Upload
cadtil
View
215
Download
0
Embed Size (px)
Citation preview
7/31/2019 Circuit Breaker - PDMaintenance
1/47
Protective DevicesProtective Devices
Maintenance as it Applies toMaintenance as it Applies tothe Arc/Flash Hazardthe Arc/Flash Hazard
Presented byPresented by
Dennis K. Neitzel,Dennis K. Neitzel, CPECPEDirectorDirector
Training Institute Dallas, TexasTraining Institute Dallas, TexasA DIVISION OF MEGGERA DIVISION OF MEGGER
7/31/2019 Circuit Breaker - PDMaintenance
2/47
22
IntroductionIntroduction
FFKey component of the Flash Hazard Analysis:Key component of the Flash Hazard Analysis:
Protective device clearing time.Protective device clearing time.
uuPrimarily circuit breakers and relays.Primarily circuit breakers and relays.
FFFuses do not have operating mechanismsFuses do not have operating mechanisms
FFPrimary focus is maintenance issuesPrimary focus is maintenance issues
7/31/2019 Circuit Breaker - PDMaintenance
3/47
33
IntroductionIntroduction
FF Molded case and low-voltage power circuit breakers:Molded case and low-voltage power circuit breakers:
Will generally clear a fault condition in 3 to 8 cycles.Will generally clear a fault condition in 3 to 8 cycles.
To be conservative a clearing time of 8 cycles should beTo be conservative a clearing time of 8 cycles should beused.used.
FF Older medium-voltage circuit breakers:Older medium-voltage circuit breakers:
Will clear a fault in around 8 cyclesWill clear a fault in around 8 cycles
Newer ones clear in 3 to 5 cycles.Newer ones clear in 3 to 5 cycles.
7/31/2019 Circuit Breaker - PDMaintenance
4/47
44
IntroductionIntroduction
FF Protective relays:Protective relays:
Add approximately 3 to 4 cycles to the clearing time ofAdd approximately 3 to 4 cycles to the clearing time of
the medium circuit breaker.the medium circuit breaker.
FF Maintenance and testing not performed:Maintenance and testing not performed:
Extended clearing times could occurExtended clearing times could occur
Unintentional time delayUnintentional time delay
Results of flash hazard analysis could be affectedResults of flash hazard analysis could be affected
7/31/2019 Circuit Breaker - PDMaintenance
5/47
55
IntroductionIntroduction
FF Maintenance and testingMaintenance and testing
Accomplished in accordance with the manufacturerAccomplished in accordance with the manufacturerss
instructions, orinstructions, or
NETANETA Maintenance Testing Specifications forMaintenance Testing Specifications for
Electrical Power Distribution Equipment and SystemsElectrical Power Distribution Equipment and Systems
2001 Edition.2001 Edition.
7/31/2019 Circuit Breaker - PDMaintenance
6/47
66
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFF Maintenance on molded-case circuit breakers isMaintenance on molded-case circuit breakers is
limited to:limited to:
Proper mechanical mountingProper mechanical mounting
Electrical connectionsElectrical connections
Periodic manual operationPeriodic manual operation
FF Lighting, appliance, and power panel circuitLighting, appliance, and power panel circuit
breakersbreakers Have riveted framesHave riveted frames
Are not designed to be openedAre not designed to be opened
7/31/2019 Circuit Breaker - PDMaintenance
7/47
77
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFF All otherAll other MCCBMCCBss that are UL approved:that are UL approved:
Factory-sealed to prevent access to calibrated elements.Factory-sealed to prevent access to calibrated elements.
FF An unbroken seal indicates:An unbroken seal indicates: Mechanism has not been tampered withMechanism has not been tampered with
Should function as specified by UL.Should function as specified by UL.
FF A broken seal voids the UL listing and theA broken seal voids the UL listing and the
manufacturersmanufacturers warranty of the device:warranty of the device: Integrity of the device would be questionable.Integrity of the device would be questionable.
7/31/2019 Circuit Breaker - PDMaintenance
8/47
88
Molded-Case CircuitMolded-Case Circuit
BreakersBreakers
FF MCCBMCCBss, other than the riveted frame types:, other than the riveted frame types:
Permitted to be reconditioned and returned to thePermitted to be reconditioned and returned to themanufacturermanufacturers original condition.s original condition.
FF To conform to the manufacturerTo conform to the manufacturers original design:s original design:
Must be reconditioned according to recognized standards.Must be reconditioned according to recognized standards.
uu Professional Electrical Apparatus Recyclers League (PEARL)Professional Electrical Apparatus Recyclers League (PEARL)
7/31/2019 Circuit Breaker - PDMaintenance
9/47
99
Molded-Case CircuitMolded-Case Circuit
BreakersBreakers
FFCircuit breakers are often forgotten.Circuit breakers are often forgotten.
FFBreakers supplying power for years:Breakers supplying power for years: Several things that can go wrong.Several things that can go wrong.
uuCircuit breakers can fail to open due to a burned outCircuit breakers can fail to open due to a burned out
trip coil, ortrip coil, or
uuFail because the mechanism is frozen due to dirt, driedFail because the mechanism is frozen due to dirt, driedlubricant, or corrosion.lubricant, or corrosion.
7/31/2019 Circuit Breaker - PDMaintenance
10/47
1010
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFFOvercurrent devices can fail due to:Overcurrent devices can fail due to:
Inactivity, orInactivity, or
A burned out electronic component.A burned out electronic component.
FFProblems occur when a breaker fails to openProblems occur when a breaker fails to open
under fault conditions.under fault conditions.
Can result in fires, damage to equipment orCan result in fires, damage to equipment orinjuries to personnel.injuries to personnel.
7/31/2019 Circuit Breaker - PDMaintenance
11/47
1111
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFFA circuit breaker fails due to:A circuit breaker fails due to:
Minimum maintenance was not performed, orMinimum maintenance was not performed, or
Performed improperly.Performed improperly.
FFRecommendation:Recommendation:
If an MCCB has not been operated within as littleIf an MCCB has not been operated within as little
as six months time:as six months time:
uuRemoved from service, andRemoved from service, and
uuManually exercised several times.Manually exercised several times.
7/31/2019 Circuit Breaker - PDMaintenance
12/47
1212
Molded-Case CircuitMolded-Case Circuit
BreakersBreakers
FFManually exercising helps:Manually exercising helps:
Keep the contacts clean due to their wiping actionKeep the contacts clean due to their wiping action
Ensures that the operating mechanism movesEnsures that the operating mechanism moves
freelyfreely
Does not operate the tripping mechanismDoes not operate the tripping mechanism
7/31/2019 Circuit Breaker - PDMaintenance
13/47
1313
Molded-Case CircuitMolded-Case Circuit
BreakersBreakers
7/31/2019 Circuit Breaker - PDMaintenance
14/47
1414
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFFProper exercise of all breaker mechanisms:Proper exercise of all breaker mechanisms:
Remove the breaker from service and test theRemove the breaker from service and test the
overcurrent and short-circuit tripping capabilitiesovercurrent and short-circuit tripping capabilitiesFFA stiff or sticky mechanism can cause:A stiff or sticky mechanism can cause:
An unintentional time delay, and thereforeAn unintentional time delay, and therefore
Increase the arc/flash incident energy level.Increase the arc/flash incident energy level.
7/31/2019 Circuit Breaker - PDMaintenance
15/47
1515
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFFAnother consideration, addressed by OSHA:Another consideration, addressed by OSHA:
1910.334(b)(2) Reclosing circuits after protective1910.334(b)(2) Reclosing circuits after protective
device operationdevice operation After a circuit is deenergized by aAfter a circuit is deenergized by acircuit protective device, the circuit may NOT becircuit protective device, the circuit may NOT be
manually reenergized until it has been determinedmanually reenergized until it has been determined
that the equipment and circuit can be safelythat the equipment and circuit can be safely
reenergized. The repetitive manual reclosing ofreenergized. The repetitive manual reclosing ofcircuit breakers or reenergizing circuits throughcircuit breakers or reenergizing circuits through
replaced fuses is prohibited.replaced fuses is prohibited.
7/31/2019 Circuit Breaker - PDMaintenance
16/47
1616
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFFEmployee is at risk if the short circuit stillEmployee is at risk if the short circuit still
exists.exists.
FFThe past practice of resetting a circuitThe past practice of resetting a circuitbreaker one, two, or three times beforebreaker one, two, or three times before
investigating is no longer allowed.investigating is no longer allowed.
FF
This previous practice has caused numerousThis previous practice has caused numerousburn injuries that resulted from the explosionburn injuries that resulted from the explosion
of electrical equipment.of electrical equipment.
7/31/2019 Circuit Breaker - PDMaintenance
17/47
1717
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFFCircuit breakers, circuits, and equipment,Circuit breakers, circuits, and equipment,
must be tested and inspected by a qualifiedmust be tested and inspected by a qualified
personperson..FFMelted arc chutes will not interrupt faultMelted arc chutes will not interrupt fault
currents.currents.
FF
If the breaker cannot interrupt a second fault,If the breaker cannot interrupt a second fault,it will fail.it will fail.
May destroy enclosure and create a hazard forMay destroy enclosure and create a hazard for
personnel.personnel.
7/31/2019 Circuit Breaker - PDMaintenance
18/47
1818
Molded-Case CircuitMolded-Case Circuit
BreakersBreakersFF In an EC&M article by NEMA, Jan. 1995 :In an EC&M article by NEMA, Jan. 1995 :
After a high level fault has occurred in equipmentAfter a high level fault has occurred in equipment
that is properly rated and installed, it is not alwaysthat is properly rated and installed, it is not alwaysclear to investigating electricians what damage hasclear to investigating electricians what damage has
occurred inside encased equipment.occurred inside encased equipment.
7/31/2019 Circuit Breaker - PDMaintenance
19/47
1919
Low-Voltage Power CircuitLow-Voltage Power Circuit
BreakersBreakersFFSeveral studies have shown:Several studies have shown:
Circuit breakers, which were not maintainedCircuit breakers, which were not maintained
within a 5-year period, have a 50% failure rate.within a 5-year period, have a 50% failure rate.FFMaintenance will generally consist of keepingMaintenance will generally consist of keeping
them clean and properly lubricated.them clean and properly lubricated.
FF
Frequency of maintenance will depend toFrequency of maintenance will depend to
some extent on cleanliness of area.some extent on cleanliness of area.
7/31/2019 Circuit Breaker - PDMaintenance
20/47
2020
Low-Voltage Power CircuitLow-Voltage Power Circuit
BreakersBreakersFFGeneral inspection and lubrication isGeneral inspection and lubrication is
recommended at least once per year.recommended at least once per year.
FFSome make this recommendation after theSome make this recommendation after thefirst six months of service.first six months of service.
7/31/2019 Circuit Breaker - PDMaintenance
21/47
2121
Low-Voltage Power CircuitLow-Voltage Power Circuit
BreakersBreakersFF If the breaker remains open or closed for a longIf the breaker remains open or closed for a long
period of timeperiod of time::
Open and close the breaker several timesOpen and close the breaker several times
Exercise under load conditions (hazard-remote operation)Exercise under load conditions (hazard-remote operation)
FF Environmental conditions play a major role.Environmental conditions play a major role.
FF More frequent inspections and maintenance may beMore frequent inspections and maintenance may be
required if:required if: Severe load conditions existSevere load conditions exist
Inspection reveals heavy accumulations of dirt, moisture,Inspection reveals heavy accumulations of dirt, moisture,
or other foreign matteror other foreign matter
7/31/2019 Circuit Breaker - PDMaintenance
22/47
2222
Low-Voltage Power CircuitLow-Voltage Power Circuit
BreakersBreakersFFMechanical failure would include:Mechanical failure would include:
Unintentional time delay in the tripping operationUnintentional time delay in the tripping operation
due to:due to:uuDry, dirty or corroded pivot pointsDry, dirty or corroded pivot points
uuHardened or sticky lubricantHardened or sticky lubricant
FFThe manufacturerThe manufacturers instructions must bes instructions must be
followed in order to minimize the risk of anyfollowed in order to minimize the risk of anyunintentional time delay.unintentional time delay.
7/31/2019 Circuit Breaker - PDMaintenance
23/47
2323
Low-Voltage Power CircuitLow-Voltage Power Circuit
BreakersBreakers
7/31/2019 Circuit Breaker - PDMaintenance
24/47
2424
Medium-Voltage PowerMedium-Voltage Power
Circuit BreakersCircuit BreakersFFMost requirements the same as low-voltageMost requirements the same as low-voltage
power circuit breakers.power circuit breakers.
FFBreakers should be removed from service andBreakers should be removed from service andinspected at least once per year.inspected at least once per year.
FFAlways follow the manufacturerAlways follow the manufacturerss
instructions.instructions.
7/31/2019 Circuit Breaker - PDMaintenance
25/47
2525
Medium-Voltage PowerMedium-Voltage Power
Circuit BreakersCircuit Breakers
7/31/2019 Circuit Breaker - PDMaintenance
26/47
2626
Medium-Voltage PowerMedium-Voltage Power
Circuit BreakersCircuit Breakers
7/31/2019 Circuit Breaker - PDMaintenance
27/47
2727
Protective RelaysProtective Relays
FFRelays monitor complex power circuitRelays monitor complex power circuitconditions, such as:conditions, such as:
Current and voltage magnitudesCurrent and voltage magnitudes
Phase angle relationshipsPhase angle relationships
Direction of power flowDirection of power flow
FrequencyFrequency
FFWhen a short circuit (or fault) is detected:When a short circuit (or fault) is detected:
Relay responds and closes its contactsRelay responds and closes its contacts
The abnormal portion of the circuit isThe abnormal portion of the circuit is
deenergized via the circuit breakerdeenergized via the circuit breaker
7/31/2019 Circuit Breaker - PDMaintenance
28/47
2828
Protective RelaysProtective Relays
FFThe ultimate goal of protective relaying is toThe ultimate goal of protective relaying is to
disconnect a faulty system element as quicklydisconnect a faulty system element as quickly
as possible.as possible.
FFSensitivity and selectivity are essential toSensitivity and selectivity are essential to
ensure that the proper circuit breakers areensure that the proper circuit breakers are
tripped at the proper speed to:tripped at the proper speed to:
Clear the faultClear the fault
Minimize damage to equipmentMinimize damage to equipment
Reduce the hazards to personnelReduce the hazards to personnel
7/31/2019 Circuit Breaker - PDMaintenance
29/47
2929
Protective RelaysProtective Relays
FFSeveral things may happen to preventSeveral things may happen to prevent
primary relaying from disconnecting a powerprimary relaying from disconnecting a power
system fault:system fault: Current or voltage supplies to the relays areCurrent or voltage supplies to the relays are
incorrect.incorrect.
DC tripping voltage supply is low or absent.DC tripping voltage supply is low or absent.
Protective relay malfunctions.Protective relay malfunctions.
Tripping circuit or breaker mechanism hangs up.Tripping circuit or breaker mechanism hangs up.
7/31/2019 Circuit Breaker - PDMaintenance
30/47
3030
Protective RelaysProtective Relays
FFEach element of the system hasEach element of the system haszones ofzones of
protectionprotectionsurrounding the element.surrounding the element.
FFA fault within the given zone should cause theA fault within the given zone should cause thetripping of all circuit breakers within thattripping of all circuit breakers within that
zone and no tripping of breakers outside thatzone and no tripping of breakers outside that
zone.zone.
FF If faults occur in the overlap region, severalIf faults occur in the overlap region, several
breakers respond and isolate the sectionsbreakers respond and isolate the sections
from the power system.from the power system.
7/31/2019 Circuit Breaker - PDMaintenance
31/47
3131
Protective RelaysProtective Relays
7/31/2019 Circuit Breaker - PDMaintenance
32/47
3232
Protective RelaysProtective Relays
FFVoltage and current transformers play a vitalVoltage and current transformers play a vital
role in the power protection scheme.role in the power protection scheme.
Used to isolate and protect both people andUsed to isolate and protect both people anddevices from high voltage and current.devices from high voltage and current.
FFThe performance of a relay is only as good asThe performance of a relay is only as good as
the voltage and current transformersthe voltage and current transformers
connected to it.connected to it.
7/31/2019 Circuit Breaker - PDMaintenance
33/47
3333
Protective RelaysProtective Relays
FFSome overcurrent relays are equipped withSome overcurrent relays are equipped with
an instantaneous overcurrent unit:an instantaneous overcurrent unit:
Operates when the current reaches its minimumOperates when the current reaches its minimumpickup point.pickup point.
An instantaneous unit is a relay having noAn instantaneous unit is a relay having no
intentional time delay.intentional time delay.
7/31/2019 Circuit Breaker - PDMaintenance
34/47
3434
Protective RelaysProtective Relays
7/31/2019 Circuit Breaker - PDMaintenance
35/47
3535
Protective RelaysProtective Relays
FFThings that can go wrong:Things that can go wrong:
An open or shunted current transformerAn open or shunted current transformer
Open coilOpen coil
Dirty contactsDirty contacts
FFProtective relays, like circuit breakers,Protective relays, like circuit breakers,
require periodic inspection, maintenance, andrequire periodic inspection, maintenance, and
testing to function properly.testing to function properly.
7/31/2019 Circuit Breaker - PDMaintenance
36/47
3636
Protective RelaysProtective Relays
FFMost manufacturers recommend thatMost manufacturers recommend that
periodic inspections and maintenance beperiodic inspections and maintenance be
performed at intervals of one to two years.performed at intervals of one to two years.FFThe intervals between periodic inspection andThe intervals between periodic inspection and
maintenance will vary:maintenance will vary:
EnvironmentEnvironment
Type of relayType of relay
7/31/2019 Circuit Breaker - PDMaintenance
37/47
3737
Protective RelaysProtective Relays
FFThe periodic inspections, maintenance, andThe periodic inspections, maintenance, and
testing are intended to ensure that:testing are intended to ensure that:
Protective relays are functioning properlyProtective relays are functioning properly
Have not deviated from the design settingsHave not deviated from the design settings
uu If deviations are found, the relay must be retested andIf deviations are found, the relay must be retested and
serviced as described in the manufacturerserviced as described in the manufacturerss
instructions.instructions.
7/31/2019 Circuit Breaker - PDMaintenance
38/47
3838
Flash Hazard AnalysisFlash Hazard Analysis
FFAll calculations require the arc clearing time.All calculations require the arc clearing time.
Determine incident energyDetermine incident energy
Establish the flash protection boundaryEstablish the flash protection boundary
FFClearing time is derived from the engineeringClearing time is derived from the engineering
coordination studycoordination study
Based on what the protective devices areBased on what the protective devices are
supposed to do.supposed to do.
7/31/2019 Circuit Breaker - PDMaintenance
39/47
3939
Flash Hazard AnalysisFlash Hazard Analysis
FFMaintenance is a very critical part of the flashMaintenance is a very critical part of the flash
hazard issue.hazard issue.
FFA preventive maintenance program on theseA preventive maintenance program on thesecircuit protective devices is needed.circuit protective devices is needed.
FF Inadequate maintenance can causeInadequate maintenance can cause
unintentional time delays.unintentional time delays.
7/31/2019 Circuit Breaker - PDMaintenance
40/47
4040
Flash Hazard AnalysisFlash Hazard Analysis
FFExample:Example:
A low-voltage power circuit breaker had not beenA low-voltage power circuit breaker had not been
operated or maintained for several yearsoperated or maintained for several years The lubrication had become sticky or hardenedThe lubrication had become sticky or hardened
Circuit breaker could take several additionalCircuit breaker could take several additional
cycles, seconds, minutes, or longer to clear a faultcycles, seconds, minutes, or longer to clear a fault
condition.condition.
7/31/2019 Circuit Breaker - PDMaintenance
41/47
4141
Flash Hazard AnalysisFlash Hazard Analysis
FF Flash Hazard Analysis is performed:Flash Hazard Analysis is performed:
Based on what the system is suppose to do - 5 cyclesBased on what the system is suppose to do - 5 cycles
Unintentional time delay, due to a sticky mechanismUnintentional time delay, due to a sticky mechanism
Breaker clears in 30 cyclesBreaker clears in 30 cycles
The worker could be seriously injured or killed becauseThe worker could be seriously injured or killed because
he/she was under protected.he/she was under protected.
FF Arc/Flash situation: 20,000-amp short-circuit, 480Arc/Flash situation: 20,000-amp short-circuit, 480volts, 3-inch arc gap, the worker is 18 inches fromvolts, 3-inch arc gap, the worker is 18 inches from
the arc, with a 5 cycle clearing time for a 3-phase arcthe arc, with a 5 cycle clearing time for a 3-phase arcin a box (enclosure).in a box (enclosure).
Next slide illustrates this:Next slide illustrates this:
7/31/2019 Circuit Breaker - PDMaintenance
42/47
4242
Calculation for 5 cyclesCalculation for 5 cycles
7/31/2019 Circuit Breaker - PDMaintenance
43/47
4343
Calculation with a 5 Cycle Clearing TimeCalculation with a 5 Cycle Clearing Time
This value of 1.89431 cal/cmThis value of 1.89431 cal/cm22
is based on a single-phaseis based on a single-phasearc in open-air. As a general rule of thumb, the value ofarc in open-air. As a general rule of thumb, the value of
1.89431 would be multiplied by a factor of 2 for a single-1.89431 would be multiplied by a factor of 2 for a single-
phase arc in a box (2 x 1.89431 = 3.78862 cal/cmphase arc in a box (2 x 1.89431 = 3.78862 cal/cm22
Category 1) and by a factor of 3.4 for a multi-phase arc inCategory 1) and by a factor of 3.4 for a multi-phase arc ina box (3.4 x 1.89431 = 6.440654 cal/cma box (3.4 x 1.89431 = 6.440654 cal/cm22 Category 2).Category 2).
(The protection category is based on NFPA 70E-2000,(The protection category is based on NFPA 70E-2000,
Part II, Table 3-3.9.3.)Part II, Table 3-3.9.3.)
Due to a sticky mechanism the clearing time increases toDue to a sticky mechanism the clearing time increases to30 cycles.30 cycles.
Next slide illustrates this:Next slide illustrates this:
7/31/2019 Circuit Breaker - PDMaintenance
44/47
7/31/2019 Circuit Breaker - PDMaintenance
45/47
4545
Calculation with a 30 Cycle Clearing TimeCalculation with a 30 Cycle Clearing Time
The value of 11.36586 cal/cmThe value of 11.36586 cal/cm22 is based on a single-phase arc inis based on a single-phase arc in
open-air. Again, as a general rule of thumb, the value ofopen-air. Again, as a general rule of thumb, the value of
11.36586 would be multiplied by a factor of 2 for a single-phase11.36586 would be multiplied by a factor of 2 for a single-phase
arc in a box (2 x 11.36586 = 22.73172 cal/cmarc in a box (2 x 11.36586 = 22.73172 cal/cm22 Category 3) andCategory 3) and
by a factor of 3.4 for a multi-phase arc in a box (3.4 x 11.36586 =by a factor of 3.4 for a multi-phase arc in a box (3.4 x 11.36586 =
38.643924 cal/cm38.643924 cal/cm
22
Category 4).Category 4). (The protection category is(The protection category isbased on NFPA 70E-2000, Part II, Table 3-3.9.3.)based on NFPA 70E-2000, Part II, Table 3-3.9.3.)
As can be seen, maintenance is extremely important to anAs can be seen, maintenance is extremely important to an
electrical safety program. Maintenance must be performedelectrical safety program. Maintenance must be performed
according to the manufactureraccording to the manufacturers instructions in order tos instructions in order to
minimize the risk of having an unintentional time delay inminimize the risk of having an unintentional time delay in
the operation of the circuit protective devices.the operation of the circuit protective devices.
7/31/2019 Circuit Breaker - PDMaintenance
46/47
4646
SummarySummary
FFProper maintenance can be performed andProper maintenance can be performed and
power systems kept in a safe, reliablepower systems kept in a safe, reliable
condition with the proper mixture of:condition with the proper mixture of: Common senseCommon sense
TrainingTraining
ManufacturersManufacturers literature and spare partsliterature and spare parts
7/31/2019 Circuit Breaker - PDMaintenance
47/47
4747
SummarySummary
FFCircuit breakers, if installed within theirCircuit breakers, if installed within their
ratings and properly maintained, shouldratings and properly maintained, should
operate trouble-free for many years.operate trouble-free for many years.FF If operated outside of their ratings or withoutIf operated outside of their ratings or without
proper maintenance:proper maintenance:
Catastrophic failure of the power system, circuitCatastrophic failure of the power system, circuit
breaker, or switchgear can occurbreaker, or switchgear can occur
May cause serious injury or even death ofMay cause serious injury or even death of
employees working in the area.employees working in the area.