STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 1 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
LIST OF CONTENTS
1. PLANT DETAILS
2. TESTING OBJECTIVES
3. TESTING PROPOSALS
4. SERVICES REQUIRED
5. SAFETY PRECAUTIONS
6. EMERGENCY PROCEDURES
7. STATE OF THE PLANT
8. COMMISSIONING PROCEDURE
9. COMPLETION CRITERIA
10. APPENDICES
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 2 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
1. PLANT DETAILS:
THIS SYSTEM CONSISTS OF OLCS,CLCS AND OTHER INTERFACE SYSTEM PANELS.
Each panel consists of Power supply module, Processor, Local Bus modules, Input and output modules (Analog and
Digital),Intra plant modules ,diagnostic modules and Interface modules either all or except one or two.
Sl. No. modules Cross reference1 Binary Input 70EBXX2 Analog Input 70EAXX3 Binary output 70ABXX4 Analog output 70AAXX5 Drive control 70AS04/066 Processor for text output 70KS017 Intra plant bus Access 70FA018 Intra plant Bus coupler 70FK019 IPB Coupler with address input XV771310 IPB Cable Power Supply XV771511 IPB cable input XV7717/812 IPB Traffic Director 70FV0113 Bus access 70BA0214 Bus circuit board 70BL0115 Bus coupler serial Interface 70BK0316 Bus isolation 70BT0117 Bus end 70BA0218 Cable for local bus extension 70BL0319 IPB Bus coupling 70BK0220 Bus traffic Director for extended Add range 70BV0521 Power supply XT37Y22 DC/DC convertor KH37023 Processor 70 PR 0524 IS between IPB & PC-AT PC42125 Diagnostic/SOE 70SK3Z
XX – 01,02,03,04 or 06 depending on versions/applications, it changes
Y – 3 for distribution,6 for buffer & 7 supervision for positive voltages
Z – 1 for video controller, 2 for RS232 interface for key board,3 for test memory ,4 for computer simulation memory
coupler, 5 for output voltage signal for trend,6 for EEPROM programming , 7 for local bus to computer buscoupler
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 3 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
NAME PLATE DETAILS
MAKE:ELECTRONICS DIVISION,BHEL,BANGALORE
SYSTEM DESCRIPTION:
a) OLCS(CRB)Panels
These panels are used for operating single Drive in
open loop control system mode. In this outputs are not
controlled but monitored. Feedbacks, commands and other
parameters for drive are monitored through MMI. There are
22 such modules for NTPC Simhadri; CRB 01 to 22.
b) CLCS(CRA) Panels
These panels are used for operating Single drive in
CLCS mode i.e. the output is controlled by taking a
fraction of output as a controlling input to the system.
There are 15 such closed loop control system panels in NTPC
simhadri site. They are labeled as CRA 01 to 15.
c) IS Panels
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 4 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
These panels are used for interfacing IPB with PC-AT.
There are such 6 modules in NTPC simhadri site; labeled as
CRC 01 to 06.
2.TESTING OBJECTIVE:
TO TEST THE DDCMIS PANELS AND TO MAKE THEM READY FOR SERVICE.
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 5 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
3.TESTING PROPOSAL:
i) INTRA PLANT BUS COMMUNICATION TO BE ESTABLISHED
ii) POWER SUPPLY OF ALL PANELS ARE NOT BE MIXED UP
iii)POWER & CONTROL BUSES ARE TO BE ISOLATED FROM
EARTH.
iv) POTENTIAL ACROSS EARTH & NEUTRAL(ZERO) POINT OF
THE PANEL SHOULD BE WITHIN SOME MILLI VOLTS.
v) INPUT,OUTPUT,DRIVE CONTROL,PROCESSOR,COMMUNICATION &
DIAGNOSTIC STATION MODULES ARE TO BE TESTED AT FIRST.
vi) FIELD CONNECTIONS ARE TO BE TESTED THEREAFTER
vii) ALL LOGICS TO BE TESTED & FIND OUT EACH OUTPUTS ARE AS PER
THE GIVEN LOGICS
viii) CALIBRATION OF OUTPUT SYSTEMS SUCH AS CONTROL VALVES,SERVO
MOTORS ETC ARE TO BE CARRIED OUT.
ix) CHANGEOVER OPERATION OF INTRA PLANT BUS TRAFFIC DIRECTORS
(70FV01) & INDIVIDUAL BUSCOUPLERS OF EACH PANELS ARE TO BE CHECKED
AND FOUND OK.
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 6 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
4.SERVICES REQUIRED:
500 V DC MEGGER
230 V 1 PHASE 50 Hz AC SUPPLY
24V DC SUPPLY
DIGITAL MULTIMETER
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 7 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
5.0 SAFETY PRECAUTIONS:
GENERAL:
5.1 FUSES OF DIFFERENT RATINGS ARE PROVIDED IN EACH CARDS TO
PROTECT ITSELF FROM OVERCURRENT, SHORT AT OUTPUT SIDE OR
ANY OTHER INTERNAL FAULT.
5.2 CIRCUIT BREAKERS ARE PROVIDED TO PROTECT MAIN EQUIPMENTS
FROM SHORT, EARTHING OF INPUT POWER SUPPLIES
PERSONNEL :
5.3.1 ALL MEMBERS OF THE TEST TEAM AND ALL OTHER PERSONS
INVOLVED IN THIS TESTING SCHEDULE MUST BE MADE
FAMILIAR WITH THE CONTENTS OF THE TESTING SCHEDULE.
5.3.2 SAFE ACCESSES TO AND ADEQUATE ESCAPE ROUTES FROM
CONFINED AREAS MUST BE MAINTAINED.
5.3.3 SAFETY CLEARANCE CERTIFICATE WILL BE IN FORCE.
5.2 PLANT :
5.2.1 WHILE INSERTING MODULES IN DDCMIS, ENSURE THAT
THEY ARE NOT INSERTED UPSIDE DOWN, WHICH CAN BE
DISASTROUS.
5.2.2 ENSURE THAT WHILE CARRYING OUT THE
MEASUREMENTS/OBSERVATIONS OF THE POWER SUPPLIES, NO
ACCIDENTAL SHORTING OF WIRES OCCURS.
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 8 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
5.2.3 CABLE USED FOR RTDS & OTHER TRANSMITTER MEASUREMENTS SHOULD
NOT HAVE ANY JOINTS
5.2.4 DO NOT USE HIGH VOLTAGE SOLDERING IRON FOR REMOVING OR
FIXING ANY COMPONENT IN THE ELECTRONIC MODULE, THIS MAY
DAMAGE PRINTED CIRCUITS. USE 6V, 30V, SOLDERING IRON FOR
THIS PURPOSE.
5.2.5 VARIOUS ELECTRONIC MODULES NEED CERTAIN JUMPERS TO BE
CLOSED BY LINKS AND SOME JUMPERS ARE TO REMAIN OPEN. IN
SOME CASES, A FEW RESISTORS ARE TO BE MOUNTED BEFORE
TESTING. THIS INFORMATION IS GIVEN IN RELEVANT TEST
PROCEDURES OF THE MODULES. IT IS IMPORTANT TO CROSS CHECK
THAT ALL SUCH LINKS AND RESISTORS ARE MOUNTED BEFORE
CONDUCTING TESTS.
5.2.6 ZERO POTENTIAL AND EARTH POTENTIAL SHOULD HAVE BEEN
CONNECTED AT ONE POINT IN THE WORKS. ENSURE THAT THE SAME
HAS BEEN DONE.
5.2.7 WHILE MEGGERING, ENSURE THAT ALL ELECTRONICS MODULES AND
SUBASSEMBLIES ARE REMOVED / SHORT CIRCUITED.
5.2.8 BEFORE CONDUCTING TESTS ON ELECTRONIC MODULE, CHECK
AVAILABILITY OF RELEVANT POWER SUPPLY (IF ANY) AT THE TEST
SOCKET OF MODULE OR RACK.
5.2.9 THE EARTH CONNECTIONS AT THE SUPPLY TERMINALS OF THE CRO
SHOULD BE REMOVED AND ISOLATED. ALTERNATIVELY IT WOULD BE
PREFERABLE TO FEED THROUGH AN ISOLATING TRANSFORMER.
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 9 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
6. EMERGENCY PROCEDURE:
6.1 EMERGENCY PUT OFF PB IS AVAILABLE AS AN OPTION AND MAINLY
SERVES TO DISCONNECT THE POWER SUPPLY TO THE PROCESSORS AND
OTHER CIRCUITS.
6.2 EMERGENCY TELEPHONE NUMBERS FOR HOSPITAL & FIRE STATIONS SHALL
BE PREDOMINANTLY DISPLAYED.
6.3 A TELEPHONE MUST BE AVAILABLE NEARBY
6.4 FIRST AID CHARTS FOR ELECTRICAL SHOCKS MUST BE AVAILABLE
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 10 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
7. STATE OF THE PLANT:
7.1 PANELS ARE ERECTED.
7.2 IP BUS CABLES ARE INTERCONNECTED & TERMINATED WITH RC NETWORKS
AT THE ENDS.
7.3 APPLICATION EPROMS ARE LOADED WITH CORRECT PROGRAMS.
7.4 NO CABLE CONDUCTOR STRANDS ARE BENT INADVERTENTLY & TOUCH THE
GROUND POINTS DIRECTLY;BUT GROUNDED THROUGH CAPACITOR.
7.5 POWER SUPPLY CABLES ARE CONNECTED.
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 11 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
8.COMMISSIONING PROCEDURE:
i) ENSURE IPB CABLE IS TERMINATED AS PER SEC 2.0 OF IPB
CHECKLIST
ii) IN BK02/FV01 MODULES,CHECK S104 & S105 OF AKA/SKA &AKB/SKB
JUMPERS ARE IN POSITION 2 RESPECTIVELY TO ENABLE SWITCHOVER
TO REDUNDANT LINE IN CASE OF A FAULT IN THE WORKING LINE.
IF IN THE SAME IPB, ONE 70FV01a &70FV01b ARE USED IN
REDUNDANT MODE, THE PLUG IN JUMPER AKB/EKB(S105) MUST BE IN
POSITION 1 IN 70FV01b.
iii) DATA COMMUNICATION CHECKS
CHECK ALL DATAS ARE RECEIVED IN END MODULE THROUGH
BK02 OVER IPB; OTHERWISE FOLLOW THE PROCEDURE MENTIONED IN
THE PAGE 04,05& 06 OF 11 OF IPB CHECK LISTS
ENSURE THE FOLLOWING
a) THE MAXITERMI,70BL02/70BL03, MODULE CONNECTIONS ARE
FIRM AND OK.
b) COOLING FAN DIRECTION IS SUCH THAT IT DRAWS AIR FROM
BOTTOM AND EXHAUSTS OUT AT THE TOP
c) PROTECTIVE DIODES IN THE BACK PLANE PCB(DN,DI,CK,ADR&
Z) ARE HEALTHY.
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 12 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
d) PROPER DISTRIBUTION OF POWER SUPPLIES TO INDIVIDUAL
RACKS IN TF,TQ,TL,SOE INTER PANEL CONNECTIONS &
SYNCHRONISATION SIGNAL WIRING TO FV01s FROM
DIAGNOSTIC STATION AS PER RELEVANT DOCUMENTS
iv) INPUT MODULES
a) ALARM SIGNAL SHOULD NOT APPEAR IN HEALTHY STATE
b) ENSURE DIAGNOSTIC IS WORKING UNDER THE CONDITIONS OF WIRE
BREAK, SHORT CIRCUIT, SUPPLY FAILURE ETC
c) APPROPRIATE COMPENSATING RESISTORS ARE TO BE SUED BETWEEN
PIN 17 & 19 IN EA04 MODULES
d) INPUT SIGNALS MUST BE POTENTIAL AS WELL AS ELECTRO MAGNETIC
INTERFERENCE FREE AND FIXED CONTACTS
v)OUTPUT MODULES
a) ALARM SIGNAL SHOULD NOT APPEAR IN HEALTHY STATE b)
DIAGNOSTIC RESPONSES LIKE MODULE FAILURE, MISSING
PCB ARE TO BE CHECKED.
v) DRIVE CONTROL MODULES
a) ENSURE THAT CORRECT APPLICATION EPROM IS PUT PROPERLY WITH
CORRECT POLARITY.
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 13 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
b) ENSURE POWER SUPPLY AT A/M STATIONS, PUSH BUTTONS/LAMPS IN
CONTROL ROOM ETC
c) INTERFACE SIGNALS (TORQUE/LIMIT SWITCH/POSITION
FEEDBACKS, COMMAND OUTPUTS THROUGH RELAYS,E/P
CONVERTOR, ACTUATOR) ARE TO BE CHECKED
d) ENSURE THE MODULE IS IN NOT SIMULATOR MODE.
e) PROTECTION LOGIC IS IN ORDER FOR ALL THE O/PS
f) THE OUTPUT TELEGRAMS ARE ALL OK
g) DIAGNOSTIC INFORMATION IS PROPER FOR VARIOUS FAULT
CONDITIONS
h) ENSURE CORRECT DRIVE CONTROL STANDARD FUNCTIONS ARE
PROGRAMMED
i) ENSURE FEEDBACK TRANSMITTER IS PROPERLY TERMINATED,
GROUNDING OF THE VALVE POSITION, FEEDBACK CABLE ARE NOT
PRESENT IN CASE OF 70AS06 & ITS CALIBRATION WITH LOAD IS
PROPER
j) CHECK HARD WIRED PROTECTION IS PROPERLY TERMINATED
vii) PROCESSOR MODULE
ENSURE THE FOLLOWING
a) CORRECT VERSION OF FIRMWARE IS USED
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 14 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
b) APPLICATION EPROMS WITH CORRECT APPLICATION PROGRAM
NUMBERS ARE USED
c) PARAMETERS ARE SET ACCORDING TO THE SCHEME USING 70SK06 OR
DIAGNOSTIC STATION
d) FAULT ANNUNCIATIONS ARE ALL RIGHT UNDER ALL FAULT
CONDITIONS
e) DIAGNOSTIC EPROM READING FACILITY IS ENABLED
f) PROCESSOR NUMBERS ARE CORRECTLY SET WHEN MORE THAN ONE
PROCESSOR MODULE IN A LOCAL BUS IS PRESENT
g) PROGRAM END STATEMENT IS PROGRAMMED AFTER THE USER PROGRAM
IN ALL PROCESSOR MODULES
h) THE INTERPROCESSOR DATA TRANSFER ADDRESS RANGE IS BEYOND
THE LAST SERVICE ADDRESS USED IN 70BK02 MODULE IN CASE OF
70PR05 MODULES CONFIGURED IN HOT STANDBY MODE.
vi) COMMUNICATION MODULE
a) ENSURE WIRING IS OK BETWEEN 70BK02,70FV01 & XV7713/ 70FA01
b) ALL MODULES INSIDE XV7713/70FA01 ARE PROPERLY PLACED
c) RC CIRCUIT IS SOLDERED & PLACED PROPERLY AT THE BEGINNING
& AT THE END OF IP BUS CABLE (XV/FA BOXES)
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 15 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
d) IP BUS IS TERMINATED IN ALL PANELS WITH PROPER LUGS.
ENSURE COAXIAL CABLE CONNECTIONS
e) TO REDUCE DISTURBANCES ENSURE THAT THE IPB CABLE IS
EARTHED AT MORE POINTS(MULTIPLE EARTHING)
f) IN CASE 70BK02b IS USED WITH 70FV01a,ENSURE C80 CAPACITOR
OF 70FV01a IS CHANGED FROM 47nf TO 147nf
g) ALARM SIGNAL SHOULD NOT APPEAR IN ANY OF THE 70BK02 &
70FV01
h) IN 70BK02 MODULES, ENSURE THAT
1. LINE NUMBERS 016 & 017 ARE PROGRAMMED WITH DF02 & 03FF
RESPECTIVELY TO ENABLE EPROM READING FACILITY FROM
DIAGNOSTIC STATION
2. IN WORD MARSHALL PROGRAMMING,STARTING FROM LINE NUMBER
0400,THE BK NUMBERS ARE CALLED IN THE ASCENDING ORDER,AS
OTHERWISE THE MODULE WON’T FUNCTION
i) ENSURE EARTH LINK IS SOLDERED IN ALL XV MODULES
j) AFTER IPB IS COMMISSIONED, CHECK THE CHANGEOVER OPERATION
OF REDUNDANT IPB TRAFFIC DIRECTORS(70FV01)
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 16 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
ix) DIAGNOSTIC STATION
a) ENSURE THAT THE CORRECT VERSION OF FIRMWARE IS LOADED IN
70SK33 MODULE IN PROPER LOCATION
b) APPLICATION PROGRAM IS LOADED & NO RAMS PRESENT IN 70SK33
c) NO OTHER EPROM, RAMS ARE IN 70SK33
d) OPERATION OF DC/DC CONVERTOR MODULES ARE OK & THE OUTPUTS
ARE WITHIN PERMISSIBLE LIMITS
e) CHECK THE INTERCONNECTION CABLES/FKB FOR SOE OPERATION
f) ENSURE THAT NO DIAGNOSTIC/SOE STATION MODULES ARE
INSERTED/PULLED OUT IN POWER-ON CONDITION
g) ENSURE THAT THE WORD 02 IS MARSHALLED TO 01 IN DIAGNOSTIC
STATION AS THIS SYCHRONISATION WORD IS USED IN ALL THE P13
LOCAL BUSES
h) ENSURE THAT A 70AB01 MODULE IS PROVIDED IN DIAGNOSTIC
STATION WITH ADDRESS 01 & THE PIN 13 OF THIS MODULE IS
HARDWIRED TO ALL 70FV01 MODULES(PIN 95) TO ENABLE ALL
70FV01 MODULES TO FLOAT A ADDRESS & AT THE SAME TO HAVE
SYNCHRONISM IN FLASHING OF LAMPS ON THE DESK. PIN 95 OF
70BK02 MODULES IS HARDWIRED TO ALL 70EB10 MODULES (IF OUB
61 EXIST) TO ENABLE THEM TO START THE MILLISECOND COUNTER
AT THE SAME TIME.
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 17 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
i) ENSURE THAT THE 70BV05 MODULE CYCLE TIME IS SELECTED AS 20
ms IN BOTH DIAGNOSTIC STATION & THE SOE STATION AND SOE AS
MASTER, DIAGNOSTIC STATION AS SLAVE
j) MARSHALL THE WORDS 02,03,FE FROM SOE STATION INTO
DIAGNOSTIC STATION
k) ENSURE THAT SOE COMMAND WORD IS TRANSMITTED TO ALL
STATIONS WHEREVER 70EB10 MODULES ARE LOCATED
l) CHECK JUMPER SETTINGS AND CORRECT INSTALLATION OF
RAM,EPROM, APPLICATION EPROMS,FIRMWARE EPROMS AS PER
ANNEXURE I
x)FIELD CONNECTIONS
a) ENSURE SIGNAL/SHIELD ARE PROPERLY TERMINATED
b) FERRULES TO B E PROVIDED FOR ALL USED CABLE CORES IN
JUNCTION BOXES AND UNSIGNED CABLE ENTRIES USED TO BE
PLUGGED
xi)FLAME SCANNER
a) ENSURE THAT PROPER JUMPER SELECTIONS ARE MADE IN THE
POWER SUPPLY MODULE BEFORE PUTTING INTO SERVICE.
b) DO NOT REMOVE OR INSERT ANY MODULE UNDER POWER-ON
CONDITION
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 18 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
9.COMPLETION CRITERIA:
DDCMIS IS COMMISSIONED. ALL PARAMETERS AS PER SCHEME ARE
MONITORED & CONTROLLED FROM OPERATING STATIONS. SEQUENCE OF EVENTS IN
CASE OF TRIP ON FAULT, CHANGEOVER, PROCESS CHANGES AND
STARTING/STOPPING OF MAIN EQUIPMENTS ARE FOUND AVAILABLE IN THE
WORKSTATION MONITORS. CHANGEOVER OF PROCESSORS, IP BUS LINES ARE
FOUND OK WHEN FAULT OCCURS & NO DISTURBANCE IN THE DATA TRANSFER
STATION: NTPC SIMHADRI
BHEL REF NO : PS-DC-186-500-NTPC REF NO: SIM/1/TS/ /
SHEET 19 OF 19
PLANT AREA : CONTROL & INSTRUMENTATION
TESTING SCHEDULE : DDCMIS (OLCS,CLCS &IS)
10. APPENDICES:
DRAWINGS: EARTHING PRACTICE - ED 046 28 02/REV 01
( 19 SHEETS)
PRECOMMISSIONING OF P13/42 - EC 00001 /REV 01
( 17 SHEETS)
IPB CHECKLIST - SK 676 410 0105 REV01
( 11 SHEETS)
FV & BK LISTS FOR IPBs - 1-50-1638-01REV01(15.8.2001)
1-50-1639-01REV01(15.8.2001)
LOG SHEETS : I) INDIVIDUAL TERMINAL RESISTANCE OF IP BUS
AT VARIOUS PANEL
II)LIST OF JUMPER SETTINGS,VERSIONS OF
APPILICATION PROGRAMS USED
III) LIST OF SOEs CONFIGURED