    System Summary 147,000 ft (~28 miles) of pipe

    ranging from to 24

    25 Manholes

    144 Hydrants 907 Water Valves

    Age Distribution 7% 80+100 years 55% 4080 years 19% 2040 years 19% 020 years

    Water Supply Sources City of Madison Village of Shorewood Hills Direct connection to City mains

    Water Usage 3,204,000 GPDAverage daily

    use 32,000 people served

    Domestic Water Overview

    Installation of water main and fire hydrant

    Domestic Water Upgrades

  • 8/12/2019 City Presentation April 2005 SMT2

    24/52

    Eliminate undersized mains

    Increase pressure in Eagle Heights

    Add isolation valves to high prioritybuildings

    Eliminate lines under buildings Replace obsolete piping materials

    Domestic Water Upgrades

    Sanitary Sewer Overview

  • 8/12/2019 City Presentation April 2005 SMT2

    25/52

    System Type/Summary 102,760 ft (~19 miles) of pipe

    Pipe size is 4 to 24 476 Manholes

    63% pumped - 12 pumpstations

    Wastewater flows to MMSD City of Madison Interceptors

    City of Madison Mains

    Age Distribution

    7% 80100+ years 50% 4080 years

    33% 2040 years

    10% 020 years

    Sanitary Sewer Overview

    Sanitary Sewer Manhole Installation

    Sanitary Sewer Upgrades

  • 8/12/2019 City Presentation April 2005 SMT2

    26/52

    Improve reliability

    Televise older sewers to quantifycondition

    Repair/replace older manholes

    Improve pump stations for more efficientand reliable operation

    Sanitary Sewer Upgrades

    Storm Sewer Overview

  • 8/12/2019 City Presentation April 2005 SMT2

    27/52

    System serves: Building roof drains

    Area drains Catch basins

    System Type/Summary 122,640 ft (~23 miles) of

    pipe ranging from 3 to 68

    777 Manholes Pipe types: Vitrified Clay,

    Reinforced Concrete,Ductile Iron, or PVC

    Age Distribution

    4% 80+100 years

    41% 4080 years

    32% 2040 years

    23% 020 years

    Storm Sewer Overview

    Storm sewer

    with manhole

    and catch

    basins on each

    end

    Outfall into

    Lake Mendota

    Storm Sewer Overview

  • 8/12/2019 City Presentation April 2005 SMT2

    28/52

    Storm Sewer Overview

    To ake Mendota

    To ake Monona

    790 Acres drainto Lake

    Mendota

    230 Acres drain toLake Monona

    Storm Sewer Upgrades

  • 8/12/2019 City Presentation April 2005 SMT2

    29/52

    Improve system reliability

    Upgrade undersized storm sewers -Chamberlin Hall

    Routine system maintenance - entiresystem

    Erosion and water quality control - entiresystem

    Storm Sewer Upgrades

    Storm Sewer Upgrades

  • 8/12/2019 City Presentation April 2005 SMT2

    30/52

    Techniques to improve quality of stormwater

    Rain Gardens

    Cisterns

    Water Quality Ponds

    Swales Green Roofs

    Pervious pavements

    Treatment units

    Reuse rain water for irrigation, etc.

    Storm Sewer Upgrades

    Planning Principles

  • 8/12/2019 City Presentation April 2005 SMT2

    31/52

    Create high level of reliability and redundancy

    Implement planned phase out of old equipment Maximize energy efficiency and minimize

    energy cost

    Minimize maintenance requirements Maintain flexibility for future technologies

    Coordinate with building/transportation plan

    Investigate alternative energy resources Plan for future technologies

    Planning Principles

    Load Management (Existing Buildings)

  • 8/12/2019 City Presentation April 2005 SMT2

    32/52

    Upgrade Boiler Controls (2-3%

    efficiency increase) Ongoing multiple year building energy

    conservation program through the

    Wisconsin Energy Initiative (WEI) The energy conservation program has

    spent approximately $29,500,000 onbuilding improvements

    Load Management (Existing Buildings)

    Load Management WEI Accomplishments

  • 8/12/2019 City Presentation April 2005 SMT2

    33/52

    Load Management

    WEI Accomplishments

    Energy audits performed for 12,000,000 SF

    Retrofitted lighting with newer lower wattage efficientfixtures

    Replaced 1000 electric motors with premiumefficiency motors

    Installed variable speed driven electric motors

    Installed 2000 ultra low water usage plumbingfixtures

    Replaced/repaired 2700 steam traps

    Upgraded controls (occupancy sensors, HVACenergy monitoring)

    Adding 8000 storm windows

    Load Management (New Buildings)

  • 8/12/2019 City Presentation April 2005 SMT2

    34/52

    Current State Building Requirements:

    Building Envelope thermal insulationrequirements exceeds ASHRAE EnergyStandard 90.1

    Selection of Mechanical Systems based

    on Life Cycle Cost Analysis Mandatory use of heat recovery

    Daylighting investigation

    Investigation into Photo Voltaic (PV) use

    Load Management (New Buildings)

    Load Management (New Buildings)

  • 8/12/2019 City Presentation April 2005 SMT2

    35/52

    Leadership in Energy and

    Environmental Design (LEED) Current State design specifications and

    criteria are equivalent to LEEDCertification standards

    Emphasis of LEED Sustainable site development

    Energy efficiency and atmospheric impact

    Water conservation Materials selection

    Indoor air quality (IAQ)

    Load Management (New Buildings)

    Utility Project Drivers

  • 8/12/2019 City Presentation April 2005 SMT2

    36/52

    Replace Obsolete Equipment due to:

    Age Condition

    Efficiency

    Capacity Needs Reduce energy consumption in buildings

    Add new capacity when required basedon load growth and distribution system

    Utility Project Drivers

    Utility Project Drivers

  • 8/12/2019 City Presentation April 2005 SMT2

    37/52

    Environmental Improvements

    Higher efficiency usually means loweremissions

    Evaluating fuel selection and changes intechnology to reduce emissions

    Improved boiler technologies

    Improved controls

    Utility Project Drivers

    Load Growth Projections (Heating)

  • 8/12/2019 City Presentation April 2005 SMT2

    38/52

    Load Growth Projections (Heating)

    Adequate Plant Heating Capacity

    Phase

    1

    Phase

    2

    Phase

    3

    TIMELINE

    STEAML

    OAD

    (LBS./HOUR)

    WALNUT STREET CAPACITY

    CHARTER STREET CAPACITY

    WCCF CAPACITY

    ESTIMATED HEATING LOAD

    GROWTH

    Load Growth Projections (Cooling)

  • 8/12/2019 City Presentation April 2005 SMT2

    39/52

    Load Growth Projections (Cooling)

    Adequate Plant Cooling Capacity

    Phase

    1

    Phase

    2

    Phase

    3

    TIMELINE

    COOLINGL

    OAD

    (

    TONS)

    WALNUT STREET CAPACITY

    CHARTER STREET CAPACITY

    ESTIMATED COOLING LOAD GROWTH

    WCCF CAPACITY

    Load Growth Projections (Electrical)

  • 8/12/2019 City Presentation April 2005 SMT2

    40/52

    Load Growth Projections (Electrical)

    Potential Shortage of Electrical Capacity

    Phase

    1

    Phase

    2

    Phase

    3

    TIMELINE

    ELECTR

    ICALLOAD

    (

    kVA)

    INSTALLED SUBSTATION CAPACITY

    ESTIMATED ELECTRICAL LOAD GROWTH

    Thermal Utility Expansion Requirements

  • 8/12/2019 City Presentation April 2005 SMT2

    41/52

    Existing Heating & Cooling PlantsFuture Cooling Plant

    Section of campus that will require

    additional cooling plants

    Thermal Utility Expansion Requirements

    WCCF

    WalnutStreet Plant

    Charter

    Street Plant

    Thermal Utility Expansion Requirements

  • 8/12/2019 City Presentation April 2005 SMT2

    42/52

    Thermal Utility Expansion Requirements

    Sample Campus

    Cooling Plants

    Electrical Utility Expansion Requirements

  • 8/12/2019 City Presentation April 2005 SMT2

    43/52

    Existing Electrical Substation

    Future or Expanded Electrical

    Substation

    Electrical Utility Expansion Requirements

    Options for Exploring (Increase Efficiency)

  • 8/12/2019 City Presentation April 2005 SMT2

    44/52

    Investigate High Efficient Energy

    Generation Methods: Cogeneration with Combustion Turbines

    (similar to WCCF)

    Clean burning coal techniques(atmospheric fluidized bed combustor -

    AFBC)

    Options for Exploring (Increase Efficiency)

    Options for Exploring (Increase Efficiency)

  • 8/12/2019 City Presentation April 2005 SMT2

    45/52

    Options for Exploring (Increase Efficiency)

    New AFBC Heating Plant at UNC

    Cleaner burning coaltechniques

    (atmosphericfluidized bedcombustor -AFBC)

    Options for Exploring (Increase Efficiency)

  • 8/12/2019 City Presentation April 2005 SMT2

    46/52

    Options for Exploring (Increase Efficiency)

    New AFBC Heating Plant at UNC

    Options for Exploring (Increase Efficiency)

  • 8/12/2019 City Presentation April 2005 SMT2

    47/52

    Options for Exploring (Increase Efficiency)

    New AFBC Heating Plant at UNC

    Options for Exploring (Increase Efficiency)

  • 8/12/2019 City Presentation April 2005 SMT2

    48/52

    Options for Exploring (Increase Efficiency)

    Thermal Energy Storage(chilled water)reduceselectrical use for chilledwater generation duringpeak times

    Options for Exploring (Renewable Energy)

  • 8/12/2019 City Presentation April 2005 SMT2

    49/52

    Commitment toIncreasing the use of

    Alternative/RenewableEnergy Resources Increase co-firing of coal

    boilers with renewablebiomass energyresources Waste wood products,

    corn stalks, energycrops (grasses, trees)

    Historically the wastesource must be in

  • 8/12/2019 City Presentation April 2005 SMT2

    50/52

    Wind Power(purchase off site

    through utilityprovider)

    Hydrogen (fuel cells)

    Geothermal

    p p g ( gy)

    Fuel Cell

  • 8/12/2019 City Presentation April 2005 SMT2

    51/52