TO: All Bidders
FROM: City of Cambridge
DATE: October 5, 2020
RE: File No. 9360 – DPW Mooney Street Alteration – Addendum No. 1
This addendum is comprised of:
1. Pre-bid sign in sheet (attached)
2. Changes to drawings
CHANGES TO DRAWINGS
Sheet AD-101 Demolition Floor Plan, RCP & Notes
Item 1: REPLACE sheet in its entirety. Changes include, but are not limited to:
(a) Demolition scope has changed; Some walls, openings and doors/frames that were
previously slated for demolition have changed. See rooms 205, 206, 208, 212, 213, 214,
215, 217/218.
(b) Door and frames associated with those walls have changed.
(c) Finishes in Rooms 213 and 214.
(d) All room numbers have been changed to reflect room changes.
Sheet A-101 Proposed Floor Plan, RCP, Furniture Plan, Notes and Finish Schedule
Item 1: REPLACE sheet in its entirety. Changes include, but are not limited to:
(a) All room/door numbers have been changed to reflect room changes.
(b) Some walls that were previously slated for demolition will remain.
(c) New walls have been added in Room 209/209A and 214.
(d) Room 205: New infill at door/frame #205 to reflect move of door #205 to opening for
door # 205A.
(e) Door Schedule has been updated to reflect doors that will remain, doors that are
slated for reuse and new doors.
(f) Finishes in Rooms 213 and 214 have changed.
(g) New General Notes section and imagery have been added
(h) Locations of Wireless access points have been added to the RCP
(i) Location of Telecommunications have been added to furniture plan
(j) Locations and number of lockers on furniture plan have been added
795 Massachusetts Avenue, Cambridge, Massachusetts 02139 Voice: 617-349-4310 Fax: 617-349-4008 TTY: 617.349.4242
Sheet FP0.1 Floor Plan – Fire Protection
Item 1: REPLACE sheet in its entirety. Changes include, but are not limited to:
(a) Revised locations for sprinkler heads to reflect wall changes.
(b) Other items as noted.
ATTACHMENTS
Sheet AD-101 Demolition Floor Plan, RCP & Notes
Sheet A-101 Proposed Floor Plan, RCP, Furniture Plan, Notes and Finish Schedule
Sheet FP0.1 Floor Plan – Fire Protection
All other details remain the same.
Elizabeth Unger
Purchasing Agent
Addendum No. 1
SECOND FLOOR PLAN - FIRE PROTECTION
SCALE: 3/16" = 1' - 0"
EXISTING UPRIGHT SPRINKLER
SYSTEM ABOVE SUSPENDED CEILING
SHALL REMAIN IN OPERATION.
F
EX. 6" FIRE SERVICE
EX. FIRE DEPT.
CONNECTION
EX. 6" D.C.V.A.
EX. 6" SP. RISE
EX. 4"
EX. CHECK VALVE
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
EX. 4" SP. MAIN
FOLLOWING SLOPE
OF ROOF
EX. SWING JOINT
EX. 4" SP. MAIN
FOLLOWING SLOPE
OF ROOF
SP SP SP SP
SP SP SP SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP SP
3"
3" 3"3"
EX. SPRINKLER SYSTEM
TO REMAIN ACTIVE
DESIGN WORK AREA
AS LIGHT HAZARD
SP
CUT IN NEW 3" SP. INTO EX. BRANCH LINE
COORDINATE SYSTEM SHUTDOWN w/BUILDING
RUN SPRINKLER DRAIN
TO EXTERIOR OF BLDG
NEW SPRINKLER CONTROL
VALVE FOR SECOND FLR.
T
F
WITH TAMPER & FLOW SWITCH
OWNER. ONCE CUT IN IS COMPLETE
EXISTING SPRINKLER SYSTEM
SHALL BE REACTIVATED & OPERATIONAL
TYP. SEMI-RECESSED PENDENT
SPRINKLER HEAD IN ACT CEILING
3"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"1
-1
/4
"
1-1
/4
"1
-1
/4
"
1-1
/4
"1
-1
/4
"
1-1
/4
"1
-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"1
-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"1
-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
1-1
/4
"
SP
1-1
/4
"1
-1
/4
"
IT RM
223
TOILET
220
TOILET
221
OFFICE
219
OFFICE
217
LOCKER RM
2
215
KITCHENETTE
214
OFFICE
212
STAIR 1
ST1
OFFICE
211
STORAGE
210
CORR
203
CORR
202
OFFICE
209
OFFICE
208
OFFICE
207
OFFICE
206
OFFICE
205
OFFICE
204
CORR
201
COPIER
222
ETR
CPT
VCT
CPT
CPT
STAIR 2
ST2
ETR
ETR
LOCKER RM
1
213
OFFICE
216
LOCKER
RM 3
218
OFFICE
209A
DISHARGE DRAIN
AT 18" ABV. FIN. GRADE
1
City of Cam
bridge
Mooney St. O
ffice Plan
Consultants
Registrations
Number Revision Date
24 Roland Street, Ste. 301Charlestown, MA 02129T: 617.776.6545F: 617.776.6678www.hktarchitects.com
Drawing number
Drawing set
Job number
Date
Checked byDrawn by
Draw
ing
Title
21941
GGD CMG
SEPT 10, 2020
GARCIA GALUSKA DESOUSA
1 Addendum 1 10-02-2020
FL
OO
R P
LA
N - F
IR
E P
RO
TE
CT
IO
N
FP0.1
GENERAL NOTES
THE WORK HEREIN REQUIRED INCLUDES A HYDRAULICALLY DESIGNED SPRINKLER SYSTEM AS SPECIFIED
IN THE DOCUMENTS AND AS APPROVED BY THE ARCHITECT.
THE FIRE PROTECTION DRAWINGS ARE DIAGRAMMATIC AND ARE TO BE USED FOR THE PURPOSE OF
ESTABLISHING GENERAL LOCATIONS OF PIPING RUNS, SIZES OF PIPING, AND QUANTITIES OF FIXTURES
AND EQUIPMENT TO BE FURNISHED HEREIN. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS
FOR EXACT LOCATIONS OF ALL SPRINKLER HEADS, AND EQUIPMENT, INCLUDING MOUNTING HEIGHTS. IN
THE EVENT OF CONFLICT OR IF DIMENSIONS ARE NOT SHOWN, OBTAIN FIELD DIRECTIVE FROM THE
ARCHITECT AS TO THE LOCATIONS OF ALL VISIBLE EQUIPMENT.
ALL PIPING SHOWN ON THESE PLANS OR THOSE TO BE DESIGNED HEREIN SHALL BE RUN CONCEALED
ABOVE SUSPENDED CEILINGS, IN CHASES, OR IN PARTITIONS UNLESS SPECIFICALLY NOTED OTHERWISE.
ALL SPRINKLER HEADS IN CEILING TILES SHALL BE LOCATED IN THE EXACT CENTER OF TILE UNLESS
SPECIFICALLY APPROVED OTHERWISE BY THE ARCHITECT.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING HEIGHTS AND CEILING MATERIALS
AND LAYOUTS. IN THE EVENT OF CONFLICT OR IF DIMENSIONS ARE NOT SHOWN, OBTAIN FIELD
DIRECTIVE FROM THE ARCHITECT AS TO THE LOCATIONS OF ALL VISIBLE EQUIPMENT.
ATTENTION IS CALLED TO THE REQUIREMENT FOR THE PREPARATION OF COORDINATION DRAWINGS. IN
ADDITION TO THE PREPARATION OF SHOP DRAWINGS ALSO PREPARE COORDINATION DRAWINGS AS
OUTLINED IN THE SPECIFICATION. THE APPROVAL OF THE SHOP DRAWINGS INCLUDING DIMENSIONS
SHOWN THEREIN DOES NOT RELIEVE THE CONTRACTOR.
SPECIFIC ATTENTION IS DIRECTED TO THE REQUIREMENTS OF STATE BUILDING CODE AND NFPA 241
REGARDING THE MAINTENANCE OF FIRE PROTECTION SYSTEMS. MAINTAIN THE SYSTEMS AS REQUIRED
BY THESE STANDARDS AS A MINIMUM.
REFER TO NFPA 13 TABLE 8.3.2.5(a) FOR TEMPERATURE RATING OF SPRINKLERS BASED ON DISTANCE
FROM HEAT SOURCES SUCH AS HEATING DUCTS, DIFFUSERS AND UNIT HEATERS.
1.
2.
3.
4.
5.
6.
7.
8.
UL/FM HANGER ASSEMBLY
FROM STRUCTURE
HANGER ROD SUPPORTED
PIPE
EXTEND HANGER ROD
ADJUSTABLE SWIVEL RING
TIGHT TO PIPE
ALTERNATE: USE UL/FM
SURGE SUPPRESSOR CLIPS
NOTE: TO BE USED AT ALL END-OF-LINE BRANCH
HANGERS THROUGHOUT PROJECT
TYPICAL END-OF-LINE BRANCH
PIPE HANGER DETAIL
N.T.S.
1
LEGEND
NOTE: NOT ALL SYMBOLS LISTED ARE APPLICABLE TO THIS PROJECT.
HEAT, VENT & AIR CONDITIONER. CONTRACTOR
DOUBLE CHECK VALVE ASSEMBLY
PRE-ACTION
SPRINKLER FLOOR CONTROL VALVE ASSEMBLY
EXP
SCVA
FDVC
FHC
FDV
LPD
HVAC
DCVA
EC
PA
GC
@C
AP
AFF
PC
F&I
EXPOSED
FIRE HOSE CABINET
FIRE DEPT. VALVE CABINET
FIRE DEPARTMENT VALVE
NO AUTOMATIC SPRINKLERS
LOW POINT DRAIN
EXPOSED AT CEILING
FURNISH AND INSTALL
ABOVE FINISHED FLOOR
GENERAL CONTRACTOR
PLUMBING CONTRACTOR
ELECTRICAL CONTRACTOR
ACCESS PANEL
FIRE DEPARTMENT CONNECTION (STORZ)
EXPOSED UPRIGHT SPRINKLER HEAD
WMG
AC
TYP.
PIV
ABD
VIV
FS
FDC
CV
SCV
PG
DP,DN
UP
CONCEALED ABOVE CEILING
SUPERVISED CONTROL VALVE
VALVE ON VERTICAL
WATER MOTOR GONG
AUTOMATIC BALL DRIP
POST INDICATOR VALVE
TYPICAL
CHECK VALVE
FLOW SWITCH
PRESSURE GAGE
PIPE RISE OR UP
TEE LOOKING DOWN
PIPE DROP OR DOWN
CAP ON END OF PIPE
STRAINER
UNION
ABBREV
SYMBOL
SP
F
SP
F
PENDANT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
DESCRIPTION
SPRINKLER LINE (WET)
FIRE MAIN UNDERGROUND
FIRE PROTECTION CONTRACTORFPC
SDSD SPRINKLER DRAIN
PRESSURE RELIEF VALVE
ITS
REMOTE INSPECTORS TEST STATION
ITC INSPECTORS TEST CONNECTION
SLOPED PIPE
MAIN WET ALARM CHECK VALVEMACV
F F FIRE MAIN ABOVEGROUND
TAMPER (SUPERVISORY) SWITCH
TS
FLOW SWITCH
FS
T
F
18"
MIN
.
FINISH GRADE
FINISH FLOOR
PIPE HANGER SUPPORTED
EXTERIOR WALL
WATER TIGHT
SLEEVE
1" GALVANIZED
PIPE THRU WALL
W/ 45° ELBOW &
BUG SCREEN
SPRINKLER DRAIN
PIPING SCHEMATIC
N.T.S.
FURNISH & INSTALL 2' X 3'
CONCRETE SPLASH PAD
3
FIRE PROTECTION CONTRACTOR IS TO
PROTECT ALL SURFACES DURING
TESTING, ETC. ALL DAMAGE TO
EXISTING FINISHES IS TO BE
REPAIRED AT NO ADDITIONAL COST
TO OWNER.
NOTE:
FP0.1
FP0.1
GWB GYPSUM WALL BOARD
IDENTIFICATION SIGN
INSPECTOR'S TEST STATION PIPING SCHEMATIC
U.L. LISTED COMBINATION
UNION
2" DRAIN RISER BY FIRE PROTECTION CONTR.
THROUGH EXTERIOR WALL AS DETAILED ON THE
COMBINATION F/SP. STANDPIPE
UL/FM INDICATING TYPE CONTROL VALVE
PRESSURE GAUGE WITH COCK
TO SPRINKLER SYSTEM
WATERFLOW SWITCH
5
3
4
1
2
9
8
6
7
7
9
1
2
4
3
UL/FM CHECK VALVE10
10
5
6
1" DRAIN LINE
TEST DRAIN, AUX. DRAIN,
8
AND SIGHT GLASS
11
11 3/4" RELIEF VALVE PROVIDE
ON ASSEMBLIES WITH PRESSURE
REDUCING & CHECK VALVES
ASSEMBLY (SCVA) DETAIL
N.T.S.
FP0.1
2
SPRINKLER CONTROL VALVE DETAIL
9. THE FIRE PROTECTION CONTRACTOR SHALL COORDINATE WITH THE OWNER AND THE OWNER'S
REPRESENTATIVE ALL NECESSARY INTERRUPTIONS OF SERVICE TO THE TENANTS. CONTRACTOR SHALL
SCHEDULE AND PERFORM THE WORK SO AS TO MINIMIZE DISRUPTIONS TO THE OCCUPANTS. ANY WORK
NECESSARY THAT IN THE OPINION OF THE OWNER IS DEEMED TO BE DISRUPTIVE TO THE TENANTS
SHALL BE PERFORMED DURING NON BUSINESS HOURS.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY SPRINKLER INSTALLATION
REQUIREMENTS NECESSARY TO ACCOMMODATE THE PHASING OF THE WORK DURING THE CONSTRUCTION
PERIOD. HE SHALL BE FURTHER RESPONSIBLE FOR ANY AND ALL REQUIRED FIRE DEPARTMENT DETAILS
DEEMED NECESSARY TO COMPLETE THE WORK.
11. THE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR PLACING THE SPRINKLER SYSTEM BACK
ON LINE AND OPERATIONAL AT THE END OF EACH WORKING DAY.
FROM EXISTING BLDG STRUCTURE
FIRE PROTECTION CRITERIA
1. THE PURPOSE OF THE FIRE PROTECTION DRAWINGS AND SPECIFICATIONS IS TO ESTABLISH THE
CRITERIA FOR DESIGN, MATERIALS, AND LOCATIONS OF THE COMPLETE SPRINKLER SYSTEM. THE FIRE
PROTECTION SUB-CONTRACTOR IS RESPONSIBLE FOR THE FINAL DESIGN OF THE SPRINKLER SYSTEM
AND SAID DESIGN AND INSTALLATION SHALL INCLUDE ALL COMPONENTS TO PROVIDE FOR THE
COMPLETE SYSTEM WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER. THE SUB-CONTRACTOR
SHALL VERIFY THAT THE NUMBER OF HEADS SHOWN ON HIS WORKING PLANS AND HYDRAULIC
CALCULATIONS ARE ADEQUATE TO PROTECT ALL AREAS OF THE BUILDING AND SHALL INCLUDE ANY
COST FOR ADDITIONAL SPRINKLER HEADS AND PIPING NOT SHOWN ON THESE DRAWINGS IN HIS
CONTRACT PRICE.
2. THE WORK AREA IS TO BE 100% SPRINKLERED INCLUDING ALL CLOSETS AND ELECTRIC ROOMS.
3. THE BUILDING IS GENERALLY STEEL CONSTRUCTION. THE BUILDING IS PROTECTED WITH AN
AUTOMATIC SPRINKLER SYSTEM. CONTRACTOR SHALL CONNECT TO EXISTING SYSTEM AND INSTALL
NEW PENDENT SPRINKLER IN THE RENOVATED CEILINGS. THE WORK AREA SHALL BE PROTECTED
THROUGHOUT WITH A WET TYPE SPRINKLER SYSTEM AND THE HEADS LOCATED WHERE SHOWN.
4. PROVIDE COMPLETE HYDRAULIC CALCULATIONS AND DISTRIBUTION SYSTEM DESIGN UTILIZING THE
DESIGN CRITERIA ESTABLISHED ON THE CONTRACT DOCUMENTS. SYSTEM DESIGN SHALL BE BASED ON
FLOW TEST PERFORMED BY THIS CONTRACTOR.
5. REQUIRED DESIGN FLOWS:
A. DESIGN HAZARDS = LIGHT HAZARD
B. REQUIRED DESIGN DENSITIES = 0.10 GPM OVER 1,500 S.F.
6. SPRINKLER SPACING (MAX.) = 225 S.F.
7. FOLLOW THE HEAD LAYOUTS SHOWN ON THE DRAWINGS IN FINISHED AREAS. ALL SPRINKLER HEADS
SHALL BE LOCATED CENTER ON THE CEILING TILE AND SWING JOINTS IF REQUIRED MAY BE USED TO
MEET THIS REQUIREMENT.
8. HYDRAULIC CALCULATIONS FOR THE SYSTEM SHALL INCLUDE A 10 PSI CUSHION AND SHALL LIMIT
WATER FLOW VELOCITY TO A MAXIMUM OF 20 FT./SEC.